                                    Confidential Inspection Report
                                                  For Sample Report
                                                  12345 Your Street
                                               Newport Beach, California
                                                   Date 01/05/2010




                                          Prepared by: Building Specs Inc.
                                      34145 Pacific Coast Highyway; Suite 513
                                               Dana Point, Ca 92629
                                     949-494-5624 Info@buildingspecscorp.com


This report is the exclusive property of the inspection company and the client whose name appears herewith and
                                its use by any unauthorized persons is prohibited.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                        Page1
34145 Pacific Coast Highway Suite 513
                                                                                                 Dana Point CA 92629
                                                                                                 p 949.466.7265 f 661.0581
                                                                                                 www.buildingspecscorp.com



                                          Report Table of Contents

GENERAL INFORMATION                                                                                                     9
GROUNDS                                                                                                                 10
FOUNDATION & STRUCTURE                                                                                                  11
EXTERIOR SURFACES                                                                                                       12
ROOFS                                                                                                                   13
DOORS, WINDOWS, ENERGY CONSERVATION                                                                                     14
ATTIC                                                                                                                   14
GARAGE & CARPORT                                                                                                        16
SAFETY                                                                                                                  17
KITCHEN & APPLIANCES                                                                                                    18
BATHROOM(s)                                                                                                             20
INTERIOR                                                                                                                21
ELECTRICAL                                                                                                              24
PLUMBING                                                                                                                25
HEATING & COOLING SYSTEMS                                                                                               26
FIREPLACE/CHIMNEY/ENVIRONMENTAL OVERVIEW                                                                                27
POOL/SPA & EQUIPMENT                                                                                                    28




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                        Page2
34145 Pacific Coast Highway Suite 513
                                                                                                 Dana Point CA 92629
                                                                                                 p 949.466.7265 f 661.0581
                                                                                                 www.buildingspecscorp.com




                                                  Inspection Report
                                                     For Sample Report
                                                     12345 Your Street
                                                  Newport Beach, California
                                                      Date 01/05/2010

As requested, we have performed a property inspection report for the address above.

Thank you for choosing BUILDING SPECS INC. to perform a visual inspection on the above property. We've taken great
pride developing a reporting system we feel is unique to the industry. It's with pleasure that we submit it to you at this time.
You are encouraged to read the entire report, as it will give you a detailed overview of the general condition of the property.

Please understand an inspection is intended to assist you in evaluating the overall condition of the property. The inspection
report is an aid to help you make a more informed purchasing decision. Also understand that there are limitations to this
inspection. Many components of the building are not visible during the inspection and very little historical information is
provided in advance of the inspection. While we can reduce your risk of purchasing the building, we cannot eliminate it, nor
can we assume it. Even the most comprehensive inspection cannot be expected to reveal every condition you may
consider significant to ownership. The inspection is based on observation of the visible and apparent condition of the
building and its components on the date of the inspection. It is not intended to make any representation regarding latent or
concealed defects that may exist. It is not intended for cosmetic or aesthetic evaluation.

Photographs, when provided, are simply a tool to convey our findings, they are not intended to enhance those findings or
diminish any findings not photographed.

BUILDING SPECS, INC. follows the standards of practice and code of ethics established by the California Real Estate
Inspection Association. These can be reviewed at www.creia.org/i4a/pages/index.cfm?pageid=3283

If you have any questions regarding this report or the condition of the property, please feel free to call anytime.

Rick Yerger
BUILDING SPECS, INC




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                        Page3
34145 Pacific Coast Highway Suite 513
                                                                                                 Dana Point CA 92629
                                                                                                 p 949.466.7265 f 661.0581
                                                                                                 www.buildingspecscorp.com



Inspection Summary NOTENOTENOTE: Client Must Read Entire Report And Not Rely Solely On The
                                                      Summary Notes. Clien summary notes.

CLIENT:       Sample Report
INSPECTION ADDRESS:         12345 Your Street Newport Beach, California

PRIORITY #1 MAJOR:           Immediate repairs, service, upgrades and/or Further Evaluation recommended by the
                          appropriate licensed contractor and/or appropriate professional prior to close of escrow.

GENERAL INFORMATION
      101] INSPECTION:
      1.4 Overall Building Condition;
      What may be possible modifications to building. Client is advised to request all documentation and building permits
      for work observed. If no documentation is available the client should be aware these components may not have been
      properly installed and may pose adverse conditions.

         Bedroom(s)

GROUNDS
      206] LANDSCAPE PLANTERS
      2.10 Observations:
      Substandard fabrication. Concern for moisture infiltration. Planter is raised above interior floor line and tight against
      exterior wall. lacking capillary break (air space). Located Rear Side of Building.

         215] AUXILIARY STRUCTURES (Outside the scope of our inspection. Consult with specialist for operation &
         maintenance)
         2.20 Observations:
         Loose, Tip Concern. Recommend verifying fountains are mechanically secured for safety. Substandard Electrical
         Wiring. Extension cord or exposed wiring. Located Rear Side of Building.

EXTERIOR SURFACES
       500] SIDING MATERIAL
       4.1 Conditions Noted:
       At or Below Grade, Susceptible to Rot and or Wood Destroying Insect Damage, Located Left Side of Building,
       Located Rear Side of Building.

         505] SOFFIT
         4.10 Observations:
         Water Stains , suggests possible roof leak. Located Front Side of Building.

         509] ELECTRICAL
         4.11 Observations:
         Substandard hazardous Wring several locations, Located Rear Side of Building. Receptacles- Recommended GFCI,
         Located Rear Side of Building.

ROOFS
         600] ROOF
         5.1 General Comments:
         Repairs Recommended, Recommend Further Evaluation by a Qualified Roofing Contractor. Client is advised to Have
      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                        Page4
34145 Pacific Coast Highway Suite 513
                                                                                                 Dana Point CA 92629
                                                                                                 p 949.466.7265 f 661.0581
                                                                                                 www.buildingspecscorp.com


         Roof and all Related components Evaluation by Roofing Contractor Prior to Purchase.


         608] TILE/ SLATE
         5.4 Observations:
         Exposed Fasteners (Nails), Over Exposed (inadequate Lap), Weather-Seals cracking/loose/missing, At or Nearing End
         of Life. Cracking at isolated areas.

DOORS, WINDOWS, ENERGY CONSERVATION
       810] WATER HEATER
       6.14 Temperature:
       140-160 F- A scalding hazard exists.

ATTIC
         900] ATTIC AREAS
         7.1 General Comments:
         Repairs Recommended, Further Evaluation Recommended.

         902] ATTIC FRAME
         7.4 Truss/ Rafter Observation:
         Trusses have been cut, notched, Field repaired or modified. Improper, Refer To the Truss Manufacturer or a
         Structural engineer for a Course of action.

         904] MOISTURE, STAINS
         7.11 Related to?
         Chimney(s)

         907] ATTIC LIGHT(S)
         7.13 Observations:
         Substandard Installation (sloppy Improper wiring or materials) Safety Concern.

         910] FIREPLACE FLUE(S)
         7.17 Observation:
         Clearances to combustible material inadequate. see cellulose insulation, Recommend repairs by certified chimney
         sweep.

GARAGE & CARPORT
      916] OVERALL CONDITION
      8.2 1) Overall Condition:
      Water Stains- Walls, Ceiling, Unknown source, repair cause & effect.

         917] ATTACHED?
         8.3 If Yes; Fire Rated
         Fire Walls Damaged or Breached at; Ceiling. Not able to verify the presence of fire assembly at water heater platform.
         Recommended.

         918] GARAGE VEHICLE DOOR(S)
         8.7 Garage Opener Observations:
         photoelectric Safety Eye too High. 6" Max off Grade. Safety.

      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                        Page5
34145 Pacific Coast Highway Suite 513
                                                                                                 Dana Point CA 92629
                                                                                                 p 949.466.7265 f 661.0581
                                                                                                 www.buildingspecscorp.com


         920] GARAGE RECEPTACLES
         8.9 Observations:
         Ground Fault Circuit Interrupters

         Recommended.

         921] GARAGE LIGHTING
         8.10 Observations:
         Substandard workmanship, Repairs by qualified individual recommended.

KITCHEN & APPLIANCES
       1003.C] Sink Drains
       10.10 Observations:
       Substandard Installation or Materials, Prone to Leak/Fail, Leaks.

         1003.D] Disposal
         10.11 Observations:
         Improper, Unrated power Cord.

         1007] Dishwasher
         10.16 Observations:
         Air gap missing, Concern for back siphoning into dishwasher.

         1009] Oven
         10.19 Observations:
         Handle damaged.

INTERIOR
        1202] FAMILY ROOM
       12.20 14) Ceiling Fan Observations:
       Inoperable.

         1212] BEDROOM #5
         12.78 1) Overall Condition:
         Closet modified Into wine room. several electrical Concerns observed. repairs recommended.

ELECTRICAL
       1302] PANEL(S)
       13.3 MAIN PANEL (AMPS):
       Location; Exterior Wall of Building, Left Side of building, 125 amps.

         13.5 Observations:
         Sloppy workmanship, Over Fusing, Risk Of Wire Over-Heating. ( size of wire insufficient to carry load), Missing, Wire
         Connector(s)

HEATING & COOLING SYSTEMS
       1500] HEATING SYSTEM #1
       15.7 7) DUCTWORK:
       Insulated Fiberboard (Fiberglass lined), Plastic Flex, Observations: Disconnected Connection(s) See return plenum.

      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                        Page6
34145 Pacific Coast Highway Suite 513
                                                                                                 Dana Point CA 92629
                                                                                                 p 949.466.7265 f 661.0581
                                                                                                 www.buildingspecscorp.com


         1506] AIR CONDITIONER #1:
         15.14 4) CONDENSATE:
         Disconnected. Abandoned lines.Risk of leaking.

FIREPLACE/CHIMNEY/ENVIRONMENTAL OVERVIEW
       1601] FAMILY ROOM FIREPLACE
       16.7 Hearth Extension Observations:
       Inadequate Size /Depth or Width.



PRIORITY #2 MARGINAL:          Repairs, service, replacement and/or upgrades are recommended by the appropriate
                            professional in the near future. Items are declining in usefulness or ability to perform purpose.

GROUNDS
      208] FENCE (limited to contact w/ house)
      2.14 Observations:
      Loose, Located Rear Side of Building.

EXTERIOR SURFACES
       STUCCO
       4.3 Observations:
       Weep Screed Below Grade, Susceptible to Allow Moisture Infiltration.

         501] PAINTS & SEALANT(S)
         4.6 Observations:
         Weathered (Susceptible To Water Infiltration and/or Damage)

GARAGE & CARPORT
      922] GARAGE WALLS/CEILING
      8.12 Wall/Ceiling Observations:
      Moisture Stains, using a moisture meter, no active moisture present. May indicate prior or active water infiltration.
      Monitor for activity. Repairs may become necessary. at water heater.

         Mildew/Mold like material (Raised, Fuzzy, Discoloration) Observed. Recommend Further evaluation by a Mold
         identification/Removal contractor.


         923] VENTILATION
         8.13
         Screens Damaged, potential for animal intrusion.

BATHROOM(s)
      1104] MASTER BATH
      11.61 C. Shower Doors:
      Seals Failing.

HEATING & COOLING SYSTEMS
       1506] AIR CONDITIONER #1:
       15.11 3) COMPRESSOR UNIT:
      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                        Page7
34145 Pacific Coast Highway Suite 513
                                                                                                 Dana Point CA 92629
                                                                                                 p 949.466.7265 f 661.0581
                                                                                                 www.buildingspecscorp.com


         Located At: Left side of building, Not Secured/ Anchored. Unit Not Operational.

POOL/SPA & EQUIPMENT
      POOL LIGHT:
      17.6
      Not operable. If a defective bulb is at fault, replacement will cost $50-100 Otherwise, further evaluation and repairs
      will be needed by a licensed electrician.



PRIORITY #3 NOTES:          General notes, comments and/or Recommended Maintenance and/or Recommended upgrades
                             for increased safety or to enhance buildings performance.

BATHROOM(s)
      1102] FIRST FLOOR HALL BATH
      11.13 B. Tub Faucets:
      unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs Recommended.

         1104] MASTER BATH
         11.54 B. Tub Faucets:
         unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs Recommended.

         11.63 E. Shower Valves:
         unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs Recommended.

INTERIOR
       1213]
       12.97 13) Lighting Provisions:
       Observations; Could Not Locate Or Verify All Switch(s) Function Seller Demonstrate.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                        Page8
34145 Pacific Coast Highway Suite 513
                                                                                                        Dana Point CA 92629
                                                                                                        p 949.466.7265 f 661.0581
                                                                                                        www.buildingspecscorp.com




                                                       GENERAL INFORMATION
IMPORTANT INFORMATION:It is the sole responsibility of the client to read each page of this report. The client is responsible to research any and all
jurisdictions permits required by the local authorities regarding the property in contract before the close of escrow. You, the client, are to personally
perform a diligent visual inspection of the property after the seller vacates to insure the no "conditions" was concealed by personal property and/or
stored items while occupied or that may have been damaged during he seller's evacuation of the building. Should any "conditions" be revealed that
was not address within this report prior to or after the close of escrow, please contact our office immediately for an additional evaluation regarding
such "conditions".
     100] CLIENT
          1.1 Name:                       Sample Report.
          1.2 Date:                       01/05/2010.

Inspection Performed According To The Standards Of Practice Of The California Real Estate Inspection Association. These can be viewed at
www.creia.org/i4a/pages/index.cfm?pageid=3283
     101] INSPECTION:
          1.3 Building Status;            Vacant, A vacant house may not show evidence of water or moisture leaks or problems until the house has
                                          been occupied for a period of time and the fixtures have been in use.
          1.4 Overall Building Condition; What may be possible modifications to building. Client is advised to request all documentation and building
                                          permits for work observed. If no documentation is available the client should be aware these components
                                          may not have been properly installed and may pose adverse conditions.

                                          Bedroom(s)




          1.5 Street:                     12345 Your Street.
          1.6 City:                       Newport Beach.
          1.7 State:                      California.
          1.8 County:                     Orange.
          1.9 Country:                    U.S.A.
          1.10 Type of Building:          Residential.
          1.11 Style of House:            Two Story.
     102] TYPE OF INSPECTION(S) ORDERED
          1.11                            Standard Inspection.
     104] CONDITIONS
          1.12 *Age of Building           13 years.
     Weather Conditions
          1.13 Temperature Approx. ° F    60-70.
          1.14 Weather Conditions         Previous Rain- 1-week Partly Cloudy.
          1.15 People Present During      Buyer, Buyer's Agent.
          Inspection:
          1.16 Client Accompanied         100%
          Inspector:
     Time
          1.17 Started:                   10:30 am.
          1.18 Completed:                 1:00/1:30 pm.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                            May 28, 2010                                                            Page9
34145 Pacific Coast Highway Suite 513
                                                                                                          Dana Point CA 92629
                                                                                                          p 949.466.7265 f 661.0581
                                                                                                          www.buildingspecscorp.com



    105] INSPECTOR(S)
         1.19                            Rick Yerger.

ADDITIONAL COMMENTS If the building is occupied, furniture, boxes, rugs, wall coverings, storage and other personal items may block, cover or
impede inspection, a re-inspection is recommended prior to purchase. A vacant house may not show an active water or moisture problems until it has
been occupied and the plumbing is in use for a period of time.


                                                                   GROUNDS
IMPORTANT INFORMATION: This inspection is not intended to address or include any geological conditions or site stability information. We do not
comment on coatings or cosmetic deficiencies, which would be apparent to the average person. Any reference to grade is limited to only areas around
the exterior of the exposed areas of foundation or exterior walls. We cannot determine drainage performance of the site or the condition of any
underground piping, including subterranean drainage systems and municipal water and sewer service piping or septic systems , Client is advised to
have these items inspected and tested by the Appropriate Qualified person(s). Any areas too low to enter or not accessible are excluded from the
inspection. We do not evaluate any detached structures such as storage sheds and stables, nor mechanical or remotely controlled components such
as driveway gates. We do not evaluate or move landscape components such as trees, shrubs, fountains, ponds, statuary, pottery, fire pits, patio
fans, heat lamps, and decorative or low-voltage lighting. Any such mention of these items is informational only and not to be construed as inspected.
    GROUNDS
         2.1 General Comments:           Appears adequate at this time.
    200] CONDITIONS
         2.2 Observations:               Damp.
    201] DRAINAGE NEXT TO HOUSE
         2.3 Grade Type:                 Near Level.
         2.4 Observations:               Appears adequate at this time.
    202] EROSION
         2.5 Observations:               None observed.
    203] TREES, BUSHES
         2.6 Observations:               Appears adequate at this time.
    204] STOOP, STAIRS
         2.7 General Comments:           Appears adequate at this time.
    205] WALKWAY(S)
         2.8 Materials:                  Concrete.
         2.9 Observations:               Appears adequate.
    206] LANDSCAPE PLANTERS
         2.10 Observations:              Substandard fabrication. Concern for moisture infiltration. Planter is raised above interior floor line and tight
                                         against exterior wall. lacking capillary break (air space). Located Rear Side of Building.




    207] DRIVEWAY
         2.11 Materials:                 Concrete.
         2.12 Observations:              Appears adequate.
    208] FENCE (limited to contact w/ house)
         2.13 Material:                  Wood, Vinyl Clad.
         2.14 Observations:              Loose, Located Rear Side of Building.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                          May 28, 2010                                                                Page10
34145 Pacific Coast Highway Suite 513
                                                                                                       Dana Point CA 92629
                                                                                                       p 949.466.7265 f 661.0581
                                                                                                       www.buildingspecscorp.com




    209] BASEMENT ENTRY WALL
          2.15 Overview:                 Not applicable.
    210] RETAINING WALL
          2.16 Material:                 Not applicable.
    211] FOUNDATION VENTS
          2.17 Observations:             Not applicable.
    212] FOUNDATION WINDOWS
          2.18 Observations:             Not applicable.
    213] FOUNDATION CRAWLSPACE ACCESS
          2.19 Observations:             Not applicable.
    215] AUXILIARY STRUCTURES (Outside the scope of our inspection. Consult with specialist for operation &
    maintenance)
          2.20 Observations:             Loose, Tip Concern. Recommend verifying fountains are mechanically secured for safety. Substandard
                                         Electrical Wiring. Extension cord or exposed wiring. Located Rear Side of Building.

ADDITIONAL COMMENTS: Low voltage Lighting and Landscape Sprinklers are excluded. We recommend having these systems demonstrated to
you. Underground drainage piping systems are not tested for operation, Client should have these systems demonstrated to you.


                                                   FOUNDATION & STRUCTURE
IMPORTANT INFORMATION: In accordance with our standards of practice, we identify foundation types and look for any evidence of structural
deficiencies. However, minor cracks or deteriorated surfaces are common in many foundations and most do not represent a structural problem.
Any cracks or water damage should be repaired and monitored as needed by a licensed or qualified individual. Severe problems such as major
cracking, amateur work or water damage could lead to a structural failure. If major cracking is visible we recommend further evaluation by a structural
engineer. Any cracks need to be monitored to determine if active or from previous movement. All exterior grades should allow for surface and roof
water to flow away from the foundation. All concrete floor slabs experience some degree of cracking due to shrinkage in the curing process. In most
instances floor coverings prevent recognition of cracks or settlement in all but the most severe cases. Where carpeting and other floor coverings are
installed, the materials and condition of the flooring underneath cannot be determined. Areas hidden from view by finished walls or stored items
cannot be judged and are not a part of this inspection. However, we are not specialists, and in the absence of any major defects, we may not
recommend that you consult with a foundation contractor, a structural engineer, or a geologist, but this should not deter you from seeking the opinion
of any such expert. We also routinely recommend that inquiry be made with the seller about knowledge of any prior foundation or structural repairs.
    FOUNDATION
          3.1 General Comments:          Limited or No Access For Evaluation.
    B] Water Damage
          3.2 Signs of Water Damage?     None Observed.
    BOLTS & BRACING
          3.3 Observations:              Not Visible due to construction design.
    308] WOOD FRAMING
          3.4 A] Style:                  Platform.
          3.5 Observations:              Appears Adequate.
          3.6 B) Floor Structure:        Not Visible Could Not Evaluate Internal Components.
          3.7 Observations:              Appears Adequate.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                          May 28, 2010                                                             Page11
34145 Pacific Coast Highway Suite 513
                                                                                                     Dana Point CA 92629
                                                                                                     p 949.466.7265 f 661.0581
                                                                                                     www.buildingspecscorp.com




                                                      EXTERIOR SURFACES
ADDITIONAL COMMENTS:
    500] SIDING MATERIAL
         4.1 Conditions Noted:         At or Below Grade, Susceptible to Rot and or Wood Destroying Insect Damage, Located Left Side of
                                       Building, Located Rear Side of Building.
         4.2 Predominant Material      STUCCO.
         Type(s):
    STUCCO
         4.3 Observations:             Weep Screed Below Grade, Susceptible to Allow Moisture
                                       Infiltration.




    SHINGLES / CLAPBOARD / PREFAB PANELS
         4.4 Style:                    Located Rear Side of Building.
    501] PAINTS & SEALANT(S)
         4.5 Type:                     Paint.
         4.6 Observations:             Weathered (Susceptible To Water Infiltration and/or Damage)
    503] TRIM
         4.7 Type:                     Wood.
    505] SOFFIT
         4.8 Type:                     Wood, Exposed Rafter Tails.
         4.9 Venting                   Yes, Partial.
         4.10 Observations:            Water Stains , suggests possible roof leak. Located Front Side of Building.




    509] ELECTRICAL
         4.11 Observations:            Substandard hazardous Wring several locations, Located Rear Side of Building. Receptacles-
                                       Recommended GFCI, Located Rear Side of Building.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                             Page12
34145 Pacific Coast Highway Suite 513
                                                                                                          Dana Point CA 92629
                                                                                                          p 949.466.7265 f 661.0581
                                                                                                          www.buildingspecscorp.com




                                                                       ROOFS
Although not required to, we generally attempt to evaluate various roof types by walking on their surfaces. If we are unable or unwilling to do this for
any reason, we will indicate the method used to evaluate them. Every roof will wear differently relative to its age, number of layers, quality of material,
method of application, exposure to weather conditions, and the regularity of its maintenance. W e can only offer an opinion of the general quality and
condition of the roofing material.

The inspector cannot and does not offer an opinion or warranty as to whether the roof leaks or may be subject to future leakage. The waterproof
membrane beneath roofing materials is generally concealed and cannot be examined without removing the roof material. Although roof condition can
be evaluated, it is virtually impossible for anyone to detect a leak except as it is occurring or by specific water tests, which are beyond the scope of our
service. Even water stains on ceilings or on framing within attics will not necessarily confirm an active leak without some corroborative evidence, and
such evidence can be deliberately concealed. We cannot predict roofing materials remaining life expectancy, or guarantee that it will not leak.
Naturally, the sellers or the occupants of a residence will generally have the most intimate knowledge of the roof and of its history. Therefore, we
recommend that you ask the sellers about it, and that you either include comprehensive roof coverage in your home insurance policy. We do not
inspect attached accessories including by not limited to solar systems, antennae, and lightning arrestors.
     600] ROOF
          5.1 General Comments:           Repairs Recommended, Recommend Further Evaluation by a Qualified Roofing Contractor. Client is
                                          advised to Have Roof and all Related components Evaluation by Roofing Contractor Prior to Purchase.
     602] ACCESS
          5.2 Inspection Restricted for   Height.
          following reasons-
     608] TILE/ SLATE
          5.3 Material Type:.             Barrel Concrete Tiles.
          5.4 Observations:               Exposed Fasteners (Nails), Over Exposed (inadequate Lap), Weather-Seals cracking/loose/missing, At or
                                          Nearing End of Life. Cracking at isolated areas.




     612] VENTILATION
          5.5 Type:                       Soffit, Dormer.
     613] STRUCTURE
          5.6 Observations:               Appears Adequate.
     615] GUTTERS
          5.7 Type:                       Aluminum.
          5.8 Observations:               Appears Adequate.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                           May 28, 2010                                                               Page13
34145 Pacific Coast Highway Suite 513
                                                                                                      Dana Point CA 92629
                                                                                                      p 949.466.7265 f 661.0581
                                                                                                      www.buildingspecscorp.com




                                       DOORS, WINDOWS, ENERGY CONSERVATION
ADDITIONAL COMMENTS


    800] ENTRY(S)
         6.1 Predominant Door Type:     Single.
         6.2 Material:                  Metal.
    Door Condition:
         6.3 Door Observations:         Adequate.

ADDITIONAL COMMENTS Exterior sealants must be maintained to prevent water infiltration and damage. Single glaze or aluminum sash windows
may condensate inside. Reporting of failing thermal pane seals (glazing) in beyond the scope of the inspection. The inspector may report on apparent
failing thermal pane seals if visible at the time of the inspection. Some failing seals may become visible as the weather and daylight conditions
change.


    STYLE(S)
         6.4 Predominant Style:         Gliding.
         6.5 Frames & Sashes:           Aluminum.
         6.6 Glass & Glazing:           Double Glaze.
    804] INSULATED GLAZING
         6.7 Insulated Glazing in Use? Yes, Double.
    805] STORM WINDOWS
         6.8 Present?                   Not Applicable.
    806] DOORS
         6.9 Insulated?                 No.
         6.10 Storm Doors Present?      No.
    809] INSULATION
         6.11 Installed at Walls?       N/V.
         6.12 Installed at Ceilings?    Yes.
         6.13 Depth:                    10 inches.
    810] WATER HEATER
         6.14 Temperature:              140-160 F- A scalding hazard exists.

ADDITIONAL COMMENTS           Maintaining the water heater temperature to 125° F to help reduce the chance of scalding and burns. This will also help
you save money on energy.


    811] DUCT WORK
         6.15 Insulated?                Yes.
    812] ATTIC VENTILATION
         6.16 Observations:             Adequate.
    813] APPLIANCES
         6.17 Observations:             Medium Efficiency.


                                                                     ATTIC
ADDITIONAL COMMENTS Attics with boxes, etc. could impede inspection and be a possible fire hazard. Attics that are not accessible or blocked
to the Inspector should be reinspected . DO NOT attempt to repair damaged trusses without a repair detail from the Truss Manufacturer or a Design
Professional.
    900] ATTIC AREAS
         7.1 General Comments:          Repairs Recommended, Further Evaluation Recommended.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                          May 28, 2010                                                           Page14
34145 Pacific Coast Highway Suite 513
                                                                                                    Dana Point CA 92629
                                                                                                    p 949.466.7265 f 661.0581
                                                                                                    www.buildingspecscorp.com



    901] ATTIC ACCESS
         7.2 Viewing Method:           Pull Down Stairs.
    902] ATTIC FRAME
         7.3 Trusses                    24"oc, Wood.
         7.4 Truss/ Rafter Observation: Trusses have been cut, notched, Field repaired or modified. Improper, Refer To the Truss Manufacturer or
                                        a Structural engineer for a Course of action.




         7.5 Ridge Pole Observations: None.
         7.6 Purlins Observation :     Not Applicable.
         7.7 Collar Ties Observations: Not Applicable.
    903] ROOF SHEATHING
         7.8 Material Type:            Oriented Strand Board (OSB)
         7.9 Observations:             Adequate.
    904] MOISTURE, STAINS
         7.10 Observed?                Yes.
         7.11 Related to?              Chimney(s)




    905] ATTIC INSULATION
         7.12 Type Of Insulation:      Loose Fill, Depth, 6-8"
    907] ATTIC LIGHT(S)
         7.13 Observations:            Substandard Installation (sloppy Improper wiring or materials) Safety Concern.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                            Page15
34145 Pacific Coast Highway Suite 513
                                                                                                    Dana Point CA 92629
                                                                                                    p 949.466.7265 f 661.0581
                                                                                                    www.buildingspecscorp.com



    908] ATTIC PLUMBING
         7.14 Observations:            Adequate.
    909] ATTIC VENTILATION
         7.15 Venting Type:            Dormer, Soffit.
         7.16 Observations:            Adequate.
    910] FIREPLACE FLUE(S)
         7.17 Observation:             Clearances to combustible material inadequate. see cellulose insulation, Recommend repairs by certified
                                       chimney sweep.




                                                         GARAGE & CARPORT
ADDITIONAL COMMENTS           If slab and walls are covered with personal items, the inspection may be blocked or impeded. Recommend a final
walk-through when area is cleared. Auto safety reverse devices are recommended for an overhead garage door; however, the impact-style are not
tested since damage could result to the door. NOTE: any repairs to the garage door and door components must be performed by a trained door
systems technician.


    915] GARAGE & CARPORT
         8.1 General Comments:         Present.
    916] OVERALL CONDITION
         8.2 1) Overall Condition:     Water Stains- Walls, Ceiling, Unknown source, repair cause & effect.




    917] ATTACHED?
         8.3 If Yes; Fire Rated        Fire Walls Damaged or Breached at; Ceiling. Not able to verify the presence of fire assembly at water heater
                                       platform. Recommended.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                        May 28, 2010                                                           Page16
34145 Pacific Coast Highway Suite 513
                                                                                                       Dana Point CA 92629
                                                                                                       p 949.466.7265 f 661.0581
                                                                                                       www.buildingspecscorp.com



    918] GARAGE VEHICLE DOOR(S)
         8.4 # of Garage Doors &        2 Metal.
         Type:
         8.5 Garage Door                Adequate.
         Observations:
         8.6 Garage Door Auto           Yes.
         Opener?
         8.7 Garage Opener              photoelectric Safety Eye too High. 6" Max off Grade. Safety.
         Observations:
    919] GARAGE SLAB / APRON
         8.8 Evidence of Cracking?      No.
    920] GARAGE RECEPTACLES
         8.9 Observations:              Ground Fault Circuit Interrupters

                                        Recommended.
    921] GARAGE LIGHTING
         8.10 Observations:             Substandard workmanship, Repairs by qualified individual recommended.
    922] GARAGE WALLS/CEILING
         8.11 3) Walls/Ceiling          Drywall, Plaster.
         Materials:
         8.12 Wall/Ceiling              Moisture Stains, using a moisture meter, no active moisture present. May indicate prior or active water
         Observations:                  infiltration. Monitor for activity. Repairs may become necessary. at water heater.

                                        Mildew/Mold like material (Raised, Fuzzy, Discoloration) Observed. Recommend Further evaluation by a
                                        Mold identification/Removal contractor.




    923] VENTILATION
         8.13                           Screens Damaged, potential for animal intrusion.


                                                                   SAFETY
ADDITIONAL COMMENTS: inspector will note the presence of smoke detectors but not test for operation. Buyer is responsible for testing prior to
closing escrow.
    926] SMOKE ALARMS
         9.1 Observations;              Yes.

ADDITIONAL COMMENTS Carbon Monoxide monitors are recommended on all floors with any type of combustion units; such as fireplace, wood
stove, oil furnace and gas furnace. Carbon monoxide is a colorless, odorless gas that can cause nausea, headaches and even death. Keyed
deadbolts should have key readily accessible in case of fire.
    927] CARBON MONOXIDE DETECTORS
         9.2 Present?                   No.
    928] FIRE SPRINKLER
         9.3 Present?                   No.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                          May 28, 2010                                                           Page17
34145 Pacific Coast Highway Suite 513
                                                                                                     Dana Point CA 92629
                                                                                                     p 949.466.7265 f 661.0581
                                                                                                     www.buildingspecscorp.com



    929] ALARM SYSTEM
         9.4 Present?                  No.
    930] DEAD BOLTS
         9.5 Present?                  Yes.
    931] WINDOW LOCKS
         9.6 Present?                  Yes.
    932] FALL CONCERNS
         9.7 Present?                  No.
    933] TRIP CONCERNS
         9.8 Present?                  None Observed.
    934] SAFETY GLASS
         9.9                           Adequate.


                                                     KITCHEN & APPLIANCES
ADDITIONAL COMMENTS



    1001] CABINETS
         10.1 Materials:               Solid Wood.
         10.2 Surface Finish:          Painted.
         10.3 Observations:            Adequate.
    1002] COUNTER(S)
         10.4 Materials:               Marble, Granite, Stone.
         10.5 Observations:            Adequate.
    1003] SINK(S)
         10.6 Material:                Stainless.
         10.7 Observation:             Adequate.
    1003.A] Sink Faucets
         10.8 Observations:            Adequate.
    1003.B] Sink Spray
         10.9 Observations:            Adequate.
    1003.C] Sink Drains
         10.10 Observations:           Substandard Installation or Materials, Prone to Leak/Fail, Leaks.




    1003.D] Disposal
         10.11 Observations:           Improper, Unrated power Cord.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                         May 28, 2010                                                       Page18
34145 Pacific Coast Highway Suite 513
                                                                                                       Dana Point CA 92629
                                                                                                       p 949.466.7265 f 661.0581
                                                                                                       www.buildingspecscorp.com




    1004] FLOOR
         10.12 Visible Areas:           Wood.
         10.13 Observations:            Adequate.
    1005] RECEPTACLE
         10.14 Observations:            Adequate.

ADDITIONAL COMMENTS Appliances are checked for operation, no life expectancy is implied or given. A separate warranty may be
available. An older unit may be nearing the end of it's useful life. Appliances should be monitored and maintained routinely. We routinely
recommend a metal dryer vent, vinyl may be a potential fire hazard. Excluded items are not evaluated, Client may want to have excluded items
serviced.
    1006) Exhaust Discharge Hood
         10.15 Observations:            Adequate.
    1007] Dishwasher
         10.16 Observations:            Air gap missing, Concern for back siphoning into dishwasher.




    1008] Refrigerator
         10.17 Observations:            None.
    1009] Oven
         10.18 Fuel Type:               Gas.
         10.19 Observations:            Handle damaged.




    1010] Range
         10.20 Range/Fuel Type:         Gas.
         10.21 Observations:            Adequate.



      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                        May 28, 2010                                                          Page19
34145 Pacific Coast Highway Suite 513
                                                                                                      Dana Point CA 92629
                                                                                                      p 949.466.7265 f 661.0581
                                                                                                      www.buildingspecscorp.com



    1011] Microwave
         10.22 Observations:            Adequate.
    1012] Compactor
         10.23 Observations:            None.
    1013] Clothes Washer
         10.24 Observations:            None.
    1014] Clothes Dryer
         10.25 Observations:            None.


                                                              BATHROOM(s)
ADDITIONAL COMMENTS A ground fault interrupter is recommended within 6' of all water sources to prevent electrical shock. Caulking must be
maintained at all shower and tub wall fixtures and penetrations to help prevent water damage to the wall and adjacent floor. Inspection does not
include towel bars, etc.
    1102] FIRST FLOOR HALL BATH
         11.1 2) TOILET                 Base of toilet not sealed to floor, recommended for sanitation.
         Observations:
         11.2 4) SINKS:                 Built In.
         11.3 Sink(s) Observations:     Adequate.
         11.4 A. Sink Faucets:          Adequate.
         11.5 B. Sink Drains:           Adequate.
         11.6 C. Cabinet:               Water Stains, Damage.
         11.7 5) COUTERS TOPS           Stone.
         11.8 Counter Observations:     Adequate.
         11.9 6) TUB                    Fiberglass.
         11.10 Tub Observations:        Adequate.
         11.11 A. Tub Wall Type         Fiberglass.
         11.12 Tub Wall Observations:   Adequate.
         11.13 B. Tub Faucets:          unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs
                                        Recommended.
         11.14 C. Tub Drains:           Adequate.
         11.15 7) SHOWER TYPE           In Tub.
         11.16 D. Shower Head:          Adequate.
         11.17 8) VENTILATION           Adequate.
         Observations:
         11.18 9) HEAT REGISTERS:       FAU ( Forced Air Unit), Observations: Adequate.
         11.19 10) FLOORING TYPE:       Hardwood Planks, Tiles.
         11.20 Flooring Observations:   Adequate.
         11.21 11) LIGHTING             Adequate.
    1103] SECOND FLOOR HALL BATH
         11.22 2) TOILET                Adequate.
         Observations:
         11.23 4) SINKS:                Built In.
         11.24 Sink(s) Observations:    Adequate.
         11.25 A. Sink Faucets:         Adequate.
         11.26 B. Sink Drains:          Adequate.
         11.27 C. Cabinet:              Adequate.
         11.28 5) COUTERS TOPS          Ceramic Tile.
         11.29 Counter Observations:    Adequate.
         11.30 6) TUB                   Fiberglass.
         11.31 Tub Observations:        Adequate.
         11.32 A. Tub Wall Type         Fiberglass.
         11.33 Tub Wall Observations:   Adequate.
         11.34 7) SHOWER TYPE           In Tub.
         11.35 B. Water Damaged         None.
         Areas:
         11.36 D. Shower Head:          Adequate.
         11.37 8) VENTILATION           Window, Minimal.
         Observations:
         11.38 9) HEAT REGISTERS:       FAU ( Forced Air Unit), Observations: Adequate.
         11.39 10) FLOORING TYPE:       Ceramic, Marble Tile.

      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                        May 28, 2010                                                            Page20
34145 Pacific Coast Highway Suite 513
                                                                                                         Dana Point CA 92629
                                                                                                         p 949.466.7265 f 661.0581
                                                                                                         www.buildingspecscorp.com


          11.40 Flooring Observations:    Adequate.
          11.41 11) LIGHTING              Adequate.
     1104] MASTER BATH
          11.42 2) TOILET                 Adequate.
          Observations:
          11.43 4) SINKS:                 Built In, Multiple Basins- Two noted.
          11.44 Sink(s) Observations:     Adequate.
          11.45 A. Sink Faucets:          Adequate.
          11.46 B. Sink Drains:           Adequate.
          11.47 C. Cabinet:               Adequate.
          11.48 5) COUTERS TOPS           Stone.
          11.49 Counter Observations:     Adequate.
          11.50 6) TUB                    Fiberglass.
          11.51 Tub Observations:         Adequate.
          11.52 A. Tub Wall Type          Fiberglass.
          11.53 Tub Wall Observations:    Adequate.
          11.54 B. Tub Faucets:           unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs
                                          Recommended.
          11.55 C. Tub Drains:            Adequate.
          11.56 7) SHOWER TYPE            Stall.
          11.57 Shower Pan:               Fiberglass, Observations: Adequate.
          11.58 A. Shower Wall Type       Fiberglass.
          11.59 Shower Wall               Adequate.
          Observations:
          11.60 B. Water Damaged          None.
          Areas:
          11.61 C. Shower Doors:          Seals Failing.
          11.62 D. Shower Head:           Adequate.
          11.63 E. Shower Valves:         unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs
                                          Recommended.
          11.64 8) VENTILATION            Adequate.
          Observations:
          11.65 9) HEAT REGISTERS:        FAU ( Forced Air Unit), Observations: Adequate.
          11.66 10) FLOORING TYPE:        Carpet.
          11.67 Flooring Observations:    Adequate.
          11.68 11) LIGHTING              Adequate.
          11.69 12) RECEPLACLE            Adequate.
          Observations:


                                                                     INTERIOR
Our inspection of living space includes the visually accessible areas of walls, floors, cabinets and closets, and the testing of a representative number
of windows and doors, switches and outlets. We do not evaluate window treatments, move furnishings or possessions, lift carpets or rugs, empty
closets or cabinets, nor comment on cosmetic deficiencies. W e may not comment on cracks that appear around windows and doors, along lines of
framing members or along seams of drywall and plasterboard. These are typically caused by minor movement, such as wood shrinkage, common
settling, and seismic activity, and will often reappear if they are not correctly repaired. Such cracks can become the subject of disputes, and are
therefore best evaluated by a specialist. Floor covering damage or stains may be hidden by furniture, and the condition of floors underlying floor
coverings is not inspected. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting
conditions. Check with owners for further information. Testing, identifying, or identifying the source of environmental pollutants or odors (including but
not limited to lead, mold, allergens, odors from household pets and cigarette smoke) is beyond the scope of our service, but can become equally
contentious or difficult to eradicate. We recommend you carefully determine and schedule whatever remedial services may be deemed advisable or
necessary before the close of escrow.
     1201] LIVING ROOM:
          12.1 1) Overall Condition:      Appears in overall adequate condition with no visible concerns to room components.
          12.2 2) Floor Structure:        Adequate.
          12.3 7) Wood / Laminate         Adequate.
          Observations:
          12.4 8) Wall                    Drywall, Plaster, Appears adequate.
          Materials/Observations:
          12.5 9) Ceiling                 Drywall, Plaster, Appears adequate.
          Materials/Observations:
          12.6 10) Window                 Adequate.
          Observations:
          12.7 12) Receptacle             Adequate.
          Observations:
      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                           May 28, 2010                                                              Page21
34145 Pacific Coast Highway Suite 513
                                                                                                    Dana Point CA 92629
                                                                                                    p 949.466.7265 f 661.0581
                                                                                                    www.buildingspecscorp.com


         12.8 13) Lighting Provisions:   Ceiling, Switched Receptacle, Observations; Adequate.
         12.9 15) Heat Observations:     Appears Adequate.
         12.10 16) Stair & Railing       Adequate.
         Observations:
         12.11 17) Trim                  Wood.
         Types/Observations:
    1202] FAMILY ROOM
         12.12 1) Overall Condition:     Appears in overall adequate condition with no visible concerns to room components.
         12.13 2) Floor Structure:       Adequate.
         12.14 7) Wood / Laminate        Adequate.
         Observations:
         12.15 8) Wall                   Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.16 9) Ceiling                Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.17 10) Window                Adequate.
         Observations:
         12.18 12) Receptacle            Adequate.
         Observations:
         12.19 13) Lighting              Ceiling, Observations; Adequate.
         Provisions:
         12.20 14) Ceiling Fan           Inoperable.
         Observations:
         12.21 15) Heat Observations:    Appears Adequate.
         12.22 17) Trim                  Wood, Trim Observations: Appears adequate.
         Types/Observations:
    1206] LAUNDRY ROOM
         12.23 1) Overall Condition:     Appears in overall adequate condition with no visible concerns to room components.
         12.24 7) Wood / Laminate        Adequate.
         Observations:
         12.25 8) Wall                   Drywall, Plaster, Holes.
         Materials/Observations:
         12.26 9) Ceiling                Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.27 11) Door                  Hinged, Observations; Adequate.
         Types/Observations:
         12.28 12) Receptacle            Adequate.
         Observations:
         12.29 13) Lighting              Ceiling.
         Provisions:
         12.30 15) Heat Observations:    None.
         12.31 17) Trim                  Wood, Trim Observations: Appears adequate.
         Types/Observations:
    1207]
         12.32 1) Overall Condition:     Appears in overall adequate condition with no visible concerns to room components.
         12.33 2) Floor Structure:       Adequate.
         12.34 3) Carpet Observations:   Adequate.
         12.35 8) Wall                   Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.36 9) Ceiling                Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.37 10) Window                Adequate.
         Observations:
         12.38 11) Door                  Hinged, Observations; Adequate.
         Types/Observations:
         12.39 12) Receptacle            Adequate.
         Observations:
         12.40 13) Lighting              Ceiling, Observations; Adequate.
         Provisions:
         12.41 14) Ceiling Fan           Adequate.
         Observations:
         12.42 15) Heat Observations:    Appears Adequate.
         12.43 17) Trim                  Wood, Trim Observations: Appears adequate.
         Types/Observations:

      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                         May 28, 2010                                                          Page22
34145 Pacific Coast Highway Suite 513
                                                                                                    Dana Point CA 92629
                                                                                                    p 949.466.7265 f 661.0581
                                                                                                    www.buildingspecscorp.com



    1208] MASTER BEDROOM:
         12.44 1) Overall Condition:     Appears in overall adequate condition with no visible concerns to room components.
         12.45 2) Floor Structure:       Adequate.
         12.46 3) Carpet Observations:   Adequate.
         12.47 8) Wall                   Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.48 9) Ceiling                Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.49 10) Window                Adequate.
         Observations:
         12.50 11) Door                  Hinged, Observations; Adequate.
         Types/Observations:
         12.51 12) Receptacle            Adequate.
         Observations:
         12.52 13) Lighting              Ceiling, Observations; Adequate.
         Provisions:
         12.53 15) Heat Observations:    Appears Adequate.
         12.54 17) Trim                  Wood, Trim Observations: Appears adequate.
         Types/Observations:
    1209] BEDROOM #2
         12.55 1) Overall Condition:     Appears in overall adequate condition with no visible concerns to room components.
         12.56 2) Floor Structure:       Adequate.
         12.57 3) Carpet Observations:   Adequate.
         12.58 8) Wall                   Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.59 9) Ceiling                Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.60 10) Window                Adequate.
         Observations:
         12.61 11) Door                  Hinged, Observations; Adequate.
         Types/Observations:
         12.62 12) Receptacle            Adequate.
         Observations:
         12.63 13) Lighting              Ceiling, Observations; Adequate.
         Provisions:
         12.64 14) Ceiling Fan           Adequate.
         Observations:
         12.65 15) Heat Observations:    Appears Adequate.
         12.66 17) Trim                  Wood, Trim Observations: Appears adequate.
         Types/Observations:
    1210] BEDROOM #3
         12.67 1) Overall Condition:     Appears in overall adequate condition with no visible concerns to room components.
         12.68 2) Floor Structure:       Adequate.
         12.69 3) Carpet Observations:   Adequate.
         12.70 8) Wall                   Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.71 9) Ceiling                Drywall, Plaster, Appears adequate.
         Materials/Observations:
         12.72 10) Window                Adequate.
         Observations:
         12.73 11) Door                  Hinged, Sliding, Mirrored, Observations; Adequate.
         Types/Observations:
         12.74 12) Receptacle            Adequate.
         Observations:
         12.75 13) Lighting              Ceiling, Observations; Adequate.
         Provisions:
         12.76 15) Heat Observations:    Appears Adequate.
         12.77 17) Trim                  Wood, Trim Observations: Appears adequate.
         Types/Observations:




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                         May 28, 2010                                                          Page23
34145 Pacific Coast Highway Suite 513
                                                                                                         Dana Point CA 92629
                                                                                                         p 949.466.7265 f 661.0581
                                                                                                         www.buildingspecscorp.com



     1212] BEDROOM #5
          12.78 1) Overall Condition:     Closet modified Into wine room. several electrical Concerns observed. repairs recommended.
          12.79 2) Floor Structure:       Adequate.
          12.80 7) Wood / Laminate        Adequate.
          Observations:
          12.81 8) Wall                   Drywall, Plaster, Appears adequate.
          Materials/Observations:
          12.82 9) Ceiling                Drywall, Plaster, Appears adequate.
          Materials/Observations:
          12.83 10) Window                Adequate.
          Observations:
          12.84 11) Door                  Hinged, Observations; Adequate.
          Types/Observations:
          12.85 12) Receptacle            Adequate.
          Observations:
          12.86 13) Lighting              Ceiling, Observations; Adequate.
          Provisions:
          12.87 15) Heat Observations:    Appears Adequate.
          12.88 17) Trim                  Wood, Trim Observations: Appears adequate.
          Types/Observations:
     1213]
          12.89 1) Overall Condition:     Appears in overall adequate condition with no visible concerns to room components.
          12.90 2) Floor Structure:       Bouncy Slightly.
          12.91 7) Wood / Laminate        Adequate.
          Observations:
          12.92 8) Wall                   Drywall, Plaster, Appears adequate.
          Materials/Observations:
          12.93 9) Ceiling                Drywall, Plaster, Appears adequate.
          Materials/Observations:
          12.94 10) Window                Adequate.
          Observations:
          12.95 11) Door                  Sliding, Observations; Adequate.
          Types/Observations:
          12.96 12) Receptacle            Adequate.
          Observations:
          12.97 13) Lighting              Observations; Could Not Locate Or Verify All Switch(s) Function Seller Demonstrate.
          Provisions:
          12.98 15) Heat Observations:    Appears Adequate.
          12.99 17) Trim                  Wood, Trim Observations: Appears adequate.
          Types/Observations:


                                                                  ELECTRICAL
ADDITIONAL COMMENTS Inspection is for visible, exposed wiring only, and is limited to random sampling. New occupants may put different load
demands on the electrical system which can in no way be anticipated. Any repairs should be conducted by a licensed electrician. Rag, cloth wiring,
Knob & Tube, or other should be replaced if sheathing is deteriorating, and are non grounded systems. Aluminum wiring has a history of being a
potential fire hazard and approved connectors should be installed by a licensed electrician. FPE Federal Pacific Panels (Stab-lok) have a history of
failure of the breaker to trip properly. Also see Receptacles under Interior, Bathroom & Basement Report pages.

We are not electricians and in accordance with the standards of practice we only test a representative number of switches and outlets and do not
perform load-calculations to determine if the supply meets the demand. However, every electrical deficiency or recommended upgrade should be
regarded as a latent hazard that should be serviced as soon as possible, along with evaluation and certification of the entire system as safe by a
licensed contractor. Therefore, it is essential that any recommendations that we may make for service or upgrades should be completed before the
close of escrow, because an electrician could reveal additional deficiencies or recommend additional upgrades for which we disclaim any
responsibility. Any electrical repairs or upgrades should be made by a licensed electrician. Smoke Alarms should be installed in all bedrooms at
designated locations, and tested regularly.

Operation of time clock motors is not verified. Inoperative light fixtures often lack bulbs or have dead bulbs installed. The inspector is not required to
insert any tool, probe, or testing device inside the panels, test or operate any over-current device except for ground fault interrupters, nor dismantle
any electrical device or control other than to remove the covers of the main and auxiliary distribution panels. Any ancillary wiring or system that is not
part of the primary electrical distribution system is not part of this inspection but may be mentioned for informational purposes only, including but not
limited to low voltage systems, security system devices, heat detectors, carbon monoxide detectors, telephone, security, cable TV, intercoms, and
built in vacuum equipment.


      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                           May 28, 2010                                                              Page24
34145 Pacific Coast Highway Suite 513
                                                                                                         Dana Point CA 92629
                                                                                                         p 949.466.7265 f 661.0581
                                                                                                         www.buildingspecscorp.com



     1301] SERVICE ENTRY
          13.1 Entry Means:               120/240 Volt system.
          13.2 Wire Size:                 Not Visible due to panel design.
     1302] PANEL(S)
          13.3 MAIN PANEL (AMPS):         Location; Exterior Wall of Building, Left Side of building, 125 amps.
          13.4 Overload Protection:       Breakers.
          13.5 Observations:              Sloppy workmanship, Over Fusing, Risk Of Wire Over-Heating. (
                                          size of wire insufficient to carry load), Missing, Wire Connector(s)




     1303] BRANCH CIRCUITS
          13.6 Wiring Conductor           Copper.
          Materials:
          13.7 Wiring Methodology:        Romex (NM)
     1304] GFCI'S
          13.8 Observations:              Missing In Recommended Areas.
     1305] GROUNDING
          13.9 Observations:              Not Visible.


                                                                   PLUMBING
IMPORTANT INFORMATION: All underground piping related to water supply, waste, or sprinkler use are excluded from this inspection. Leakage,
corrosion or blockage in underground piping cannot be detected by a visual inspection. Plumbing components such as gas pipes, potable water pipes,
drain and vent pipes, and shut-off valves are not generally tested if not in daily use. The inspector cannot state the effectiveness or operation of any
anti-siphon devices, automatic safety controls, water conditioning equipment, fire and lawn sprinkler systems, on-site water quality and quantity,
on-site waste disposal systems, foundation irrigation systems, spa and swimming pool equipment, solar water heating equipment, or observe the
system for proper sizing, design, or use of materials.

The water pressure within pipes is commonly confused with water volume, but whereas high water volume is good high water pressure is not.
Therefore a regulator is recommended whenever street pressure exceeds 80 psi. Regardless of pressure, leaks will occur in any system, and
particularly in one with older galvanized pipes.

Waste and drainpipes pipe condition is usually directly related to their age. Older pipes are subject to damage through decay and root movement,
whereas the more modern ABS pipes are virtually impervious to damage, although some rare batches have been alleged to be defective. Older
homes with galvanized or cast iron supply or waste lines can be obstructed and barely working, and later fail under heavy use. If the water is turned
off or not used for periods of time (such as a vacant house waiting for closing), rust or deposits within the piping can further clog the piping system.
However, inasmuch as significant portions of drainpipes are concealed, we can only infer their condition by observing the draw at drains at the time of
inspection. Nonetheless, blockages will still occur in the life of any system.
     1401] SUPPLY
          14.1 Water Source:              Public Water.
          14.2 A: Main Supply Line        Location of Shut-Off Valve, Right Yard adjacent to building, Copper, 1"
          14.3 Main Line Observations:    Adequate.
          14.4 B: Distribution Lines:     Copper.
          14.5 Distribution Lines         Adequate.
          Observations:
     1402] WASTE
          14.6 Waste Provisions:          Public Sewer.
          14.7 Waste Piping Materials:    Visible areas Plastic, ABS.
          14.8 Observations:              Adequate.
          14.9 A. Traps:                  Plastic, P-Traps.
          14.10 Trap Observations:        Visible Leaks.



      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                          May 28, 2010                                                              Page25
34145 Pacific Coast Highway Suite 513
                                                                                                       Dana Point CA 92629
                                                                                                       p 949.466.7265 f 661.0581
                                                                                                       www.buildingspecscorp.com



    1403] FUEL SYSTEMS
          14.11 Gas Meter:               Location; Left Yard Adjacent To Building, Shut off Valve location, At The Meter, Appears Adequate.
    1407] WATER HEATER #1
          14.12 Location:                Garage.
          14.13 Manufacture Date:        2008.
          14.14 Fuel:                    Gas.
          14.15 Capacity:                40 gallons.
          14.16 Water Heater             Adequate.
          Observations:
          14.17 Combustion Air           Appears adequate.
          14.18 8) FLUE:                 Rigid Metal, Observations: Adequate.
          14.19 Seismic Strapping        Appear Adequate.


                                                   HEATING & COOLING SYSTEMS
The inspector can only readily open access panels provided by the manufacturer or installer for routine homeowner maintenance, and will not operate
components when weather conditions or other circumstances apply that may cause equipment damage. The inspector does not light pilot lights or
ignite or extinguish solid fuel fires, nor are safety devices tested by the inspector. The inspector is not equipped to inspect furnace heat exchangers
for evidence of cracks or holes, or inspect concealed portions of evaporator and condensing coils, heat exchanger or firebox, electronic air filters,
humidifiers and de-humidifiers, ducts and in-line duct motors or dampers, as this can only be done by dismantling the unit. This is beyond the scope
of this inspection. Thermostats are not checked for calibration or timed functions. Adequacy, efficiency or the even distribution of air throughout a
building cannot be addressed by a visual inspection. Have these systems evaluated by a qualified individual. The inspector does not perform
pressure tests on coolant systems, therefore no representation is made regarding coolant charge or line integrity. We perform a conscientious
evaluation of the system, but we are not specialists.

Please note that even modern heating systems can produce carbon monoxide, which in a poorly ventilated room can result in sickness and even
death. Therefore, it is essential that any recommendations we make for service or further evaluation be scheduled before the close of escrow,
because a specialist could reveal additional defects or recommend further upgrades that could affect your evaluation of the property, and our service
does not include any form or warranty or guarantee. Normal service and maintenance is recommended on a yearly basis. Determining the presence
of asbestos materials commonly used in heating systems can ONLY be preformed by laboratory testing and is beyond the scope of this inspection.
Determining the condition of oil tanks, whether exposed or buried, is beyond the scope of this inspection.
    1500] HEATING SYSTEM #1
          15.1 LOCATION &                Attic.
          OVERVIEW:
          15.2 1) TYPE OF SYSTEM:        Forced Air-
          15.3 2] FUEL/ POWER            Natural Gas, Brass Flexible Gas Line Noted, History of Failure.
          SUPPLY:
          15.4 4) FILTER:                Disposable.
          15.5 Filter Location/          Air Return, Filter Observations, Adequate.
          Observation:
          15.6 5) AIR HANDLER:           Adequate.
          15.7 7) DUCTWORK:              Insulated Fiberboard (Fiberglass lined), Plastic Flex, Observations: Disconnected Connection(s) See
                                         return plenum.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                             May 28, 2010                                                          Page26
34145 Pacific Coast Highway Suite 513
                                                                                                         Dana Point CA 92629
                                                                                                         p 949.466.7265 f 661.0581
                                                                                                         www.buildingspecscorp.com




          15.8 8) FLUE:                   Rigid Metal, OBSERVATIONS: Adequate.
          15.9 9) THERMOSTAT:             Adequate.

ADDITIONAL COMMENTS Air conditioners and heat pumps have a life expectancy of 8 to 12 years. Air conditioners and heat pumps are checked
for operation and no remaining life expectancy or warranty is implied. An older unit may be nearing or at the end of it's life. See additional information
for heating systems, ductwork ,filters, etc, below.
     1506] AIR CONDITIONER #1:
          15.10 1] TYPE OF SYSTEM:        Air Conditioner, Split System. (A.C. Unit Not Checked in Temperatures Which Have Been Below 60°F
                                          in the Past 24 Hours.)
          15.11 3) COMPRESSOR             Located At: Left side of building, Not Secured/ Anchored. Unit Not Operational.
          UNIT:
          15.12 Manufacture Date:         2001.
          15.13 Unit Size in Tons:        5.0 tons.
          15.14 4) CONDENSATE:            Disconnected. Abandoned lines.Risk of leaking.




                                 FIREPLACE/CHIMNEY/ENVIRONMENTAL OVERVIEW
ADDITIONAL COMMENTS Internal components of the chimney are not covered under this inspection, such as the inside of the flue. A chimney
specialist should be consulted for this. Annual maintenance must be maintained for maximum safety and to help sustain the life of the unit and its
components. Woodstoves should be inspected by a woodstove expert. All fireplaces should be cleaned and inspected on a regular basis to make sure
that no cracks have developed. Large fires in the firebox can overheat the firebox and flue liners, sometimes resulting in internal damage
     1601] FAMILY ROOM FIREPLACE
          16.1 1] TYPE OF UNIT(S);        Manufactured (Zero Clearance), Gas Log or Wood Burning.
          16.2 2) FIRE BOX:               Panels.
          16.3 Firebox Observations:      Appears adequate.
          16.4 4) DAMPER                  Operating as intended.
          OBERVATIONS:
          16.5 5) FLUE:                   Metal.
          16.6 Flue Observations:         Visible area adequate.
          16.7 Hearth Extension           Inadequate Size /Depth or Width.
      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                           May 28, 2010                                                              Page27
34145 Pacific Coast Highway Suite 513
                                                                                                       Dana Point CA 92629
                                                                                                       p 949.466.7265 f 661.0581
                                                                                                       www.buildingspecscorp.com


         Observations:




         16.8 7) CHIMNEY:                Wood (Flue chase)
         16.9 Chimney Observations:      Adequate.
         16.10 Chimney Cap               Not Accessible (Recommend further evaluation)
         Observations:

ADDITIONAL COMMENTS: Inspector is Not required to evaluate presence of environmental hazards according to most national standards. Any
concerns pointed out during the inspection are based on the inspectors discretion and experience.


                                                      POOL/SPA & EQUIPMENT
CONFIDENTIAL - FOR CLIENT USE ONLY



Inspection was limited to those areas which are above ground or water level. The only way to detect an underground leak in a supply line, buried pipe
fitting, or pool surface crack is by observation of the persistant and continuous loss of water from the pool over an extended period of time.
Purchasers are encouraged to ask sellers about the existance of any past or present leaks in the pool, spa or associated equipment. Pool filtering
devices are not disassembled to determine the condition of any installed filter elements. Operation of time clock motors and thermostatic temperature
controls cannot be verified during a visual inspection. Testing of backflush mechanisms is beyond the scope of this inspection. Pilot lights on gas
pool heaters are not lit during the inspection.
    POOL SURFACE:
         17.1 Type:                      Concrete/Marcite.(Plaster)
         17.2 Condition:                 Fair overall condition.Moderate wear.
         17.3 Pool Coping:               Good overall.
         17.4 Pool/Spa Drains:           Adequate.
    SKIMMER & BASKET:
         17.5 Condition:                 Good.
    POOL LIGHT:
         17.6                            Not operable. If a defective bulb is at fault, replacement will cost $50-100 Otherwise, further evaluation and
                                         repairs will be needed by a licensed electrician.
    PUMPING EQUIPMENT:
         17.7 Pump and Motor             1 HP motor. Good.
         Condition:
         17.8 Hair/Lint Filter:          Good- no significant air bubbles noted.
         17.9 Filter Type:               Diatomaceous earth.
         17.10 Filter Pressure in PSI:   25.
         17.11 Chlorinator: Type:        Chlorine Generator- Inquire with seller about equipment condition and operational procedures.
    VISIBLE PLUMBING LINE:
         17.12 Condition:                Good.
    POOL FILL:
         17.13 TYPE:                     Manual, Adequate.
    HEATERS:
         17.14 Type and Condition:       Natural Gas, Good visual condition.




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                         May 28, 2010                                                              Page28
34145 Pacific Coast Highway Suite 513
                                                                                                 Dana Point CA 92629
                                                                                                 p 949.466.7265 f 661.0581
                                                                                                 www.buildingspecscorp.com



    ELECTRIC CONTROLS:
         17.15 Subpanels:              Good.
         17.16 Timers:                 Good.
         17.17 Electrical Bonding      Good.
    POOL DECKING:
         17.18 Type:                   Concrete
         17.19 Condition:              Adequate, No concerns visible.
         17.20 Child Protection        Good.
         Fencing:




      This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon
     therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or
observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or
             company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading.

Report #Sample Report                       May 28, 2010                                                        Page29
BuildingInspecs.com - Sample Report
BuildingInspecs.com - Sample Report
BuildingInspecs.com - Sample Report

Weitere ähnliche Inhalte

Mehr von Justin Macduff

Pccc july2010-newsletter
Pccc july2010-newsletterPccc july2010-newsletter
Pccc july2010-newsletterJustin Macduff
 
Membership renewal 2010
Membership renewal 2010Membership renewal 2010
Membership renewal 2010Justin Macduff
 
Membership renewal 2010
Membership renewal 2010Membership renewal 2010
Membership renewal 2010Justin Macduff
 
Global Home USA: Home Warranty 1 year
Global Home USA: Home Warranty 1 yearGlobal Home USA: Home Warranty 1 year
Global Home USA: Home Warranty 1 yearJustin Macduff
 
Home Improvement Costs
Home Improvement CostsHome Improvement Costs
Home Improvement CostsJustin Macduff
 
Full House Inspections Sample Report
Full House Inspections Sample ReportFull House Inspections Sample Report
Full House Inspections Sample ReportJustin Macduff
 

Mehr von Justin Macduff (10)

PCCC Archive 8/9/2007
PCCC Archive 8/9/2007PCCC Archive 8/9/2007
PCCC Archive 8/9/2007
 
Pccc july2010-newsletter
Pccc july2010-newsletterPccc july2010-newsletter
Pccc july2010-newsletter
 
Membership renewal 2010
Membership renewal 2010Membership renewal 2010
Membership renewal 2010
 
Membership renewal 2010
Membership renewal 2010Membership renewal 2010
Membership renewal 2010
 
Membershiprenewal2010
Membershiprenewal2010Membershiprenewal2010
Membershiprenewal2010
 
PCCC June Newsletter
PCCC June NewsletterPCCC June Newsletter
PCCC June Newsletter
 
Global Home USA: Home Warranty 1 year
Global Home USA: Home Warranty 1 yearGlobal Home USA: Home Warranty 1 year
Global Home USA: Home Warranty 1 year
 
Ahwa90
Ahwa90Ahwa90
Ahwa90
 
Home Improvement Costs
Home Improvement CostsHome Improvement Costs
Home Improvement Costs
 
Full House Inspections Sample Report
Full House Inspections Sample ReportFull House Inspections Sample Report
Full House Inspections Sample Report
 

Kürzlich hochgeladen

Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...lizamodels9
 
Famous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st CenturyFamous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st Centuryrwgiffor
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear RegressionRavindra Nath Shukla
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Dipal Arora
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 DelhiCall Girls in Delhi
 
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxB.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxpriyanshujha201
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...Paul Menig
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...Aggregage
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayNZSG
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Delhi Call girls
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
Understanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key InsightsUnderstanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key Insightsseri bangash
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesDipal Arora
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...Any kyc Account
 
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...Suhani Kapoor
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfPaul Menig
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒anilsa9823
 
Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Roland Driesen
 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsMichael W. Hawkins
 

Kürzlich hochgeladen (20)

Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 
Famous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st CenturyFamous Olympic Siblings from the 21st Century
Famous Olympic Siblings from the 21st Century
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear Regression
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
 
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxB.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
 
Understanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key InsightsUnderstanding the Pakistan Budgeting Process: Basics and Key Insights
Understanding the Pakistan Budgeting Process: Basics and Key Insights
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
KYC-Verified Accounts: Helping Companies Handle Challenging Regulatory Enviro...
 
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdf
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
 
Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...
 
HONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael HawkinsHONOR Veterans Event Keynote by Michael Hawkins
HONOR Veterans Event Keynote by Michael Hawkins
 

BuildingInspecs.com - Sample Report

  • 1. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com Confidential Inspection Report For Sample Report 12345 Your Street Newport Beach, California Date 01/05/2010 Prepared by: Building Specs Inc. 34145 Pacific Coast Highyway; Suite 513 Dana Point, Ca 92629 949-494-5624 Info@buildingspecscorp.com This report is the exclusive property of the inspection company and the client whose name appears herewith and its use by any unauthorized persons is prohibited. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page1
  • 2. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com Report Table of Contents GENERAL INFORMATION 9 GROUNDS 10 FOUNDATION & STRUCTURE 11 EXTERIOR SURFACES 12 ROOFS 13 DOORS, WINDOWS, ENERGY CONSERVATION 14 ATTIC 14 GARAGE & CARPORT 16 SAFETY 17 KITCHEN & APPLIANCES 18 BATHROOM(s) 20 INTERIOR 21 ELECTRICAL 24 PLUMBING 25 HEATING & COOLING SYSTEMS 26 FIREPLACE/CHIMNEY/ENVIRONMENTAL OVERVIEW 27 POOL/SPA & EQUIPMENT 28 This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page2
  • 3. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com Inspection Report For Sample Report 12345 Your Street Newport Beach, California Date 01/05/2010 As requested, we have performed a property inspection report for the address above. Thank you for choosing BUILDING SPECS INC. to perform a visual inspection on the above property. We've taken great pride developing a reporting system we feel is unique to the industry. It's with pleasure that we submit it to you at this time. You are encouraged to read the entire report, as it will give you a detailed overview of the general condition of the property. Please understand an inspection is intended to assist you in evaluating the overall condition of the property. The inspection report is an aid to help you make a more informed purchasing decision. Also understand that there are limitations to this inspection. Many components of the building are not visible during the inspection and very little historical information is provided in advance of the inspection. While we can reduce your risk of purchasing the building, we cannot eliminate it, nor can we assume it. Even the most comprehensive inspection cannot be expected to reveal every condition you may consider significant to ownership. The inspection is based on observation of the visible and apparent condition of the building and its components on the date of the inspection. It is not intended to make any representation regarding latent or concealed defects that may exist. It is not intended for cosmetic or aesthetic evaluation. Photographs, when provided, are simply a tool to convey our findings, they are not intended to enhance those findings or diminish any findings not photographed. BUILDING SPECS, INC. follows the standards of practice and code of ethics established by the California Real Estate Inspection Association. These can be reviewed at www.creia.org/i4a/pages/index.cfm?pageid=3283 If you have any questions regarding this report or the condition of the property, please feel free to call anytime. Rick Yerger BUILDING SPECS, INC This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page3
  • 4. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com Inspection Summary NOTENOTENOTE: Client Must Read Entire Report And Not Rely Solely On The Summary Notes. Clien summary notes. CLIENT: Sample Report INSPECTION ADDRESS: 12345 Your Street Newport Beach, California PRIORITY #1 MAJOR: Immediate repairs, service, upgrades and/or Further Evaluation recommended by the appropriate licensed contractor and/or appropriate professional prior to close of escrow. GENERAL INFORMATION 101] INSPECTION: 1.4 Overall Building Condition; What may be possible modifications to building. Client is advised to request all documentation and building permits for work observed. If no documentation is available the client should be aware these components may not have been properly installed and may pose adverse conditions. Bedroom(s) GROUNDS 206] LANDSCAPE PLANTERS 2.10 Observations: Substandard fabrication. Concern for moisture infiltration. Planter is raised above interior floor line and tight against exterior wall. lacking capillary break (air space). Located Rear Side of Building. 215] AUXILIARY STRUCTURES (Outside the scope of our inspection. Consult with specialist for operation & maintenance) 2.20 Observations: Loose, Tip Concern. Recommend verifying fountains are mechanically secured for safety. Substandard Electrical Wiring. Extension cord or exposed wiring. Located Rear Side of Building. EXTERIOR SURFACES 500] SIDING MATERIAL 4.1 Conditions Noted: At or Below Grade, Susceptible to Rot and or Wood Destroying Insect Damage, Located Left Side of Building, Located Rear Side of Building. 505] SOFFIT 4.10 Observations: Water Stains , suggests possible roof leak. Located Front Side of Building. 509] ELECTRICAL 4.11 Observations: Substandard hazardous Wring several locations, Located Rear Side of Building. Receptacles- Recommended GFCI, Located Rear Side of Building. ROOFS 600] ROOF 5.1 General Comments: Repairs Recommended, Recommend Further Evaluation by a Qualified Roofing Contractor. Client is advised to Have This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page4
  • 5. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com Roof and all Related components Evaluation by Roofing Contractor Prior to Purchase. 608] TILE/ SLATE 5.4 Observations: Exposed Fasteners (Nails), Over Exposed (inadequate Lap), Weather-Seals cracking/loose/missing, At or Nearing End of Life. Cracking at isolated areas. DOORS, WINDOWS, ENERGY CONSERVATION 810] WATER HEATER 6.14 Temperature: 140-160 F- A scalding hazard exists. ATTIC 900] ATTIC AREAS 7.1 General Comments: Repairs Recommended, Further Evaluation Recommended. 902] ATTIC FRAME 7.4 Truss/ Rafter Observation: Trusses have been cut, notched, Field repaired or modified. Improper, Refer To the Truss Manufacturer or a Structural engineer for a Course of action. 904] MOISTURE, STAINS 7.11 Related to? Chimney(s) 907] ATTIC LIGHT(S) 7.13 Observations: Substandard Installation (sloppy Improper wiring or materials) Safety Concern. 910] FIREPLACE FLUE(S) 7.17 Observation: Clearances to combustible material inadequate. see cellulose insulation, Recommend repairs by certified chimney sweep. GARAGE & CARPORT 916] OVERALL CONDITION 8.2 1) Overall Condition: Water Stains- Walls, Ceiling, Unknown source, repair cause & effect. 917] ATTACHED? 8.3 If Yes; Fire Rated Fire Walls Damaged or Breached at; Ceiling. Not able to verify the presence of fire assembly at water heater platform. Recommended. 918] GARAGE VEHICLE DOOR(S) 8.7 Garage Opener Observations: photoelectric Safety Eye too High. 6" Max off Grade. Safety. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page5
  • 6. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 920] GARAGE RECEPTACLES 8.9 Observations: Ground Fault Circuit Interrupters Recommended. 921] GARAGE LIGHTING 8.10 Observations: Substandard workmanship, Repairs by qualified individual recommended. KITCHEN & APPLIANCES 1003.C] Sink Drains 10.10 Observations: Substandard Installation or Materials, Prone to Leak/Fail, Leaks. 1003.D] Disposal 10.11 Observations: Improper, Unrated power Cord. 1007] Dishwasher 10.16 Observations: Air gap missing, Concern for back siphoning into dishwasher. 1009] Oven 10.19 Observations: Handle damaged. INTERIOR 1202] FAMILY ROOM 12.20 14) Ceiling Fan Observations: Inoperable. 1212] BEDROOM #5 12.78 1) Overall Condition: Closet modified Into wine room. several electrical Concerns observed. repairs recommended. ELECTRICAL 1302] PANEL(S) 13.3 MAIN PANEL (AMPS): Location; Exterior Wall of Building, Left Side of building, 125 amps. 13.5 Observations: Sloppy workmanship, Over Fusing, Risk Of Wire Over-Heating. ( size of wire insufficient to carry load), Missing, Wire Connector(s) HEATING & COOLING SYSTEMS 1500] HEATING SYSTEM #1 15.7 7) DUCTWORK: Insulated Fiberboard (Fiberglass lined), Plastic Flex, Observations: Disconnected Connection(s) See return plenum. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page6
  • 7. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 1506] AIR CONDITIONER #1: 15.14 4) CONDENSATE: Disconnected. Abandoned lines.Risk of leaking. FIREPLACE/CHIMNEY/ENVIRONMENTAL OVERVIEW 1601] FAMILY ROOM FIREPLACE 16.7 Hearth Extension Observations: Inadequate Size /Depth or Width. PRIORITY #2 MARGINAL: Repairs, service, replacement and/or upgrades are recommended by the appropriate professional in the near future. Items are declining in usefulness or ability to perform purpose. GROUNDS 208] FENCE (limited to contact w/ house) 2.14 Observations: Loose, Located Rear Side of Building. EXTERIOR SURFACES STUCCO 4.3 Observations: Weep Screed Below Grade, Susceptible to Allow Moisture Infiltration. 501] PAINTS & SEALANT(S) 4.6 Observations: Weathered (Susceptible To Water Infiltration and/or Damage) GARAGE & CARPORT 922] GARAGE WALLS/CEILING 8.12 Wall/Ceiling Observations: Moisture Stains, using a moisture meter, no active moisture present. May indicate prior or active water infiltration. Monitor for activity. Repairs may become necessary. at water heater. Mildew/Mold like material (Raised, Fuzzy, Discoloration) Observed. Recommend Further evaluation by a Mold identification/Removal contractor. 923] VENTILATION 8.13 Screens Damaged, potential for animal intrusion. BATHROOM(s) 1104] MASTER BATH 11.61 C. Shower Doors: Seals Failing. HEATING & COOLING SYSTEMS 1506] AIR CONDITIONER #1: 15.11 3) COMPRESSOR UNIT: This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page7
  • 8. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com Located At: Left side of building, Not Secured/ Anchored. Unit Not Operational. POOL/SPA & EQUIPMENT POOL LIGHT: 17.6 Not operable. If a defective bulb is at fault, replacement will cost $50-100 Otherwise, further evaluation and repairs will be needed by a licensed electrician. PRIORITY #3 NOTES: General notes, comments and/or Recommended Maintenance and/or Recommended upgrades for increased safety or to enhance buildings performance. BATHROOM(s) 1102] FIRST FLOOR HALL BATH 11.13 B. Tub Faucets: unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs Recommended. 1104] MASTER BATH 11.54 B. Tub Faucets: unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs Recommended. 11.63 E. Shower Valves: unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs Recommended. INTERIOR 1213] 12.97 13) Lighting Provisions: Observations; Could Not Locate Or Verify All Switch(s) Function Seller Demonstrate. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page8
  • 9. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com GENERAL INFORMATION IMPORTANT INFORMATION:It is the sole responsibility of the client to read each page of this report. The client is responsible to research any and all jurisdictions permits required by the local authorities regarding the property in contract before the close of escrow. You, the client, are to personally perform a diligent visual inspection of the property after the seller vacates to insure the no "conditions" was concealed by personal property and/or stored items while occupied or that may have been damaged during he seller's evacuation of the building. Should any "conditions" be revealed that was not address within this report prior to or after the close of escrow, please contact our office immediately for an additional evaluation regarding such "conditions". 100] CLIENT 1.1 Name: Sample Report. 1.2 Date: 01/05/2010. Inspection Performed According To The Standards Of Practice Of The California Real Estate Inspection Association. These can be viewed at www.creia.org/i4a/pages/index.cfm?pageid=3283 101] INSPECTION: 1.3 Building Status; Vacant, A vacant house may not show evidence of water or moisture leaks or problems until the house has been occupied for a period of time and the fixtures have been in use. 1.4 Overall Building Condition; What may be possible modifications to building. Client is advised to request all documentation and building permits for work observed. If no documentation is available the client should be aware these components may not have been properly installed and may pose adverse conditions. Bedroom(s) 1.5 Street: 12345 Your Street. 1.6 City: Newport Beach. 1.7 State: California. 1.8 County: Orange. 1.9 Country: U.S.A. 1.10 Type of Building: Residential. 1.11 Style of House: Two Story. 102] TYPE OF INSPECTION(S) ORDERED 1.11 Standard Inspection. 104] CONDITIONS 1.12 *Age of Building 13 years. Weather Conditions 1.13 Temperature Approx. ° F 60-70. 1.14 Weather Conditions Previous Rain- 1-week Partly Cloudy. 1.15 People Present During Buyer, Buyer's Agent. Inspection: 1.16 Client Accompanied 100% Inspector: Time 1.17 Started: 10:30 am. 1.18 Completed: 1:00/1:30 pm. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page9
  • 10. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 105] INSPECTOR(S) 1.19 Rick Yerger. ADDITIONAL COMMENTS If the building is occupied, furniture, boxes, rugs, wall coverings, storage and other personal items may block, cover or impede inspection, a re-inspection is recommended prior to purchase. A vacant house may not show an active water or moisture problems until it has been occupied and the plumbing is in use for a period of time. GROUNDS IMPORTANT INFORMATION: This inspection is not intended to address or include any geological conditions or site stability information. We do not comment on coatings or cosmetic deficiencies, which would be apparent to the average person. Any reference to grade is limited to only areas around the exterior of the exposed areas of foundation or exterior walls. We cannot determine drainage performance of the site or the condition of any underground piping, including subterranean drainage systems and municipal water and sewer service piping or septic systems , Client is advised to have these items inspected and tested by the Appropriate Qualified person(s). Any areas too low to enter or not accessible are excluded from the inspection. We do not evaluate any detached structures such as storage sheds and stables, nor mechanical or remotely controlled components such as driveway gates. We do not evaluate or move landscape components such as trees, shrubs, fountains, ponds, statuary, pottery, fire pits, patio fans, heat lamps, and decorative or low-voltage lighting. Any such mention of these items is informational only and not to be construed as inspected. GROUNDS 2.1 General Comments: Appears adequate at this time. 200] CONDITIONS 2.2 Observations: Damp. 201] DRAINAGE NEXT TO HOUSE 2.3 Grade Type: Near Level. 2.4 Observations: Appears adequate at this time. 202] EROSION 2.5 Observations: None observed. 203] TREES, BUSHES 2.6 Observations: Appears adequate at this time. 204] STOOP, STAIRS 2.7 General Comments: Appears adequate at this time. 205] WALKWAY(S) 2.8 Materials: Concrete. 2.9 Observations: Appears adequate. 206] LANDSCAPE PLANTERS 2.10 Observations: Substandard fabrication. Concern for moisture infiltration. Planter is raised above interior floor line and tight against exterior wall. lacking capillary break (air space). Located Rear Side of Building. 207] DRIVEWAY 2.11 Materials: Concrete. 2.12 Observations: Appears adequate. 208] FENCE (limited to contact w/ house) 2.13 Material: Wood, Vinyl Clad. 2.14 Observations: Loose, Located Rear Side of Building. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page10
  • 11. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 209] BASEMENT ENTRY WALL 2.15 Overview: Not applicable. 210] RETAINING WALL 2.16 Material: Not applicable. 211] FOUNDATION VENTS 2.17 Observations: Not applicable. 212] FOUNDATION WINDOWS 2.18 Observations: Not applicable. 213] FOUNDATION CRAWLSPACE ACCESS 2.19 Observations: Not applicable. 215] AUXILIARY STRUCTURES (Outside the scope of our inspection. Consult with specialist for operation & maintenance) 2.20 Observations: Loose, Tip Concern. Recommend verifying fountains are mechanically secured for safety. Substandard Electrical Wiring. Extension cord or exposed wiring. Located Rear Side of Building. ADDITIONAL COMMENTS: Low voltage Lighting and Landscape Sprinklers are excluded. We recommend having these systems demonstrated to you. Underground drainage piping systems are not tested for operation, Client should have these systems demonstrated to you. FOUNDATION & STRUCTURE IMPORTANT INFORMATION: In accordance with our standards of practice, we identify foundation types and look for any evidence of structural deficiencies. However, minor cracks or deteriorated surfaces are common in many foundations and most do not represent a structural problem. Any cracks or water damage should be repaired and monitored as needed by a licensed or qualified individual. Severe problems such as major cracking, amateur work or water damage could lead to a structural failure. If major cracking is visible we recommend further evaluation by a structural engineer. Any cracks need to be monitored to determine if active or from previous movement. All exterior grades should allow for surface and roof water to flow away from the foundation. All concrete floor slabs experience some degree of cracking due to shrinkage in the curing process. In most instances floor coverings prevent recognition of cracks or settlement in all but the most severe cases. Where carpeting and other floor coverings are installed, the materials and condition of the flooring underneath cannot be determined. Areas hidden from view by finished walls or stored items cannot be judged and are not a part of this inspection. However, we are not specialists, and in the absence of any major defects, we may not recommend that you consult with a foundation contractor, a structural engineer, or a geologist, but this should not deter you from seeking the opinion of any such expert. We also routinely recommend that inquiry be made with the seller about knowledge of any prior foundation or structural repairs. FOUNDATION 3.1 General Comments: Limited or No Access For Evaluation. B] Water Damage 3.2 Signs of Water Damage? None Observed. BOLTS & BRACING 3.3 Observations: Not Visible due to construction design. 308] WOOD FRAMING 3.4 A] Style: Platform. 3.5 Observations: Appears Adequate. 3.6 B) Floor Structure: Not Visible Could Not Evaluate Internal Components. 3.7 Observations: Appears Adequate. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page11
  • 12. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com EXTERIOR SURFACES ADDITIONAL COMMENTS: 500] SIDING MATERIAL 4.1 Conditions Noted: At or Below Grade, Susceptible to Rot and or Wood Destroying Insect Damage, Located Left Side of Building, Located Rear Side of Building. 4.2 Predominant Material STUCCO. Type(s): STUCCO 4.3 Observations: Weep Screed Below Grade, Susceptible to Allow Moisture Infiltration. SHINGLES / CLAPBOARD / PREFAB PANELS 4.4 Style: Located Rear Side of Building. 501] PAINTS & SEALANT(S) 4.5 Type: Paint. 4.6 Observations: Weathered (Susceptible To Water Infiltration and/or Damage) 503] TRIM 4.7 Type: Wood. 505] SOFFIT 4.8 Type: Wood, Exposed Rafter Tails. 4.9 Venting Yes, Partial. 4.10 Observations: Water Stains , suggests possible roof leak. Located Front Side of Building. 509] ELECTRICAL 4.11 Observations: Substandard hazardous Wring several locations, Located Rear Side of Building. Receptacles- Recommended GFCI, Located Rear Side of Building. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page12
  • 13. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com ROOFS Although not required to, we generally attempt to evaluate various roof types by walking on their surfaces. If we are unable or unwilling to do this for any reason, we will indicate the method used to evaluate them. Every roof will wear differently relative to its age, number of layers, quality of material, method of application, exposure to weather conditions, and the regularity of its maintenance. W e can only offer an opinion of the general quality and condition of the roofing material. The inspector cannot and does not offer an opinion or warranty as to whether the roof leaks or may be subject to future leakage. The waterproof membrane beneath roofing materials is generally concealed and cannot be examined without removing the roof material. Although roof condition can be evaluated, it is virtually impossible for anyone to detect a leak except as it is occurring or by specific water tests, which are beyond the scope of our service. Even water stains on ceilings or on framing within attics will not necessarily confirm an active leak without some corroborative evidence, and such evidence can be deliberately concealed. We cannot predict roofing materials remaining life expectancy, or guarantee that it will not leak. Naturally, the sellers or the occupants of a residence will generally have the most intimate knowledge of the roof and of its history. Therefore, we recommend that you ask the sellers about it, and that you either include comprehensive roof coverage in your home insurance policy. We do not inspect attached accessories including by not limited to solar systems, antennae, and lightning arrestors. 600] ROOF 5.1 General Comments: Repairs Recommended, Recommend Further Evaluation by a Qualified Roofing Contractor. Client is advised to Have Roof and all Related components Evaluation by Roofing Contractor Prior to Purchase. 602] ACCESS 5.2 Inspection Restricted for Height. following reasons- 608] TILE/ SLATE 5.3 Material Type:. Barrel Concrete Tiles. 5.4 Observations: Exposed Fasteners (Nails), Over Exposed (inadequate Lap), Weather-Seals cracking/loose/missing, At or Nearing End of Life. Cracking at isolated areas. 612] VENTILATION 5.5 Type: Soffit, Dormer. 613] STRUCTURE 5.6 Observations: Appears Adequate. 615] GUTTERS 5.7 Type: Aluminum. 5.8 Observations: Appears Adequate. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page13
  • 14. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com DOORS, WINDOWS, ENERGY CONSERVATION ADDITIONAL COMMENTS 800] ENTRY(S) 6.1 Predominant Door Type: Single. 6.2 Material: Metal. Door Condition: 6.3 Door Observations: Adequate. ADDITIONAL COMMENTS Exterior sealants must be maintained to prevent water infiltration and damage. Single glaze or aluminum sash windows may condensate inside. Reporting of failing thermal pane seals (glazing) in beyond the scope of the inspection. The inspector may report on apparent failing thermal pane seals if visible at the time of the inspection. Some failing seals may become visible as the weather and daylight conditions change. STYLE(S) 6.4 Predominant Style: Gliding. 6.5 Frames & Sashes: Aluminum. 6.6 Glass & Glazing: Double Glaze. 804] INSULATED GLAZING 6.7 Insulated Glazing in Use? Yes, Double. 805] STORM WINDOWS 6.8 Present? Not Applicable. 806] DOORS 6.9 Insulated? No. 6.10 Storm Doors Present? No. 809] INSULATION 6.11 Installed at Walls? N/V. 6.12 Installed at Ceilings? Yes. 6.13 Depth: 10 inches. 810] WATER HEATER 6.14 Temperature: 140-160 F- A scalding hazard exists. ADDITIONAL COMMENTS Maintaining the water heater temperature to 125° F to help reduce the chance of scalding and burns. This will also help you save money on energy. 811] DUCT WORK 6.15 Insulated? Yes. 812] ATTIC VENTILATION 6.16 Observations: Adequate. 813] APPLIANCES 6.17 Observations: Medium Efficiency. ATTIC ADDITIONAL COMMENTS Attics with boxes, etc. could impede inspection and be a possible fire hazard. Attics that are not accessible or blocked to the Inspector should be reinspected . DO NOT attempt to repair damaged trusses without a repair detail from the Truss Manufacturer or a Design Professional. 900] ATTIC AREAS 7.1 General Comments: Repairs Recommended, Further Evaluation Recommended. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page14
  • 15. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 901] ATTIC ACCESS 7.2 Viewing Method: Pull Down Stairs. 902] ATTIC FRAME 7.3 Trusses 24"oc, Wood. 7.4 Truss/ Rafter Observation: Trusses have been cut, notched, Field repaired or modified. Improper, Refer To the Truss Manufacturer or a Structural engineer for a Course of action. 7.5 Ridge Pole Observations: None. 7.6 Purlins Observation : Not Applicable. 7.7 Collar Ties Observations: Not Applicable. 903] ROOF SHEATHING 7.8 Material Type: Oriented Strand Board (OSB) 7.9 Observations: Adequate. 904] MOISTURE, STAINS 7.10 Observed? Yes. 7.11 Related to? Chimney(s) 905] ATTIC INSULATION 7.12 Type Of Insulation: Loose Fill, Depth, 6-8" 907] ATTIC LIGHT(S) 7.13 Observations: Substandard Installation (sloppy Improper wiring or materials) Safety Concern. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page15
  • 16. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 908] ATTIC PLUMBING 7.14 Observations: Adequate. 909] ATTIC VENTILATION 7.15 Venting Type: Dormer, Soffit. 7.16 Observations: Adequate. 910] FIREPLACE FLUE(S) 7.17 Observation: Clearances to combustible material inadequate. see cellulose insulation, Recommend repairs by certified chimney sweep. GARAGE & CARPORT ADDITIONAL COMMENTS If slab and walls are covered with personal items, the inspection may be blocked or impeded. Recommend a final walk-through when area is cleared. Auto safety reverse devices are recommended for an overhead garage door; however, the impact-style are not tested since damage could result to the door. NOTE: any repairs to the garage door and door components must be performed by a trained door systems technician. 915] GARAGE & CARPORT 8.1 General Comments: Present. 916] OVERALL CONDITION 8.2 1) Overall Condition: Water Stains- Walls, Ceiling, Unknown source, repair cause & effect. 917] ATTACHED? 8.3 If Yes; Fire Rated Fire Walls Damaged or Breached at; Ceiling. Not able to verify the presence of fire assembly at water heater platform. Recommended. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page16
  • 17. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 918] GARAGE VEHICLE DOOR(S) 8.4 # of Garage Doors & 2 Metal. Type: 8.5 Garage Door Adequate. Observations: 8.6 Garage Door Auto Yes. Opener? 8.7 Garage Opener photoelectric Safety Eye too High. 6" Max off Grade. Safety. Observations: 919] GARAGE SLAB / APRON 8.8 Evidence of Cracking? No. 920] GARAGE RECEPTACLES 8.9 Observations: Ground Fault Circuit Interrupters Recommended. 921] GARAGE LIGHTING 8.10 Observations: Substandard workmanship, Repairs by qualified individual recommended. 922] GARAGE WALLS/CEILING 8.11 3) Walls/Ceiling Drywall, Plaster. Materials: 8.12 Wall/Ceiling Moisture Stains, using a moisture meter, no active moisture present. May indicate prior or active water Observations: infiltration. Monitor for activity. Repairs may become necessary. at water heater. Mildew/Mold like material (Raised, Fuzzy, Discoloration) Observed. Recommend Further evaluation by a Mold identification/Removal contractor. 923] VENTILATION 8.13 Screens Damaged, potential for animal intrusion. SAFETY ADDITIONAL COMMENTS: inspector will note the presence of smoke detectors but not test for operation. Buyer is responsible for testing prior to closing escrow. 926] SMOKE ALARMS 9.1 Observations; Yes. ADDITIONAL COMMENTS Carbon Monoxide monitors are recommended on all floors with any type of combustion units; such as fireplace, wood stove, oil furnace and gas furnace. Carbon monoxide is a colorless, odorless gas that can cause nausea, headaches and even death. Keyed deadbolts should have key readily accessible in case of fire. 927] CARBON MONOXIDE DETECTORS 9.2 Present? No. 928] FIRE SPRINKLER 9.3 Present? No. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page17
  • 18. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 929] ALARM SYSTEM 9.4 Present? No. 930] DEAD BOLTS 9.5 Present? Yes. 931] WINDOW LOCKS 9.6 Present? Yes. 932] FALL CONCERNS 9.7 Present? No. 933] TRIP CONCERNS 9.8 Present? None Observed. 934] SAFETY GLASS 9.9 Adequate. KITCHEN & APPLIANCES ADDITIONAL COMMENTS 1001] CABINETS 10.1 Materials: Solid Wood. 10.2 Surface Finish: Painted. 10.3 Observations: Adequate. 1002] COUNTER(S) 10.4 Materials: Marble, Granite, Stone. 10.5 Observations: Adequate. 1003] SINK(S) 10.6 Material: Stainless. 10.7 Observation: Adequate. 1003.A] Sink Faucets 10.8 Observations: Adequate. 1003.B] Sink Spray 10.9 Observations: Adequate. 1003.C] Sink Drains 10.10 Observations: Substandard Installation or Materials, Prone to Leak/Fail, Leaks. 1003.D] Disposal 10.11 Observations: Improper, Unrated power Cord. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page18
  • 19. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 1004] FLOOR 10.12 Visible Areas: Wood. 10.13 Observations: Adequate. 1005] RECEPTACLE 10.14 Observations: Adequate. ADDITIONAL COMMENTS Appliances are checked for operation, no life expectancy is implied or given. A separate warranty may be available. An older unit may be nearing the end of it's useful life. Appliances should be monitored and maintained routinely. We routinely recommend a metal dryer vent, vinyl may be a potential fire hazard. Excluded items are not evaluated, Client may want to have excluded items serviced. 1006) Exhaust Discharge Hood 10.15 Observations: Adequate. 1007] Dishwasher 10.16 Observations: Air gap missing, Concern for back siphoning into dishwasher. 1008] Refrigerator 10.17 Observations: None. 1009] Oven 10.18 Fuel Type: Gas. 10.19 Observations: Handle damaged. 1010] Range 10.20 Range/Fuel Type: Gas. 10.21 Observations: Adequate. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page19
  • 20. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 1011] Microwave 10.22 Observations: Adequate. 1012] Compactor 10.23 Observations: None. 1013] Clothes Washer 10.24 Observations: None. 1014] Clothes Dryer 10.25 Observations: None. BATHROOM(s) ADDITIONAL COMMENTS A ground fault interrupter is recommended within 6' of all water sources to prevent electrical shock. Caulking must be maintained at all shower and tub wall fixtures and penetrations to help prevent water damage to the wall and adjacent floor. Inspection does not include towel bars, etc. 1102] FIRST FLOOR HALL BATH 11.1 2) TOILET Base of toilet not sealed to floor, recommended for sanitation. Observations: 11.2 4) SINKS: Built In. 11.3 Sink(s) Observations: Adequate. 11.4 A. Sink Faucets: Adequate. 11.5 B. Sink Drains: Adequate. 11.6 C. Cabinet: Water Stains, Damage. 11.7 5) COUTERS TOPS Stone. 11.8 Counter Observations: Adequate. 11.9 6) TUB Fiberglass. 11.10 Tub Observations: Adequate. 11.11 A. Tub Wall Type Fiberglass. 11.12 Tub Wall Observations: Adequate. 11.13 B. Tub Faucets: unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs Recommended. 11.14 C. Tub Drains: Adequate. 11.15 7) SHOWER TYPE In Tub. 11.16 D. Shower Head: Adequate. 11.17 8) VENTILATION Adequate. Observations: 11.18 9) HEAT REGISTERS: FAU ( Forced Air Unit), Observations: Adequate. 11.19 10) FLOORING TYPE: Hardwood Planks, Tiles. 11.20 Flooring Observations: Adequate. 11.21 11) LIGHTING Adequate. 1103] SECOND FLOOR HALL BATH 11.22 2) TOILET Adequate. Observations: 11.23 4) SINKS: Built In. 11.24 Sink(s) Observations: Adequate. 11.25 A. Sink Faucets: Adequate. 11.26 B. Sink Drains: Adequate. 11.27 C. Cabinet: Adequate. 11.28 5) COUTERS TOPS Ceramic Tile. 11.29 Counter Observations: Adequate. 11.30 6) TUB Fiberglass. 11.31 Tub Observations: Adequate. 11.32 A. Tub Wall Type Fiberglass. 11.33 Tub Wall Observations: Adequate. 11.34 7) SHOWER TYPE In Tub. 11.35 B. Water Damaged None. Areas: 11.36 D. Shower Head: Adequate. 11.37 8) VENTILATION Window, Minimal. Observations: 11.38 9) HEAT REGISTERS: FAU ( Forced Air Unit), Observations: Adequate. 11.39 10) FLOORING TYPE: Ceramic, Marble Tile. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page20
  • 21. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 11.40 Flooring Observations: Adequate. 11.41 11) LIGHTING Adequate. 1104] MASTER BATH 11.42 2) TOILET Adequate. Observations: 11.43 4) SINKS: Built In, Multiple Basins- Two noted. 11.44 Sink(s) Observations: Adequate. 11.45 A. Sink Faucets: Adequate. 11.46 B. Sink Drains: Adequate. 11.47 C. Cabinet: Adequate. 11.48 5) COUTERS TOPS Stone. 11.49 Counter Observations: Adequate. 11.50 6) TUB Fiberglass. 11.51 Tub Observations: Adequate. 11.52 A. Tub Wall Type Fiberglass. 11.53 Tub Wall Observations: Adequate. 11.54 B. Tub Faucets: unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs Recommended. 11.55 C. Tub Drains: Adequate. 11.56 7) SHOWER TYPE Stall. 11.57 Shower Pan: Fiberglass, Observations: Adequate. 11.58 A. Shower Wall Type Fiberglass. 11.59 Shower Wall Adequate. Observations: 11.60 B. Water Damaged None. Areas: 11.61 C. Shower Doors: Seals Failing. 11.62 D. Shower Head: Adequate. 11.63 E. Shower Valves: unconventional valve. Hot and Cold positions technically backwards. Risk of scalding. repairs Recommended. 11.64 8) VENTILATION Adequate. Observations: 11.65 9) HEAT REGISTERS: FAU ( Forced Air Unit), Observations: Adequate. 11.66 10) FLOORING TYPE: Carpet. 11.67 Flooring Observations: Adequate. 11.68 11) LIGHTING Adequate. 11.69 12) RECEPLACLE Adequate. Observations: INTERIOR Our inspection of living space includes the visually accessible areas of walls, floors, cabinets and closets, and the testing of a representative number of windows and doors, switches and outlets. We do not evaluate window treatments, move furnishings or possessions, lift carpets or rugs, empty closets or cabinets, nor comment on cosmetic deficiencies. W e may not comment on cracks that appear around windows and doors, along lines of framing members or along seams of drywall and plasterboard. These are typically caused by minor movement, such as wood shrinkage, common settling, and seismic activity, and will often reappear if they are not correctly repaired. Such cracks can become the subject of disputes, and are therefore best evaluated by a specialist. Floor covering damage or stains may be hidden by furniture, and the condition of floors underlying floor coverings is not inspected. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. Check with owners for further information. Testing, identifying, or identifying the source of environmental pollutants or odors (including but not limited to lead, mold, allergens, odors from household pets and cigarette smoke) is beyond the scope of our service, but can become equally contentious or difficult to eradicate. We recommend you carefully determine and schedule whatever remedial services may be deemed advisable or necessary before the close of escrow. 1201] LIVING ROOM: 12.1 1) Overall Condition: Appears in overall adequate condition with no visible concerns to room components. 12.2 2) Floor Structure: Adequate. 12.3 7) Wood / Laminate Adequate. Observations: 12.4 8) Wall Drywall, Plaster, Appears adequate. Materials/Observations: 12.5 9) Ceiling Drywall, Plaster, Appears adequate. Materials/Observations: 12.6 10) Window Adequate. Observations: 12.7 12) Receptacle Adequate. Observations: This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page21
  • 22. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 12.8 13) Lighting Provisions: Ceiling, Switched Receptacle, Observations; Adequate. 12.9 15) Heat Observations: Appears Adequate. 12.10 16) Stair & Railing Adequate. Observations: 12.11 17) Trim Wood. Types/Observations: 1202] FAMILY ROOM 12.12 1) Overall Condition: Appears in overall adequate condition with no visible concerns to room components. 12.13 2) Floor Structure: Adequate. 12.14 7) Wood / Laminate Adequate. Observations: 12.15 8) Wall Drywall, Plaster, Appears adequate. Materials/Observations: 12.16 9) Ceiling Drywall, Plaster, Appears adequate. Materials/Observations: 12.17 10) Window Adequate. Observations: 12.18 12) Receptacle Adequate. Observations: 12.19 13) Lighting Ceiling, Observations; Adequate. Provisions: 12.20 14) Ceiling Fan Inoperable. Observations: 12.21 15) Heat Observations: Appears Adequate. 12.22 17) Trim Wood, Trim Observations: Appears adequate. Types/Observations: 1206] LAUNDRY ROOM 12.23 1) Overall Condition: Appears in overall adequate condition with no visible concerns to room components. 12.24 7) Wood / Laminate Adequate. Observations: 12.25 8) Wall Drywall, Plaster, Holes. Materials/Observations: 12.26 9) Ceiling Drywall, Plaster, Appears adequate. Materials/Observations: 12.27 11) Door Hinged, Observations; Adequate. Types/Observations: 12.28 12) Receptacle Adequate. Observations: 12.29 13) Lighting Ceiling. Provisions: 12.30 15) Heat Observations: None. 12.31 17) Trim Wood, Trim Observations: Appears adequate. Types/Observations: 1207] 12.32 1) Overall Condition: Appears in overall adequate condition with no visible concerns to room components. 12.33 2) Floor Structure: Adequate. 12.34 3) Carpet Observations: Adequate. 12.35 8) Wall Drywall, Plaster, Appears adequate. Materials/Observations: 12.36 9) Ceiling Drywall, Plaster, Appears adequate. Materials/Observations: 12.37 10) Window Adequate. Observations: 12.38 11) Door Hinged, Observations; Adequate. Types/Observations: 12.39 12) Receptacle Adequate. Observations: 12.40 13) Lighting Ceiling, Observations; Adequate. Provisions: 12.41 14) Ceiling Fan Adequate. Observations: 12.42 15) Heat Observations: Appears Adequate. 12.43 17) Trim Wood, Trim Observations: Appears adequate. Types/Observations: This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page22
  • 23. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 1208] MASTER BEDROOM: 12.44 1) Overall Condition: Appears in overall adequate condition with no visible concerns to room components. 12.45 2) Floor Structure: Adequate. 12.46 3) Carpet Observations: Adequate. 12.47 8) Wall Drywall, Plaster, Appears adequate. Materials/Observations: 12.48 9) Ceiling Drywall, Plaster, Appears adequate. Materials/Observations: 12.49 10) Window Adequate. Observations: 12.50 11) Door Hinged, Observations; Adequate. Types/Observations: 12.51 12) Receptacle Adequate. Observations: 12.52 13) Lighting Ceiling, Observations; Adequate. Provisions: 12.53 15) Heat Observations: Appears Adequate. 12.54 17) Trim Wood, Trim Observations: Appears adequate. Types/Observations: 1209] BEDROOM #2 12.55 1) Overall Condition: Appears in overall adequate condition with no visible concerns to room components. 12.56 2) Floor Structure: Adequate. 12.57 3) Carpet Observations: Adequate. 12.58 8) Wall Drywall, Plaster, Appears adequate. Materials/Observations: 12.59 9) Ceiling Drywall, Plaster, Appears adequate. Materials/Observations: 12.60 10) Window Adequate. Observations: 12.61 11) Door Hinged, Observations; Adequate. Types/Observations: 12.62 12) Receptacle Adequate. Observations: 12.63 13) Lighting Ceiling, Observations; Adequate. Provisions: 12.64 14) Ceiling Fan Adequate. Observations: 12.65 15) Heat Observations: Appears Adequate. 12.66 17) Trim Wood, Trim Observations: Appears adequate. Types/Observations: 1210] BEDROOM #3 12.67 1) Overall Condition: Appears in overall adequate condition with no visible concerns to room components. 12.68 2) Floor Structure: Adequate. 12.69 3) Carpet Observations: Adequate. 12.70 8) Wall Drywall, Plaster, Appears adequate. Materials/Observations: 12.71 9) Ceiling Drywall, Plaster, Appears adequate. Materials/Observations: 12.72 10) Window Adequate. Observations: 12.73 11) Door Hinged, Sliding, Mirrored, Observations; Adequate. Types/Observations: 12.74 12) Receptacle Adequate. Observations: 12.75 13) Lighting Ceiling, Observations; Adequate. Provisions: 12.76 15) Heat Observations: Appears Adequate. 12.77 17) Trim Wood, Trim Observations: Appears adequate. Types/Observations: This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page23
  • 24. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 1212] BEDROOM #5 12.78 1) Overall Condition: Closet modified Into wine room. several electrical Concerns observed. repairs recommended. 12.79 2) Floor Structure: Adequate. 12.80 7) Wood / Laminate Adequate. Observations: 12.81 8) Wall Drywall, Plaster, Appears adequate. Materials/Observations: 12.82 9) Ceiling Drywall, Plaster, Appears adequate. Materials/Observations: 12.83 10) Window Adequate. Observations: 12.84 11) Door Hinged, Observations; Adequate. Types/Observations: 12.85 12) Receptacle Adequate. Observations: 12.86 13) Lighting Ceiling, Observations; Adequate. Provisions: 12.87 15) Heat Observations: Appears Adequate. 12.88 17) Trim Wood, Trim Observations: Appears adequate. Types/Observations: 1213] 12.89 1) Overall Condition: Appears in overall adequate condition with no visible concerns to room components. 12.90 2) Floor Structure: Bouncy Slightly. 12.91 7) Wood / Laminate Adequate. Observations: 12.92 8) Wall Drywall, Plaster, Appears adequate. Materials/Observations: 12.93 9) Ceiling Drywall, Plaster, Appears adequate. Materials/Observations: 12.94 10) Window Adequate. Observations: 12.95 11) Door Sliding, Observations; Adequate. Types/Observations: 12.96 12) Receptacle Adequate. Observations: 12.97 13) Lighting Observations; Could Not Locate Or Verify All Switch(s) Function Seller Demonstrate. Provisions: 12.98 15) Heat Observations: Appears Adequate. 12.99 17) Trim Wood, Trim Observations: Appears adequate. Types/Observations: ELECTRICAL ADDITIONAL COMMENTS Inspection is for visible, exposed wiring only, and is limited to random sampling. New occupants may put different load demands on the electrical system which can in no way be anticipated. Any repairs should be conducted by a licensed electrician. Rag, cloth wiring, Knob & Tube, or other should be replaced if sheathing is deteriorating, and are non grounded systems. Aluminum wiring has a history of being a potential fire hazard and approved connectors should be installed by a licensed electrician. FPE Federal Pacific Panels (Stab-lok) have a history of failure of the breaker to trip properly. Also see Receptacles under Interior, Bathroom & Basement Report pages. We are not electricians and in accordance with the standards of practice we only test a representative number of switches and outlets and do not perform load-calculations to determine if the supply meets the demand. However, every electrical deficiency or recommended upgrade should be regarded as a latent hazard that should be serviced as soon as possible, along with evaluation and certification of the entire system as safe by a licensed contractor. Therefore, it is essential that any recommendations that we may make for service or upgrades should be completed before the close of escrow, because an electrician could reveal additional deficiencies or recommend additional upgrades for which we disclaim any responsibility. Any electrical repairs or upgrades should be made by a licensed electrician. Smoke Alarms should be installed in all bedrooms at designated locations, and tested regularly. Operation of time clock motors is not verified. Inoperative light fixtures often lack bulbs or have dead bulbs installed. The inspector is not required to insert any tool, probe, or testing device inside the panels, test or operate any over-current device except for ground fault interrupters, nor dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels. Any ancillary wiring or system that is not part of the primary electrical distribution system is not part of this inspection but may be mentioned for informational purposes only, including but not limited to low voltage systems, security system devices, heat detectors, carbon monoxide detectors, telephone, security, cable TV, intercoms, and built in vacuum equipment. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page24
  • 25. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 1301] SERVICE ENTRY 13.1 Entry Means: 120/240 Volt system. 13.2 Wire Size: Not Visible due to panel design. 1302] PANEL(S) 13.3 MAIN PANEL (AMPS): Location; Exterior Wall of Building, Left Side of building, 125 amps. 13.4 Overload Protection: Breakers. 13.5 Observations: Sloppy workmanship, Over Fusing, Risk Of Wire Over-Heating. ( size of wire insufficient to carry load), Missing, Wire Connector(s) 1303] BRANCH CIRCUITS 13.6 Wiring Conductor Copper. Materials: 13.7 Wiring Methodology: Romex (NM) 1304] GFCI'S 13.8 Observations: Missing In Recommended Areas. 1305] GROUNDING 13.9 Observations: Not Visible. PLUMBING IMPORTANT INFORMATION: All underground piping related to water supply, waste, or sprinkler use are excluded from this inspection. Leakage, corrosion or blockage in underground piping cannot be detected by a visual inspection. Plumbing components such as gas pipes, potable water pipes, drain and vent pipes, and shut-off valves are not generally tested if not in daily use. The inspector cannot state the effectiveness or operation of any anti-siphon devices, automatic safety controls, water conditioning equipment, fire and lawn sprinkler systems, on-site water quality and quantity, on-site waste disposal systems, foundation irrigation systems, spa and swimming pool equipment, solar water heating equipment, or observe the system for proper sizing, design, or use of materials. The water pressure within pipes is commonly confused with water volume, but whereas high water volume is good high water pressure is not. Therefore a regulator is recommended whenever street pressure exceeds 80 psi. Regardless of pressure, leaks will occur in any system, and particularly in one with older galvanized pipes. Waste and drainpipes pipe condition is usually directly related to their age. Older pipes are subject to damage through decay and root movement, whereas the more modern ABS pipes are virtually impervious to damage, although some rare batches have been alleged to be defective. Older homes with galvanized or cast iron supply or waste lines can be obstructed and barely working, and later fail under heavy use. If the water is turned off or not used for periods of time (such as a vacant house waiting for closing), rust or deposits within the piping can further clog the piping system. However, inasmuch as significant portions of drainpipes are concealed, we can only infer their condition by observing the draw at drains at the time of inspection. Nonetheless, blockages will still occur in the life of any system. 1401] SUPPLY 14.1 Water Source: Public Water. 14.2 A: Main Supply Line Location of Shut-Off Valve, Right Yard adjacent to building, Copper, 1" 14.3 Main Line Observations: Adequate. 14.4 B: Distribution Lines: Copper. 14.5 Distribution Lines Adequate. Observations: 1402] WASTE 14.6 Waste Provisions: Public Sewer. 14.7 Waste Piping Materials: Visible areas Plastic, ABS. 14.8 Observations: Adequate. 14.9 A. Traps: Plastic, P-Traps. 14.10 Trap Observations: Visible Leaks. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page25
  • 26. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 1403] FUEL SYSTEMS 14.11 Gas Meter: Location; Left Yard Adjacent To Building, Shut off Valve location, At The Meter, Appears Adequate. 1407] WATER HEATER #1 14.12 Location: Garage. 14.13 Manufacture Date: 2008. 14.14 Fuel: Gas. 14.15 Capacity: 40 gallons. 14.16 Water Heater Adequate. Observations: 14.17 Combustion Air Appears adequate. 14.18 8) FLUE: Rigid Metal, Observations: Adequate. 14.19 Seismic Strapping Appear Adequate. HEATING & COOLING SYSTEMS The inspector can only readily open access panels provided by the manufacturer or installer for routine homeowner maintenance, and will not operate components when weather conditions or other circumstances apply that may cause equipment damage. The inspector does not light pilot lights or ignite or extinguish solid fuel fires, nor are safety devices tested by the inspector. The inspector is not equipped to inspect furnace heat exchangers for evidence of cracks or holes, or inspect concealed portions of evaporator and condensing coils, heat exchanger or firebox, electronic air filters, humidifiers and de-humidifiers, ducts and in-line duct motors or dampers, as this can only be done by dismantling the unit. This is beyond the scope of this inspection. Thermostats are not checked for calibration or timed functions. Adequacy, efficiency or the even distribution of air throughout a building cannot be addressed by a visual inspection. Have these systems evaluated by a qualified individual. The inspector does not perform pressure tests on coolant systems, therefore no representation is made regarding coolant charge or line integrity. We perform a conscientious evaluation of the system, but we are not specialists. Please note that even modern heating systems can produce carbon monoxide, which in a poorly ventilated room can result in sickness and even death. Therefore, it is essential that any recommendations we make for service or further evaluation be scheduled before the close of escrow, because a specialist could reveal additional defects or recommend further upgrades that could affect your evaluation of the property, and our service does not include any form or warranty or guarantee. Normal service and maintenance is recommended on a yearly basis. Determining the presence of asbestos materials commonly used in heating systems can ONLY be preformed by laboratory testing and is beyond the scope of this inspection. Determining the condition of oil tanks, whether exposed or buried, is beyond the scope of this inspection. 1500] HEATING SYSTEM #1 15.1 LOCATION & Attic. OVERVIEW: 15.2 1) TYPE OF SYSTEM: Forced Air- 15.3 2] FUEL/ POWER Natural Gas, Brass Flexible Gas Line Noted, History of Failure. SUPPLY: 15.4 4) FILTER: Disposable. 15.5 Filter Location/ Air Return, Filter Observations, Adequate. Observation: 15.6 5) AIR HANDLER: Adequate. 15.7 7) DUCTWORK: Insulated Fiberboard (Fiberglass lined), Plastic Flex, Observations: Disconnected Connection(s) See return plenum. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page26
  • 27. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com 15.8 8) FLUE: Rigid Metal, OBSERVATIONS: Adequate. 15.9 9) THERMOSTAT: Adequate. ADDITIONAL COMMENTS Air conditioners and heat pumps have a life expectancy of 8 to 12 years. Air conditioners and heat pumps are checked for operation and no remaining life expectancy or warranty is implied. An older unit may be nearing or at the end of it's life. See additional information for heating systems, ductwork ,filters, etc, below. 1506] AIR CONDITIONER #1: 15.10 1] TYPE OF SYSTEM: Air Conditioner, Split System. (A.C. Unit Not Checked in Temperatures Which Have Been Below 60°F in the Past 24 Hours.) 15.11 3) COMPRESSOR Located At: Left side of building, Not Secured/ Anchored. Unit Not Operational. UNIT: 15.12 Manufacture Date: 2001. 15.13 Unit Size in Tons: 5.0 tons. 15.14 4) CONDENSATE: Disconnected. Abandoned lines.Risk of leaking. FIREPLACE/CHIMNEY/ENVIRONMENTAL OVERVIEW ADDITIONAL COMMENTS Internal components of the chimney are not covered under this inspection, such as the inside of the flue. A chimney specialist should be consulted for this. Annual maintenance must be maintained for maximum safety and to help sustain the life of the unit and its components. Woodstoves should be inspected by a woodstove expert. All fireplaces should be cleaned and inspected on a regular basis to make sure that no cracks have developed. Large fires in the firebox can overheat the firebox and flue liners, sometimes resulting in internal damage 1601] FAMILY ROOM FIREPLACE 16.1 1] TYPE OF UNIT(S); Manufactured (Zero Clearance), Gas Log or Wood Burning. 16.2 2) FIRE BOX: Panels. 16.3 Firebox Observations: Appears adequate. 16.4 4) DAMPER Operating as intended. OBERVATIONS: 16.5 5) FLUE: Metal. 16.6 Flue Observations: Visible area adequate. 16.7 Hearth Extension Inadequate Size /Depth or Width. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page27
  • 28. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com Observations: 16.8 7) CHIMNEY: Wood (Flue chase) 16.9 Chimney Observations: Adequate. 16.10 Chimney Cap Not Accessible (Recommend further evaluation) Observations: ADDITIONAL COMMENTS: Inspector is Not required to evaluate presence of environmental hazards according to most national standards. Any concerns pointed out during the inspection are based on the inspectors discretion and experience. POOL/SPA & EQUIPMENT CONFIDENTIAL - FOR CLIENT USE ONLY Inspection was limited to those areas which are above ground or water level. The only way to detect an underground leak in a supply line, buried pipe fitting, or pool surface crack is by observation of the persistant and continuous loss of water from the pool over an extended period of time. Purchasers are encouraged to ask sellers about the existance of any past or present leaks in the pool, spa or associated equipment. Pool filtering devices are not disassembled to determine the condition of any installed filter elements. Operation of time clock motors and thermostatic temperature controls cannot be verified during a visual inspection. Testing of backflush mechanisms is beyond the scope of this inspection. Pilot lights on gas pool heaters are not lit during the inspection. POOL SURFACE: 17.1 Type: Concrete/Marcite.(Plaster) 17.2 Condition: Fair overall condition.Moderate wear. 17.3 Pool Coping: Good overall. 17.4 Pool/Spa Drains: Adequate. SKIMMER & BASKET: 17.5 Condition: Good. POOL LIGHT: 17.6 Not operable. If a defective bulb is at fault, replacement will cost $50-100 Otherwise, further evaluation and repairs will be needed by a licensed electrician. PUMPING EQUIPMENT: 17.7 Pump and Motor 1 HP motor. Good. Condition: 17.8 Hair/Lint Filter: Good- no significant air bubbles noted. 17.9 Filter Type: Diatomaceous earth. 17.10 Filter Pressure in PSI: 25. 17.11 Chlorinator: Type: Chlorine Generator- Inquire with seller about equipment condition and operational procedures. VISIBLE PLUMBING LINE: 17.12 Condition: Good. POOL FILL: 17.13 TYPE: Manual, Adequate. HEATERS: 17.14 Type and Condition: Natural Gas, Good visual condition. This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page28
  • 29. 34145 Pacific Coast Highway Suite 513 Dana Point CA 92629 p 949.466.7265 f 661.0581 www.buildingspecscorp.com ELECTRIC CONTROLS: 17.15 Subpanels: Good. 17.16 Timers: Good. 17.17 Electrical Bonding Good. POOL DECKING: 17.18 Type: Concrete 17.19 Condition: Adequate, No concerns visible. 17.20 Child Protection Good. Fencing: This report has been produced in accordance with the signed contract and is subject to the terms and conditions agreed upon therein. Please read this report carefully. Call our office for any consultation that you may need, (949) 494-5624. Any comments or observations require further evaluation and/or repair. Any repairs or evaluations should be conducted by a licensed or qualified specialist or company. The client is advised that any substandard workmanship may need further evaluation and/or upgrading. Report #Sample Report May 28, 2010 Page29