SlideShare ist ein Scribd-Unternehmen logo
1 von 18
Power Transformer Protection
Rishi Tandon
Assistant Manager – WWO
Wind World (India) Limited
Introduction
 Transformer is a static device used to transform the electrical energy
from one alternating current circuit to another without any change in
frequency.
 Power Transformer is a vital link in a power transmission system and
distribution
 A Power Transformer is an expensive part of a power network.
 The impact of a transformer outage due to fault is more serious than a
transmission line outage.
 To Protect the Transformer from severe damages.
 Time required to rectify the Transformer in case of damages is more and
it is very difficult.
 Operation of a power network when the power transformer is out of
service is always difficult.
 A Power Transformer fault therefore often is a more severe disturbance
for the network than an overhead line fault which usually can be
repaired rather quickly.
Why Protection Required….?
Types of Fault
1. Incipient faults
2. Internal faults
3. External fault
What are causes for the faults in a transformer ?
1. Insulation Breakdown
2. Over heating due to over excitation
3. Oil contamination and leakage
4. Reduced Cooling
5. Phase to phase and Phase to Ground Fault
6. Turn to Turn Fault
7. Transformer Overload
General Scheme of Differential Protection
Protection Functions
 Bias Differential Protection (87)
 Harmonic Restraint Protection
 Over Fluxing i.e V/f Protection (24)
 Over Voltage (59)
 Under Voltage (27)
 Neutral Unbalance (64R)
 Restricted Earth Fault (64REF)
 Back up O/C & E/F (50/51/67)
Operating Characteristics
Calculation for Transformer Differential Protection
Given Details:
Power Transformer Details:
Voltage = 132 / 33KV
Rating = 60MVA
Tap Changer = +5% - 15%
Vector Group = Yd1
Current Transformer Details:
CT Ratio
For HV Side = 300/1
For LV Side = 1200/1
Calculation for Transformer Differential Protection
HV rated current = 60MVA / (132 * 1.732) = 262.4A.
LV rated current = 60MVA / (33* 1.732) = 1049.76A
Mean Tap value = [(+5) + (-15)] / 2 = -5%
HV current at –5% tap = (60MVA) / (1.732 * 132KV *0.95) = 276.2A
HV Multiplier = 300 / 276.2 = 1.086 = 1.09
LV CT secondary current = 1049.7 / 1200 = 0.87475A
So the LV multiplier = 1200 / 1049.7 = 1.143 = 1.14
Initial Setting = 200mA (20%)
Bias setting = Selectable Slope
Bias Slope Limit = 4 times of full load current
HV ICT multiplier = 1.09
LV ICT multiplier = 1.14
Differential Relay Operation
Differential Relay Operation
Differential Relay Operation
Models of Transformer Differential Protection
• ABB (RET 650)
• GE (T60)
• Alstom MiCOM (P632 & P633)
• Siemens (7SA611)
• ERL (T-Pro)
• NR (PCS-9708)
• SIFANG (CSC 326)
Case Study:
100MVA Power Transformer #2 Trip on Restricted Earth
Fault-LV at 220/33kv GSS, Bhu (Jaisalmer)
Incident : Transformer tripped on REF LV. Trip followed by fault in 33kV
feeder.Post tripping checks :
After tripping transformer got isolated from HV & LV and testing started by team to
investigate root cause.
Following test conducted :
1. Meggering done for HV-E, LV-E, HV-LV.
HV-E 16.7G Ohm Good
LV-E 1.18G Ohm Good
HV-LV 500M Ohm Good
Test results normal.
Case Study: Continued
2. REF stability test conducted by 1ph method and found relay pickup for
external fault on LV side. Observation of REF stability are as under:
Voltage applied HV R-ph 230V
Measured current
HV CT Differential core 12mA
HV NCT current 12mA
Current measured at HV REF relay terminal 0.34mA Which is Nearly Zero
LV CT Differential core 12mA
LV NCT current 12mA
Current measured at LV REF relay terminal 12mA
Same observation for Y & B phases.
3. BDV of oil sample collected from top as well as bottom are found ok. Test
values are as below:
BDV Bottom Sample~ 75.7KV,
Top Sample~ 65.1KV
Case Study: Continued
REF Stability Demo:
Case Study: Continued
4. No other protection operated, Buchholz & PRV Healthy.
Conclusion :
From above few points and test results it is concluded that REF LV relay is
sensing current for fault external to transformer i.e. After LV side CT. Hence
REF relay tripped for external fault. After confirming from above tests
transformer considered healthy and there is no internal fault, Transformer
charged by 20:10 hrs.
Thank You

Weitere ähnliche Inhalte

Was ist angesagt?

Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
ashwin fcc
 

Was ist angesagt? (20)

Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Types of relay
Types of relayTypes of relay
Types of relay
 
Transformer vector group_test_conditions
Transformer vector group_test_conditionsTransformer vector group_test_conditions
Transformer vector group_test_conditions
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Transformer Differential Protection Setting Calculations
Transformer Differential Protection Setting CalculationsTransformer Differential Protection Setting Calculations
Transformer Differential Protection Setting Calculations
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Over current protection
Over current protectionOver current protection
Over current protection
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protection
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Differential Relay.pptx
Differential Relay.pptxDifferential Relay.pptx
Differential Relay.pptx
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
 
Unit 05 Protection of feeders and bus-bars
Unit  05 Protection of feeders and bus-bars Unit  05 Protection of feeders and bus-bars
Unit 05 Protection of feeders and bus-bars
 
Differential relay
Differential relayDifferential relay
Differential relay
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
 

Andere mochten auch

Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protection
Binit Das
 
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Sourabh Ghosh
 
Generator protection
Generator protectionGenerator protection
Generator protection
Keshar Rawal
 
Power system protection
Power system protectionPower system protection
Power system protection
Anu Priya
 
PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substation
Ishank Ranjan
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
moiz89
 

Andere mochten auch (20)

Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protection
 
Transformers
TransformersTransformers
Transformers
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protection
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
 
Protection primer
Protection primerProtection primer
Protection primer
 
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
 
Symmetrical and un-symmetrical fault
Symmetrical and un-symmetrical faultSymmetrical and un-symmetrical fault
Symmetrical and un-symmetrical fault
 
Generator protection
Generator protectionGenerator protection
Generator protection
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protection
 
Differential protection of power transformer
Differential protection of power transformerDifferential protection of power transformer
Differential protection of power transformer
 
Relays
RelaysRelays
Relays
 
Protective relay
Protective relay Protective relay
Protective relay
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
 
protection and relay scheme
protection and relay schemeprotection and relay scheme
protection and relay scheme
 
PPt on 220 kV substation
PPt on 220 kV substationPPt on 220 kV substation
PPt on 220 kV substation
 
Over current Relays
Over current RelaysOver current Relays
Over current Relays
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
Basic protection and relaying
Basic protection and relayingBasic protection and relaying
Basic protection and relaying
 

Ähnlich wie Differential protection

HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
Shankar Singh
 
Basiic Electronicss_chapter third-3.pptx
Basiic Electronicss_chapter third-3.pptxBasiic Electronicss_chapter third-3.pptx
Basiic Electronicss_chapter third-3.pptx
ssuser566f62
 

Ähnlich wie Differential protection (20)

industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substation
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
 
Transformer
TransformerTransformer
Transformer
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
 
Untitled document.PDF
Untitled document.PDFUntitled document.PDF
Untitled document.PDF
 
I010246467
I010246467I010246467
I010246467
 
BPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdfBPMI TRANSFORMER PROTECTION.pptx.pdf
BPMI TRANSFORMER PROTECTION.pptx.pdf
 
TRANSFORMER DESIGN.pptx
TRANSFORMER DESIGN.pptxTRANSFORMER DESIGN.pptx
TRANSFORMER DESIGN.pptx
 
Switchgear & Rectifier ppt
Switchgear & Rectifier pptSwitchgear & Rectifier ppt
Switchgear & Rectifier ppt
 
Transformer ppt.
Transformer ppt.Transformer ppt.
Transformer ppt.
 
Aec manual for III SEM ECE Students VTU
Aec manual for III SEM ECE Students VTUAec manual for III SEM ECE Students VTU
Aec manual for III SEM ECE Students VTU
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
 
Transformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisTransformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response Analysis
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.ppt
 
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.ppt
 
Basiic Electronicss_chapter third-3.pptx
Basiic Electronicss_chapter third-3.pptxBasiic Electronicss_chapter third-3.pptx
Basiic Electronicss_chapter third-3.pptx
 
220kv grid wapda town lahore
220kv grid wapda town lahore220kv grid wapda town lahore
220kv grid wapda town lahore
 

Kürzlich hochgeladen

FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 

Kürzlich hochgeladen (20)

Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 

Differential protection

  • 1. Power Transformer Protection Rishi Tandon Assistant Manager – WWO Wind World (India) Limited
  • 2. Introduction  Transformer is a static device used to transform the electrical energy from one alternating current circuit to another without any change in frequency.  Power Transformer is a vital link in a power transmission system and distribution  A Power Transformer is an expensive part of a power network.  The impact of a transformer outage due to fault is more serious than a transmission line outage.
  • 3.  To Protect the Transformer from severe damages.  Time required to rectify the Transformer in case of damages is more and it is very difficult.  Operation of a power network when the power transformer is out of service is always difficult.  A Power Transformer fault therefore often is a more severe disturbance for the network than an overhead line fault which usually can be repaired rather quickly. Why Protection Required….?
  • 4. Types of Fault 1. Incipient faults 2. Internal faults 3. External fault What are causes for the faults in a transformer ? 1. Insulation Breakdown 2. Over heating due to over excitation 3. Oil contamination and leakage 4. Reduced Cooling 5. Phase to phase and Phase to Ground Fault 6. Turn to Turn Fault 7. Transformer Overload
  • 5. General Scheme of Differential Protection
  • 6. Protection Functions  Bias Differential Protection (87)  Harmonic Restraint Protection  Over Fluxing i.e V/f Protection (24)  Over Voltage (59)  Under Voltage (27)  Neutral Unbalance (64R)  Restricted Earth Fault (64REF)  Back up O/C & E/F (50/51/67)
  • 8. Calculation for Transformer Differential Protection Given Details: Power Transformer Details: Voltage = 132 / 33KV Rating = 60MVA Tap Changer = +5% - 15% Vector Group = Yd1 Current Transformer Details: CT Ratio For HV Side = 300/1 For LV Side = 1200/1
  • 9. Calculation for Transformer Differential Protection HV rated current = 60MVA / (132 * 1.732) = 262.4A. LV rated current = 60MVA / (33* 1.732) = 1049.76A Mean Tap value = [(+5) + (-15)] / 2 = -5% HV current at –5% tap = (60MVA) / (1.732 * 132KV *0.95) = 276.2A HV Multiplier = 300 / 276.2 = 1.086 = 1.09 LV CT secondary current = 1049.7 / 1200 = 0.87475A So the LV multiplier = 1200 / 1049.7 = 1.143 = 1.14 Initial Setting = 200mA (20%) Bias setting = Selectable Slope Bias Slope Limit = 4 times of full load current HV ICT multiplier = 1.09 LV ICT multiplier = 1.14
  • 13. Models of Transformer Differential Protection • ABB (RET 650) • GE (T60) • Alstom MiCOM (P632 & P633) • Siemens (7SA611) • ERL (T-Pro) • NR (PCS-9708) • SIFANG (CSC 326)
  • 14. Case Study: 100MVA Power Transformer #2 Trip on Restricted Earth Fault-LV at 220/33kv GSS, Bhu (Jaisalmer) Incident : Transformer tripped on REF LV. Trip followed by fault in 33kV feeder.Post tripping checks : After tripping transformer got isolated from HV & LV and testing started by team to investigate root cause. Following test conducted : 1. Meggering done for HV-E, LV-E, HV-LV. HV-E 16.7G Ohm Good LV-E 1.18G Ohm Good HV-LV 500M Ohm Good Test results normal.
  • 15. Case Study: Continued 2. REF stability test conducted by 1ph method and found relay pickup for external fault on LV side. Observation of REF stability are as under: Voltage applied HV R-ph 230V Measured current HV CT Differential core 12mA HV NCT current 12mA Current measured at HV REF relay terminal 0.34mA Which is Nearly Zero LV CT Differential core 12mA LV NCT current 12mA Current measured at LV REF relay terminal 12mA Same observation for Y & B phases. 3. BDV of oil sample collected from top as well as bottom are found ok. Test values are as below: BDV Bottom Sample~ 75.7KV, Top Sample~ 65.1KV
  • 16. Case Study: Continued REF Stability Demo:
  • 17. Case Study: Continued 4. No other protection operated, Buchholz & PRV Healthy. Conclusion : From above few points and test results it is concluded that REF LV relay is sensing current for fault external to transformer i.e. After LV side CT. Hence REF relay tripped for external fault. After confirming from above tests transformer considered healthy and there is no internal fault, Transformer charged by 20:10 hrs.