HAP, boiler, coal, biomas, ISO 50001, Qualified Energy Assessor, major source, area source, NOCS, notice of compliance status, thermal energy recovery, condensate recovery, ECMs, energy conservation measures,
2. Energy Assessment Who & What
ห Who is required to conduct EA?
๏ถ HAP major with existing boiler or process heater of any size &
fuel that is not limited use (FEACF<10%)
๏ถ HAP minor with existing coal, biomass, oil boiler >10
MMBtu/hr. that is not limited use (FEACF<10%)
๏ถ Exempts facilities operating under ISO 50001 compatible
EnMS, or post January 2008 EA, that includes affected units
ห What is required?
๏ถ Scope & duration determined by firing capacity
โฆ Site Visit (8-24 hrs., not to exceed 160 hrs.)
๏ถ Performed by Qualified Energy Assessor
๏ถ No report submittal but submit NOCS by due date
๏ถ Not required to implement any ECMs identified
3. ห When is it required?
๏ถ Major sources (ยง63.7510(e)):
โฆ Assessment and report due by:
โฆ Compliance date โ January 31, 2016
๏ถ Area sources (ยง63.11196(a)(3)):
โฆ Assessment and report due by:
โฆ Compliance date โ March 21, 2014
ห Submit certification of completion in Notice of
Compliance Status (NOCS)
๏ถ NOCS due:
โฆ 60 days after performance test for Major Sources
โฆ 60 days after perfor. test for Area Sources, if no perfor. test
required 120 days after compliance date (7/19/2014)
Energy Assessment - When
4. ห Someone who has demonstrated capabilities to evaluate
energy savings opportunities for steam generation and
major energy using systems, including, but not limited to:
๏ถ Boiler combustion management
๏ถ Boiler thermal energy recovery, including
โฆ Conventional feed water economizer,
โฆ Conventional combustion air preheater, and
โฆ Condensing economizer.
๏ถ Boiler blowdown thermal energy recovery
๏ถ Primary energy resource selection, including
โฆ Fuel (primary energy source) switching, and
โฆ Applied steam energy versus direct-fired energy versus
electricity
๏ถ Insulation issues
๏ถ Steam trap and steam leak management
๏ถ Condensate recovery
๏ถ Steam end-use management
Qualified Energy Assessor
5. Energy Assessment โ QEA How
ห Visual inspection & testing of the
๏ถ Boiler/heater system (comb., DA, economizers, blowdown, etc.)
๏ถ Steam distribution system (piping, steam traps, insulation)
๏ถ Condensate return system (piping, insulation)
๏ถ End use systems (insulation, leaks, direct injection, efficiency)
ห Evaluation of operating characteristics of boiler/heater
systems, energy use systems, O & M procedures, and
unusual operating constraints
ห Review of available architectural and engineering plans,
facility operation and maintenance procedures and logs,
and fuel usage
6. Energy Assessment โ QEA Report
ห Comprehensive report detailing:
๏ถ List of major energy conservation measures (ECMs)
that are within the facilityโs control
๏ถ List of the energy savings potential of the ECMs
identified
โฆ How many Btuโs am I going to save?
โฆ How much $$ are those Btuโs worth?
๏ถ Cost of specific improvements, benefits, and the
simple payback for recouping those investments
7. Efficiency Credits Option
ห Option for meeting BMACT emission limits in
lieu of installing controls
ห Only for existing units at major sources
ห Take credit for equivalent emissions reduction
from implementing ECMs identified in EA to
comply with emission limits
ห Must elect to comply with output-based
emission limits