SlideShare ist ein Scribd-Unternehmen logo
1 von 33
A
PRESENTATION
ON
OPERATION & MAINTENANCE OF DISTRIBUTION TRANSFORMERS
BY
PREPAIRED BY- KAPIL SINGH
(ENGINEER-THERMAX LTD. C&H SSBU O&M)
Definition:
Transformer is a static Electro – magnetic equipment which
transforms alternating current from one voltage level to another voltage
level with out change in frequency. Transformer transfers power from one
winding to another winding via a common magnetic core.
Working Principle:
A transformer works under the principle of mutual electro magnetic
induction (Faraday’s laws of Electro-magnetic induction). It says that, when
ever a changing flux links with a coil an emf is induced in it and this induced
emf is proportional to the rate of change of flux and the number of turns in
the coils linking the flux.
Definition & Working Principle of Transformer
Equation for transformation ratio is,
E2/E1 = N2/N1 = k
k = >1 in step up transformer, where secondary turns are more and thus
voltage is more to reduce the transmission current.
k = <1 in step down transformer, where secondary turns are less than
primary and low voltage for consumer use.
If we include the current in transformation ratio the equation is,
E2/E1 = N2/N1 = I1/I2 = k
Transformation Ratio
Purpose:
a. Electrical energy may be transmitted economically over long distance by
stepping up of voltages to reduce the line losses.
b. To distribute the low voltages at consumer side by stepping down the
voltages.
Advantage:
a. Transformer is a static machine and losses are very less. There by
efficiency is high and about 95 to 98%.
b. Practically maintenance is very less.
Purpose & Advantage
Transformers can be classified into different groups and types based on the
following factors.
Types of Transformers
1. Type of core.
a. Core type transformer core.
b. Shell type transformer core.
c. Berry type transformer core.
d. Spiral type transformer core.
2. Method of cooling.
a. Natural cooling transformer.
b. Artificial cooling transformer.
c. Artificial cooling (water) transformer.
d. Mixed cooling transformer.
3. As per transformer ratio.
a. One to one transformer.
b. Step down transformer.
c. Step up transformer.
4. Based on number of phases.
a. Single-phase transformer.
b. Two-phase transformer.
c. Three phase transformer.
5. As per winding connection.
a. Star-star connected.
b. Star-delta connected.
c. Delta-delta connected.
d. Delta-star connected.
e. Open delta connected.
f. Scott connected.
6. As per the size of the transformer.
a. Distribution transformer.
b. Power transformer.
7. Based on function and utilization.
a. Auto transformer.
b. Potential transformer (instrument
transformer).
c. Current transformer (instrument
transformer).
Parts of the Transformer
LT Side
Buchlotz Relay
Neutral Bushing
Breather
Conservator Tank
OLTC Tank
Pr. Relief valve
Inspection
Window
Flanges for
Radiator
assembly
Thermo well for
OTI & WTI
Parts of the Winding
HT winding
Tapping's
of windings
for OLTC
Core
HT
termination
LT
termination
Insulation of Transformers
Two main kinds of Insulations:
1.Major Insulation:
 Insulating cylinder between LV & core
 Also between HV & LV
 Insulating barriers between limbs, coils & core yoke
 Oil impregnated paper used as it has high dielectric strength
2.Minor Insulation:
 Insulation between
individual turns & between layers
 Conductor Insulation: paper & cotton
 Air insulated Transformer
insulation used is glass tap
Taping of Transformers
Main two location:
1. Inside Tank
2. Outside Tank
Considered as integral part of transformer
Tapping is terminated just bellow oil level
External handle
Taping is done on HV winding
Provided in middle (axial & radial force)
Daily operational check of the Transformer
1. H.T. Voltage and current reading.
2. L.T. Voltage and current reading.
3. WTI current and maximum reading
4. OTI current and maximum reading
5. Oil level in conservator tank
6. Oil level in OLTC tank
7. Tap position
8. Tap changer counter reading
9. Tap changer motor MPCB and limit switch status.
10. PRV status.
11. Buchholz relay status.
12. Condition of silica gel in breathers.
13. Cleanliness of transformer and accessories.
14. Visual leakage / seepage of oil.
15. Humming/any abnormal sound of transformer and accessories.
Quarterly check of the Transformer
1)Cleaning of Transformer
2)Note down of Maximum temp of HV LV Winding. & LV Winding.
3)Checking of OLTC mechanism Step by step
4)Tightening of HV & LV connection
5)Checking of gas collection in Buchholz relay, cleaning of glass cover
6)Operation of tap changer from local and remote.
7) Condition check/replacement of silica gel.
8) Alarm/Tripping signal checking of OTI,WTI,Buchholz and PRV signal at panel.
Yearly check of the Transformer
1. Cleaning of Transformer
2. Oil leakages checks for all joint
3. Note down of Maximum temp of HV LV Winding. & LV Winding.
4. Checking of OLTC mechanism Step by step
5. Tightening of HV & LV connection
6. Checking of gas collection in Buchholz relay, cleaning of glass cover
7. Operation of tap changer from local and remote.
8. Condition check/replacement of silica gel.
9. Alarm/Tripping signal checking of OTI,WTI,Buchholz and PRV signal at panel
10. Oil dehydration
11. BDV of main Oil and OLTC oil
12. PPM of oil.
13. Ratio test in every tap
14. Magnetizing current test.
15. Magnetic balance
16. Winding resistance
17. Insulation resistance.
18. Other inter lock if any.
Tests on the Transformer
Routine Test
1. Ratio and Polarity test
2. Load Losses
3. Impedance measurements
4. Insulation resistance
5. Resistance of windings
6. No load losses
7. No load current
8. Voltage test
a. Separate source
b. Induced voltage
9. Core insulation test
Type Test
1. Temperature rise test.
2. Impulse voltage test.
3. Noise level test
Special Test
1. Partial discharge.
2. Radio interference.
3. Vibration test.
4. Short circuit withstand test.
5. Tan delta test.
Characteristics of Transformer Oil
Characteristics Requirement Method of testing Remarks
Appearance The oil shall be clear
and transparent and
free from suspended
matter of sediments.
A representative sample of the oil
shall be examined in a 100-mm
thick layer at 27°C.
Density at 29.5°C
max.
0.89 gm / cm3 IS-1448(P:16):1977
Kinematic viscosity max.
at
a. 27°C
b. 40°C
27 cSt
under consideration
IS-1448(P:25):1976
Interfacial tension at 27°C
min.
0.04 N/m IS- 6104:1971
Flash point penskymarten
(closed)
140°C IS-1448(P:21):1970
Pour point max. -6°C IS-1448(P:10):1970
Characteristics of Transformer Oil
CharacteristicsCharacteristics RequirementRequirement Method of testingMethod of testing RemarksRemarks
Neutralization valueNeutralization value
a. Total acidity maxa. Total acidity max
b. Inorganicb. Inorganic
acidity/alkalinityacidity/alkalinity
0.03 mg KOH/g0.03 mg KOH/g
nilnil
IS-1448(P:2):1967IS-1448(P:2):1967
IS-1448(P:2):1967IS-1448(P:2):1967
Alcoholic PotassiumAlcoholic Potassium
hydroxide solution ofhydroxide solution of
0.02 N should be in0.02 N should be in
place of 0.1 N Indicatedplace of 0.1 N Indicated
in test Method.in test Method.
Electric strengthElectric strength
(Breakdown voltage)(Breakdown voltage)
a. New unfiltered oil min.a. New unfiltered oil min.
b. After filtration min.b. After filtration min.
30 kV (rms)30 kV (rms)
If the above value is notIf the above value is not
attained the oilattained the oil
shall be filtered 60 kV.shall be filtered 60 kV.
IS-6792:1972IS-6792:1972 See noteSee note
mentioned belowmentioned below
Dielectric dissipationDielectric dissipation
factor (tanfactor (tan δδ) at 90) at 90°°CC
max.max.
0.0020.002 IS-6262:1971IS-6262:1971
Specific resistanceSpecific resistance
(resistivity)(resistivity)
a. At 90a. At 90°°C min.C min.
b. At 27b. At 27°°C min.C min.
35 * 1035 * 101212 ΩΩ-cm-cm
1500* 101500* 101212 ΩΩ-cm-cm
IS-6103:1971IS-6103:1971
Note: As a consequence of the tendency for water absorption to occur due to breathing on storage even when drums are sealed the oil shall be
filtered to remove moisture and particulate contaminates present in the original sample before the test as follows.
a. A sufficient quantity of oil is heated to 90 ± 2°C, then filtered hot under vacuum corresponding to an absolute pressure of about 2.5 kPa
through a sintered glass filter of porosity grade 4’.
b. A portion of filtered is cooled in a desiccator and used immediately to measure electric strength, if required, and specific resistance at 27°C.
The remaining hot filtrate is immediately used for measuring dielectric dissipation factor at 90°C and specific resistance at 90°C.
Characteristics of Transformer Oil
CharacteristicsCharacteristics RequirementRequirement Method of testingMethod of testing RemarksRemarks
Ageing characteristics
after
accelerated ageing
(open beaker method
with copper catalyst)
a. Specific resistance
at
27°C min. & at 90°C
min..
b. Tan δ at 90°C max.
c. Total acidity max
d. Total sludge max.
2.5 * 1012Ω-cm
0.2 * 1012Ω-cm
0.2
0.05 mg KOH/g
0.05% by weight.
IS-12177:1987
IS-6103:1971
IS-6262:1971
IS-1448(P:2):1967
IS-12177
Presence oxidation
inhibitor
The oil shall contain
antioxidant additives
IS-13631:1992 See note below
Note: For both phenol and amine types of indicators, qualitative methods shall be adopted. In case of ambiguity (marginal cases) in finding the
intensity of colour, a quantitativemethod shall be adopted. Value of 0.5 (max.) shall be treated as absence of DBPCPhenolic type inhibitor
(quantitative method for amine is under consideration).
Water content max. 50 ppm IS-13567:1992
Transformer oil Brands available in market
confirming to different
Standards/specifications as per products
Tests to be conducted on the Transformer
Test Purpose Item Required condition of transformer
IR value and PI
value.
Detects serious flaws, moisture
absorption and cleanliness of
winding. Winding. Winding has to be isolated.
Tan delta or dielectric
loss or power factor
or HV test.
Indicates insulation deterioration,
contamination and physical damage.
Winding, oil and
bushings.
Winding has to be isolated,
oil sample should be collected.
Excitation current at
high voltage.
Indicates defects in the magnetic core
structure, shifting or windings, failures
in turn to turn insulation. Winding Winding has to be isolated.
Turns ratio
Indicates short circuited turns and
internal connections Winding Winding has to be isolated.
Winding resistance Detects poor connections and
conductor shorts Winding Winding has to be isolated.
Core IR and
inadvertent grounds
Indicates deterioration of core
insulation system Core Winding has to be isolated.
Water contents Indicates moisture level in oil Oil Oil sample has to be collected
Total acidity,
neutralization number
Measures organic and inorganic
acids Oil Oil sample has to be collected
Dissolved
gas analysis
Indicates specific gases
generated Oil Oil sample has to be collected
Furanite compounds Indicates cellulose degradation Winding Oil sample has to be collected
First Stage: When we start the filtering process initially the temperature will be low, as the
insulation value is high. But as temperature increases the IR value starts to decrease because
the moisture entrapped in the coils are released due to rise in temperature and this causes the
IR value to go down.
Second Stage: Then comes the point where all the moisture is released and then will be no
decrease in IR value or rise in the temperature.
Third Stage: At this point the heaters are switched off. Now the moisture is removed by the oil
filters and the IR value goes up and as the heaters are off the temperature decreases.
Drying out of Transformer
150
700
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
Time
IRVaule
25
Temperature
Stage 1
Stage 2
Stage 3
Temperature
At this point the heaters
are switched off
IR
Humming in the transformer is a sound, which is produced due to the
vibration of the cores in the transformer.
The vibrations are produced due to the change in polarity of an
alternating current or voltage and by the loose of lamination of the core.
Both can be minimized by tightening the core of the transformer.
Humming Sound of the Transformer
Ratio test - Apply 3ph, 415V to high voltage winding of the transformer and
measure the induced voltage on the low voltage terminals at all taps. Ensure
variation in secondary volts as the taps are changed and compare the results
with manufacturers test report or ratio mentioned on transformer nameplate. If
delta tertiary stabilizing winding is provided (usually provided for Y-Y
transformers), open the delta shorting link and measure the voltage across the
two terminals during ratio test - it should be negligible.
No load / magnetising current test - Remove the shorting between primary &
secondary and measure the currents in all the phases while maintaining the
supply at primary. This test is done at nominal tap, and at the minimum and
maximum taps.
Expected currents - Ir / Iy / Ib-- 1: 0.8: 1 for star transformer
- Ir / Iy / Ib-- 1: 1: 1.3 for delta transformer
Ratio Test and No Load Test
Short circuit test
With the transformer at nominal tap, apply 3ph ,415V to the primary and
adequate shorting on the secondary side( depending on % impedance );
ensure bushing CT secondary’s and WTI CT secondary’s are through.
a) Measure currents in primary and secondary
b) Check the currents in CT secondary of bushing CT, WTI CT, and LDC CT.
Repeat point (a) at maximum & minimum taps.
Core balance test
Apply 415V between phase-phase (for delta transformer) and phase-neutral (for
star transformer) on secondary side. Ensure that adequate safety precautions
are taken on the primary side, as high voltage will be induced.
Measure the current and voltages for the following phases--
For delta trafo - Vry, Vyb, Vbr
For star trafo - Vry, Vyb, Vbr, Vrn, Vyn, Vbn.
Short Circuit and Core Balance Test
Insulation test
Insulation tester of 2.5 or 5 KV may be used. Polarisation index is recorded by IR
value at 10/1 min ratio.
Insulation Test
PI Value
Insulation
Condition
Recommendation
1.0 to 1.5 Bad
Drying is
Mandatory
1.5 to 2 Doubtful
Drying is
recommended.
2.0 to 3.0 Good
No drying is
required.
3.0 to 4.0 Excellent
No drying is
required.
Transformer oil testing at site:
Prior to charging of transformer confirm the healthiness of the oil by testing the
dielectric strength of oil. The oil is to be tested at 2.5 mm gap. 3 readings have
to be taken and a average of these readings is the ‘breakdown voltage of the
oil’. BDV should be >60 KV.
Transformer Oil Testing
Transformer oil testing at Lab:
 Electric strength
 Water contents
 Dissolved gas analysis
 Dielectric dissipation factor (Dielectric dissipation factor (Tan δ)
 Total acidity max
 Total sludge max
In transformer there are mainly three types of losses
1-iron loss or core loss
2-Copper loss or I
2
R loss.
3-Stray and Dielectric loss.
These losses due to,
1. Resistance of the winding (copper losses).
2. Eddy current and Hysteresis in the iron parts and core (core and iron losses).
3. Losses due to leakage reactance (leakage flux).
At No load the copper losses and leakage flux losses are negligible due to the very
less primary current.
At loaded condition copper losses and leakage flux losses will exist in considerable
manner.
Copper losses are variable and can be calculated by Ip2
*Rp and Is2
*Rs.
(Where I-current , R-resistance p-primary winding s-secondary winding)
Losses in the Transformer
1. Check oil leakage from bushings, valves, air release plugs, etc.
2. Direction of mounting of Buchholz relay, as per arrow on the relay; the arrow
should point towards the conservator
3. Oil level in condenser bushings
4. Oil level of Main Tank and OLTC Tank should be up to the filling mark on MOG
(Minimum Oil Level Gauge)
5. Transformer is earthed at two points
6. Stoppers provided for locking of wheels
7. Test taps on HV condenser bushings are fixed Valves on each radiator, both top
and bottom, should be open.
8. Valves on either side of Buchholz relay should be open
10. Tightness of conductors / cables on Trafo. HV side, LV side and Neutral.
11. Check resistance and IR value of NGR, if provided
12. Check that oil is filled in OTI and WTI pockets.
13. Check that colour of silica gel in breathers of main conservator and OLTC
conservator is blue.
14. Oil in breather cups to be filled up to level indicated
Commissioning Procedure for a Transformer
.
OLTC separate chamber type
OLTC in-built in the main tank
a) For in-built OLTC (diverter switch) ensure that the tap number on the Drive mechanism
(DM) is same as the one in the display on the main tank. Then connect the main
operating rod between the OLTC DM and diverter switch.
Conduct mechanical operations on the OLTC taking it through all the taps. Ensure that
the final end position (upper and lower limit) switches operate.
b) During the raise / lower operation note the direction of operating mechanism. Switch’ off’
the 3 PH AC supply and check operation of raise/lower contactor as per commands from
DM.
c) With OLTC at some intermediate tap, switch on the 3 phase supply and give either raise /
lower command to the OLTC. Check whether the mechanism is moving in the right
direction for the command given. If the direction is reverse, switch ‘off’ the AC & DC
supply, verify that the phase sequence of the supply is correct; if not correct, reverse the
phase sequence at the motor terminal box.
d) Observe the operation of OLTC and check blocking of operation at the end positions
e) Verify that insertion of manual operating handle cuts off electrical operation.
f) Test the Automatic Voltage Regulating Relay (AVRR), if provided. Perform automatic
operation from the AVRR.
Commissioning Procedure for an
OLTC of Transformer
1. Cleaning of the transformer, especially the bushings. Ensure that all protections are
operative. Buchholz relay maybe tested by using the test screw, or by pumping in air with
a bicycle pump , or by draining oil from the relay after closing both side valves.
2. Air release from the transformer is to be done from air release plugs on the main tank,
radiators, HV &LV bushings, Buchholz relay and OLTC prior to charging of transformer.
Do not release air from the Condenser bushings as they are hermetically sealed.
3. Check operation of OTI/WTI, ensure oil in the temperature probe pots.
4. Check that all interconnecting valves are in open position.
5. Check IR values between each winding an earth, and between windings. Neutral
earthing is to be disconnected for this purpose.
6. Check that HV and LV neutral earthing has been re–connected after megger test.
7. Earthing and delta shorting of tertiary stabilizing winding (if provided), to be checked.
8. Proper setting of OTI & WTI to be done.
9. Perform trip test from all the transformer protections, including Buchholz relay, PRD, Oil
surge relay, OTI and WTI.
10. All protection relays to be properly set.
11. Reset the Maximum Reading Pointer (MRP) of OTI & WTI.
12. Ammeter selector switches should be selected to read some phase current.
13. All MCBs, fuses and switches in Marshalling boxes, CRPs, isolator cubicles and breaker
cubicles should be in circuit.
14. If the transformer is provided with an OLTC, energise it at Tap #1; if the transformer is
provided with an off-circuit tap changer, energise it at the nominal tap.
Prior to Energizing the Transformer
After energising the transformer :
1. If OLTC is provided, run the tap changer from Tap #1 up to nominal tap.
2. Check the phase sequence and magnitude of the transformer secondary
voltage at the incoming line PTs.
3. If the transformer is an extension to an existing system, do the phasing out
w.r.t. the existing PTs.
4. Check for any abnormal sound or vibration in the transformer.
5. Keep the transformer energised on no-load for 24 hours; take readings of
OTI, WTI and current.
After Energizing the Transformer
CONDITIONS LEADING TO FAULTS
Insulation breakdown
Aging of insulation
Overheating due to over excitation
Oil contamination and leakage
Reduced cooling
External circuit fault
NATURE OF TRANSFORMER FAULTS
Although an electrical power transformer is a static device, but internal stresses
arising from abnormal system conditions, must be taken into consideration.
A transformer generally suffers from following types of transformer fault-Over
current due to overloads and external short circuits,
Terminal faults,
Winding faults,
Incipient faults.
All the above mentioned transformer faults cause mechanical and thermal stresses
inside the transformer winding and its connecting terminals. Thermal stresses lead
to overheating which ultimately affect the insulation system of transformer.
Deterioration of insulation leads to winding faults. Some time failure of transformer
cooling system leads to overheating of transformer. So the transformer protection
schemes are very much required.
The short circuit current of an electrical transformer is normally limited by its
reactance and for low reactance, the value of short circuit current may be
excessively high.
TRANSFORMER PROTECTION
It is common practice to provide buchholz relay protection to all 0.5 MVA and above
transformers. While for all small size distribution transformers, only high voltage
fuses are used as main protective device. For all larger rated and important
distribution transformers, over current protection along with restricted earth fault
protection is applied. Differential protection should be provided in the transformers
rated above 5 MVA. Depending upon the normal service condition, nature of
transformer faults, degree of sustained over load, scheme of tap changing, and
many other factors, the suitable transformer protection schemes are chosen
Some Typical protection equipments are enlisted below
1.Buchholz relay
2.PRV
3.OTI
4.WTI
5.MOG
6.O/V current and E/F relay
7.Differential protection relay
ch
THANK YOU
C&H SSBU O&M REGION-DELHI

Weitere ähnliche Inhalte

Was ist angesagt?

Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protectionmichaeljmack
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introductionH. Kheir
 
transformer protection
transformer protection transformer protection
transformer protection jason adidela
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHShankar Singh
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenancekarikalan123
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guideSlides Hub
 
Electrical Design calculations
Electrical Design calculationsElectrical Design calculations
Electrical Design calculationsPankaj Chavan
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protectionRakesh Joshi
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNikhil Kachare
 

Was ist angesagt? (20)

Tap changer
Tap changerTap changer
Tap changer
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Buchholz relay
Buchholz relayBuchholz relay
Buchholz relay
 
Electrical SUBSTATION ppt
Electrical SUBSTATION pptElectrical SUBSTATION ppt
Electrical SUBSTATION ppt
 
transformer protection
transformer protection transformer protection
transformer protection
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGHHIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
HIGH VOL TAGE TESTING OF TRANSFORMER BY HARI SHANKAR SINGH
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenance
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
Motor starter
Motor starterMotor starter
Motor starter
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
 
Electrical Design calculations
Electrical Design calculationsElectrical Design calculations
Electrical Design calculations
 
HT and LT SWITCHGEAR
HT and LT SWITCHGEARHT and LT SWITCHGEAR
HT and LT SWITCHGEAR
 
Motor Protection
Motor ProtectionMotor Protection
Motor Protection
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protection
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 

Ähnlich wie Operation and maintenance of transformer

PROTECTIVE DEVICES & MAINTENANCE.ppt
PROTECTIVE DEVICES & MAINTENANCE.pptPROTECTIVE DEVICES & MAINTENANCE.ppt
PROTECTIVE DEVICES & MAINTENANCE.pptQwer401863
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsSumeet Ratnawat
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rAshish Patel
 
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitPRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitJimit Dhruv
 
Transformer Repair Workshop Report [EEE]
Transformer Repair Workshop Report [EEE] Transformer Repair Workshop Report [EEE]
Transformer Repair Workshop Report [EEE] Nik Sharma
 
Tranformer general , operation and maintenace by walid
Tranformer general , operation and maintenace by walidTranformer general , operation and maintenace by walid
Tranformer general , operation and maintenace by walidWalidkarim884
 
CIRCUIT BREAKER USED IN THERMAL POWER PLANTS
CIRCUIT BREAKER USED IN THERMAL POWER PLANTSCIRCUIT BREAKER USED IN THERMAL POWER PLANTS
CIRCUIT BREAKER USED IN THERMAL POWER PLANTSDigantaSinha1
 
Maintenance schedule of Substation.
Maintenance schedule of Substation.Maintenance schedule of Substation.
Maintenance schedule of Substation.Sheikh Nazmul Islam
 
Presentation_Power_Transformers-1
Presentation_Power_Transformers-1Presentation_Power_Transformers-1
Presentation_Power_Transformers-1Nageswar Rao
 
Power-Transformer-Testing-Brochure-ENU.pdf
Power-Transformer-Testing-Brochure-ENU.pdfPower-Transformer-Testing-Brochure-ENU.pdf
Power-Transformer-Testing-Brochure-ENU.pdfNguyenXuanTung12
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformervikasgupta1965
 
Liquid Insulation Dissipation factor and Dielectric Factor Measurement Unit
Liquid Insulation Dissipation factor and Dielectric Factor Measurement UnitLiquid Insulation Dissipation factor and Dielectric Factor Measurement Unit
Liquid Insulation Dissipation factor and Dielectric Factor Measurement UnitNadiiaHubar
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptChristinaBoyd12
 
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.pptsantubanga333
 

Ähnlich wie Operation and maintenance of transformer (20)

transformers.ppt
transformers.ppttransformers.ppt
transformers.ppt
 
PROTECTIVE DEVICES & MAINTENANCE.ppt
PROTECTIVE DEVICES & MAINTENANCE.pptPROTECTIVE DEVICES & MAINTENANCE.ppt
PROTECTIVE DEVICES & MAINTENANCE.ppt
 
Testing and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation EquipmentsTesting and Condition Monitoring of Substation Equipments
Testing and Condition Monitoring of Substation Equipments
 
Transformer
TransformerTransformer
Transformer
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines r
 
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitPRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
 
tcee-161003100321.pptx
tcee-161003100321.pptxtcee-161003100321.pptx
tcee-161003100321.pptx
 
3 condition monitoring of oil
3 condition monitoring of oil3 condition monitoring of oil
3 condition monitoring of oil
 
Transformer Repair Workshop Report [EEE]
Transformer Repair Workshop Report [EEE] Transformer Repair Workshop Report [EEE]
Transformer Repair Workshop Report [EEE]
 
Tranformer general , operation and maintenace by walid
Tranformer general , operation and maintenace by walidTranformer general , operation and maintenace by walid
Tranformer general , operation and maintenace by walid
 
CIRCUIT BREAKER USED IN THERMAL POWER PLANTS
CIRCUIT BREAKER USED IN THERMAL POWER PLANTSCIRCUIT BREAKER USED IN THERMAL POWER PLANTS
CIRCUIT BREAKER USED IN THERMAL POWER PLANTS
 
Maintenance schedule of Substation.
Maintenance schedule of Substation.Maintenance schedule of Substation.
Maintenance schedule of Substation.
 
Presentation_Power_Transformers-1
Presentation_Power_Transformers-1Presentation_Power_Transformers-1
Presentation_Power_Transformers-1
 
Executive summary
Executive summaryExecutive summary
Executive summary
 
Wapda Engineering Acadmy Report
Wapda Engineering Acadmy ReportWapda Engineering Acadmy Report
Wapda Engineering Acadmy Report
 
Power-Transformer-Testing-Brochure-ENU.pdf
Power-Transformer-Testing-Brochure-ENU.pdfPower-Transformer-Testing-Brochure-ENU.pdf
Power-Transformer-Testing-Brochure-ENU.pdf
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Liquid Insulation Dissipation factor and Dielectric Factor Measurement Unit
Liquid Insulation Dissipation factor and Dielectric Factor Measurement UnitLiquid Insulation Dissipation factor and Dielectric Factor Measurement Unit
Liquid Insulation Dissipation factor and Dielectric Factor Measurement Unit
 
TESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.pptTESTING,MAINTENANCE&PROTECTION.ppt
TESTING,MAINTENANCE&PROTECTION.ppt
 
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
93518813-TESTING-MAINTENANCE-PROTECTION-OF-DISTRIBUTION-TRANSFORMERS.ppt
 

Kürzlich hochgeladen

COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxSCMS School of Architecture
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxSCMS School of Architecture
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"mphochane1998
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityMorshed Ahmed Rahath
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...Amil baba
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxchumtiyababu
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersMairaAshraf6
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayEpec Engineered Technologies
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxmaisarahman1
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARKOUSTAV SARKAR
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxNadaHaitham1
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdfKamal Acharya
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 

Kürzlich hochgeladen (20)

COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptx
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Online electricity billing project report..pdf
Online electricity billing project report..pdfOnline electricity billing project report..pdf
Online electricity billing project report..pdf
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 

Operation and maintenance of transformer

  • 1. A PRESENTATION ON OPERATION & MAINTENANCE OF DISTRIBUTION TRANSFORMERS BY PREPAIRED BY- KAPIL SINGH (ENGINEER-THERMAX LTD. C&H SSBU O&M)
  • 2. Definition: Transformer is a static Electro – magnetic equipment which transforms alternating current from one voltage level to another voltage level with out change in frequency. Transformer transfers power from one winding to another winding via a common magnetic core. Working Principle: A transformer works under the principle of mutual electro magnetic induction (Faraday’s laws of Electro-magnetic induction). It says that, when ever a changing flux links with a coil an emf is induced in it and this induced emf is proportional to the rate of change of flux and the number of turns in the coils linking the flux. Definition & Working Principle of Transformer
  • 3. Equation for transformation ratio is, E2/E1 = N2/N1 = k k = >1 in step up transformer, where secondary turns are more and thus voltage is more to reduce the transmission current. k = <1 in step down transformer, where secondary turns are less than primary and low voltage for consumer use. If we include the current in transformation ratio the equation is, E2/E1 = N2/N1 = I1/I2 = k Transformation Ratio
  • 4. Purpose: a. Electrical energy may be transmitted economically over long distance by stepping up of voltages to reduce the line losses. b. To distribute the low voltages at consumer side by stepping down the voltages. Advantage: a. Transformer is a static machine and losses are very less. There by efficiency is high and about 95 to 98%. b. Practically maintenance is very less. Purpose & Advantage
  • 5. Transformers can be classified into different groups and types based on the following factors. Types of Transformers 1. Type of core. a. Core type transformer core. b. Shell type transformer core. c. Berry type transformer core. d. Spiral type transformer core. 2. Method of cooling. a. Natural cooling transformer. b. Artificial cooling transformer. c. Artificial cooling (water) transformer. d. Mixed cooling transformer. 3. As per transformer ratio. a. One to one transformer. b. Step down transformer. c. Step up transformer. 4. Based on number of phases. a. Single-phase transformer. b. Two-phase transformer. c. Three phase transformer. 5. As per winding connection. a. Star-star connected. b. Star-delta connected. c. Delta-delta connected. d. Delta-star connected. e. Open delta connected. f. Scott connected. 6. As per the size of the transformer. a. Distribution transformer. b. Power transformer. 7. Based on function and utilization. a. Auto transformer. b. Potential transformer (instrument transformer). c. Current transformer (instrument transformer).
  • 6. Parts of the Transformer LT Side Buchlotz Relay Neutral Bushing Breather Conservator Tank OLTC Tank Pr. Relief valve Inspection Window Flanges for Radiator assembly Thermo well for OTI & WTI
  • 7. Parts of the Winding HT winding Tapping's of windings for OLTC Core HT termination LT termination
  • 8. Insulation of Transformers Two main kinds of Insulations: 1.Major Insulation:  Insulating cylinder between LV & core  Also between HV & LV  Insulating barriers between limbs, coils & core yoke  Oil impregnated paper used as it has high dielectric strength 2.Minor Insulation:  Insulation between individual turns & between layers  Conductor Insulation: paper & cotton  Air insulated Transformer insulation used is glass tap
  • 9. Taping of Transformers Main two location: 1. Inside Tank 2. Outside Tank Considered as integral part of transformer Tapping is terminated just bellow oil level External handle Taping is done on HV winding Provided in middle (axial & radial force)
  • 10. Daily operational check of the Transformer 1. H.T. Voltage and current reading. 2. L.T. Voltage and current reading. 3. WTI current and maximum reading 4. OTI current and maximum reading 5. Oil level in conservator tank 6. Oil level in OLTC tank 7. Tap position 8. Tap changer counter reading 9. Tap changer motor MPCB and limit switch status. 10. PRV status. 11. Buchholz relay status. 12. Condition of silica gel in breathers. 13. Cleanliness of transformer and accessories. 14. Visual leakage / seepage of oil. 15. Humming/any abnormal sound of transformer and accessories.
  • 11. Quarterly check of the Transformer 1)Cleaning of Transformer 2)Note down of Maximum temp of HV LV Winding. & LV Winding. 3)Checking of OLTC mechanism Step by step 4)Tightening of HV & LV connection 5)Checking of gas collection in Buchholz relay, cleaning of glass cover 6)Operation of tap changer from local and remote. 7) Condition check/replacement of silica gel. 8) Alarm/Tripping signal checking of OTI,WTI,Buchholz and PRV signal at panel.
  • 12. Yearly check of the Transformer 1. Cleaning of Transformer 2. Oil leakages checks for all joint 3. Note down of Maximum temp of HV LV Winding. & LV Winding. 4. Checking of OLTC mechanism Step by step 5. Tightening of HV & LV connection 6. Checking of gas collection in Buchholz relay, cleaning of glass cover 7. Operation of tap changer from local and remote. 8. Condition check/replacement of silica gel. 9. Alarm/Tripping signal checking of OTI,WTI,Buchholz and PRV signal at panel 10. Oil dehydration 11. BDV of main Oil and OLTC oil 12. PPM of oil. 13. Ratio test in every tap 14. Magnetizing current test. 15. Magnetic balance 16. Winding resistance 17. Insulation resistance. 18. Other inter lock if any.
  • 13. Tests on the Transformer Routine Test 1. Ratio and Polarity test 2. Load Losses 3. Impedance measurements 4. Insulation resistance 5. Resistance of windings 6. No load losses 7. No load current 8. Voltage test a. Separate source b. Induced voltage 9. Core insulation test Type Test 1. Temperature rise test. 2. Impulse voltage test. 3. Noise level test Special Test 1. Partial discharge. 2. Radio interference. 3. Vibration test. 4. Short circuit withstand test. 5. Tan delta test.
  • 14. Characteristics of Transformer Oil Characteristics Requirement Method of testing Remarks Appearance The oil shall be clear and transparent and free from suspended matter of sediments. A representative sample of the oil shall be examined in a 100-mm thick layer at 27°C. Density at 29.5°C max. 0.89 gm / cm3 IS-1448(P:16):1977 Kinematic viscosity max. at a. 27°C b. 40°C 27 cSt under consideration IS-1448(P:25):1976 Interfacial tension at 27°C min. 0.04 N/m IS- 6104:1971 Flash point penskymarten (closed) 140°C IS-1448(P:21):1970 Pour point max. -6°C IS-1448(P:10):1970
  • 15. Characteristics of Transformer Oil CharacteristicsCharacteristics RequirementRequirement Method of testingMethod of testing RemarksRemarks Neutralization valueNeutralization value a. Total acidity maxa. Total acidity max b. Inorganicb. Inorganic acidity/alkalinityacidity/alkalinity 0.03 mg KOH/g0.03 mg KOH/g nilnil IS-1448(P:2):1967IS-1448(P:2):1967 IS-1448(P:2):1967IS-1448(P:2):1967 Alcoholic PotassiumAlcoholic Potassium hydroxide solution ofhydroxide solution of 0.02 N should be in0.02 N should be in place of 0.1 N Indicatedplace of 0.1 N Indicated in test Method.in test Method. Electric strengthElectric strength (Breakdown voltage)(Breakdown voltage) a. New unfiltered oil min.a. New unfiltered oil min. b. After filtration min.b. After filtration min. 30 kV (rms)30 kV (rms) If the above value is notIf the above value is not attained the oilattained the oil shall be filtered 60 kV.shall be filtered 60 kV. IS-6792:1972IS-6792:1972 See noteSee note mentioned belowmentioned below Dielectric dissipationDielectric dissipation factor (tanfactor (tan δδ) at 90) at 90°°CC max.max. 0.0020.002 IS-6262:1971IS-6262:1971 Specific resistanceSpecific resistance (resistivity)(resistivity) a. At 90a. At 90°°C min.C min. b. At 27b. At 27°°C min.C min. 35 * 1035 * 101212 ΩΩ-cm-cm 1500* 101500* 101212 ΩΩ-cm-cm IS-6103:1971IS-6103:1971 Note: As a consequence of the tendency for water absorption to occur due to breathing on storage even when drums are sealed the oil shall be filtered to remove moisture and particulate contaminates present in the original sample before the test as follows. a. A sufficient quantity of oil is heated to 90 ± 2°C, then filtered hot under vacuum corresponding to an absolute pressure of about 2.5 kPa through a sintered glass filter of porosity grade 4’. b. A portion of filtered is cooled in a desiccator and used immediately to measure electric strength, if required, and specific resistance at 27°C. The remaining hot filtrate is immediately used for measuring dielectric dissipation factor at 90°C and specific resistance at 90°C.
  • 16. Characteristics of Transformer Oil CharacteristicsCharacteristics RequirementRequirement Method of testingMethod of testing RemarksRemarks Ageing characteristics after accelerated ageing (open beaker method with copper catalyst) a. Specific resistance at 27°C min. & at 90°C min.. b. Tan δ at 90°C max. c. Total acidity max d. Total sludge max. 2.5 * 1012Ω-cm 0.2 * 1012Ω-cm 0.2 0.05 mg KOH/g 0.05% by weight. IS-12177:1987 IS-6103:1971 IS-6262:1971 IS-1448(P:2):1967 IS-12177 Presence oxidation inhibitor The oil shall contain antioxidant additives IS-13631:1992 See note below Note: For both phenol and amine types of indicators, qualitative methods shall be adopted. In case of ambiguity (marginal cases) in finding the intensity of colour, a quantitativemethod shall be adopted. Value of 0.5 (max.) shall be treated as absence of DBPCPhenolic type inhibitor (quantitative method for amine is under consideration). Water content max. 50 ppm IS-13567:1992
  • 17. Transformer oil Brands available in market confirming to different Standards/specifications as per products
  • 18. Tests to be conducted on the Transformer Test Purpose Item Required condition of transformer IR value and PI value. Detects serious flaws, moisture absorption and cleanliness of winding. Winding. Winding has to be isolated. Tan delta or dielectric loss or power factor or HV test. Indicates insulation deterioration, contamination and physical damage. Winding, oil and bushings. Winding has to be isolated, oil sample should be collected. Excitation current at high voltage. Indicates defects in the magnetic core structure, shifting or windings, failures in turn to turn insulation. Winding Winding has to be isolated. Turns ratio Indicates short circuited turns and internal connections Winding Winding has to be isolated. Winding resistance Detects poor connections and conductor shorts Winding Winding has to be isolated. Core IR and inadvertent grounds Indicates deterioration of core insulation system Core Winding has to be isolated. Water contents Indicates moisture level in oil Oil Oil sample has to be collected Total acidity, neutralization number Measures organic and inorganic acids Oil Oil sample has to be collected Dissolved gas analysis Indicates specific gases generated Oil Oil sample has to be collected Furanite compounds Indicates cellulose degradation Winding Oil sample has to be collected
  • 19. First Stage: When we start the filtering process initially the temperature will be low, as the insulation value is high. But as temperature increases the IR value starts to decrease because the moisture entrapped in the coils are released due to rise in temperature and this causes the IR value to go down. Second Stage: Then comes the point where all the moisture is released and then will be no decrease in IR value or rise in the temperature. Third Stage: At this point the heaters are switched off. Now the moisture is removed by the oil filters and the IR value goes up and as the heaters are off the temperature decreases. Drying out of Transformer 150 700 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Time IRVaule 25 Temperature Stage 1 Stage 2 Stage 3 Temperature At this point the heaters are switched off IR
  • 20. Humming in the transformer is a sound, which is produced due to the vibration of the cores in the transformer. The vibrations are produced due to the change in polarity of an alternating current or voltage and by the loose of lamination of the core. Both can be minimized by tightening the core of the transformer. Humming Sound of the Transformer
  • 21. Ratio test - Apply 3ph, 415V to high voltage winding of the transformer and measure the induced voltage on the low voltage terminals at all taps. Ensure variation in secondary volts as the taps are changed and compare the results with manufacturers test report or ratio mentioned on transformer nameplate. If delta tertiary stabilizing winding is provided (usually provided for Y-Y transformers), open the delta shorting link and measure the voltage across the two terminals during ratio test - it should be negligible. No load / magnetising current test - Remove the shorting between primary & secondary and measure the currents in all the phases while maintaining the supply at primary. This test is done at nominal tap, and at the minimum and maximum taps. Expected currents - Ir / Iy / Ib-- 1: 0.8: 1 for star transformer - Ir / Iy / Ib-- 1: 1: 1.3 for delta transformer Ratio Test and No Load Test
  • 22. Short circuit test With the transformer at nominal tap, apply 3ph ,415V to the primary and adequate shorting on the secondary side( depending on % impedance ); ensure bushing CT secondary’s and WTI CT secondary’s are through. a) Measure currents in primary and secondary b) Check the currents in CT secondary of bushing CT, WTI CT, and LDC CT. Repeat point (a) at maximum & minimum taps. Core balance test Apply 415V between phase-phase (for delta transformer) and phase-neutral (for star transformer) on secondary side. Ensure that adequate safety precautions are taken on the primary side, as high voltage will be induced. Measure the current and voltages for the following phases-- For delta trafo - Vry, Vyb, Vbr For star trafo - Vry, Vyb, Vbr, Vrn, Vyn, Vbn. Short Circuit and Core Balance Test
  • 23. Insulation test Insulation tester of 2.5 or 5 KV may be used. Polarisation index is recorded by IR value at 10/1 min ratio. Insulation Test PI Value Insulation Condition Recommendation 1.0 to 1.5 Bad Drying is Mandatory 1.5 to 2 Doubtful Drying is recommended. 2.0 to 3.0 Good No drying is required. 3.0 to 4.0 Excellent No drying is required.
  • 24. Transformer oil testing at site: Prior to charging of transformer confirm the healthiness of the oil by testing the dielectric strength of oil. The oil is to be tested at 2.5 mm gap. 3 readings have to be taken and a average of these readings is the ‘breakdown voltage of the oil’. BDV should be >60 KV. Transformer Oil Testing Transformer oil testing at Lab:  Electric strength  Water contents  Dissolved gas analysis  Dielectric dissipation factor (Dielectric dissipation factor (Tan δ)  Total acidity max  Total sludge max
  • 25. In transformer there are mainly three types of losses 1-iron loss or core loss 2-Copper loss or I 2 R loss. 3-Stray and Dielectric loss. These losses due to, 1. Resistance of the winding (copper losses). 2. Eddy current and Hysteresis in the iron parts and core (core and iron losses). 3. Losses due to leakage reactance (leakage flux). At No load the copper losses and leakage flux losses are negligible due to the very less primary current. At loaded condition copper losses and leakage flux losses will exist in considerable manner. Copper losses are variable and can be calculated by Ip2 *Rp and Is2 *Rs. (Where I-current , R-resistance p-primary winding s-secondary winding) Losses in the Transformer
  • 26. 1. Check oil leakage from bushings, valves, air release plugs, etc. 2. Direction of mounting of Buchholz relay, as per arrow on the relay; the arrow should point towards the conservator 3. Oil level in condenser bushings 4. Oil level of Main Tank and OLTC Tank should be up to the filling mark on MOG (Minimum Oil Level Gauge) 5. Transformer is earthed at two points 6. Stoppers provided for locking of wheels 7. Test taps on HV condenser bushings are fixed Valves on each radiator, both top and bottom, should be open. 8. Valves on either side of Buchholz relay should be open 10. Tightness of conductors / cables on Trafo. HV side, LV side and Neutral. 11. Check resistance and IR value of NGR, if provided 12. Check that oil is filled in OTI and WTI pockets. 13. Check that colour of silica gel in breathers of main conservator and OLTC conservator is blue. 14. Oil in breather cups to be filled up to level indicated Commissioning Procedure for a Transformer .
  • 27. OLTC separate chamber type OLTC in-built in the main tank a) For in-built OLTC (diverter switch) ensure that the tap number on the Drive mechanism (DM) is same as the one in the display on the main tank. Then connect the main operating rod between the OLTC DM and diverter switch. Conduct mechanical operations on the OLTC taking it through all the taps. Ensure that the final end position (upper and lower limit) switches operate. b) During the raise / lower operation note the direction of operating mechanism. Switch’ off’ the 3 PH AC supply and check operation of raise/lower contactor as per commands from DM. c) With OLTC at some intermediate tap, switch on the 3 phase supply and give either raise / lower command to the OLTC. Check whether the mechanism is moving in the right direction for the command given. If the direction is reverse, switch ‘off’ the AC & DC supply, verify that the phase sequence of the supply is correct; if not correct, reverse the phase sequence at the motor terminal box. d) Observe the operation of OLTC and check blocking of operation at the end positions e) Verify that insertion of manual operating handle cuts off electrical operation. f) Test the Automatic Voltage Regulating Relay (AVRR), if provided. Perform automatic operation from the AVRR. Commissioning Procedure for an OLTC of Transformer
  • 28. 1. Cleaning of the transformer, especially the bushings. Ensure that all protections are operative. Buchholz relay maybe tested by using the test screw, or by pumping in air with a bicycle pump , or by draining oil from the relay after closing both side valves. 2. Air release from the transformer is to be done from air release plugs on the main tank, radiators, HV &LV bushings, Buchholz relay and OLTC prior to charging of transformer. Do not release air from the Condenser bushings as they are hermetically sealed. 3. Check operation of OTI/WTI, ensure oil in the temperature probe pots. 4. Check that all interconnecting valves are in open position. 5. Check IR values between each winding an earth, and between windings. Neutral earthing is to be disconnected for this purpose. 6. Check that HV and LV neutral earthing has been re–connected after megger test. 7. Earthing and delta shorting of tertiary stabilizing winding (if provided), to be checked. 8. Proper setting of OTI & WTI to be done. 9. Perform trip test from all the transformer protections, including Buchholz relay, PRD, Oil surge relay, OTI and WTI. 10. All protection relays to be properly set. 11. Reset the Maximum Reading Pointer (MRP) of OTI & WTI. 12. Ammeter selector switches should be selected to read some phase current. 13. All MCBs, fuses and switches in Marshalling boxes, CRPs, isolator cubicles and breaker cubicles should be in circuit. 14. If the transformer is provided with an OLTC, energise it at Tap #1; if the transformer is provided with an off-circuit tap changer, energise it at the nominal tap. Prior to Energizing the Transformer
  • 29. After energising the transformer : 1. If OLTC is provided, run the tap changer from Tap #1 up to nominal tap. 2. Check the phase sequence and magnitude of the transformer secondary voltage at the incoming line PTs. 3. If the transformer is an extension to an existing system, do the phasing out w.r.t. the existing PTs. 4. Check for any abnormal sound or vibration in the transformer. 5. Keep the transformer energised on no-load for 24 hours; take readings of OTI, WTI and current. After Energizing the Transformer
  • 30. CONDITIONS LEADING TO FAULTS Insulation breakdown Aging of insulation Overheating due to over excitation Oil contamination and leakage Reduced cooling External circuit fault
  • 31. NATURE OF TRANSFORMER FAULTS Although an electrical power transformer is a static device, but internal stresses arising from abnormal system conditions, must be taken into consideration. A transformer generally suffers from following types of transformer fault-Over current due to overloads and external short circuits, Terminal faults, Winding faults, Incipient faults. All the above mentioned transformer faults cause mechanical and thermal stresses inside the transformer winding and its connecting terminals. Thermal stresses lead to overheating which ultimately affect the insulation system of transformer. Deterioration of insulation leads to winding faults. Some time failure of transformer cooling system leads to overheating of transformer. So the transformer protection schemes are very much required. The short circuit current of an electrical transformer is normally limited by its reactance and for low reactance, the value of short circuit current may be excessively high.
  • 32. TRANSFORMER PROTECTION It is common practice to provide buchholz relay protection to all 0.5 MVA and above transformers. While for all small size distribution transformers, only high voltage fuses are used as main protective device. For all larger rated and important distribution transformers, over current protection along with restricted earth fault protection is applied. Differential protection should be provided in the transformers rated above 5 MVA. Depending upon the normal service condition, nature of transformer faults, degree of sustained over load, scheme of tap changing, and many other factors, the suitable transformer protection schemes are chosen Some Typical protection equipments are enlisted below 1.Buchholz relay 2.PRV 3.OTI 4.WTI 5.MOG 6.O/V current and E/F relay 7.Differential protection relay
  • 33. ch THANK YOU C&H SSBU O&M REGION-DELHI