SlideShare ist ein Scribd-Unternehmen logo
1 von 36
Downloaden Sie, um offline zu lesen
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 1
Arc Flash Analysis
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 2
Arc Flash Definition
• What is Arc Flash?
- It is a Short Circuit through the air that flashes
from one exposed conductor to another.
- Also known, as an arc blast, is a type of
electrical arc supplied with electrical energy.
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 3
Electrical Arc Hazards
• Electrical Arcs
– Can occur when a conductive object gets too
close to a high-amp current source (energized
conductor)
– Typically Arc Flash is seen in higher voltages,
such as 408 volts and higher
– Some instances, Arc Flash can occur less than
208 volts
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 4
Electrical Arc Hazards
• Arc Flash Burns
– The arc can heat the air to temperatures as
high as 35,000 F and vaporize metal.
– Arc flash can cause severe skin burns by direct
heat exposure and by igniting clothing.
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 5
Electrical Arc Hazards
• Arc Blast Impacts
– The heating of the air and vaporization of metal
creates a pressure wave that can damage
hearing and cause memory loss (from
concussion) and other injuries. Flying metal
parts are also a hazard.
• Falls
– Electric shocks and arc blasts can cause falls,
especially from ladders or unguarded
scaffolding.
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 6
Definitions
• Limited Approach Boundary: A shock protection
boundary not to be crossed by unqualified persons
unless escorted by qualified personnel.
• Restricted Approach Boundary: A shock protection
boundary to be crossed by only qualified persons.
Shock protection is required.
• Prohibited Approach Boundary: A shock protection
boundary to be crossed by only qualified persons. The
use of techniques that may require direct contact with
energized equipment.
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 7
Definition of Approach Boundaries
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 8
Definitions
• Arc Flash Boundary: Distance at which the incident
energy equals 1.2 Cal/cm^2.
• Incident Energy: The amount of energy impressed on
a surface, a certain distance from the source,
generated during and electrical arc event.
• Working Distance: The dimension between the
possible arc point and the head and body of a worker
positioned in place to perform the task.
• Bolted fault current: A short-circuit contact between
two conductors at different potentials in which the
impedance between the conductors is zero.
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 9
Definitions
• Available fault current: The electrical current that can
be provided by the serving utility and facility-owned
electrical generating devices and large electrical
motors considering the amount of impedance in the
current path.
• Arcing fault current: A fault current flowing through an
electrical arc-plasma, also called arc fault current and
arc current.
• Voltage (Nominal): A nominal value assigned to a
circuit or system for the purpose of designating its
voltage class (I.e. 120/240 V, 480Y/277 V, 600V, etc).
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 10
Regulating Authorities
• OSHA 29 CFR 1910.132 (d) requires
employers to assess the workplace to
determine if hazards are present, or likely to be
present and select and have each employee
use the types of PPE that will protect them.
• OSHA 29 CFR 1910.333 Requires employees
who are exposed to electrical shock hazard to
be qualified for the specific task that they are
performing and use the appropriate PPE
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 11
Regulating Authorities
• OSHA 29 CFR 1910.335 (a)(1)(I): Protective
equipment for specific body parts
• OSHA 29 CFR 1910.335 (a)(2)(I): use of Insulated
tools when working around energized equipment.
• NEC 110.6: equipment must be marked to warn
qualified persons of potential electrical arc-flash
hazards.
• NFPA 70E Part II Chapter 2, paragraph 2-1.3.3 states
that arc-flash analysis must be performed in order to
determine the incident energy level and appropriate
PPE for given tasks.
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 12
IEEE 1584 2002 “Guide for Performing Arc Flash
Hazard Calculations”
NFPA 70E “Standard for Electrical Safety Requirements
for Employee Workplaces”
Protection From Arc Flash Hazards
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 13
NFPA 70E
(Annex D.2, 5, 6 Eqs.)
IEEE 1584-2002
Voltage Range 208 V – 600 V
208 – 15 kV (Empirical)
15 kV+ (Lee Method)
Current Range 16 kA – 50 kA 0.7 kA to 106 kA
Arc Duration Range No limit No Limit
Installations
Open Air,
Cubic Box
Open Air, Cubic Box,
Cable Bus
Working Distance 18 inches + 18 inches +
Unit of Measure Cal/cm2 or J/cm2 Cal/cm2 or J/cm2
Comparison of Arc Flash Standards
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 14
Incident energy exposure at a working distance of 18”
for a 19.5 kA Arc @ 600 Volts (open air equipment)
0
5
10
15
20
0 10 20
Calorie/cm^2
Fault clearing time (Cycles)
600 Volt Arc in Open Air Incident energyExposure @ 18 in.
NFPA 70E
IEEE 1584-2002
Incident Energy Comparison
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 15
0
5
10
15
20
0 10 20
Calorie/cm^2
Fault clearing time (Cycles)
600 Volt Arc in Closed Box Incident energyExposure @ 18 in.
NFPA 70E
IEEE 1584-2002
Incident energy exposure at a working distance of 18”
for a 19.5 kA Arc @ 600 Volts (enclosed equipment)
Incident Energy Comparison
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 16
Required Parameter
NFPA
70E
IEEE
1584
System Nominal Voltage X X
Gap Between Conductors X
Distance X Factor X
System Grounding
(Grounded/Ungrounded) X
Open/Enclosed Equipment X X
Working Distance X X
Coordination Information (TCC) X X
Data Collection for Arc Flash
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 17
Gap between Conductors
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 18
Standards for Short-Circuit
• IEEE Std 141-1993 (IEEE Red Book)
• IEEE Std 242-2001 (IEEE Buff Book)
• ANSI (different standards like C37, etc)
• IEC (60909, 60363, etc)
• See ETAP help file for more standards
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 19
Why use 3-Phase Faults
• Line to Line faults quickly escalate into three- phase
faults
• LV L-G faults in solidly grounded systems quickly
escalate into three phase faults
• LV L-G faults in Ungrounded / High resistance
grounded systems do not release enough energy.
• MV faults in low resistance or reactance grounded
systems should be cleared quickly, but worst case
scenario 3-phase fault should be considered
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 20
3-Phase Bolted Fault Current
• Perform ANSI/IEC short circuit study that considers
the following:
– 3-phase bolted fault
– ½ cycle or 1½-4 cycle fault current depending on the
type of device or system voltage
– Include all cables & Overload heaters
– Prefault voltage (nominal circuit voltage)
– Short-circuit Calculation should be more accurate rather
than too conservative (faults may persist longer at lower
current levels which may translate into higher energy)
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 21
))(lg(**00304.0))(lg(**5588.0
*000526.0*0966.0)lg(*662.0)lg(
bfbf
bf
IGIV
GVIKIa


For buses with nominal kV in the range of 0.208 to 1.0 kV:
In general, arcing current in systems below 15.0 kV will be less
than the 3-phase fault current because of arc impedance.
Arcing Current
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 22
For buses with nominal kV rating greater than 15 kV, the
arcing current can be considered to be the same as the
bolted fault current:
For buses with nominal kV rating in the range of 1 to 15.0 kV:
)Ilg(*983.000402.0)Ialg( bf
bfIIa 
Arcing Current
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 23
System Modes of Operation
• Open or looped
• One or more utility feeders in service
• Utility interface substation secondary bus tie breaker
open or closed
• Unit substation with one or two primary feeders
• Unit substation with two transformers with secondary
tie opened or closed
• MCC with one or two feeders, one or both energized.
• Generators running in parallel with the utility supply or
in standby mode
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 24
Arc Duration LV CB
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 25
Arc Duration LV CB
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 26
Arc Duration for Fuses
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 27
Incident Energy
Empirical method (1.0 to 15.0 kV)












 x
x
nf
D
t
ECE
610
*
2.0
**184.4
Lee method (higher than 15.0 kV)






 2
6
**10*142.2
D
t
IVE bf
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 28
Arc Flash Boundary
Empirical method (1.0 to 15.0 kV)












 x
x
nf
D
t
EC
610
*
2.0
**184.42.1
Lee method (higher than 15.0 kV)






 2
6
**10*142.22.1
D
t
IV bf
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 29
Incident Energy
Exposure cal/cm2 Protective Clothing and PPE
1.2 > cal/cm2  0
Nonmelting or untreated natural fiber for long sleeve shirt
and pants/coverall, Face shield for projectile protection,
Safety glasses, Hearing protection and Leather gloves.
12 > cal/cm2  1.2
Arc-rated long-sleeve shirt and arc-rated pants or arc-rated
coverall and/or arc flash suit, Arc-rated face shield, Arc rated
jacket, Hard hat, hard hat liner, Safety glasses, Hearing
protection, Leather gloves and Leather work shoes.
cal/cm2  12
Arc-rated long-sleeve shirt and arc-rated pants, Arc-rated
arc flash suit hood, Arc-rated gloves, Arc-rated jacket, Hard
hat, hard hat liner, Safety glasses, Hearing protection, Arc-
rated gloves, Leather work shoes.
Incident Energy Levels
(NFPA 70E 2012 Annex H.3)
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 30
Up to 1.2 Cal/cm2
• Nonmelting or untreated
natural fiber for long sleeve
shirt and pants/coverall
• Face shield for projectile
protection
• Safety glasses
• Hearing protection
• Leather gloves
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 31
1.2 up to 12 Cal/cm2
• Arc-rated long-sleeve shirt and arc-rated
pants or arc-rated coverall and/or arc
flash suit
• Arc-rated face shield
• Arc rated jacket
• Hard hat
• Arc rated hard hat liner
• Safety glasses
• Hearing protection
• Leather gloves
• Leather work shoes
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 32
Greater than 12 Cal/cm2
• Arc Flash Suit
• Arc-rated arc flash hood
• Arc-rated gloves
• Arc-rated jacket, parka
• Hard Hat
• Arc-rated hard hat liner
• Hearing Protection
• Arc-rated gloves
• Leather work shoes
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 33
PPE Incident Energy Rating
• ATPV: is the defined as the incident energy on a fabric or
material that results in sufficient heat transfer through the
fabric or material to cause the onset of a second degree
burn.
• EBT: is defined as the average of the five highest incident
energy exposures values below the Stoll curve where the
specimens do not exhibit breakopen. EBT is reported when
the ATPV cannot be determined due to FR fabric
breakopen.
• HAF%: is the heat transfer capability of the fabric or
material
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 34
Stoll Curve
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 35
Equipment Layering
©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 36
Types of Insulating Glove Max. use voltage AC
(L-L) (V-Rating
field)
Class Bus nominal kV range
Low Voltage Gloves
500 00 kV ≤ 0.500 Bus kV ≤≥
1000 0 0.500 kV < Bus kV ≤ 1.0 kV
High Voltage Gloves
7500 1 1.0 kV < Bus kV ≤ 7.5 kV
17000 2 7.5 kV < Bus kV ≤ 17.0 kV
26500 3 17.0 kV < Bus kV ≤ 26.5 kV
36000 4 26.5 kV < Bus kV ≤ 36.0 kV
ASTM Insulating Glove Voltage Classes

Weitere ähnliche Inhalte

Was ist angesagt?

ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2Himmelstern
 
ETAP - device coordination
ETAP - device coordinationETAP - device coordination
ETAP - device coordinationHimmelstern
 
ETAP - Short circuit ansi standard
ETAP - Short circuit ansi standardETAP - Short circuit ansi standard
ETAP - Short circuit ansi standardHimmelstern
 
ETAP - Cable pulling
ETAP - Cable pullingETAP - Cable pulling
ETAP - Cable pullingHimmelstern
 
ETAP - Power system modeling
ETAP - Power system modelingETAP - Power system modeling
ETAP - Power system modelingHimmelstern
 
ETAP - unbalanced load flow
ETAP - unbalanced load flowETAP - unbalanced load flow
ETAP - unbalanced load flowHimmelstern
 
ETAP - Harmonics Analysis
ETAP - Harmonics AnalysisETAP - Harmonics Analysis
ETAP - Harmonics AnalysisHimmelstern
 
ETAP - Transient stability 2
ETAP - Transient stability 2ETAP - Transient stability 2
ETAP - Transient stability 2Himmelstern
 
Overcurrent and Distance Protection in DigSilent PowerFactory
Overcurrent and Distance Protection in DigSilent PowerFactoryOvercurrent and Distance Protection in DigSilent PowerFactory
Overcurrent and Distance Protection in DigSilent PowerFactoryAreeb Abdullah
 
ETAP - pde gis - Data Exchange
ETAP -   pde gis - Data ExchangeETAP -   pde gis - Data Exchange
ETAP - pde gis - Data ExchangeHimmelstern
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapHimmelstern
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Basic short circuit calculation procedure
Basic short circuit calculation procedureBasic short circuit calculation procedure
Basic short circuit calculation procedureMustafa Ismail
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
ETAP - Ac networks
ETAP - Ac networksETAP - Ac networks
ETAP - Ac networksHimmelstern
 
Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakersPrasant Kumar
 

Was ist angesagt? (20)

ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2
 
ETAP - device coordination
ETAP - device coordinationETAP - device coordination
ETAP - device coordination
 
ETAP - Short circuit ansi standard
ETAP - Short circuit ansi standardETAP - Short circuit ansi standard
ETAP - Short circuit ansi standard
 
ETAP - Cable pulling
ETAP - Cable pullingETAP - Cable pulling
ETAP - Cable pulling
 
ETAP - Power system modeling
ETAP - Power system modelingETAP - Power system modeling
ETAP - Power system modeling
 
ETAP - unbalanced load flow
ETAP - unbalanced load flowETAP - unbalanced load flow
ETAP - unbalanced load flow
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
ETAP - Harmonics Analysis
ETAP - Harmonics AnalysisETAP - Harmonics Analysis
ETAP - Harmonics Analysis
 
ETAP - Transient stability 2
ETAP - Transient stability 2ETAP - Transient stability 2
ETAP - Transient stability 2
 
Time current curves
Time current curvesTime current curves
Time current curves
 
Overcurrent and Distance Protection in DigSilent PowerFactory
Overcurrent and Distance Protection in DigSilent PowerFactoryOvercurrent and Distance Protection in DigSilent PowerFactory
Overcurrent and Distance Protection in DigSilent PowerFactory
 
ETAP - pde gis - Data Exchange
ETAP -   pde gis - Data ExchangeETAP -   pde gis - Data Exchange
ETAP - pde gis - Data Exchange
 
ETAP - Transformer sizing using etap
ETAP - Transformer sizing using etapETAP - Transformer sizing using etap
ETAP - Transformer sizing using etap
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Overcurrent coordination
Overcurrent coordinationOvercurrent coordination
Overcurrent coordination
 
RELAY.pptx
RELAY.pptxRELAY.pptx
RELAY.pptx
 
Basic short circuit calculation procedure
Basic short circuit calculation procedureBasic short circuit calculation procedure
Basic short circuit calculation procedure
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
ETAP - Ac networks
ETAP - Ac networksETAP - Ac networks
ETAP - Ac networks
 
Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakers
 

Ähnlich wie ETAP - Arc flash introduction

Arc Flash Safety Training by Pennsylvania Department of Labor and Indusry
Arc Flash Safety Training by Pennsylvania Department of Labor and IndusryArc Flash Safety Training by Pennsylvania Department of Labor and Indusry
Arc Flash Safety Training by Pennsylvania Department of Labor and IndusryAtlantic Training, LLC.
 
Short-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash AnalysisShort-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash AnalysisPower System Operation
 
arc-flash-analysis-done-right.pdf
arc-flash-analysis-done-right.pdfarc-flash-analysis-done-right.pdf
arc-flash-analysis-done-right.pdfssusera5c9a31
 
ETAP - Arc flash analysis etap
ETAP - Arc flash analysis etapETAP - Arc flash analysis etap
ETAP - Arc flash analysis etapHimmelstern
 
ETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done RightETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done RightHimmelstern
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyAtlantic Training, LLC.
 
Michael Wood - Loader electric shocks, a case study
Michael Wood - Loader electric shocks, a case studyMichael Wood - Loader electric shocks, a case study
Michael Wood - Loader electric shocks, a case studyNSW Environment and Planning
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodinationmichaeljmack
 
Arc Flas presentation doc 2 rev b
Arc Flas presentation doc 2 rev bArc Flas presentation doc 2 rev b
Arc Flas presentation doc 2 rev bchabchoub Mohamed
 
An Engineer’s Guide to OSHA’s New Recommendations for Arc Flash Studies
An Engineer’s Guide to OSHA’s New Recommendations for Arc Flash StudiesAn Engineer’s Guide to OSHA’s New Recommendations for Arc Flash Studies
An Engineer’s Guide to OSHA’s New Recommendations for Arc Flash StudiesWindpower Engineering & Development
 
Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushingNovia Putri
 
Introduction-to-MV-Design-Guide.ppt
Introduction-to-MV-Design-Guide.pptIntroduction-to-MV-Design-Guide.ppt
Introduction-to-MV-Design-Guide.pptAhmed Ramadan
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsJames S Nasby
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersThorne & Derrick International
 

Ähnlich wie ETAP - Arc flash introduction (20)

Frank Conte Arc flash program
Frank Conte Arc flash programFrank Conte Arc flash program
Frank Conte Arc flash program
 
Shortcircuit-IEC.pdf
Shortcircuit-IEC.pdfShortcircuit-IEC.pdf
Shortcircuit-IEC.pdf
 
Ellis Patents Cable Cleats Guide - Black Book
Ellis Patents Cable Cleats Guide - Black BookEllis Patents Cable Cleats Guide - Black Book
Ellis Patents Cable Cleats Guide - Black Book
 
Arc Flash Safety Training by Pennsylvania Department of Labor and Indusry
Arc Flash Safety Training by Pennsylvania Department of Labor and IndusryArc Flash Safety Training by Pennsylvania Department of Labor and Indusry
Arc Flash Safety Training by Pennsylvania Department of Labor and Indusry
 
Short-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash AnalysisShort-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash Analysis
 
Dl arc flash presentation2013 r3
Dl arc flash presentation2013 r3Dl arc flash presentation2013 r3
Dl arc flash presentation2013 r3
 
L.v tech presentation 2
L.v tech presentation 2L.v tech presentation 2
L.v tech presentation 2
 
arc-flash-analysis-done-right.pdf
arc-flash-analysis-done-right.pdfarc-flash-analysis-done-right.pdf
arc-flash-analysis-done-right.pdf
 
ETAP - Arc flash analysis etap
ETAP - Arc flash analysis etapETAP - Arc flash analysis etap
ETAP - Arc flash analysis etap
 
ETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done RightETAP - Arc flash analysis done Right
ETAP - Arc flash analysis done Right
 
Arc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of TechnologyArc Flash Analysis Training by Illinois Institute of Technology
Arc Flash Analysis Training by Illinois Institute of Technology
 
Michael Wood - Loader electric shocks, a case study
Michael Wood - Loader electric shocks, a case studyMichael Wood - Loader electric shocks, a case study
Michael Wood - Loader electric shocks, a case study
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodination
 
Arc Flas presentation doc 2 rev b
Arc Flas presentation doc 2 rev bArc Flas presentation doc 2 rev b
Arc Flas presentation doc 2 rev b
 
An Engineer’s Guide to OSHA’s New Recommendations for Arc Flash Studies
An Engineer’s Guide to OSHA’s New Recommendations for Arc Flash StudiesAn Engineer’s Guide to OSHA’s New Recommendations for Arc Flash Studies
An Engineer’s Guide to OSHA’s New Recommendations for Arc Flash Studies
 
Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushing
 
Introduction-to-MV-Design-Guide.ppt
Introduction-to-MV-Design-Guide.pptIntroduction-to-MV-Design-Guide.ppt
Introduction-to-MV-Design-Guide.ppt
 
Fire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC ConsiderationsFire Pump Short Circuit and WIC Considerations
Fire Pump Short Circuit and WIC Considerations
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 

Kürzlich hochgeladen

PSYCHIATRIC History collection FORMAT.pptx
PSYCHIATRIC   History collection FORMAT.pptxPSYCHIATRIC   History collection FORMAT.pptx
PSYCHIATRIC History collection FORMAT.pptxPoojaSen20
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...EduSkills OECD
 
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdfssuser54595a
 
Arihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdfArihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdfchloefrazer622
 
URLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppURLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppCeline George
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxRoyAbrique
 
Alper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentAlper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentInMediaRes1
 
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991RKavithamani
 
Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3JemimahLaneBuaron
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformChameera Dedduwage
 
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdfBASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdfSoniaTolstoy
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Educationpboyjonauth
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introductionMaksud Ahmed
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docxPoojaSen20
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting DataJhengPantaleon
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxpboyjonauth
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeThiyagu K
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxheathfieldcps1
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingTechSoup
 

Kürzlich hochgeladen (20)

PSYCHIATRIC History collection FORMAT.pptx
PSYCHIATRIC   History collection FORMAT.pptxPSYCHIATRIC   History collection FORMAT.pptx
PSYCHIATRIC History collection FORMAT.pptx
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
 
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
18-04-UA_REPORT_MEDIALITERAСY_INDEX-DM_23-1-final-eng.pdf
 
Arihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdfArihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdf
 
URLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website AppURLs and Routing in the Odoo 17 Website App
URLs and Routing in the Odoo 17 Website App
 
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptxContemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
Contemporary philippine arts from the regions_PPT_Module_12 [Autosaved] (1).pptx
 
Alper Gobel In Media Res Media Component
Alper Gobel In Media Res Media ComponentAlper Gobel In Media Res Media Component
Alper Gobel In Media Res Media Component
 
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
Industrial Policy - 1948, 1956, 1973, 1977, 1980, 1991
 
Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3Q4-W6-Restating Informational Text Grade 3
Q4-W6-Restating Informational Text Grade 3
 
Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Bikash Puri  Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Bikash Puri Delhi reach out to us at 🔝9953056974🔝
 
A Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy ReformA Critique of the Proposed National Education Policy Reform
A Critique of the Proposed National Education Policy Reform
 
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdfBASLIQ CURRENT LOOKBOOK  LOOKBOOK(1) (1).pdf
BASLIQ CURRENT LOOKBOOK LOOKBOOK(1) (1).pdf
 
Introduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher EducationIntroduction to ArtificiaI Intelligence in Higher Education
Introduction to ArtificiaI Intelligence in Higher Education
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 
mini mental status format.docx
mini    mental       status     format.docxmini    mental       status     format.docx
mini mental status format.docx
 
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data_Math 4-Q4 Week 5.pptx Steps in Collecting Data
_Math 4-Q4 Week 5.pptx Steps in Collecting Data
 
Introduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptxIntroduction to AI in Higher Education_draft.pptx
Introduction to AI in Higher Education_draft.pptx
 
Measures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and ModeMeasures of Central Tendency: Mean, Median and Mode
Measures of Central Tendency: Mean, Median and Mode
 
The basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptxThe basics of sentences session 2pptx copy.pptx
The basics of sentences session 2pptx copy.pptx
 
Grant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy ConsultingGrant Readiness 101 TechSoup and Remy Consulting
Grant Readiness 101 TechSoup and Remy Consulting
 

ETAP - Arc flash introduction

  • 1. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 1 Arc Flash Analysis
  • 2. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 2 Arc Flash Definition • What is Arc Flash? - It is a Short Circuit through the air that flashes from one exposed conductor to another. - Also known, as an arc blast, is a type of electrical arc supplied with electrical energy.
  • 3. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 3 Electrical Arc Hazards • Electrical Arcs – Can occur when a conductive object gets too close to a high-amp current source (energized conductor) – Typically Arc Flash is seen in higher voltages, such as 408 volts and higher – Some instances, Arc Flash can occur less than 208 volts
  • 4. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 4 Electrical Arc Hazards • Arc Flash Burns – The arc can heat the air to temperatures as high as 35,000 F and vaporize metal. – Arc flash can cause severe skin burns by direct heat exposure and by igniting clothing.
  • 5. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 5 Electrical Arc Hazards • Arc Blast Impacts – The heating of the air and vaporization of metal creates a pressure wave that can damage hearing and cause memory loss (from concussion) and other injuries. Flying metal parts are also a hazard. • Falls – Electric shocks and arc blasts can cause falls, especially from ladders or unguarded scaffolding.
  • 6. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 6 Definitions • Limited Approach Boundary: A shock protection boundary not to be crossed by unqualified persons unless escorted by qualified personnel. • Restricted Approach Boundary: A shock protection boundary to be crossed by only qualified persons. Shock protection is required. • Prohibited Approach Boundary: A shock protection boundary to be crossed by only qualified persons. The use of techniques that may require direct contact with energized equipment.
  • 7. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 7 Definition of Approach Boundaries
  • 8. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 8 Definitions • Arc Flash Boundary: Distance at which the incident energy equals 1.2 Cal/cm^2. • Incident Energy: The amount of energy impressed on a surface, a certain distance from the source, generated during and electrical arc event. • Working Distance: The dimension between the possible arc point and the head and body of a worker positioned in place to perform the task. • Bolted fault current: A short-circuit contact between two conductors at different potentials in which the impedance between the conductors is zero.
  • 9. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 9 Definitions • Available fault current: The electrical current that can be provided by the serving utility and facility-owned electrical generating devices and large electrical motors considering the amount of impedance in the current path. • Arcing fault current: A fault current flowing through an electrical arc-plasma, also called arc fault current and arc current. • Voltage (Nominal): A nominal value assigned to a circuit or system for the purpose of designating its voltage class (I.e. 120/240 V, 480Y/277 V, 600V, etc).
  • 10. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 10 Regulating Authorities • OSHA 29 CFR 1910.132 (d) requires employers to assess the workplace to determine if hazards are present, or likely to be present and select and have each employee use the types of PPE that will protect them. • OSHA 29 CFR 1910.333 Requires employees who are exposed to electrical shock hazard to be qualified for the specific task that they are performing and use the appropriate PPE
  • 11. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 11 Regulating Authorities • OSHA 29 CFR 1910.335 (a)(1)(I): Protective equipment for specific body parts • OSHA 29 CFR 1910.335 (a)(2)(I): use of Insulated tools when working around energized equipment. • NEC 110.6: equipment must be marked to warn qualified persons of potential electrical arc-flash hazards. • NFPA 70E Part II Chapter 2, paragraph 2-1.3.3 states that arc-flash analysis must be performed in order to determine the incident energy level and appropriate PPE for given tasks.
  • 12. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 12 IEEE 1584 2002 “Guide for Performing Arc Flash Hazard Calculations” NFPA 70E “Standard for Electrical Safety Requirements for Employee Workplaces” Protection From Arc Flash Hazards
  • 13. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 13 NFPA 70E (Annex D.2, 5, 6 Eqs.) IEEE 1584-2002 Voltage Range 208 V – 600 V 208 – 15 kV (Empirical) 15 kV+ (Lee Method) Current Range 16 kA – 50 kA 0.7 kA to 106 kA Arc Duration Range No limit No Limit Installations Open Air, Cubic Box Open Air, Cubic Box, Cable Bus Working Distance 18 inches + 18 inches + Unit of Measure Cal/cm2 or J/cm2 Cal/cm2 or J/cm2 Comparison of Arc Flash Standards
  • 14. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 14 Incident energy exposure at a working distance of 18” for a 19.5 kA Arc @ 600 Volts (open air equipment) 0 5 10 15 20 0 10 20 Calorie/cm^2 Fault clearing time (Cycles) 600 Volt Arc in Open Air Incident energyExposure @ 18 in. NFPA 70E IEEE 1584-2002 Incident Energy Comparison
  • 15. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 15 0 5 10 15 20 0 10 20 Calorie/cm^2 Fault clearing time (Cycles) 600 Volt Arc in Closed Box Incident energyExposure @ 18 in. NFPA 70E IEEE 1584-2002 Incident energy exposure at a working distance of 18” for a 19.5 kA Arc @ 600 Volts (enclosed equipment) Incident Energy Comparison
  • 16. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 16 Required Parameter NFPA 70E IEEE 1584 System Nominal Voltage X X Gap Between Conductors X Distance X Factor X System Grounding (Grounded/Ungrounded) X Open/Enclosed Equipment X X Working Distance X X Coordination Information (TCC) X X Data Collection for Arc Flash
  • 17. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 17 Gap between Conductors
  • 18. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 18 Standards for Short-Circuit • IEEE Std 141-1993 (IEEE Red Book) • IEEE Std 242-2001 (IEEE Buff Book) • ANSI (different standards like C37, etc) • IEC (60909, 60363, etc) • See ETAP help file for more standards
  • 19. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 19 Why use 3-Phase Faults • Line to Line faults quickly escalate into three- phase faults • LV L-G faults in solidly grounded systems quickly escalate into three phase faults • LV L-G faults in Ungrounded / High resistance grounded systems do not release enough energy. • MV faults in low resistance or reactance grounded systems should be cleared quickly, but worst case scenario 3-phase fault should be considered
  • 20. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 20 3-Phase Bolted Fault Current • Perform ANSI/IEC short circuit study that considers the following: – 3-phase bolted fault – ½ cycle or 1½-4 cycle fault current depending on the type of device or system voltage – Include all cables & Overload heaters – Prefault voltage (nominal circuit voltage) – Short-circuit Calculation should be more accurate rather than too conservative (faults may persist longer at lower current levels which may translate into higher energy)
  • 21. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 21 ))(lg(**00304.0))(lg(**5588.0 *000526.0*0966.0)lg(*662.0)lg( bfbf bf IGIV GVIKIa   For buses with nominal kV in the range of 0.208 to 1.0 kV: In general, arcing current in systems below 15.0 kV will be less than the 3-phase fault current because of arc impedance. Arcing Current
  • 22. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 22 For buses with nominal kV rating greater than 15 kV, the arcing current can be considered to be the same as the bolted fault current: For buses with nominal kV rating in the range of 1 to 15.0 kV: )Ilg(*983.000402.0)Ialg( bf bfIIa  Arcing Current
  • 23. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 23 System Modes of Operation • Open or looped • One or more utility feeders in service • Utility interface substation secondary bus tie breaker open or closed • Unit substation with one or two primary feeders • Unit substation with two transformers with secondary tie opened or closed • MCC with one or two feeders, one or both energized. • Generators running in parallel with the utility supply or in standby mode
  • 24. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 24 Arc Duration LV CB
  • 25. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 25 Arc Duration LV CB
  • 26. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 26 Arc Duration for Fuses
  • 27. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 27 Incident Energy Empirical method (1.0 to 15.0 kV)              x x nf D t ECE 610 * 2.0 **184.4 Lee method (higher than 15.0 kV)        2 6 **10*142.2 D t IVE bf
  • 28. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 28 Arc Flash Boundary Empirical method (1.0 to 15.0 kV)              x x nf D t EC 610 * 2.0 **184.42.1 Lee method (higher than 15.0 kV)        2 6 **10*142.22.1 D t IV bf
  • 29. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 29 Incident Energy Exposure cal/cm2 Protective Clothing and PPE 1.2 > cal/cm2  0 Nonmelting or untreated natural fiber for long sleeve shirt and pants/coverall, Face shield for projectile protection, Safety glasses, Hearing protection and Leather gloves. 12 > cal/cm2  1.2 Arc-rated long-sleeve shirt and arc-rated pants or arc-rated coverall and/or arc flash suit, Arc-rated face shield, Arc rated jacket, Hard hat, hard hat liner, Safety glasses, Hearing protection, Leather gloves and Leather work shoes. cal/cm2  12 Arc-rated long-sleeve shirt and arc-rated pants, Arc-rated arc flash suit hood, Arc-rated gloves, Arc-rated jacket, Hard hat, hard hat liner, Safety glasses, Hearing protection, Arc- rated gloves, Leather work shoes. Incident Energy Levels (NFPA 70E 2012 Annex H.3)
  • 30. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 30 Up to 1.2 Cal/cm2 • Nonmelting or untreated natural fiber for long sleeve shirt and pants/coverall • Face shield for projectile protection • Safety glasses • Hearing protection • Leather gloves
  • 31. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 31 1.2 up to 12 Cal/cm2 • Arc-rated long-sleeve shirt and arc-rated pants or arc-rated coverall and/or arc flash suit • Arc-rated face shield • Arc rated jacket • Hard hat • Arc rated hard hat liner • Safety glasses • Hearing protection • Leather gloves • Leather work shoes
  • 32. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 32 Greater than 12 Cal/cm2 • Arc Flash Suit • Arc-rated arc flash hood • Arc-rated gloves • Arc-rated jacket, parka • Hard Hat • Arc-rated hard hat liner • Hearing Protection • Arc-rated gloves • Leather work shoes
  • 33. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 33 PPE Incident Energy Rating • ATPV: is the defined as the incident energy on a fabric or material that results in sufficient heat transfer through the fabric or material to cause the onset of a second degree burn. • EBT: is defined as the average of the five highest incident energy exposures values below the Stoll curve where the specimens do not exhibit breakopen. EBT is reported when the ATPV cannot be determined due to FR fabric breakopen. • HAF%: is the heat transfer capability of the fabric or material
  • 34. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 34 Stoll Curve
  • 35. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 35 Equipment Layering
  • 36. ©1996-2010 ETAP/Operation Technology, Inc. – Workshop Notes: Arc Flash Analysis Slide 36 Types of Insulating Glove Max. use voltage AC (L-L) (V-Rating field) Class Bus nominal kV range Low Voltage Gloves 500 00 kV ≤ 0.500 Bus kV ≤≥ 1000 0 0.500 kV < Bus kV ≤ 1.0 kV High Voltage Gloves 7500 1 1.0 kV < Bus kV ≤ 7.5 kV 17000 2 7.5 kV < Bus kV ≤ 17.0 kV 26500 3 17.0 kV < Bus kV ≤ 26.5 kV 36000 4 26.5 kV < Bus kV ≤ 36.0 kV ASTM Insulating Glove Voltage Classes