SlideShare ist ein Scribd-Unternehmen logo
1 von 20
Substation
Neutral
Earthing
Distribution systems are earthed to create a reference point for the
system voltage, to facilitate the detection and discriminative isolation
of faults involving contact to earth, and to limit over-voltages under
transient conditions.
A neutral earthing system is a system in which the neutral is connected
to earth, either solidly, or through a resistance or reactance of value
sufficient to materially reduce transients, and to give sufficient current
for selective earth fault protection devices to operate.
Sensitive fault detectors allow the reduction of fault currents to very
low values.
Unearthed neutrals were used in the past due to the fact that the first
earth fault did not require tripping of the system. An unscheduled
shutdown on the first earth fault was
particularly undesirable for industries
that were based on continuous
processes and where continuation
of the supply even under single fault
conditions was necessary.
Although achieving the initial goal,
the unearthed system provided no
control of transient over-voltages.
Neutral earthing systems are similar to fuses in that they do nothing until
something in the system goes wrong. Then, like fuses, they protect personnel and
equipment from damage.
Damage comes from two factors, how long the fault lasts and how large the fault
current is. Earth fault relays trip breakers and limit how long a fault lasts and
neutral earthing resistors limit how large the fault current is.
There are Five Methods of Neutral Earthing:
•Unearthed neutral system
•Solid neutral earthed system
•Resistance neutral earthing system
o Low resistance earthing
o High resistance earthing
•Resonant neutral earthing system
•Transformer earthing system
Unearthed Systems
In a unearthed neutral system there is no internal connection between the
conductors and earth. However capacative coupling exists between the system
conductors and the adjacent earthed surfaces. Consequently, the “unearthed
system” is, in reality, a “capacative earthed system” by virtue of the distributed
capacitance.
As a result, this series resonant
L-C circuit can create over-voltages
well in excess of line-to-line voltage
when subjected to repetitive re-strikes
of one phase to earth.
This in turn, reduces insulation life
resulting in possible equipment failure
(Fig.1).
Under normal operating conditions, this distributed capacitance causes no
problems. In fact, it is beneficial because it establishes, in effect, a neutral point
for the system. As a result, the phase conductors are stressed at only line-to-
neutral voltage above earth potential.
But problems can rise in earth fault conditions.
A earth fault on one line results in full
line-to-line voltage appearing throughout the
system, between the conductors and earthed
surfaces.
Thus, a voltage 1,73 times the normal voltage
is present on all insulation in the system.
This situation can often cause failures in
transformers, due to insulation breakdown.
Solidly Earthed Systems
In a solidly earthed system, the neutral point is connected directly to earth, either
directly or via a virtual neutral transformer. Generally all LV systems are solidly
earthed. For MV and HV systems, solid earthing is the cheapest method but has a
number of serious drawbacks.
•High fault currents with resultant damage to plant
•High current will cause tripping of all phases
Neutral earthing resistors are used to limit the fault current in transformers When
a phase to earth occurs, the fault current is limited only by the soil resistance.
This current, which can be very high, can damage the windings.
Low voltage networks are generally solidly earthed and resistive neutral earthing
is generally only applied to MV and HV lines.
Resistive Earthed Systems
The main reasons for limiting the phase to earth current by resistance earthing
are:
•To reduce burning and melting effects in faulted electrical equipment such
as switchgear, transformers, cables.
•To reduce mechanical stresses in circuits/equipment carrying fault currents.
•To reduce electrical-shock hazards to personnel caused by stray earth fault.
•To reduce the arc blast or flash hazard.
•To reduce the momentary line-voltage dip.
•To secure control of the transient over-voltages
while at the same time.
•To improve the detection of the earth fault in a
power system.
Fig. 2: A solidly earthed system [4].
Earthing resistors are generally connected between earth and the neutral of
substation transformers, (Fig. 3), to limit maximum fault current to a value which
will not damage equipment, while allowing sufficient fault current to
operate earth fault protective relays. Although it is possible to limit fault currents
with high resistance neutral earthing resistors, earth short circuit currents may be
extremely reduced and protection devices may not sense the fault.
Fig. 3: Resistive neutral earthing [4].
It is common to limit single phase fault
currents with low resistance neutral earthing
resistors to approximately the rated current of
the transformer. In addition, limiting fault
currents to predetermined maximum values
permits selective coordination of protective
devices, which minimises system disruption
and allows for quick location of faults.
Earthing resistance can be classified into high and low value types. The resistance
is also categorised on the basis of time they can withstand the fault current.
Typical durations are 1 s, 10 s, 1 min and 10 min rating. The extended time rating
resistor is used in systems where the reliability of the system is critical. In these
situations, a high resistance which can sustain the fault for a long period is used.
When an earth fault occurs of one phase, an alarm is generated. However, the
system continues to run until the next scheduled shutdown.
Earth fault current flowing through either type of resistor when a single phase
faults to earth will increase the phase-to-earth voltage of the remaining two
phases. As a result, conductor insulation and surge arrestor ratings must be based
on line-to-line voltage. This temporary increase in phase-to-earth voltage should
also be considered when selecting two and three pole breakers installed on
resistance earthed low voltage systems
High Resistance Neutral Earthing Systems
High resistance earthing systems are designed for limiting phase-to-earth fault
currents in distribution systems by using a neutral earthed resistor between the
transformer or generator neutral and earth. With this type of system earthing
there is no need to trip the corresponding circuit breaker in the case of a phase-
to-earth fault.
The system will only provide an
alarm while the faulted feeder remains
operational until the fault is located and
cleared. This functionality is required in
certain electrical applications where
the risks associated to interrupting the
electrical service are higher than the
risk of letting the system run with a
phase-to-earth fault limited by the resistor. Fig. 4: Delta star transformer earthing [4].
Besides preventing the feeder from tripping by limiting the fault current, some
of the advantages of a High Resistance earthing system include:
•Transient overvoltages are reduced
•Arc flash risks are diminished
•Fault location is easily accomplished
The disadvantage is that, in case of single earth fault, the voltage at the two other
healthy phases tends to reach the value of the line-to-line voltage, depending on
the relation between zero and direct sequence impedance seen from the fault.
This rise in phase voltage increases the probability of a second earth fault in a
different phase and a different feeder.
In this case, a phase-to-earth-to-phase fault current will flow with a
magnitude limited by:
•The total impedance of the earth path
•The possible occurrence of an arc flash
The neutral earthing resistor cannot limit the magnitude of this fault because the
resistor is outside of its trajectory. The fault will evolve until being finally cut off
by the overcurrent protection of the feeders involved, and the risks associated to
a sudden interruption will not be avoided. Second Earth Fault Protection
Systems have been developed to prevent this situation by tripping only one of
the feeders, the one with the lowest priority, in the event of a second phase-to-
earth fault, leaving the rest of the system operational with only a phase-to-earth
fault limited in magnitude by the neutral earthing resistor.
Coordination with circuit breakers’ overcurrent protection and priority settings
are important considerations. If the second phase-to-earth fault in a different
phase occurs in the same feeder that had the initial fault the second earth fault
protection system will not operate, leaving the responsibility for tripping or
disconnecting the feeder to the circuit breaker’s overcurrent protection or fuses.
Fig. 5: Zig-zag transformer neutral earthing [4].
Low Resistance Neutral Earthing
Systems
Low resistance earthing is used in
large MV/HV electrical networks
where there is a high level of capital
equipment and network interruptions
have a significant economic impact.
These NERs are generally sized to
limit the fault current to a level
enough to operate protective devices
yet not enough to create major
damage at the fault point.
Earthing via a Transformer or Neutral Electromagnetic Coupler (NEC)
Where the neutral point is not available, an artificial earth can be created by
using a transformer. The earthing transformer is used to provide a path to an
unearthed system or when the system neutral is not available for some reason,
for example, when a system is delta connected. It provides a low impedance path
to the neutral and also limits the transient overvoltage when the earth faults
occur in the system. The earthing of the system can be done in the following
way:
Delta-Star Earthing Transformer
In a case of delta-star earthing transformer, the delta side is closed to provide a
path for zero-sequence current. The star winding must be of the same voltage
rating as the circuit that is to be earthed, whereas the delta voltage rating can be
chosen to be any standard voltage level.
Fig. 6: The Petersen coil system [4].
Zig-zag Transformer
A zig-zag transformer can be used for
providing earthing on the transformer. It
provides insulation between the earth and
the component so that the system
component may not be affected by the fault
currents. The zig-zag transformer cancels
out the harmonics of the power system. It
also protects the power system by reducing
the stress of the voltage under a fault
condition. The zig-zag transformer has no
secondary winding. It is a three-limbed
(branched) transformer where each limb has
two identical windings. One set of windings
is connected in the star to provide the
neutral point.
Resonant Earthed Neutral
Fault currents can also be reduced by
earthing the neutral through an inductive
impedance. Adding inductive reactance from
the system neutral point to earth is an easy
method of limiting the available earth fault
from something near the maximum 3-phase
short circuit capacity to a relatively low
value.
To limit the reactive part of the earth fault
current in a power system a neutral point
reactor can be connected between the
transformer neutral and the station earthing
system.
Fig. 7: Plunger type NERC (Trench).
Petersen Coil Earthing
A Peterson coil is an adjustable iron cored reactor used to neutralise the capacitive earth fault current in
a power system. When a phase-to-earth fault occurs in unearthed 3-phase systems, the phase voltage of
the faulty phase is reduced to the earth potential as the capacitance of the faulty line is discharged at the
fault location, the phase-to-earth voltage of the other two phases rises by √3 times. A charging current
occurs between these phase-to-earth capacitances, which will continue to flow via the fault path while it
remains.
A modern steplessly adjustable Petersen coil consists of an iron-cored reactor connected between the
star point of the substation transformer and earth in a three-phase system. In the event of a fault, the
capacative earth fault current (Ir +Iy) is now neutralised by the current in the reactor (Ir) as this is equal
in magnitude, but 180° out-of-phase. Petersen coils adjust automatically to compensate for the earth
fault current. Fig. 7 shows a plunger type adjustable Petersen coil.
The value of the inductance in the Petersen coil needs to match the value of the network capacitance
which may vary, as and when switching in the network is carried out. Modern coil controllers
continually monitor the zero-sequence voltage and detect any change which occurs. When there is a
change in the network capacitance, the controller auto-tunes the Petersen coil to this new level to ensure
that it is tuned to the correct point to immediately neutralise any earth fault which may occur. This rapid
earth fault current limiting occurs automatically without any further intervention from the system [2].
The Petersen coil may also be referred to as an arc
suppression coil (ASC).
Technology and Design
Liquid neutral earthing resistors (LNER)
The design of a liquid neutral earthing resistor
is a large tank containing an electrolyte
solution (distilled water with a small amount of
electrolytic powder).(Fig.8) The outer case of
the tank is connected solidly to the earth point.
An inner electrode which is insulated from the
tank, provides the connection to the
transformer neutral point.
At commissioning, small amounts of
electrolyte are added to the water to increase
the conductivity of the solution until it reaches
the calibrated resistance level. The final result
is a high current carrying capacity fluid with a
high resistance, in a very robust and low
maintenance package.
The LNER has a fixed structure as
opposed to the more familiar liquid starter
resistors or rheostats, and is therefore
simpler to construct and calibrate.
The amount of liquid in the tank provides
a high heat absorption capacity. Problems
with LNERs include a wide tolerance on
ohmic values , and the necessity to
recalibrate at regular intervals.
Fig. 9: Solid earthing resistor (Postglover).
Solid Earthing Resistors
Solid neutral earthing resistors consist of coils of resistive material wound on insulators. The
resistor uses unforced air cooling, and carful design is required to ensure that temperature limits
are not exceeded. Resistive material is usually stainless steel or some other alloy.
The solid earthing resistor may include a current transformer to drive a protection device. The
current transformer is required to withstand the fault current. However in the case of resistive
earthing, the fault current is greatly reduced and the design of the CT is not so severe.

Weitere ähnliche Inhalte

Was ist angesagt?

FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONPower System Operation
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptxMuhd Hafizi Idris
 
switchgear and protection by vala kamlesh
switchgear and protection by vala kamleshswitchgear and protection by vala kamlesh
switchgear and protection by vala kamleshKamlesh Vala
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltageMuhammedArifTanoli
 
Power quality 1341013148
Power quality 1341013148Power quality 1341013148
Power quality 1341013148Pradosh Dhal
 
Insulation coordination.
Insulation coordination.Insulation coordination.
Insulation coordination.Parth Patel
 
Thyristor switched capacitor PPT
Thyristor switched capacitor PPTThyristor switched capacitor PPT
Thyristor switched capacitor PPTKLS' S GIT, BELGAUM
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guideSlides Hub
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in briefMuthar Hussain
 
Protective relay
Protective relay Protective relay
Protective relay Uday Wankar
 
Switchgear Equipment in a Substation
Switchgear Equipment in a SubstationSwitchgear Equipment in a Substation
Switchgear Equipment in a SubstationMd. Atiqur Rahman
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.Hemendra Kumar Rajput
 

Was ist angesagt? (20)

FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Earthing system
Earthing system   Earthing system
Earthing system
 
switchgear and protection by vala kamlesh
switchgear and protection by vala kamleshswitchgear and protection by vala kamlesh
switchgear and protection by vala kamlesh
 
Underground cables vs overhead lines
Underground cables vs overhead linesUnderground cables vs overhead lines
Underground cables vs overhead lines
 
Protection against over voltage
Protection against over voltageProtection against over voltage
Protection against over voltage
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Unit commitment
Unit commitmentUnit commitment
Unit commitment
 
Power quality 1341013148
Power quality 1341013148Power quality 1341013148
Power quality 1341013148
 
Insulation coordination.
Insulation coordination.Insulation coordination.
Insulation coordination.
 
Thyristor switched capacitor PPT
Thyristor switched capacitor PPTThyristor switched capacitor PPT
Thyristor switched capacitor PPT
 
Unit 1-2-a
Unit 1-2-aUnit 1-2-a
Unit 1-2-a
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
 
Faults in Power System.pptx
Faults in Power System.pptxFaults in Power System.pptx
Faults in Power System.pptx
 
surge arrester
surge arrestersurge arrester
surge arrester
 
Protective relay
Protective relay Protective relay
Protective relay
 
Switchgear Equipment in a Substation
Switchgear Equipment in a SubstationSwitchgear Equipment in a Substation
Switchgear Equipment in a Substation
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.
 

Ähnlich wie Substation Neutral Earthing

High voltage grounding methods
High voltage grounding methods High voltage grounding methods
High voltage grounding methods Adnan Khan
 
Earthing of epg
Earthing  of epg Earthing  of epg
Earthing of epg marwadi
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGDr. Rohit Babu
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2Dr. Rohit Babu
 
Multi – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptxMulti – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptxMarlonAgustin3
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protectionMahesh Chandra Manav
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformerRitesh Verma
 
Neutral Grounding Resistors
Neutral Grounding ResistorsNeutral Grounding Resistors
Neutral Grounding ResistorsElifAksoy13
 
Neutral Grounding
Neutral GroundingNeutral Grounding
Neutral GroundingNoman Nomi
 
GOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.pptGOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.pptsqhuet1
 
GOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.pptGOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.pptganesh2428364
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the LightningAmeen San
 
Power system earthing.pptx
Power system earthing.pptxPower system earthing.pptx
Power system earthing.pptxSrinivas Yadav
 
Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Muhammad Zaeem Sarfraz
 

Ähnlich wie Substation Neutral Earthing (20)

High voltage grounding methods
High voltage grounding methods High voltage grounding methods
High voltage grounding methods
 
s.pdf
s.pdfs.pdf
s.pdf
 
Earthing of epg
Earthing  of epg Earthing  of epg
Earthing of epg
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
 
Multi – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptxMulti – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptx
 
Presentation best practice earthing and protection
Presentation   best practice earthing and protectionPresentation   best practice earthing and protection
Presentation best practice earthing and protection
 
Presentation jmv internal
Presentation jmv internalPresentation jmv internal
Presentation jmv internal
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
Neutral Grounding Resistors
Neutral Grounding ResistorsNeutral Grounding Resistors
Neutral Grounding Resistors
 
Neutral Grounding
Neutral GroundingNeutral Grounding
Neutral Grounding
 
Transient Suppressors
Transient SuppressorsTransient Suppressors
Transient Suppressors
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
GOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.pptGOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.ppt
 
GOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.pptGOOD GROUNDING PRACTICES.ppt
GOOD GROUNDING PRACTICES.ppt
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
 
Power system earthing.pptx
Power system earthing.pptxPower system earthing.pptx
Power system earthing.pptx
 
Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)
 
Conexiones cross bonding
Conexiones cross bondingConexiones cross bonding
Conexiones cross bonding
 

Mehr von Power System Operation

Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panelsPower System Operation
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsPower System Operation
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action SchemePower System Operation
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...Power System Operation
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & PartsPower System Operation
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools Power System Operation
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy SystemPower System Operation
 
SCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data AcquisitionSCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data AcquisitionPower System Operation
 

Mehr von Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 
SCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data AcquisitionSCADA System ? Supervisory Control & Data Acquisition
SCADA System ? Supervisory Control & Data Acquisition
 

Kürzlich hochgeladen

Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 

Kürzlich hochgeladen (20)

★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 

Substation Neutral Earthing

  • 2. Distribution systems are earthed to create a reference point for the system voltage, to facilitate the detection and discriminative isolation of faults involving contact to earth, and to limit over-voltages under transient conditions. A neutral earthing system is a system in which the neutral is connected to earth, either solidly, or through a resistance or reactance of value sufficient to materially reduce transients, and to give sufficient current for selective earth fault protection devices to operate. Sensitive fault detectors allow the reduction of fault currents to very low values.
  • 3. Unearthed neutrals were used in the past due to the fact that the first earth fault did not require tripping of the system. An unscheduled shutdown on the first earth fault was particularly undesirable for industries that were based on continuous processes and where continuation of the supply even under single fault conditions was necessary. Although achieving the initial goal, the unearthed system provided no control of transient over-voltages.
  • 4. Neutral earthing systems are similar to fuses in that they do nothing until something in the system goes wrong. Then, like fuses, they protect personnel and equipment from damage. Damage comes from two factors, how long the fault lasts and how large the fault current is. Earth fault relays trip breakers and limit how long a fault lasts and neutral earthing resistors limit how large the fault current is. There are Five Methods of Neutral Earthing: •Unearthed neutral system •Solid neutral earthed system •Resistance neutral earthing system o Low resistance earthing o High resistance earthing •Resonant neutral earthing system •Transformer earthing system
  • 5. Unearthed Systems In a unearthed neutral system there is no internal connection between the conductors and earth. However capacative coupling exists between the system conductors and the adjacent earthed surfaces. Consequently, the “unearthed system” is, in reality, a “capacative earthed system” by virtue of the distributed capacitance. As a result, this series resonant L-C circuit can create over-voltages well in excess of line-to-line voltage when subjected to repetitive re-strikes of one phase to earth. This in turn, reduces insulation life resulting in possible equipment failure (Fig.1).
  • 6. Under normal operating conditions, this distributed capacitance causes no problems. In fact, it is beneficial because it establishes, in effect, a neutral point for the system. As a result, the phase conductors are stressed at only line-to- neutral voltage above earth potential. But problems can rise in earth fault conditions. A earth fault on one line results in full line-to-line voltage appearing throughout the system, between the conductors and earthed surfaces. Thus, a voltage 1,73 times the normal voltage is present on all insulation in the system. This situation can often cause failures in transformers, due to insulation breakdown.
  • 7. Solidly Earthed Systems In a solidly earthed system, the neutral point is connected directly to earth, either directly or via a virtual neutral transformer. Generally all LV systems are solidly earthed. For MV and HV systems, solid earthing is the cheapest method but has a number of serious drawbacks. •High fault currents with resultant damage to plant •High current will cause tripping of all phases Neutral earthing resistors are used to limit the fault current in transformers When a phase to earth occurs, the fault current is limited only by the soil resistance. This current, which can be very high, can damage the windings. Low voltage networks are generally solidly earthed and resistive neutral earthing is generally only applied to MV and HV lines.
  • 8. Resistive Earthed Systems The main reasons for limiting the phase to earth current by resistance earthing are: •To reduce burning and melting effects in faulted electrical equipment such as switchgear, transformers, cables. •To reduce mechanical stresses in circuits/equipment carrying fault currents. •To reduce electrical-shock hazards to personnel caused by stray earth fault. •To reduce the arc blast or flash hazard. •To reduce the momentary line-voltage dip. •To secure control of the transient over-voltages while at the same time. •To improve the detection of the earth fault in a power system. Fig. 2: A solidly earthed system [4].
  • 9. Earthing resistors are generally connected between earth and the neutral of substation transformers, (Fig. 3), to limit maximum fault current to a value which will not damage equipment, while allowing sufficient fault current to operate earth fault protective relays. Although it is possible to limit fault currents with high resistance neutral earthing resistors, earth short circuit currents may be extremely reduced and protection devices may not sense the fault. Fig. 3: Resistive neutral earthing [4]. It is common to limit single phase fault currents with low resistance neutral earthing resistors to approximately the rated current of the transformer. In addition, limiting fault currents to predetermined maximum values permits selective coordination of protective devices, which minimises system disruption and allows for quick location of faults.
  • 10. Earthing resistance can be classified into high and low value types. The resistance is also categorised on the basis of time they can withstand the fault current. Typical durations are 1 s, 10 s, 1 min and 10 min rating. The extended time rating resistor is used in systems where the reliability of the system is critical. In these situations, a high resistance which can sustain the fault for a long period is used. When an earth fault occurs of one phase, an alarm is generated. However, the system continues to run until the next scheduled shutdown. Earth fault current flowing through either type of resistor when a single phase faults to earth will increase the phase-to-earth voltage of the remaining two phases. As a result, conductor insulation and surge arrestor ratings must be based on line-to-line voltage. This temporary increase in phase-to-earth voltage should also be considered when selecting two and three pole breakers installed on resistance earthed low voltage systems
  • 11. High Resistance Neutral Earthing Systems High resistance earthing systems are designed for limiting phase-to-earth fault currents in distribution systems by using a neutral earthed resistor between the transformer or generator neutral and earth. With this type of system earthing there is no need to trip the corresponding circuit breaker in the case of a phase- to-earth fault. The system will only provide an alarm while the faulted feeder remains operational until the fault is located and cleared. This functionality is required in certain electrical applications where the risks associated to interrupting the electrical service are higher than the risk of letting the system run with a phase-to-earth fault limited by the resistor. Fig. 4: Delta star transformer earthing [4].
  • 12. Besides preventing the feeder from tripping by limiting the fault current, some of the advantages of a High Resistance earthing system include: •Transient overvoltages are reduced •Arc flash risks are diminished •Fault location is easily accomplished The disadvantage is that, in case of single earth fault, the voltage at the two other healthy phases tends to reach the value of the line-to-line voltage, depending on the relation between zero and direct sequence impedance seen from the fault. This rise in phase voltage increases the probability of a second earth fault in a different phase and a different feeder. In this case, a phase-to-earth-to-phase fault current will flow with a magnitude limited by: •The total impedance of the earth path •The possible occurrence of an arc flash
  • 13. The neutral earthing resistor cannot limit the magnitude of this fault because the resistor is outside of its trajectory. The fault will evolve until being finally cut off by the overcurrent protection of the feeders involved, and the risks associated to a sudden interruption will not be avoided. Second Earth Fault Protection Systems have been developed to prevent this situation by tripping only one of the feeders, the one with the lowest priority, in the event of a second phase-to- earth fault, leaving the rest of the system operational with only a phase-to-earth fault limited in magnitude by the neutral earthing resistor. Coordination with circuit breakers’ overcurrent protection and priority settings are important considerations. If the second phase-to-earth fault in a different phase occurs in the same feeder that had the initial fault the second earth fault protection system will not operate, leaving the responsibility for tripping or disconnecting the feeder to the circuit breaker’s overcurrent protection or fuses.
  • 14. Fig. 5: Zig-zag transformer neutral earthing [4]. Low Resistance Neutral Earthing Systems Low resistance earthing is used in large MV/HV electrical networks where there is a high level of capital equipment and network interruptions have a significant economic impact. These NERs are generally sized to limit the fault current to a level enough to operate protective devices yet not enough to create major damage at the fault point.
  • 15. Earthing via a Transformer or Neutral Electromagnetic Coupler (NEC) Where the neutral point is not available, an artificial earth can be created by using a transformer. The earthing transformer is used to provide a path to an unearthed system or when the system neutral is not available for some reason, for example, when a system is delta connected. It provides a low impedance path to the neutral and also limits the transient overvoltage when the earth faults occur in the system. The earthing of the system can be done in the following way: Delta-Star Earthing Transformer In a case of delta-star earthing transformer, the delta side is closed to provide a path for zero-sequence current. The star winding must be of the same voltage rating as the circuit that is to be earthed, whereas the delta voltage rating can be chosen to be any standard voltage level.
  • 16. Fig. 6: The Petersen coil system [4]. Zig-zag Transformer A zig-zag transformer can be used for providing earthing on the transformer. It provides insulation between the earth and the component so that the system component may not be affected by the fault currents. The zig-zag transformer cancels out the harmonics of the power system. It also protects the power system by reducing the stress of the voltage under a fault condition. The zig-zag transformer has no secondary winding. It is a three-limbed (branched) transformer where each limb has two identical windings. One set of windings is connected in the star to provide the neutral point.
  • 17. Resonant Earthed Neutral Fault currents can also be reduced by earthing the neutral through an inductive impedance. Adding inductive reactance from the system neutral point to earth is an easy method of limiting the available earth fault from something near the maximum 3-phase short circuit capacity to a relatively low value. To limit the reactive part of the earth fault current in a power system a neutral point reactor can be connected between the transformer neutral and the station earthing system. Fig. 7: Plunger type NERC (Trench).
  • 18. Petersen Coil Earthing A Peterson coil is an adjustable iron cored reactor used to neutralise the capacitive earth fault current in a power system. When a phase-to-earth fault occurs in unearthed 3-phase systems, the phase voltage of the faulty phase is reduced to the earth potential as the capacitance of the faulty line is discharged at the fault location, the phase-to-earth voltage of the other two phases rises by √3 times. A charging current occurs between these phase-to-earth capacitances, which will continue to flow via the fault path while it remains. A modern steplessly adjustable Petersen coil consists of an iron-cored reactor connected between the star point of the substation transformer and earth in a three-phase system. In the event of a fault, the capacative earth fault current (Ir +Iy) is now neutralised by the current in the reactor (Ir) as this is equal in magnitude, but 180° out-of-phase. Petersen coils adjust automatically to compensate for the earth fault current. Fig. 7 shows a plunger type adjustable Petersen coil. The value of the inductance in the Petersen coil needs to match the value of the network capacitance which may vary, as and when switching in the network is carried out. Modern coil controllers continually monitor the zero-sequence voltage and detect any change which occurs. When there is a change in the network capacitance, the controller auto-tunes the Petersen coil to this new level to ensure that it is tuned to the correct point to immediately neutralise any earth fault which may occur. This rapid earth fault current limiting occurs automatically without any further intervention from the system [2].
  • 19. The Petersen coil may also be referred to as an arc suppression coil (ASC). Technology and Design Liquid neutral earthing resistors (LNER) The design of a liquid neutral earthing resistor is a large tank containing an electrolyte solution (distilled water with a small amount of electrolytic powder).(Fig.8) The outer case of the tank is connected solidly to the earth point. An inner electrode which is insulated from the tank, provides the connection to the transformer neutral point. At commissioning, small amounts of electrolyte are added to the water to increase the conductivity of the solution until it reaches the calibrated resistance level. The final result is a high current carrying capacity fluid with a high resistance, in a very robust and low maintenance package.
  • 20. The LNER has a fixed structure as opposed to the more familiar liquid starter resistors or rheostats, and is therefore simpler to construct and calibrate. The amount of liquid in the tank provides a high heat absorption capacity. Problems with LNERs include a wide tolerance on ohmic values , and the necessity to recalibrate at regular intervals. Fig. 9: Solid earthing resistor (Postglover). Solid Earthing Resistors Solid neutral earthing resistors consist of coils of resistive material wound on insulators. The resistor uses unforced air cooling, and carful design is required to ensure that temperature limits are not exceeded. Resistive material is usually stainless steel or some other alloy. The solid earthing resistor may include a current transformer to drive a protection device. The current transformer is required to withstand the fault current. However in the case of resistive earthing, the fault current is greatly reduced and the design of the CT is not so severe.