TECHNICAL SPECIFICATIONS
AIR CONDITIONING & MECHANICAL VENTILATION INSTALLATION
TS/A/40/1
SECTION 40 – WATER DETECTION SYSTEM
1 General
1.1 This section sets out the requirements for water detection system and
covers the supply, delivery, installation, testing and commissioning
and twelve (12) months free maintenance and warranty of the system
and associated equipment.
1.2 The system components shall be designed to be installed according to
pre-test limitations as approved or listed by a recognised testing
laboratory.
1.3 All devices shall be designed for service encountered and shall not be
readily rendered in-operative or susceptible to accidental operation.
They shall be located, installed or suitably protected against
mechanical, chemical or other damage, which may render them in-
operative. All devices for activating supplementary equipment shall be
considered as integral parts of the system and shall function with
system operation.
1.4 The complete system shall include electronics alarm module, sensing
cable, graphic display map, and auxiliary equipment, as indicated on
the design drawings. The system shall simultaneously detect the
presence of water at any point along the cable's length and activate
the module's leak alarm relays. The sensing cable shall be of such
construction that no metallic parts shall be exposed to the
environment. The system shall be provided with pre-connectorised
sensing cable components.
2 Alarm Locator Module
2.1 The alarm module shall be capable of monitoring up to 1500 meters of
sensing cable.
2.2 The alarm module shall have LEDs indicating "power" (green), "alarm"
(red), and "continuity" (yellow). The system shall sound an audible
alarm upon sensing a leak. Once the alarm condition has been
cleared, the module is reset with a single keystroke.
2.3 Basic Features of the alarm locator module
 In addition to detecting leaks, the system shall warn of fault
conditions and indicates when maintenance is required.
 An event history log allows leaks (and other events) to be
tracked.
 The settings can be customised to suit the user’s application.
 Both the events history log and any user settings are held in
non-volatile memory.
 The unit shall has an in-built system-wide diagnostic functions
TECHNICAL SPECIFICATIONS
AIR CONDITIONING & MECHANICAL VENTILATION INSTALLATION
TS/A/40/2
2.4 The alarm module will be powered by 240 VAC. The module shall
have a pair of contacts open on an alarm, and a pair of contacts close
on an alarm. These contacts shall be used to actuate other alarms
and shall be capable of switching 10 amps at 250 VAC.
2.5 In additions, the module shall be provided with 4-20 mA signal and
RS232/RS-485 series port for connection to building management
system.
2.6 The module enclosure shall be NEMA 1, constructed of 16- gauge
steel with dimensions of 8" x 8" x 4". The enclosure shall be capable
of either semi-flush of surface mounting.
3 Sensing Cable
3.1 The water sensing cable shall detect the presence of water and other
conductive fluids. The cable shall consist of four wires: two sensor
wires, a continuity wire, and a return wire. All four wires shall be
coated or insulated with fluoropolymer and would helically around a
central fluoropolymer core.
3.2 Cables using exposed metal or non-fluoropolymer constructions shall
not be acceptable. The cable, including connectors, shall have a
breaking strength of at least 70 pounds as per ASTM D-638. The
cable shall have an abrasion resistance of >65 cycles as per UL 719.
3.3 The cable shall be UL-listed to UL 910, Test Method for Fire and
Smoke Characteristics of Electrical and Optical-Fibre Cables used in
Air-Handling Spaces, and shall be of class 2 plenum cable as per NEC
725-51 (a).
4 Accessories
A complete system accessories (jumper cable, end terminations etc) shall be
provided by the system manufacturer.
5 Performance
5.1 Leak Size Required To Alarm
Maximum wetted length of cable required to produce an alarm with tap
water shall be no greater the 1 inch. Sensitivity shall be adjustable at
the module.
5.2 Continuous Coverage
The system shall provide continuous, distributed coverage of the area
to be protected. Spot or point sensors are not acceptable.
TECHNICAL SPECIFICATIONS
AIR CONDITIONING & MECHANICAL VENTILATION INSTALLATION
TS/A/40/3
5.3 Supervision
The system shall be continuously monitored for continuity. The loss of
continuity in any of the wires shall cause an alarm to sound and
energise the continuity LED.
5.4 Cleaning
If required, cleaning the cable without removing it shall be possible
using a damp cloth.
5.5 Drying
The cable shall dry and reset at the module within 15 seconds of
removal from free water. No shaking, wiping, air-drying, or other
mechanical action shall be required to dry the cable.
5.6 The alarm panel shall have a voltage free-contact (NO/NC) for
external interfacing.
5.7 Provide a current transmitter that capable of providing 4 - 20 mA
signal.
The current transmitter allows the transfer of leak location of continuity
fault information from the water alarm module to any instrument
capable of interpreting a 4 - 20 mA analogue signal.
6 Testing and Commissioning
6.1 The completed installation shall be in full operational condition before
testing is to be carried out. The Contractor shall commission the entire
installation in the presence of the S.O. and manufacturer’s
representative. Test results shall be recorded and certified by the
Contractor and the manufacturer’s representative.
6.2 The Contractor shall provide all equipment, labor and materials
necessary.
6.3 All defects and deficiencies in performance, reliability, safety,
efficiency, appearance of finish shall be rectified and resettled by the
Contractor to the entire satisfaction of the S.O. before acceptance.
6.4 The Contractor shall on commissioning conduct an instructional
briefing to the users concerned on the safe and proper use of the
system and necessary evacuation drills in the event of an agent
discharged.

Weitere ähnliche Inhalte

Was ist angesagt?

Ifm efector octavis brochure England 2013
Ifm efector octavis brochure England 2013Ifm efector octavis brochure England 2013
Ifm efector octavis brochure England 2013ifm electronic gmbh
 
Top Ten Advances In RTD Signal Conditioning
Top Ten Advances In RTD Signal ConditioningTop Ten Advances In RTD Signal Conditioning
Top Ten Advances In RTD Signal ConditioningM.S. Jacobs & Associates
 
Application overview
Application overviewApplication overview
Application overviewĐặng Hảo
 
VltFC 102 hvac drive operating instructions
VltFC 102  hvac drive  operating instructionsVltFC 102  hvac drive  operating instructions
VltFC 102 hvac drive operating instructionsToàn Huỳnh
 
Plasma Asher AW-1008
Plasma Asher AW-1008Plasma Asher AW-1008
Plasma Asher AW-1008Peter Chen
 
Series One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchSeries One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchIves Equipment
 
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...Thorne & Derrick International
 
Process Signal Isolated Transmitters, 4-20 ma
Process Signal Isolated Transmitters, 4-20 maProcess Signal Isolated Transmitters, 4-20 ma
Process Signal Isolated Transmitters, 4-20 maM.S. Jacobs & Associates
 
IRZ artificial lift solutions [version 1.4 july 2016]
IRZ artificial lift solutions [version 1.4 july 2016]IRZ artificial lift solutions [version 1.4 july 2016]
IRZ artificial lift solutions [version 1.4 july 2016]Ivan Isaev
 
Raising the Bar: Foundry Expectations for Equipment Capability and Control
Raising the Bar: Foundry Expectations for Equipment Capability and ControlRaising the Bar: Foundry Expectations for Equipment Capability and Control
Raising the Bar: Foundry Expectations for Equipment Capability and ControlKimberly Daich
 
System Sensor APA151
System Sensor APA151System Sensor APA151
System Sensor APA151JMAC Supply
 
Safety rules 2014
Safety rules 2014Safety rules 2014
Safety rules 2014AYM1979
 
Andel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
Andel – Leak Detection Cables, Panels, Sensors & Systems - BrochureAndel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
Andel – Leak Detection Cables, Panels, Sensors & Systems - BrochureThorne & Derrick UK
 
Catalog Biến tần FVR Micro Fuji Electric-Beeteco.com
Catalog Biến tần FVR Micro Fuji Electric-Beeteco.comCatalog Biến tần FVR Micro Fuji Electric-Beeteco.com
Catalog Biến tần FVR Micro Fuji Electric-Beeteco.comBeeteco
 

Was ist angesagt? (18)

Ifm efector octavis brochure England 2013
Ifm efector octavis brochure England 2013Ifm efector octavis brochure England 2013
Ifm efector octavis brochure England 2013
 
Top Ten Advances In RTD Signal Conditioning
Top Ten Advances In RTD Signal ConditioningTop Ten Advances In RTD Signal Conditioning
Top Ten Advances In RTD Signal Conditioning
 
NGR Monitor
NGR MonitorNGR Monitor
NGR Monitor
 
Application overview
Application overviewApplication overview
Application overview
 
VltFC 102 hvac drive operating instructions
VltFC 102  hvac drive  operating instructionsVltFC 102  hvac drive  operating instructions
VltFC 102 hvac drive operating instructions
 
Vlt aqua fc 202
Vlt aqua fc 202Vlt aqua fc 202
Vlt aqua fc 202
 
Plasma Asher AW-1008
Plasma Asher AW-1008Plasma Asher AW-1008
Plasma Asher AW-1008
 
Series One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature SwitchSeries One Safety Transmitter, Pressure and Temperature Switch
Series One Safety Transmitter, Pressure and Temperature Switch
 
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
 
Process Signal Isolated Transmitters, 4-20 ma
Process Signal Isolated Transmitters, 4-20 maProcess Signal Isolated Transmitters, 4-20 ma
Process Signal Isolated Transmitters, 4-20 ma
 
SitrackVibes - Wind
SitrackVibes - WindSitrackVibes - Wind
SitrackVibes - Wind
 
IRZ artificial lift solutions [version 1.4 july 2016]
IRZ artificial lift solutions [version 1.4 july 2016]IRZ artificial lift solutions [version 1.4 july 2016]
IRZ artificial lift solutions [version 1.4 july 2016]
 
Raising the Bar: Foundry Expectations for Equipment Capability and Control
Raising the Bar: Foundry Expectations for Equipment Capability and ControlRaising the Bar: Foundry Expectations for Equipment Capability and Control
Raising the Bar: Foundry Expectations for Equipment Capability and Control
 
System Sensor APA151
System Sensor APA151System Sensor APA151
System Sensor APA151
 
Safety rules 2014
Safety rules 2014Safety rules 2014
Safety rules 2014
 
Andel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
Andel – Leak Detection Cables, Panels, Sensors & Systems - BrochureAndel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
Andel – Leak Detection Cables, Panels, Sensors & Systems - Brochure
 
Catalog Biến tần FVR Micro Fuji Electric-Beeteco.com
Catalog Biến tần FVR Micro Fuji Electric-Beeteco.comCatalog Biến tần FVR Micro Fuji Electric-Beeteco.com
Catalog Biến tần FVR Micro Fuji Electric-Beeteco.com
 
Single phase pole mounted circuit recloser catalog
Single phase pole mounted circuit recloser catalogSingle phase pole mounted circuit recloser catalog
Single phase pole mounted circuit recloser catalog
 

Ähnlich wie Water Detection System for Air Conditional&Mechanical Ventilation Installation

System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279Henry Rosa
 
EST3 Installation and Service Manual.pdf
EST3 Installation and Service Manual.pdfEST3 Installation and Service Manual.pdf
EST3 Installation and Service Manual.pdfAndre Cardoso
 
single-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdfsingle-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdfacrelenergy
 
Access control basics-7
Access control basics-7Access control basics-7
Access control basics-7grantlerc
 
conf-type-test-2007-03.ppt
conf-type-test-2007-03.pptconf-type-test-2007-03.ppt
conf-type-test-2007-03.pptssuser1f60f6
 
Fire alarm checklist
Fire alarm checklistFire alarm checklist
Fire alarm checklistirhabsyam
 
PCS_902_Line_Distance_Relay_Instruction.pdf
PCS_902_Line_Distance_Relay_Instruction.pdfPCS_902_Line_Distance_Relay_Instruction.pdf
PCS_902_Line_Distance_Relay_Instruction.pdfteddyteddy40
 
WirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible GasWirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible GasMiller Energy, Inc.
 
Edwards Signaling SD-VTK Data Sheet
Edwards Signaling SD-VTK Data SheetEdwards Signaling SD-VTK Data Sheet
Edwards Signaling SD-VTK Data SheetJMAC Supply
 
Edwards Signaling SD-PH Data Sheet
Edwards Signaling SD-PH Data SheetEdwards Signaling SD-PH Data Sheet
Edwards Signaling SD-PH Data SheetJMAC Supply
 
Edwards Signaling SD-GSK Data Sheet
Edwards Signaling SD-GSK Data SheetEdwards Signaling SD-GSK Data Sheet
Edwards Signaling SD-GSK Data SheetJMAC Supply
 
Edwards Signaling SD2W Data Sheet
Edwards Signaling SD2W Data SheetEdwards Signaling SD2W Data Sheet
Edwards Signaling SD2W Data SheetJMAC Supply
 

Ähnlich wie Water Detection System for Air Conditional&Mechanical Ventilation Installation (20)

109 manual rad3_db3c
109 manual rad3_db3c109 manual rad3_db3c
109 manual rad3_db3c
 
System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279
 
EST3 Installation and Service Manual.pdf
EST3 Installation and Service Manual.pdfEST3 Installation and Service Manual.pdf
EST3 Installation and Service Manual.pdf
 
Ultisolar VS2048BN-VS3048BN-VS4548BN-VS6048BN User Manual
Ultisolar VS2048BN-VS3048BN-VS4548BN-VS6048BN User ManualUltisolar VS2048BN-VS3048BN-VS4548BN-VS6048BN User Manual
Ultisolar VS2048BN-VS3048BN-VS4548BN-VS6048BN User Manual
 
Ultisolar VS1024BN-VS2024BN-VS3024BN-VS4524BN-VS6024BN User Manual
Ultisolar VS1024BN-VS2024BN-VS3024BN-VS4524BN-VS6024BN User ManualUltisolar VS1024BN-VS2024BN-VS3024BN-VS4524BN-VS6024BN User Manual
Ultisolar VS1024BN-VS2024BN-VS3024BN-VS4524BN-VS6024BN User Manual
 
single-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdfsingle-phase-acr10r-d16te-manual.pdf
single-phase-acr10r-d16te-manual.pdf
 
Catalog biến tần Inovance MD310
Catalog biến tần Inovance MD310Catalog biến tần Inovance MD310
Catalog biến tần Inovance MD310
 
NDOKI VILLAGE
NDOKI VILLAGENDOKI VILLAGE
NDOKI VILLAGE
 
Spam 20
Spam 20Spam 20
Spam 20
 
Access control basics-7
Access control basics-7Access control basics-7
Access control basics-7
 
conf-type-test-2007-03.ppt
conf-type-test-2007-03.pptconf-type-test-2007-03.ppt
conf-type-test-2007-03.ppt
 
16928 6274 1
16928 6274 116928 6274 1
16928 6274 1
 
Bionet bm3 manual de servicio
Bionet bm3 manual de servicioBionet bm3 manual de servicio
Bionet bm3 manual de servicio
 
Fire alarm checklist
Fire alarm checklistFire alarm checklist
Fire alarm checklist
 
PCS_902_Line_Distance_Relay_Instruction.pdf
PCS_902_Line_Distance_Relay_Instruction.pdfPCS_902_Line_Distance_Relay_Instruction.pdf
PCS_902_Line_Distance_Relay_Instruction.pdf
 
WirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible GasWirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible Gas
 
Edwards Signaling SD-VTK Data Sheet
Edwards Signaling SD-VTK Data SheetEdwards Signaling SD-VTK Data Sheet
Edwards Signaling SD-VTK Data Sheet
 
Edwards Signaling SD-PH Data Sheet
Edwards Signaling SD-PH Data SheetEdwards Signaling SD-PH Data Sheet
Edwards Signaling SD-PH Data Sheet
 
Edwards Signaling SD-GSK Data Sheet
Edwards Signaling SD-GSK Data SheetEdwards Signaling SD-GSK Data Sheet
Edwards Signaling SD-GSK Data Sheet
 
Edwards Signaling SD2W Data Sheet
Edwards Signaling SD2W Data SheetEdwards Signaling SD2W Data Sheet
Edwards Signaling SD2W Data Sheet
 

Mehr von Johnny Tsai

Comparing Traditional Methods with Modern Fuel Leak Detection Solutions.pdf
Comparing Traditional Methods with Modern Fuel Leak Detection Solutions.pdfComparing Traditional Methods with Modern Fuel Leak Detection Solutions.pdf
Comparing Traditional Methods with Modern Fuel Leak Detection Solutions.pdfJohnny Tsai
 
Water leak detection system smart gateway
Water leak detection system smart gatewayWater leak detection system smart gateway
Water leak detection system smart gatewayJohnny Tsai
 
The Applications of Water Sensing System
The Applications of Water Sensing SystemThe Applications of Water Sensing System
The Applications of Water Sensing SystemJohnny Tsai
 
Water leak-detection-rope
Water leak-detection-ropeWater leak-detection-rope
Water leak-detection-ropeJohnny Tsai
 
Water Leak Detection Systems
Water Leak Detection SystemsWater Leak Detection Systems
Water Leak Detection SystemsJohnny Tsai
 
Water Leakage Detection Expert
Water Leakage Detection ExpertWater Leakage Detection Expert
Water Leakage Detection ExpertJohnny Tsai
 
Position Water Leak Detection Cable
Position Water Leak Detection Cable Position Water Leak Detection Cable
Position Water Leak Detection Cable Johnny Tsai
 
Non-locating Water Leak Detection Cable
Non-locating Water Leak Detection CableNon-locating Water Leak Detection Cable
Non-locating Water Leak Detection CableJohnny Tsai
 

Mehr von Johnny Tsai (8)

Comparing Traditional Methods with Modern Fuel Leak Detection Solutions.pdf
Comparing Traditional Methods with Modern Fuel Leak Detection Solutions.pdfComparing Traditional Methods with Modern Fuel Leak Detection Solutions.pdf
Comparing Traditional Methods with Modern Fuel Leak Detection Solutions.pdf
 
Water leak detection system smart gateway
Water leak detection system smart gatewayWater leak detection system smart gateway
Water leak detection system smart gateway
 
The Applications of Water Sensing System
The Applications of Water Sensing SystemThe Applications of Water Sensing System
The Applications of Water Sensing System
 
Water leak-detection-rope
Water leak-detection-ropeWater leak-detection-rope
Water leak-detection-rope
 
Water Leak Detection Systems
Water Leak Detection SystemsWater Leak Detection Systems
Water Leak Detection Systems
 
Water Leakage Detection Expert
Water Leakage Detection ExpertWater Leakage Detection Expert
Water Leakage Detection Expert
 
Position Water Leak Detection Cable
Position Water Leak Detection Cable Position Water Leak Detection Cable
Position Water Leak Detection Cable
 
Non-locating Water Leak Detection Cable
Non-locating Water Leak Detection CableNon-locating Water Leak Detection Cable
Non-locating Water Leak Detection Cable
 

Kürzlich hochgeladen

Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.cojitesh
 
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...rajputriyana310
 
VIP Model Call Girls Viman Nagar ( Pune ) Call ON 8005736733 Starting From 5K...
VIP Model Call Girls Viman Nagar ( Pune ) Call ON 8005736733 Starting From 5K...VIP Model Call Girls Viman Nagar ( Pune ) Call ON 8005736733 Starting From 5K...
VIP Model Call Girls Viman Nagar ( Pune ) Call ON 8005736733 Starting From 5K...SUHANI PANDEY
 
Kondhwa ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Kondhwa ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Kondhwa ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Kondhwa ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 
Call Girls Ramtek Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Ramtek Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Ramtek Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Ramtek Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Call Girls Service Pune ₹7.5k Pick Up & Drop With Cash Payment 8005736733 Cal...
Call Girls Service Pune ₹7.5k Pick Up & Drop With Cash Payment 8005736733 Cal...Call Girls Service Pune ₹7.5k Pick Up & Drop With Cash Payment 8005736733 Cal...
Call Girls Service Pune ₹7.5k Pick Up & Drop With Cash Payment 8005736733 Cal...SUHANI PANDEY
 
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts ServicesBOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Servicesdollysharma2066
 
VVIP Pune Call Girls Koregaon Park (7001035870) Pune Escorts Nearby with Comp...
VVIP Pune Call Girls Koregaon Park (7001035870) Pune Escorts Nearby with Comp...VVIP Pune Call Girls Koregaon Park (7001035870) Pune Escorts Nearby with Comp...
VVIP Pune Call Girls Koregaon Park (7001035870) Pune Escorts Nearby with Comp...Call Girls in Nagpur High Profile
 
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756dollysharma2066
 
Booking open Available Pune Call Girls Yewalewadi 6297143586 Call Hot Indian...
Booking open Available Pune Call Girls Yewalewadi  6297143586 Call Hot Indian...Booking open Available Pune Call Girls Yewalewadi  6297143586 Call Hot Indian...
Booking open Available Pune Call Girls Yewalewadi 6297143586 Call Hot Indian...Call Girls in Nagpur High Profile
 
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night StandHot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Standkumarajju5765
 
RATING SYSTEMS- IGBC, GRIHA, LEED--.pptx
RATING  SYSTEMS- IGBC, GRIHA, LEED--.pptxRATING  SYSTEMS- IGBC, GRIHA, LEED--.pptx
RATING SYSTEMS- IGBC, GRIHA, LEED--.pptxJIT KUMAR GUPTA
 
Call Girls Moshi Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Moshi Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Moshi Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Moshi Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...SUHANI PANDEY
 
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...MOHANI PANDEY
 
VIP Model Call Girls Hadapsar ( Pune ) Call ON 8005736733 Starting From 5K to...
VIP Model Call Girls Hadapsar ( Pune ) Call ON 8005736733 Starting From 5K to...VIP Model Call Girls Hadapsar ( Pune ) Call ON 8005736733 Starting From 5K to...
VIP Model Call Girls Hadapsar ( Pune ) Call ON 8005736733 Starting From 5K to...SUHANI PANDEY
 
Booking open Available Pune Call Girls Budhwar Peth 6297143586 Call Hot Indi...
Booking open Available Pune Call Girls Budhwar Peth  6297143586 Call Hot Indi...Booking open Available Pune Call Girls Budhwar Peth  6297143586 Call Hot Indi...
Booking open Available Pune Call Girls Budhwar Peth 6297143586 Call Hot Indi...Call Girls in Nagpur High Profile
 
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...Call Girls in Nagpur High Profile
 

Kürzlich hochgeladen (20)

Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.
 
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
Call Girls In Bloom Boutique | GK-1 ☎ 9990224454 High Class Delhi NCR 24 Hour...
 
VIP Model Call Girls Viman Nagar ( Pune ) Call ON 8005736733 Starting From 5K...
VIP Model Call Girls Viman Nagar ( Pune ) Call ON 8005736733 Starting From 5K...VIP Model Call Girls Viman Nagar ( Pune ) Call ON 8005736733 Starting From 5K...
VIP Model Call Girls Viman Nagar ( Pune ) Call ON 8005736733 Starting From 5K...
 
Kondhwa ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Kondhwa ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Kondhwa ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Kondhwa ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Call Girls Ramtek Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Ramtek Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Ramtek Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Ramtek Call Me 7737669865 Budget Friendly No Advance Booking
 
Call Girls Service Pune ₹7.5k Pick Up & Drop With Cash Payment 8005736733 Cal...
Call Girls Service Pune ₹7.5k Pick Up & Drop With Cash Payment 8005736733 Cal...Call Girls Service Pune ₹7.5k Pick Up & Drop With Cash Payment 8005736733 Cal...
Call Girls Service Pune ₹7.5k Pick Up & Drop With Cash Payment 8005736733 Cal...
 
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts ServicesBOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
BOOK Call Girls in (Dwarka) CALL | 8377087607 Delhi Escorts Services
 
VVIP Pune Call Girls Koregaon Park (7001035870) Pune Escorts Nearby with Comp...
VVIP Pune Call Girls Koregaon Park (7001035870) Pune Escorts Nearby with Comp...VVIP Pune Call Girls Koregaon Park (7001035870) Pune Escorts Nearby with Comp...
VVIP Pune Call Girls Koregaon Park (7001035870) Pune Escorts Nearby with Comp...
 
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Wagholi ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
GENUINE Babe,Call Girls IN Chhatarpur Delhi | +91-8377877756
 
(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7
(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7
(INDIRA) Call Girl Katra Call Now 8617697112 Katra Escorts 24x7
 
Booking open Available Pune Call Girls Yewalewadi 6297143586 Call Hot Indian...
Booking open Available Pune Call Girls Yewalewadi  6297143586 Call Hot Indian...Booking open Available Pune Call Girls Yewalewadi  6297143586 Call Hot Indian...
Booking open Available Pune Call Girls Yewalewadi 6297143586 Call Hot Indian...
 
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night StandHot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Preet Vihar ☎ 9711199171 Book Your One night Stand
 
RATING SYSTEMS- IGBC, GRIHA, LEED--.pptx
RATING  SYSTEMS- IGBC, GRIHA, LEED--.pptxRATING  SYSTEMS- IGBC, GRIHA, LEED--.pptx
RATING SYSTEMS- IGBC, GRIHA, LEED--.pptx
 
Call Girls Moshi Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Moshi Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Moshi Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Moshi Call Me 7737669865 Budget Friendly No Advance Booking
 
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
VVIP Pune Call Girls Wagholi WhatSapp Number 8005736733 With Elite Staff And ...
 
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
Get Premium Hoskote Call Girls (8005736733) 24x7 Rate 15999 with A/c Room Cas...
 
VIP Model Call Girls Hadapsar ( Pune ) Call ON 8005736733 Starting From 5K to...
VIP Model Call Girls Hadapsar ( Pune ) Call ON 8005736733 Starting From 5K to...VIP Model Call Girls Hadapsar ( Pune ) Call ON 8005736733 Starting From 5K to...
VIP Model Call Girls Hadapsar ( Pune ) Call ON 8005736733 Starting From 5K to...
 
Booking open Available Pune Call Girls Budhwar Peth 6297143586 Call Hot Indi...
Booking open Available Pune Call Girls Budhwar Peth  6297143586 Call Hot Indi...Booking open Available Pune Call Girls Budhwar Peth  6297143586 Call Hot Indi...
Booking open Available Pune Call Girls Budhwar Peth 6297143586 Call Hot Indi...
 
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...Booking open Available Pune Call Girls Parvati Darshan  6297143586 Call Hot I...
Booking open Available Pune Call Girls Parvati Darshan 6297143586 Call Hot I...
 

Water Detection System for Air Conditional&Mechanical Ventilation Installation

  • 1. TECHNICAL SPECIFICATIONS AIR CONDITIONING & MECHANICAL VENTILATION INSTALLATION TS/A/40/1 SECTION 40 – WATER DETECTION SYSTEM 1 General 1.1 This section sets out the requirements for water detection system and covers the supply, delivery, installation, testing and commissioning and twelve (12) months free maintenance and warranty of the system and associated equipment. 1.2 The system components shall be designed to be installed according to pre-test limitations as approved or listed by a recognised testing laboratory. 1.3 All devices shall be designed for service encountered and shall not be readily rendered in-operative or susceptible to accidental operation. They shall be located, installed or suitably protected against mechanical, chemical or other damage, which may render them in- operative. All devices for activating supplementary equipment shall be considered as integral parts of the system and shall function with system operation. 1.4 The complete system shall include electronics alarm module, sensing cable, graphic display map, and auxiliary equipment, as indicated on the design drawings. The system shall simultaneously detect the presence of water at any point along the cable's length and activate the module's leak alarm relays. The sensing cable shall be of such construction that no metallic parts shall be exposed to the environment. The system shall be provided with pre-connectorised sensing cable components. 2 Alarm Locator Module 2.1 The alarm module shall be capable of monitoring up to 1500 meters of sensing cable. 2.2 The alarm module shall have LEDs indicating "power" (green), "alarm" (red), and "continuity" (yellow). The system shall sound an audible alarm upon sensing a leak. Once the alarm condition has been cleared, the module is reset with a single keystroke. 2.3 Basic Features of the alarm locator module  In addition to detecting leaks, the system shall warn of fault conditions and indicates when maintenance is required.  An event history log allows leaks (and other events) to be tracked.  The settings can be customised to suit the user’s application.  Both the events history log and any user settings are held in non-volatile memory.  The unit shall has an in-built system-wide diagnostic functions
  • 2. TECHNICAL SPECIFICATIONS AIR CONDITIONING & MECHANICAL VENTILATION INSTALLATION TS/A/40/2 2.4 The alarm module will be powered by 240 VAC. The module shall have a pair of contacts open on an alarm, and a pair of contacts close on an alarm. These contacts shall be used to actuate other alarms and shall be capable of switching 10 amps at 250 VAC. 2.5 In additions, the module shall be provided with 4-20 mA signal and RS232/RS-485 series port for connection to building management system. 2.6 The module enclosure shall be NEMA 1, constructed of 16- gauge steel with dimensions of 8" x 8" x 4". The enclosure shall be capable of either semi-flush of surface mounting. 3 Sensing Cable 3.1 The water sensing cable shall detect the presence of water and other conductive fluids. The cable shall consist of four wires: two sensor wires, a continuity wire, and a return wire. All four wires shall be coated or insulated with fluoropolymer and would helically around a central fluoropolymer core. 3.2 Cables using exposed metal or non-fluoropolymer constructions shall not be acceptable. The cable, including connectors, shall have a breaking strength of at least 70 pounds as per ASTM D-638. The cable shall have an abrasion resistance of >65 cycles as per UL 719. 3.3 The cable shall be UL-listed to UL 910, Test Method for Fire and Smoke Characteristics of Electrical and Optical-Fibre Cables used in Air-Handling Spaces, and shall be of class 2 plenum cable as per NEC 725-51 (a). 4 Accessories A complete system accessories (jumper cable, end terminations etc) shall be provided by the system manufacturer. 5 Performance 5.1 Leak Size Required To Alarm Maximum wetted length of cable required to produce an alarm with tap water shall be no greater the 1 inch. Sensitivity shall be adjustable at the module. 5.2 Continuous Coverage The system shall provide continuous, distributed coverage of the area to be protected. Spot or point sensors are not acceptable.
  • 3. TECHNICAL SPECIFICATIONS AIR CONDITIONING & MECHANICAL VENTILATION INSTALLATION TS/A/40/3 5.3 Supervision The system shall be continuously monitored for continuity. The loss of continuity in any of the wires shall cause an alarm to sound and energise the continuity LED. 5.4 Cleaning If required, cleaning the cable without removing it shall be possible using a damp cloth. 5.5 Drying The cable shall dry and reset at the module within 15 seconds of removal from free water. No shaking, wiping, air-drying, or other mechanical action shall be required to dry the cable. 5.6 The alarm panel shall have a voltage free-contact (NO/NC) for external interfacing. 5.7 Provide a current transmitter that capable of providing 4 - 20 mA signal. The current transmitter allows the transfer of leak location of continuity fault information from the water alarm module to any instrument capable of interpreting a 4 - 20 mA analogue signal. 6 Testing and Commissioning 6.1 The completed installation shall be in full operational condition before testing is to be carried out. The Contractor shall commission the entire installation in the presence of the S.O. and manufacturer’s representative. Test results shall be recorded and certified by the Contractor and the manufacturer’s representative. 6.2 The Contractor shall provide all equipment, labor and materials necessary. 6.3 All defects and deficiencies in performance, reliability, safety, efficiency, appearance of finish shall be rectified and resettled by the Contractor to the entire satisfaction of the S.O. before acceptance. 6.4 The Contractor shall on commissioning conduct an instructional briefing to the users concerned on the safe and proper use of the system and necessary evacuation drills in the event of an agent discharged.