8400-863
Temperature
Monitoring
Metering
Network I/O
Remote I/O
Ethernet I/O
Signal Conditioning &
Networking Applications
M O N I T O R I N G & C O N T R O L S O L U T I O N S
Industrial Instrumentation
Applications eBook
ETHERNET
PLC
REMOTE SITE 1 REMOTE SITE 3 REMOTE SITE 5 REMOTE SITE 7
REMOTE SITE 2 REMOTE SITE 4 REMOTE SITE 6 REMOTE SITE 8
Discrete I/O
XT1111-000
ETHERNET NETWORK
Discrete I/O
989EN-4C16
Application Note:
Ethernet I/O Simplifies Communication Between One
PLC and Multiple Remote Locations
Defining the Problem:
A customer has multiple remote locations linked over an Ethernet network, each requiring discrete outputs. They all need to
be sent the same communication signal at the same time.
Implementing the Solution:
1. Set up Ethernet communication between master
PLC device and the BusWorks XT discrete I/O module
(XT1111).
2. Connect the XT1111 module and the remote site discrete
I/O modules (989EN) to an Ethernet network.
3. Configure the XT module to use Acromag’s i2o peer-to-
peer communication to replicate the PLC’s discrete signal
to 8 other multiple locations by IP address.
Featured Products:
16-Channel Discrete I/O, Modbus/TCP XT1111-000
16-Channel Discrete I/O, with Counter/Timers 989EN-4C16
Software Interface Package XT-SIP
All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2014. Data subject to change without notice. Printed in USA 8/2014
Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA
Why Acromag:
Our BusWorks XT Modbus/TCP remote I/O modules include a peer-to-peer feature known as i2o, where two or more slaves
can talk to each other without requiring a master. With i2o communication, one signal from the PLC is split by the XT1111
module and sent to multiple locations. The XT1111 automatically re-transmits the discrete level to each 989EN module’s IP
address, thus reproducing the status of the original PLC input.
System Requirements:
■ All remote sites need to be controlled simultaneously from one central control room via Ethernet protocol
Bulletin #8400-822
Application Note:
Metering Project - Managing Energy Usage with Ethernet I/O
Defining the Problem:
The university power plant produces both electricity and steam for the campus. The chilled water and steam condensate need
to be monitored and recorded by totalizing the pulsed outputs from magnetic, positive displacement, and vortex flowmeters.
The volumetric flow rate, along with the liquid heat loss from the steam-to-heat transfer process, is used in steam cost
calculations to better manage the energy demand across the campus.
Implementing the Solution:
1. Connect a PC to the 989EN-4016, open an internet browser,
assign the network parameters and configure the discrete
inputs as counters to totalize the flowmeter pulse outputs.
2. Simulate input pulses and observe the count increase in the
989EN-4016 counter test page.
3. The eDNA software periodically reads the current count
value of each input from the 30,000 modbus input registers
or the 43,000 holding registers. Two registers of 16-bit
unsigned integer values yield a 32 bit totalized count value.
Featured Products:
BusWorks Discrete I/O 989EN-4016
All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2015. Data subject to change without notice. Printed in USA 8/2015
Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA
Why Acromag:
The 989EN-4016 module is an affordable, versatile discrete and counter/alarm remote I/O. With fast installations and Class 1
Div 2 ratings, duplication across the campus was easily achieved. Additionally, the campus data historian software was quickly
programmed to communicate with the 989EN solution.
System Requirements:
■ The university requires consistent installations that can be duplicated across the campus.
■ Communication with the data historian software, eDNA, via modbus TCP/IP over the campus Ethernet network.
Bulletin #8400-805d
Notes:
989EN-4016 modules have 16 discrete I/O where each channel
can be an input or an output. Optionally, this model allows the
first 8 channels to be used as non-volatile pulse counters with
the remaining 8 channels available as local output alarms for
their associated input counters.
MODBUS TCP/IP
Ethernet
Discrete I/O
989EN-4016
PULSED OUTPUTS
Control Room
Magnetic Flowmeter
Positive Displacement
Flowmeter
Vortex Flowmeter
eDNA
Data Historian
THERMOCOUPLE
Automotive
Paint Curing
Oven
THERMOCOUPLE
4-20mA COPPER WIRE
4-20mA COPPER WIRE
PLCs
TT233-0600
2-Wire Transmitters
Application Note:
Thermocouple Transmitters Monitor
Temperatures in Paint Systems
Defining the Problem:
A manufacturer’s paint curing ovens are located far away from the PLCs controlling the process. The ambient temperature around these
ovens exceeds the performance ratings of the existing instrumentation.
Implementing the Solution:
1. Run a short amount of thermocouple wiring away from the direct
heat of the ovens.
2. Install isolated Acromag thermocouple-to-current transmitters that
re-use the existing PLC 4-20mA input cards.
3. Run 4-20mA copper wiring the rest of the distance, from the
transmitters to the PLC panels.
4. Wire the transmitters’ 4-20mA outputs for either DC or loop-
powered PLC input connections. Acromag’s TT230 Series supports
sourcing (3-wire) and sinking (2-wire) output.
Featured Products:
2-Wire Thermocouple Transmitters TT233-0600
Software Interface Package TTC-SIP
All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2014. Data subject to change without notice. Printed in USA 6/2014
Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA
Why Acromag:
Our TT series offered an affordable solution with a higher operating temperature range (-40 to 80°C). The transmitters helped save on costs
by using 4-20mA copper wire, which is less expensive than thermocouple wire. Most important, the manufacturer kept their PLC 4-20mA
input cards and software setup unchanged.
System Requirements:
■ Keep the existing PLC 4-20mA input cards and ladder logic programs to maintain process standards and avoid purchasing expensive
thermocouple input cards or re-programming of the PLC.
Bulletin #8400-818
Application Note:
Record Building Water Usage with Remote Ethernet I/O
Defining the Problem:
Regulatory Compliance - To meet environmental standards by monitoring the usage and quality of water used by a school.
System will record the temperature, pressure, and flow rate for reporting purposes.
Implementing the Solution:
1. Configure the module using Acromag WindowsÂź based
software via USB connection.
2. Connect the field instruments and verify input status using
the software test & polling feature.
3. Program the BAS with the remote I/O network parameters
and Modbus registers.
Featured Products:
8 Differential Current Inputs, Modbus TCP/IP XT1211-000
Software Interface Package XT-SIP
Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA
Why Acromag:
Acromag provides a simple and cost-effective solution for interfacing data from a number of sensors to
building control systems.
System Requirements:
Field instruments used are pressure transmitters (PT), temperature sensors (T/C), and flowmeters (FM) with
Bulletin #8400-841c
4-20mA outputs. Remote I/O convert the analog inputs to Modbus TCP/IP on Ethernet which communicates with
the Building Automation System (BAS) for data logging, trending, and histograms.
4-
20
m
A
Ethernet
Modbus TCP/IP
XT1211-000
4-20m
A
(100 meters)
PTFM T/C
BAS
Application Note:
Monitoring Stator Temperatures with Remote Profibus I/O
Defining the Problem:
A Power Plant has Hydroelectric Generators with 10 ohm copper 3 wire RTDs embedded in the stator motor windings.
The RTDs are far away from a PLC in the control room. The long distance is picking up noise that is interfering with their
measurements.
Implementing the Solution:
1. Select a Slave Address and configure the 966PB-2006
parameters using a GSD file. Download the file into the PLC.
2. Wire the RTDs, power and Earth Ground.
3. Program the PLC for 50 to 80°C normal RTD temperature
ranges.
4. Validate the measurements.
Featured Products:
966PB-2006
All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2015. Data subject to change without notice. Printed in USA 5/2015
Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA
Why Acromag:
The Profibus Remote I/O are PNO-certified for interoperability with Profibus equipment ensuring ease of set up and
operation. The products are fully isolated and engineered with a Siemens SPC3 intelligent ASIC providing reliable Profibus
communications.
System Requirements:
A Siemens PLC can communicate using Profibus DP / RS485. Install Remote Profibus I/O, Class 1 Div 2 approved, close to
the RTDs. Shorter RTDs, with proper shields and grounding techniques, will significantly reduce the noise for more accurate
measurements.
Bulletin #8400-849
966PB-2006
Rotor
Stator
Control Room Turbine
Profibus DP/RS485 10 ohm copper
RTDs
PLC
Application Note:
Networking Remote Gas Detectors with Ethernet I/O
Defining the Problem:
In a wastewater treatment plant, remotely mounted gas detectors monitoring Methane CH4 (ceiling), Oxygen O2 (6 ft high)
and Hydrogen Sulfide H2S (floor) have analog outputs. The gas levels need to be saved to chart recorders located in a control
room a long distance away in the plant. To save on the cost of running copper twisted pair wires, we would like to network
the analog outputs for transmission over the Ethernet infrastructure.
Implementing the Solution:
1. In the USB configured XT software, set the IP address,
network parameters and input scaling.
2. Configure the PLC with Acromag’s ControlLogix application
note. This document includes instructions for RSLogix 5000
and RSLinx.
3. With the XT1212-000 software and inputs wired, poll the
module and check the measurements using the test page.
4. Validate the Ethernet/IP communications with an Ethernet
connection between the XT and the PLC.
Featured Products:
XT1212-000
All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2015. Data subject to change without notice. Printed in USA 7/2015
Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA
Why Acromag:
The XT series of Remote I/O has Class 1 Div 2 ratings for hazardous locations where the Gas Detectors are installed. With
simple software configuration and an application note detailing the PLC configuration, installation and testing are easily
accomplished.
System Requirements:
A ControlLogix PLC in the control room can communicate using Ethernet/IP protocol. The Ethernet remote I/O will accept
4 – 20mA inputs from the gas detectors and convert to Ethernet/IP. The PLC will output 4 – 20mA to the chart recorders
nearby. Also, the hazardous area requires Class 1 Div 2 instruments.
Bulletin #8400- 852
Control RoomTreatment Plant
Chart Recorders
CH4 O2 H2S
ControlLogix PLC
4-20mA
Inflow
Outflow
Class 1 DIV 2 Environment
Filters Pumps
CH4
O2
H2S
Electrical PanelGas Detectors
Ethernet/IP
XT1212-000
4-20mA

Weitere Àhnliche Inhalte

Andere mochten auch

Questionnaire 1
Questionnaire 1Questionnaire 1
Questionnaire 1rebeccadahl98
 
ăƒȘă‚čティングćșƒć‘Šă‹ă‚‰Facebookćșƒć‘ŠăŸă§ă€‚運甚枋ćșƒć‘Šăźćœčć‰Čăźć€‰ćŒ–
ăƒȘă‚čティングćșƒć‘Šă‹ă‚‰Facebookćșƒć‘ŠăŸă§ă€‚運甚枋ćșƒć‘Šăźćœčć‰Čăźć€‰ćŒ–ăƒȘă‚čティングćșƒć‘Šă‹ă‚‰Facebookćșƒć‘ŠăŸă§ă€‚運甚枋ćșƒć‘Šăźćœčć‰Čăźć€‰ćŒ–
ăƒȘă‚čティングćșƒć‘Šă‹ă‚‰Facebookćșƒć‘ŠăŸă§ă€‚運甚枋ćșƒć‘Šăźćœčć‰Čăźć€‰ćŒ–Anagrams
 
HART protocol for network data communication
HART protocol for network data communicationHART protocol for network data communication
HART protocol for network data communicationAmol Dudhate
 
Acoustic echo cancellation
Acoustic echo cancellationAcoustic echo cancellation
Acoustic echo cancellationchintanajoshi
 
TensorFlowăšăŻïŒŸ ăƒ‡ă‚ŁăƒŒăƒ—ăƒ©ăƒŒăƒ‹ăƒłă‚° ïŒˆæ·±ć±€ć­Šçż’ïŒ‰ ăšăŻïŒŸ
TensorFlowăšăŻïŒŸ ăƒ‡ă‚ŁăƒŒăƒ—ăƒ©ăƒŒăƒ‹ăƒłă‚° ïŒˆæ·±ć±€ć­Šçż’ïŒ‰ ăšăŻïŒŸTensorFlowăšăŻïŒŸ ăƒ‡ă‚ŁăƒŒăƒ—ăƒ©ăƒŒăƒ‹ăƒłă‚° ïŒˆæ·±ć±€ć­Šçż’ïŒ‰ ăšăŻïŒŸ
TensorFlowăšăŻïŒŸ ăƒ‡ă‚ŁăƒŒăƒ—ăƒ©ăƒŒăƒ‹ăƒłă‚° ïŒˆæ·±ć±€ć­Šçż’ïŒ‰ ăšăŻïŒŸKSK Analytics Inc.
 
ăƒȘă‚čティングćșƒć‘Šăźç‚șăźăƒ‡ăƒŒă‚żăƒ•ă‚ŁăƒŒăƒ‰ć‹‰ćŒ·äŒš
ăƒȘă‚čティングćșƒć‘Šăźç‚șăźăƒ‡ăƒŒă‚żăƒ•ă‚ŁăƒŒăƒ‰ć‹‰ćŒ·äŒšăƒȘă‚čティングćșƒć‘Šăźç‚șăźăƒ‡ăƒŒă‚żăƒ•ă‚ŁăƒŒăƒ‰ć‹‰ćŒ·äŒš
ăƒȘă‚čティングćșƒć‘Šăźç‚șăźăƒ‡ăƒŒă‚żăƒ•ă‚ŁăƒŒăƒ‰ć‹‰ćŒ·äŒšKeiji Abe
 
Hart communication
Hart communicationHart communication
Hart communicationSumit Sharma
 
【Draftă€‘ă‚”ăƒŒăƒ“ă‚čèȘŹæ˜Žèł‡æ–™2017.03.01
【Draftă€‘ă‚”ăƒŒăƒ“ă‚čèȘŹæ˜Žèł‡æ–™2017.03.01【Draftă€‘ă‚”ăƒŒăƒ“ă‚čèȘŹæ˜Žèł‡æ–™2017.03.01
【Draftă€‘ă‚”ăƒŒăƒ“ă‚čèȘŹæ˜Žèł‡æ–™2017.03.01Kohta Wada
 
Condenser in thermal power plants
Condenser in thermal power plantsCondenser in thermal power plants
Condenser in thermal power plantsSHIVAJI CHOUDHURY
 
Thermal plant instrumentation and control
Thermal plant instrumentation and controlThermal plant instrumentation and control
Thermal plant instrumentation and controlShilpa Shukla
 
Smart note taker
Smart note takerSmart note taker
Smart note takercrisane93
 

Andere mochten auch (14)

Questionnaire 1
Questionnaire 1Questionnaire 1
Questionnaire 1
 
Krohne Vibrating Fork Level Switches
Krohne Vibrating Fork Level SwitchesKrohne Vibrating Fork Level Switches
Krohne Vibrating Fork Level Switches
 
ă‚€ăƒłă‚čă‚żă‚°ăƒ©ăƒ ă‚­ăƒŁăƒłăƒšăƒŒăƒłASPă‚”ăƒŒăƒ“ă‚č TagplusInstagram campaign
ă‚€ăƒłă‚čă‚żă‚°ăƒ©ăƒ ă‚­ăƒŁăƒłăƒšăƒŒăƒłASPă‚”ăƒŒăƒ“ă‚č TagplusInstagram campaignïŒ‰ă‚€ăƒłă‚čă‚żă‚°ăƒ©ăƒ ă‚­ăƒŁăƒłăƒšăƒŒăƒłASPă‚”ăƒŒăƒ“ă‚č TagplusInstagram campaign
ă‚€ăƒłă‚čă‚żă‚°ăƒ©ăƒ ă‚­ăƒŁăƒłăƒšăƒŒăƒłASPă‚”ăƒŒăƒ“ă‚č TagplusInstagram campaign
 
ăƒȘă‚čティングćșƒć‘Šă‹ă‚‰Facebookćșƒć‘ŠăŸă§ă€‚運甚枋ćșƒć‘Šăźćœčć‰Čăźć€‰ćŒ–
ăƒȘă‚čティングćșƒć‘Šă‹ă‚‰Facebookćșƒć‘ŠăŸă§ă€‚運甚枋ćșƒć‘Šăźćœčć‰Čăźć€‰ćŒ–ăƒȘă‚čティングćșƒć‘Šă‹ă‚‰Facebookćșƒć‘ŠăŸă§ă€‚運甚枋ćșƒć‘Šăźćœčć‰Čăźć€‰ćŒ–
ăƒȘă‚čティングćșƒć‘Šă‹ă‚‰Facebookćșƒć‘ŠăŸă§ă€‚運甚枋ćșƒć‘Šăźćœčć‰Čăźć€‰ćŒ–
 
HART protocol for network data communication
HART protocol for network data communicationHART protocol for network data communication
HART protocol for network data communication
 
Acoustic echo cancellation
Acoustic echo cancellationAcoustic echo cancellation
Acoustic echo cancellation
 
integral coach factory report
integral coach factory report integral coach factory report
integral coach factory report
 
TensorFlowăšăŻïŒŸ ăƒ‡ă‚ŁăƒŒăƒ—ăƒ©ăƒŒăƒ‹ăƒłă‚° ïŒˆæ·±ć±€ć­Šçż’ïŒ‰ ăšăŻïŒŸ
TensorFlowăšăŻïŒŸ ăƒ‡ă‚ŁăƒŒăƒ—ăƒ©ăƒŒăƒ‹ăƒłă‚° ïŒˆæ·±ć±€ć­Šçż’ïŒ‰ ăšăŻïŒŸTensorFlowăšăŻïŒŸ ăƒ‡ă‚ŁăƒŒăƒ—ăƒ©ăƒŒăƒ‹ăƒłă‚° ïŒˆæ·±ć±€ć­Šçż’ïŒ‰ ăšăŻïŒŸ
TensorFlowăšăŻïŒŸ ăƒ‡ă‚ŁăƒŒăƒ—ăƒ©ăƒŒăƒ‹ăƒłă‚° ïŒˆæ·±ć±€ć­Šçż’ïŒ‰ ăšăŻïŒŸ
 
ăƒȘă‚čティングćșƒć‘Šăźç‚șăźăƒ‡ăƒŒă‚żăƒ•ă‚ŁăƒŒăƒ‰ć‹‰ćŒ·äŒš
ăƒȘă‚čティングćșƒć‘Šăźç‚șăźăƒ‡ăƒŒă‚żăƒ•ă‚ŁăƒŒăƒ‰ć‹‰ćŒ·äŒšăƒȘă‚čティングćșƒć‘Šăźç‚șăźăƒ‡ăƒŒă‚żăƒ•ă‚ŁăƒŒăƒ‰ć‹‰ćŒ·äŒš
ăƒȘă‚čティングćșƒć‘Šăźç‚șăźăƒ‡ăƒŒă‚żăƒ•ă‚ŁăƒŒăƒ‰ć‹‰ćŒ·äŒš
 
Hart communication
Hart communicationHart communication
Hart communication
 
【Draftă€‘ă‚”ăƒŒăƒ“ă‚čèȘŹæ˜Žèł‡æ–™2017.03.01
【Draftă€‘ă‚”ăƒŒăƒ“ă‚čèȘŹæ˜Žèł‡æ–™2017.03.01【Draftă€‘ă‚”ăƒŒăƒ“ă‚čèȘŹæ˜Žèł‡æ–™2017.03.01
【Draftă€‘ă‚”ăƒŒăƒ“ă‚čèȘŹæ˜Žèł‡æ–™2017.03.01
 
Condenser in thermal power plants
Condenser in thermal power plantsCondenser in thermal power plants
Condenser in thermal power plants
 
Thermal plant instrumentation and control
Thermal plant instrumentation and controlThermal plant instrumentation and control
Thermal plant instrumentation and control
 
Smart note taker
Smart note takerSmart note taker
Smart note taker
 

KĂŒrzlich hochgeladen

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...ranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 

KĂŒrzlich hochgeladen (20)

(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 

Industrial Instrumentation Application Examples

  • 1. 8400-863 Temperature Monitoring Metering Network I/O Remote I/O Ethernet I/O Signal Conditioning & Networking Applications M O N I T O R I N G & C O N T R O L S O L U T I O N S Industrial Instrumentation Applications eBook
  • 2. ETHERNET PLC REMOTE SITE 1 REMOTE SITE 3 REMOTE SITE 5 REMOTE SITE 7 REMOTE SITE 2 REMOTE SITE 4 REMOTE SITE 6 REMOTE SITE 8 Discrete I/O XT1111-000 ETHERNET NETWORK Discrete I/O 989EN-4C16 Application Note: Ethernet I/O Simplifies Communication Between One PLC and Multiple Remote Locations Defining the Problem: A customer has multiple remote locations linked over an Ethernet network, each requiring discrete outputs. They all need to be sent the same communication signal at the same time. Implementing the Solution: 1. Set up Ethernet communication between master PLC device and the BusWorks XT discrete I/O module (XT1111). 2. Connect the XT1111 module and the remote site discrete I/O modules (989EN) to an Ethernet network. 3. Configure the XT module to use Acromag’s i2o peer-to- peer communication to replicate the PLC’s discrete signal to 8 other multiple locations by IP address. Featured Products: 16-Channel Discrete I/O, Modbus/TCP XT1111-000 16-Channel Discrete I/O, with Counter/Timers 989EN-4C16 Software Interface Package XT-SIP All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2014. Data subject to change without notice. Printed in USA 8/2014 Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA Why Acromag: Our BusWorks XT Modbus/TCP remote I/O modules include a peer-to-peer feature known as i2o, where two or more slaves can talk to each other without requiring a master. With i2o communication, one signal from the PLC is split by the XT1111 module and sent to multiple locations. The XT1111 automatically re-transmits the discrete level to each 989EN module’s IP address, thus reproducing the status of the original PLC input. System Requirements: ■ All remote sites need to be controlled simultaneously from one central control room via Ethernet protocol Bulletin #8400-822
  • 3. Application Note: Metering Project - Managing Energy Usage with Ethernet I/O Defining the Problem: The university power plant produces both electricity and steam for the campus. The chilled water and steam condensate need to be monitored and recorded by totalizing the pulsed outputs from magnetic, positive displacement, and vortex flowmeters. The volumetric flow rate, along with the liquid heat loss from the steam-to-heat transfer process, is used in steam cost calculations to better manage the energy demand across the campus. Implementing the Solution: 1. Connect a PC to the 989EN-4016, open an internet browser, assign the network parameters and configure the discrete inputs as counters to totalize the flowmeter pulse outputs. 2. Simulate input pulses and observe the count increase in the 989EN-4016 counter test page. 3. The eDNA software periodically reads the current count value of each input from the 30,000 modbus input registers or the 43,000 holding registers. Two registers of 16-bit unsigned integer values yield a 32 bit totalized count value. Featured Products: BusWorks Discrete I/O 989EN-4016 All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2015. Data subject to change without notice. Printed in USA 8/2015 Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA Why Acromag: The 989EN-4016 module is an affordable, versatile discrete and counter/alarm remote I/O. With fast installations and Class 1 Div 2 ratings, duplication across the campus was easily achieved. Additionally, the campus data historian software was quickly programmed to communicate with the 989EN solution. System Requirements: ■ The university requires consistent installations that can be duplicated across the campus. ■ Communication with the data historian software, eDNA, via modbus TCP/IP over the campus Ethernet network. Bulletin #8400-805d Notes: 989EN-4016 modules have 16 discrete I/O where each channel can be an input or an output. Optionally, this model allows the first 8 channels to be used as non-volatile pulse counters with the remaining 8 channels available as local output alarms for their associated input counters. MODBUS TCP/IP Ethernet Discrete I/O 989EN-4016 PULSED OUTPUTS Control Room Magnetic Flowmeter Positive Displacement Flowmeter Vortex Flowmeter eDNA Data Historian
  • 4. THERMOCOUPLE Automotive Paint Curing Oven THERMOCOUPLE 4-20mA COPPER WIRE 4-20mA COPPER WIRE PLCs TT233-0600 2-Wire Transmitters Application Note: Thermocouple Transmitters Monitor Temperatures in Paint Systems Defining the Problem: A manufacturer’s paint curing ovens are located far away from the PLCs controlling the process. The ambient temperature around these ovens exceeds the performance ratings of the existing instrumentation. Implementing the Solution: 1. Run a short amount of thermocouple wiring away from the direct heat of the ovens. 2. Install isolated Acromag thermocouple-to-current transmitters that re-use the existing PLC 4-20mA input cards. 3. Run 4-20mA copper wiring the rest of the distance, from the transmitters to the PLC panels. 4. Wire the transmitters’ 4-20mA outputs for either DC or loop- powered PLC input connections. Acromag’s TT230 Series supports sourcing (3-wire) and sinking (2-wire) output. Featured Products: 2-Wire Thermocouple Transmitters TT233-0600 Software Interface Package TTC-SIP All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2014. Data subject to change without notice. Printed in USA 6/2014 Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA Why Acromag: Our TT series offered an affordable solution with a higher operating temperature range (-40 to 80°C). The transmitters helped save on costs by using 4-20mA copper wire, which is less expensive than thermocouple wire. Most important, the manufacturer kept their PLC 4-20mA input cards and software setup unchanged. System Requirements: ■ Keep the existing PLC 4-20mA input cards and ladder logic programs to maintain process standards and avoid purchasing expensive thermocouple input cards or re-programming of the PLC. Bulletin #8400-818
  • 5. Application Note: Record Building Water Usage with Remote Ethernet I/O Defining the Problem: Regulatory Compliance - To meet environmental standards by monitoring the usage and quality of water used by a school. System will record the temperature, pressure, and flow rate for reporting purposes. Implementing the Solution: 1. Configure the module using Acromag WindowsÂź based software via USB connection. 2. Connect the field instruments and verify input status using the software test & polling feature. 3. Program the BAS with the remote I/O network parameters and Modbus registers. Featured Products: 8 Differential Current Inputs, Modbus TCP/IP XT1211-000 Software Interface Package XT-SIP Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA Why Acromag: Acromag provides a simple and cost-effective solution for interfacing data from a number of sensors to building control systems. System Requirements: Field instruments used are pressure transmitters (PT), temperature sensors (T/C), and flowmeters (FM) with Bulletin #8400-841c 4-20mA outputs. Remote I/O convert the analog inputs to Modbus TCP/IP on Ethernet which communicates with the Building Automation System (BAS) for data logging, trending, and histograms. 4- 20 m A Ethernet Modbus TCP/IP XT1211-000 4-20m A (100 meters) PTFM T/C BAS
  • 6. Application Note: Monitoring Stator Temperatures with Remote Profibus I/O Defining the Problem: A Power Plant has Hydroelectric Generators with 10 ohm copper 3 wire RTDs embedded in the stator motor windings. The RTDs are far away from a PLC in the control room. The long distance is picking up noise that is interfering with their measurements. Implementing the Solution: 1. Select a Slave Address and configure the 966PB-2006 parameters using a GSD file. Download the file into the PLC. 2. Wire the RTDs, power and Earth Ground. 3. Program the PLC for 50 to 80°C normal RTD temperature ranges. 4. Validate the measurements. Featured Products: 966PB-2006 All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2015. Data subject to change without notice. Printed in USA 5/2015 Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA Why Acromag: The Profibus Remote I/O are PNO-certified for interoperability with Profibus equipment ensuring ease of set up and operation. The products are fully isolated and engineered with a Siemens SPC3 intelligent ASIC providing reliable Profibus communications. System Requirements: A Siemens PLC can communicate using Profibus DP / RS485. Install Remote Profibus I/O, Class 1 Div 2 approved, close to the RTDs. Shorter RTDs, with proper shields and grounding techniques, will significantly reduce the noise for more accurate measurements. Bulletin #8400-849 966PB-2006 Rotor Stator Control Room Turbine Profibus DP/RS485 10 ohm copper RTDs PLC
  • 7. Application Note: Networking Remote Gas Detectors with Ethernet I/O Defining the Problem: In a wastewater treatment plant, remotely mounted gas detectors monitoring Methane CH4 (ceiling), Oxygen O2 (6 ft high) and Hydrogen Sulfide H2S (floor) have analog outputs. The gas levels need to be saved to chart recorders located in a control room a long distance away in the plant. To save on the cost of running copper twisted pair wires, we would like to network the analog outputs for transmission over the Ethernet infrastructure. Implementing the Solution: 1. In the USB configured XT software, set the IP address, network parameters and input scaling. 2. Configure the PLC with Acromag’s ControlLogix application note. This document includes instructions for RSLogix 5000 and RSLinx. 3. With the XT1212-000 software and inputs wired, poll the module and check the measurements using the test page. 4. Validate the Ethernet/IP communications with an Ethernet connection between the XT and the PLC. Featured Products: XT1212-000 All trademarks are property of their respective owners. Copyright © Acromag, Inc. 2015. Data subject to change without notice. Printed in USA 7/2015 Tel 248-295-0880 ■ Fax 248-624-9234 ■ sales@acromag.com ■ www.acromag.com ■ 30765 Wixom Rd, Wixom, MI 48393 USA Why Acromag: The XT series of Remote I/O has Class 1 Div 2 ratings for hazardous locations where the Gas Detectors are installed. With simple software configuration and an application note detailing the PLC configuration, installation and testing are easily accomplished. System Requirements: A ControlLogix PLC in the control room can communicate using Ethernet/IP protocol. The Ethernet remote I/O will accept 4 – 20mA inputs from the gas detectors and convert to Ethernet/IP. The PLC will output 4 – 20mA to the chart recorders nearby. Also, the hazardous area requires Class 1 Div 2 instruments. Bulletin #8400- 852 Control RoomTreatment Plant Chart Recorders CH4 O2 H2S ControlLogix PLC 4-20mA Inflow Outflow Class 1 DIV 2 Environment Filters Pumps CH4 O2 H2S Electrical PanelGas Detectors Ethernet/IP XT1212-000 4-20mA