White Paper: Electrical Ground Rules
Best Practices for Grounding Your Electrical Equipment
Examining our use of ground as protection, and how ground fault circuit
interrupter devices operate to protect us from severe shock (Part 2 of 3)
Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com
2
This paper is part two of a three part series that takes a look at grounding and its role in protecting
personnel, protecting equipment, and ensuring the integrity of electrical signals. In this part, we will
examine our use of ground as a means of protection from ground faults, and how ground fault circuit
interrupter (GFCI) devices operate to protect us from severe shock.
In part one of this series (8500-993) we looked at the concept of grounding, the AC power system and its
use of ground, and gave three main reasons why we ground electrical equipment: for safety, to stabilize
electrical signals, and to limit transient voltages and current.
Part three of this series will review ground and its role as a voltage stabilizer and transient limiter. It will
offer some tips on what you can do to improve your connection to ground to realize benefits to safety
and signal integrity.
GROUNDS AS A MEANS OF PROTECTION
In Part 1 of this series, we said that one reason we connect to ground is for safety because it provides an
alternative path for fault current to flow. The voltage in a circuit will force current to travel all available
conductive paths back to the source. The majority of this current will follow the path of least resistance.
We normally provide an earth ground connection as an alternative low-resistance path for this current
flow to limit shock (as an alternative path to using your body to return current to AC neutral and earth
ground). For AC powered circuits, a ground fault is any event that causes an imbalance in current
flowing in the AC hot lead with current flowing in the AC neutral lead. The ground fault current refers to
the difference in current flowing between AC hot and AC neutral, and it could be the current flowing in
the earth ground lead or the current taking another path back to the AC source, like through a body to
earth ground (because AC neutral and earth ground are tied together at the source).
For AC powered devices, appliance manufacturers go to great lengths to make sure that you do not
become the path of least resistance for a fault condition, which allows current to flow from AC hot back
to AC neutral/earth ground via your body (Remember that AC neutral and earth ground are held in
common at the source of the AC voltage). They do this by properly insulating their product and/or by
providing a remote connection to earth ground at the product (via that third rounded conductor at your
power outlet). That is, a conductive enclosure or housing of the device will typically connect to earth
ground. Then if the AC hot or AC neutral wire to the device should fray or break, it could contact earth
ground and complete the circuit, allowing the breaker to trip when its rated limit is reached, possibly
preventing a fire, and hopefully without electrocuting yourself in the process. Of course, some
appliances are constructed using insulating materials and do not connect their chassis to earth ground
(they connect to AC using two-prong power cords). Under normal operation, the current to the device
flows from between AC Hot and AC Neutral, through your load, and returns to your breaker box and
utility meter power connection. The third wire, or earth ground wire, will become the return path for at
least part of that current, should a fault occur at the powered device. Without this third conductor or
alternate path held in reserve, your body could become the return path of least resistance to earth
ground, and this could drive serious injury. Thus, for most 3-conductor AC wired equipment, its
connection to earth ground is primarily to provide a safe path for current to flow in the event of a circuit
fault, and normally, no current flows in the ground wire. By limiting current flow in the ground wire to
only under certain conditions (ground faults), this helps to ensure that there will be no potential
difference across this conductor, and it can better act like an extension of earth ground itself (i.e. nearly
0V).
Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com
3
So what does a wired earth ground really protect you from? Does it protect you from electrocution?
And what if your appliance does not include a connection to earth ground and you become the path of
least resistance for some sort of ground fault? The answer to these questions is that a wired ground
does not protect you from fatal shock. Rather, a GFCI can protect you from fatal shock.
THE GFCI AND ITS USE OF GROUND AS A MEANS OF PROTECTION FROM
GROUND FAULTS
To further illustrate how earth ground works as a means of protection, let’s
examine the behavior of a device that you may already be familiar with--the
GFCI outlet. It looks similar to the picture at left, and usually includes a “Test”
and “Reset” button. However, a GFCI protected outlet may look identical to a
standard outlet if it happens to be connected downstream to the load side of a
GFCI outlet.
You probably have several of these in your home, perhaps in your kitchen,
laundry room, basement, bathroom, garage, or at an outdoor outlet. You
probably know that these outlets are used to help protect you from severe
shock, and are generally required in “wet” areas, but you may not have given
much thought to how this device actually works with ground to help protect
you from harmful levels of shock.
For example, as ground conducts current, a voltage difference will develop across it, forcing each
connection to it to occur at a slightly different potential. So in practice, if all connections to ground were
really made at 0V, we wouldn’t have ground faults or ground loops. And therein lies the problem with
ground—your ability to mimic its idealized behavior as a reference connection to 0V really depends on
how well you can minimize its effective impedance, chiefly its resistance and inductance. Generally at
50-60Hz power line frequencies, the resistive component of your connection to earth is more significant
than the reactive component (inductance). At higher frequencies, the reactive component gains
significance, as the inductance of your connection to ground raises its impedance to transient energy.
The bottom line is that you need to minimize the effect both components have on raising ground
impedance by keeping both the resistance and inductance of your connection to ground to a minimum.
In addition to GFCI outlets, there are Ground Fault Circuit
Interrupter (GFCI) Breakers similar to the examples shown at
left. These act similar to GFCI outlets, but will protect an
entire circuit from ground faults, while the GFCI outlet only
protects at its outlet and any downstream outlets for daisy-
chained “load” outlets. The advantage of a GFCI Breaker is
that you do not need local GFCI outlets. GFCI Breakers are
typically used on circuits where the likelihood of fatal shock is
much higher (like a public swimming pool), and like a GFCI
outlet, they can typically stop current flow within 25ms of
detecting a ground fault condition on their branch circuit.
Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com
4
As we noted in Part 1, the AC outlets in your home commonly provide 3-wires or conductors for
connection to your appliance—a line hot connection (typically via a black insulated wire that connects to
the shorter vertical slot of the outlet), a line neutral connection (typically via a white wire that connects
to the taller vertical slot of the outlet), and a ground connection (typically via a green insulated or bare
copper wire that connects to the round hole of the outlet at the top or bottom between the two vertical
slots). In any circuit, current will seek all conductive paths back to its source, but most of this current
will flow the path of least resistance. In your home, when you plug an appliance into an AC outlet, you
give current a low-resistance path to flow through and power your appliance, and then return back via
the outlet to its source. The source in this case is where your home or business connects to the power
line, usually at your power meter and service entrance. Remember, although AC neutral and AC ground
are separate conductors at your outlet, they do connect together at your service box and also connect
to earth ground near this box, usually via one or more grounding rods driven into the earth. Load
current normally flows out the line/load hot conductor, through your appliance, and returns to earth
ground via the neutral conductor, and doesn’t normally flow in the ground conductor.
GFCI refers to a type of power outlet called a Ground Fault Current Interrupter. The GFCI outlet will
usually provide a second pair of screws for a load cable connection to allow it to connect to additional
non-GFCI outlets in daisy-chain fashion, connecting them through itself to power (making it act like a
GFCI breaker for downstream loads). This type of outlet can trip and quickly stop the flow of current
through it and downstream from it to prevent serious injury if a Ground Fault occurs anywhere in the
circuit. A Ground Fault would occur if the electricity (current) is allowed to take some other path back
to the source, than neutral (including through a person’s body), as the source is where neutral and
ground connect to the earth. A GFCI outlet works to protect you by measuring the amount of current
flowing out the “Hot” wire circuit into the appliance, and monitoring the return current flowing out of
the appliance back through the “Neutral” circuit.
If the current returned in neutral does not match the current in the hot line, the GFCI will trip and
interrupt the current flow out of the hot wire. Of course, the “lost” current doesn’t really go “missing”,
but has temporarily found some other path back to the source, perhaps through your self to earth. This
errant path is the ground fault we refer to and the GFCI feeding this circuit will trip very quickly to
prevent serious shock or electrocution via current in this errant path.
The figure at left depicts one example of a ground
faulted circuit. It shows one phase of an AC line
(like that sourced from a service panel) powering a
hand drill through a GFCI outlet or breaker. The
black AC hot wire to the hand drill makes contact
with its metallic housing (causing a ground fault),
and a workman standing on the ground and holding
the drill completes a path to earth for a portion of
the circuit current. Because this circuit was made
through a GFCI outlet or breaker, the small leakage
current triggers a relay in the black hot lead to the
drill to open and stop the flow of current, protecting the workman from severe shock.
It’s important to recognize that a GFCI does not protect against circuit overloads (too much load current),
short circuits between hot and neutral, or minor electrical shocks. The man in the example above would
still feel a small shock when he makes contact with the hand drill. And, even with a GFCI protected
circuit, you can still be shocked if you touch bare wires while standing on an insulating surface, such as a
Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com
5
wood floor, and you happen to complete the neutral current path. The GFCI only protects against
current flow that does not completely follow its normal safe path along neutral to earth ground at your
service panel, but uses some other errant path to reach the earth instead. The other path could be
through a person’s body to earth ground, or even through the ground wire to earth (perhaps via a hot or
neutral short to the grounded chassis of the load device, like in the example above).
Because the GFCI outlet trips to interrupt current when it detects a ground fault (a mismatch in hot and
neutral current), it also contains a reset button used to reset its trigger mechanism. This reset has a
lockout feature that keeps it in reset for any of the following:
 There is no power being supplied to the GFCI.
 The GFCI has been miswired by reversing the line-in (source) and line-out (load) lead
connections.
 The GFCI fails an internal test, indicating that it may not be able to provide protection from a
ground fault.
The appliance that you plug into your AC outlet typically connects its other metal parts to the ground
connection (any other conductive parts other than its AC hot and neutral circuits). It does this so that if
its own AC Hot circuit was to break or fray and accidentally come in contact with another of its metal or
conductive surfaces (like its shell or chassis), that surface would instead become a path to ground. This
path to ground essentially shorts AC hot to AC ground and causes the circuit breaker or fuse to quickly
overheat and open the circuit, interrupting the current flow. The normal level of current to cause a
typical breaker to trip is 15A or 20A, but the amount of current that can put the human heart into
fibrillation is less than 100mA. So even if a person handling that faulty appliance happened to be
barefoot and standing on wet ground, a portion of that branch current would also flow through that
person to ground and this could still be fatal.
Generally, in a ground fault situation, the body path would provide a higher resistance path to earth
than the grounded chassis and would only take a portion of this current. And just like two different
resistive loads in a circuit, current is distributed along both resistive paths, but mostly along the path of
least resistance. In the example of a grounded chassis, one path is through the ground wire and another
through the body. But, even only a small portion of that 15A or 20A of branch current that flows just
before the breaker trips is enough to stop the human heart. In the example of the hand drill, without
GFCI protection, the workman may be killed. However, if the branch circuit happens to be passing
through a GFCI protected outlet, the workman might still feel a momentary shock, but at a much lower
current and of a shorter duration, as the GFCI will interrupt the hot current flow much more quickly than
a circuit breaker alone.
In fact, a GFCI protected outlet or breaker will trip if the measured difference in current between the
“hot” and “neutral” conductors is as little as 4-6mA. Momentary contact with 120V at 6mA will shock
you, but will not likely put your heart into fibrillation, as the GFCI typically trips within 1/30th
of a second
as soon as it detects a hot/neutral imbalance, a small enough duration to protect you from fatal levels of
shock.
Also note that for the purpose of discussion, we tend to think of and talk about AC current as flowing
from the hot lead, through the device, and then returning on the neutral lead. However, AC current
does not really flow in one direction or with respect to one polarity. Rather “AC” denotes Alternating
Current, and alternating current actually flows back and forth through the load (alternating its polarity),
50-60 times a second.
Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com
6
A GFCI outlet typically uses a differential or toroidal
transformer to couple the line to the load, similar to the
illustration at left. The current of the hot wire is
magnetically coupled to the toroid and then passes to the
load. The neutral wire from the load also passes through
the toroid in the opposite direction and back to the service
entrance of the house, where the line originates. These two
wires are mutually coupled via the toroid or transformer
magnetic material, such that for normal operation, the
current that flows through the hot wire balances with the
current that flows back through the neutral wire. But if
these currents do not balance, this imbalance triggers a
sensor circuit that drives relay contacts to open the Line hot
circuit (black wire), interrupting its flow. Of course, the only
way the hot and neutral line currents would not balance is if
an external source is adding current to the circuit, or the line current is being leaked through some other
external path (perhaps if line current is leaking to earth ground). A hot/neutral imbalance as small as
5mA is enough to quickly interrupt the flow of line current to the load, potentially protecting you from
fatal levels of electric shock. In this way, the GFCI interrupts the flow of current much more quickly than
the service entrance fuse or circuit breaker, in as quickly as one-thirtieth of a second.
Do not be fooled into thinking that a fuse or breaker alone can protect you from electrical shock.
Rather, it’s the purpose of a GFCI to protect you from electrical shock, while the purpose of a fuse or
breaker is to protect its premises from electrical fire by limiting the maximum current and duration of
excess current to a lower level, but not a low enough level to protect you from shock. Consider that
there are many scenarios that could cause a hot wire to accidentally come in contact with the neutral or
ground wire, causing a large amount of excess current to flow from hot to neutral. For example, an
animal might chew through the wire insulation, a person might accidentally drive a nail or screw through
the wire, or the cord connecting to an appliance might get chewed up after being pinched in a doorway
or sucked up by a vacuum cleaner. The potential fault modes are endless and difficult to prevent. These
faults will all cause excess current to flow and heat up the fuse or breaker and cause it to burn or break
open, interrupting the flow of current, possibly preventing the wire from starting a fire. The problem
with relying on a circuit breaker or fuse for shock protection is that they are tripped at much higher
levels of current (15 or 20A typical), and after longer periods of time, both of which could be fatal if you
happen to be in the path of this fault current.
We started this discussion by trying to show how a GFCI outlet works with ground to protect yourself,
but the reality is that a GFCI outlet would still protect you from electrical shock due to a ground fault,
even without a hard-wired connection to earth ground. That is, if the GFCI happened to be wired using
2-wire AC cables (hot and neutral but no earth ground), it still provides ground fault protection. This is
because a GFCI outlet monitors for current imbalances between hot and neutral, not ground. The only
possible difference in a 2-wire GFCI powered application is the ground fault current along the errant
path could potentially reach a higher level without the third wire ground path present, but the outlet
would still detect the hot-neutral imbalance and break the hot wire connection in time to protect you
from severe shock.
We spent a lot of time talking about ground as a “safe” path for current, and this is because personal
safety should be your number one priority, but we stated at the beginning of this paper that we have
Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com
7
two other important reasons for connecting to ground: to stabilize signals and to limit transient voltage
and current. In Part 3 of this series, we will discuss the other two reasons we connect to ground and
give some tips for improving your connection to ground to realize the benefits of increased safety and
signal integrity for your wired equipment.
ABOUT ACROMAG
Acromag has designed and manufactured measurement and control products for more than 50 years.
They are an AS9100 and ISO 9001-certified international corporation with a world headquarters near
Detroit, Michigan and a global network of sales representatives and distributors. Acromag offers a
complete line of industrial I/O products including a variety of process instruments, signal conditioners,
and distributed fieldbus I/O modules that are available with a 2-year warranty. Industries served include
chemical processing, manufacturing, defense, energy, and water services.
For more information about Acromag products, call the Inside Sales Department at (248) 295-0880, FAX
(248) 624-9234. E-mail sales@acromag.com or write Acromag at 30765 South Wixom Road, Wixom, MI
48393 USA. The web site is www.acromag.com.
Electrical Grounding Rules Part 1 is available for download:
www.acromag.com/page/white-paper-electrical-ground-rules

Weitere ähnliche Inhalte

Was ist angesagt?

The Complete Acromag Guide to Industrial Electrical Grounding
The Complete Acromag Guide to Industrial Electrical GroundingThe Complete Acromag Guide to Industrial Electrical Grounding
The Complete Acromag Guide to Industrial Electrical GroundingInstrument Specialties, Inc.
 
Good grounding practices
Good grounding practicesGood grounding practices
Good grounding practicesNarinder Singh
 
Neutral Grounding
Neutral GroundingNeutral Grounding
Neutral GroundingNoman Nomi
 
Earthing Arrangements 17th
Earthing  Arrangements 17thEarthing  Arrangements 17th
Earthing Arrangements 17thPaul Holden
 
Earthing Syatem
Earthing SyatemEarthing Syatem
Earthing SyatemNoman Khan
 
Vignettes in Grounding
Vignettes in GroundingVignettes in Grounding
Vignettes in Groundingmichaeljmack
 
System neutral-earthing
System neutral-earthingSystem neutral-earthing
System neutral-earthingazzaabo
 
Earthing, grounding and isolation
Earthing, grounding and isolation Earthing, grounding and isolation
Earthing, grounding and isolation Dhananjaysinh Jhala
 
Neutral grounding project seminar
Neutral grounding project seminarNeutral grounding project seminar
Neutral grounding project seminarJustin Rams
 
Protection against overvoltages
Protection against overvoltagesProtection against overvoltages
Protection against overvoltagesMaryam Nawaz
 
Factory ESD Grounding System Design Applications
Factory ESD Grounding System Design ApplicationsFactory ESD Grounding System Design Applications
Factory ESD Grounding System Design Applications?? ?
 
Overview of Grounding for Industrial and Commercial Power Systems
Overview of Grounding for Industrial and Commercial Power SystemsOverview of Grounding for Industrial and Commercial Power Systems
Overview of Grounding for Industrial and Commercial Power Systemsmichaeljmack
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the LightningAmeen San
 
Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Muhammad Zaeem Sarfraz
 
Electrical Earthing and types
Electrical Earthing and typesElectrical Earthing and types
Electrical Earthing and typesManjunath Kh
 
Grounding, neutral & earthing
Grounding, neutral & earthingGrounding, neutral & earthing
Grounding, neutral & earthingEngr Muhammad Imran
 

Was ist angesagt? (20)

The Complete Acromag Guide to Industrial Electrical Grounding
The Complete Acromag Guide to Industrial Electrical GroundingThe Complete Acromag Guide to Industrial Electrical Grounding
The Complete Acromag Guide to Industrial Electrical Grounding
 
Good grounding practices
Good grounding practicesGood grounding practices
Good grounding practices
 
Neutral Grounding
Neutral GroundingNeutral Grounding
Neutral Grounding
 
Earthing Arrangements 17th
Earthing  Arrangements 17thEarthing  Arrangements 17th
Earthing Arrangements 17th
 
Earthing Syatem
Earthing SyatemEarthing Syatem
Earthing Syatem
 
Vignettes in Grounding
Vignettes in GroundingVignettes in Grounding
Vignettes in Grounding
 
System neutral-earthing
System neutral-earthingSystem neutral-earthing
System neutral-earthing
 
Grounding and techniques
Grounding and techniquesGrounding and techniques
Grounding and techniques
 
Hv grounding final
Hv grounding finalHv grounding final
Hv grounding final
 
Earthing, grounding and isolation
Earthing, grounding and isolation Earthing, grounding and isolation
Earthing, grounding and isolation
 
Neutral grounding project seminar
Neutral grounding project seminarNeutral grounding project seminar
Neutral grounding project seminar
 
Protection against overvoltages
Protection against overvoltagesProtection against overvoltages
Protection against overvoltages
 
Grounding
GroundingGrounding
Grounding
 
Factory ESD Grounding System Design Applications
Factory ESD Grounding System Design ApplicationsFactory ESD Grounding System Design Applications
Factory ESD Grounding System Design Applications
 
Overview of Grounding for Industrial and Commercial Power Systems
Overview of Grounding for Industrial and Commercial Power SystemsOverview of Grounding for Industrial and Commercial Power Systems
Overview of Grounding for Industrial and Commercial Power Systems
 
Protection Devices and the Lightning
Protection Devices and the LightningProtection Devices and the Lightning
Protection Devices and the Lightning
 
Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)Earthing & Grounding (Easily Explained)
Earthing & Grounding (Easily Explained)
 
Electrical Earthing and types
Electrical Earthing and typesElectrical Earthing and types
Electrical Earthing and types
 
Grounding, neutral & earthing
Grounding, neutral & earthingGrounding, neutral & earthing
Grounding, neutral & earthing
 
Earthing system
Earthing system   Earthing system
Earthing system
 

Andere mochten auch

El clima no es un juego
El clima no es un juegoEl clima no es un juego
El clima no es un juegoerquimicoloco
 
Wintop healthcare fund
Wintop healthcare fundWintop healthcare fund
Wintop healthcare fundJeraldBoone
 
Jenny Harding: Usable geographic information – what does it mean to users?
Jenny Harding: Usable geographic information – what does it mean to users?Jenny Harding: Usable geographic information – what does it mean to users?
Jenny Harding: Usable geographic information – what does it mean to users?AGI Geocommunity
 
Borhani Activation Report_Actual
Borhani Activation Report_ActualBorhani Activation Report_Actual
Borhani Activation Report_ActualMd Mahbub Islam
 
Propaganda as a Tool of War
Propaganda as a Tool of WarPropaganda as a Tool of War
Propaganda as a Tool of Warbrhughes
 
Maratoniano perfecto
Maratoniano perfectoMaratoniano perfecto
Maratoniano perfectoerquimicoloco
 
Vehicle Light Weighting - A Greener, Composite Solution (for Class A Body Pan...
Vehicle Light Weighting - A Greener, Composite Solution (for Class A Body Pan...Vehicle Light Weighting - A Greener, Composite Solution (for Class A Body Pan...
Vehicle Light Weighting - A Greener, Composite Solution (for Class A Body Pan...OC_Composites
 
Walmley Wilf Inset
Walmley Wilf InsetWalmley Wilf Inset
Walmley Wilf Insetpablo01
 
Remanufacturing lecture Bologna
Remanufacturing lecture BolognaRemanufacturing lecture Bologna
Remanufacturing lecture BolognaMarcel Bovy
 
Los espacios naturales protegidos en España
Los espacios naturales protegidos en EspañaLos espacios naturales protegidos en España
Los espacios naturales protegidos en Españaerquimicoloco
 

Andere mochten auch (13)

El clima no es un juego
El clima no es un juegoEl clima no es un juego
El clima no es un juego
 
Wintop healthcare fund
Wintop healthcare fundWintop healthcare fund
Wintop healthcare fund
 
Jenny Harding: Usable geographic information – what does it mean to users?
Jenny Harding: Usable geographic information – what does it mean to users?Jenny Harding: Usable geographic information – what does it mean to users?
Jenny Harding: Usable geographic information – what does it mean to users?
 
BRAC AI Health Camp
BRAC AI Health CampBRAC AI Health Camp
BRAC AI Health Camp
 
Ka1 erasmus +cardiff
Ka1 erasmus +cardiffKa1 erasmus +cardiff
Ka1 erasmus +cardiff
 
Borhani Activation Report_Actual
Borhani Activation Report_ActualBorhani Activation Report_Actual
Borhani Activation Report_Actual
 
Propaganda as a Tool of War
Propaganda as a Tool of WarPropaganda as a Tool of War
Propaganda as a Tool of War
 
Maratoniano perfecto
Maratoniano perfectoMaratoniano perfecto
Maratoniano perfecto
 
Vehicle Light Weighting - A Greener, Composite Solution (for Class A Body Pan...
Vehicle Light Weighting - A Greener, Composite Solution (for Class A Body Pan...Vehicle Light Weighting - A Greener, Composite Solution (for Class A Body Pan...
Vehicle Light Weighting - A Greener, Composite Solution (for Class A Body Pan...
 
Walmley Wilf Inset
Walmley Wilf InsetWalmley Wilf Inset
Walmley Wilf Inset
 
Remanufacturing lecture Bologna
Remanufacturing lecture BolognaRemanufacturing lecture Bologna
Remanufacturing lecture Bologna
 
Los espacios naturales protegidos en España
Los espacios naturales protegidos en EspañaLos espacios naturales protegidos en España
Los espacios naturales protegidos en España
 
8 nerve
8 nerve8 nerve
8 nerve
 

Ähnlich wie Electrical Ground Rules Part 2

Electrical Grounding Practices- Part 1 of 3
Electrical Grounding Practices- Part 1 of 3Electrical Grounding Practices- Part 1 of 3
Electrical Grounding Practices- Part 1 of 3M.S. Jacobs & Associates
 
Ground Fault Circuit Interrupters (GFCIs) for AC & DC Systems
Ground Fault Circuit Interrupters (GFCIs) for AC & DC SystemsGround Fault Circuit Interrupters (GFCIs) for AC & DC Systems
Ground Fault Circuit Interrupters (GFCIs) for AC & DC SystemsWestern Automation R&D Ltd
 
Multi – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptxMulti – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptxMarlonAgustin3
 
Experiments manual
Experiments manual Experiments manual
Experiments manual Ramesh Meti
 
Presentation on Earthing & Grounding
Presentation on Earthing & Grounding Presentation on Earthing & Grounding
Presentation on Earthing & Grounding Vineet Shekhar
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptJatmylHarnero1
 
Electrical safety
Electrical safetyElectrical safety
Electrical safetyAnu71
 
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)Andreas ILIOU - Elektro- Solar
 
Lightning concepts iii
Lightning concepts iiiLightning concepts iii
Lightning concepts iiiILDTECH
 
IRJET- Review and Analyse of Ground Fault Circuit Interupter
IRJET- Review and Analyse of Ground Fault Circuit InterupterIRJET- Review and Analyse of Ground Fault Circuit Interupter
IRJET- Review and Analyse of Ground Fault Circuit InterupterIRJET Journal
 
Electrical grounding and earthing systems
Electrical grounding and earthing systemsElectrical grounding and earthing systems
Electrical grounding and earthing systemsBiswajit Pratihari
 
Design and Implementation of a Single Phase Earth Fault Relay
Design and Implementation of a Single  Phase Earth Fault RelayDesign and Implementation of a Single  Phase Earth Fault Relay
Design and Implementation of a Single Phase Earth Fault RelayIJSRED
 
Electrical safety
Electrical safetyElectrical safety
Electrical safetyVima Mali
 
An Article on Electrical Safety
An Article on Electrical SafetyAn Article on Electrical Safety
An Article on Electrical SafetyIJSRD
 

Ähnlich wie Electrical Ground Rules Part 2 (20)

Electrical Grounding Practices- Part 1 of 3
Electrical Grounding Practices- Part 1 of 3Electrical Grounding Practices- Part 1 of 3
Electrical Grounding Practices- Part 1 of 3
 
Ground Fault Circuit Interrupters (GFCIs) for AC & DC Systems
Ground Fault Circuit Interrupters (GFCIs) for AC & DC SystemsGround Fault Circuit Interrupters (GFCIs) for AC & DC Systems
Ground Fault Circuit Interrupters (GFCIs) for AC & DC Systems
 
Multi – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptxMulti – Grounding in the Distribution System.pptx
Multi – Grounding in the Distribution System.pptx
 
Experiments manual
Experiments manual Experiments manual
Experiments manual
 
Earthing
EarthingEarthing
Earthing
 
Presentation on Earthing & Grounding
Presentation on Earthing & Grounding Presentation on Earthing & Grounding
Presentation on Earthing & Grounding
 
Short-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.pptShort-Circuit calculation -Ppt-Slides - Copy.ppt
Short-Circuit calculation -Ppt-Slides - Copy.ppt
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
Report earthing grounding pv with shielded, armoured dc cabling (worldwide)
 
Lightning concepts iii
Lightning concepts iiiLightning concepts iii
Lightning concepts iii
 
Electrical safety potection
Electrical safety potectionElectrical safety potection
Electrical safety potection
 
IRJET- Review and Analyse of Ground Fault Circuit Interupter
IRJET- Review and Analyse of Ground Fault Circuit InterupterIRJET- Review and Analyse of Ground Fault Circuit Interupter
IRJET- Review and Analyse of Ground Fault Circuit Interupter
 
Electrical grounding and earthing systems
Electrical grounding and earthing systemsElectrical grounding and earthing systems
Electrical grounding and earthing systems
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Design and Implementation of a Single Phase Earth Fault Relay
Design and Implementation of a Single  Phase Earth Fault RelayDesign and Implementation of a Single  Phase Earth Fault Relay
Design and Implementation of a Single Phase Earth Fault Relay
 
Mcb, rccb, elcb
Mcb, rccb, elcbMcb, rccb, elcb
Mcb, rccb, elcb
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Grounding, neutral & earthing
Grounding, neutral & earthingGrounding, neutral & earthing
Grounding, neutral & earthing
 
An Article on Electrical Safety
An Article on Electrical SafetyAn Article on Electrical Safety
An Article on Electrical Safety
 

Mehr von Flow-Tech, Inc.

Bently Nevada 3500 System Datasheet
Bently Nevada 3500 System DatasheetBently Nevada 3500 System Datasheet
Bently Nevada 3500 System DatasheetFlow-Tech, Inc.
 
Brooks Instrument Series GF40 Installation and Operation Manual
Brooks Instrument Series GF40 Installation and Operation ManualBrooks Instrument Series GF40 Installation and Operation Manual
Brooks Instrument Series GF40 Installation and Operation ManualFlow-Tech, Inc.
 
Solving Critical Process Applications for the Water and Wastewater Industry
Solving Critical Process Applications for the Water and Wastewater IndustrySolving Critical Process Applications for the Water and Wastewater Industry
Solving Critical Process Applications for the Water and Wastewater IndustryFlow-Tech, Inc.
 
Campus & District BTU Energy Metering
Campus & District BTU Energy MeteringCampus & District BTU Energy Metering
Campus & District BTU Energy MeteringFlow-Tech, Inc.
 
Fired Heater and Combustion eBook
Fired Heater and Combustion eBookFired Heater and Combustion eBook
Fired Heater and Combustion eBookFlow-Tech, Inc.
 
New Class of MFCs with Embedded Flow Diagnostics
New Class of MFCs with Embedded Flow DiagnosticsNew Class of MFCs with Embedded Flow Diagnostics
New Class of MFCs with Embedded Flow DiagnosticsFlow-Tech, Inc.
 
Drager PointGard 2000 Series Gas Detection System
Drager PointGard 2000 Series Gas Detection SystemDrager PointGard 2000 Series Gas Detection System
Drager PointGard 2000 Series Gas Detection SystemFlow-Tech, Inc.
 
GE Advanced Modular Calibrator for Process Measurement Instruments
GE Advanced Modular Calibrator for Process Measurement InstrumentsGE Advanced Modular Calibrator for Process Measurement Instruments
GE Advanced Modular Calibrator for Process Measurement InstrumentsFlow-Tech, Inc.
 
Thermal dispersion switch for flow, level, interface, or temperature
Thermal dispersion switch for flow, level, interface, or temperatureThermal dispersion switch for flow, level, interface, or temperature
Thermal dispersion switch for flow, level, interface, or temperatureFlow-Tech, Inc.
 
Turbine flow meters for gas service from Hoffer
Turbine flow meters for gas service from HofferTurbine flow meters for gas service from Hoffer
Turbine flow meters for gas service from HofferFlow-Tech, Inc.
 
Measuring Compressed Air Flow
Measuring Compressed Air FlowMeasuring Compressed Air Flow
Measuring Compressed Air FlowFlow-Tech, Inc.
 
Improve Process Control Security Using Annunciators as Watchers
Improve Process Control Security Using Annunciators as WatchersImprove Process Control Security Using Annunciators as Watchers
Improve Process Control Security Using Annunciators as WatchersFlow-Tech, Inc.
 
The Wafer Cone Flowmeter
The Wafer Cone FlowmeterThe Wafer Cone Flowmeter
The Wafer Cone FlowmeterFlow-Tech, Inc.
 
Reduce Unplanned Outages and Improve Profitability with Asset Condition Monit...
Reduce Unplanned Outages and Improve Profitability with Asset Condition Monit...Reduce Unplanned Outages and Improve Profitability with Asset Condition Monit...
Reduce Unplanned Outages and Improve Profitability with Asset Condition Monit...Flow-Tech, Inc.
 
List of Detectable Gasses and Vapors by CAS-Number 2015
List of Detectable Gasses and Vapors by CAS-Number 2015List of Detectable Gasses and Vapors by CAS-Number 2015
List of Detectable Gasses and Vapors by CAS-Number 2015Flow-Tech, Inc.
 
McCrometer V Cone Flowmeter Installation, Operations, Maintenace
McCrometer V Cone Flowmeter Installation, Operations, MaintenaceMcCrometer V Cone Flowmeter Installation, Operations, Maintenace
McCrometer V Cone Flowmeter Installation, Operations, MaintenaceFlow-Tech, Inc.
 
Multivariable Transmitter for Mass Flow Measurement
Multivariable Transmitter for Mass Flow MeasurementMultivariable Transmitter for Mass Flow Measurement
Multivariable Transmitter for Mass Flow MeasurementFlow-Tech, Inc.
 
Liquid Vaporizer Systems
Liquid Vaporizer SystemsLiquid Vaporizer Systems
Liquid Vaporizer SystemsFlow-Tech, Inc.
 
Arc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC DrivesArc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC DrivesFlow-Tech, Inc.
 

Mehr von Flow-Tech, Inc. (19)

Bently Nevada 3500 System Datasheet
Bently Nevada 3500 System DatasheetBently Nevada 3500 System Datasheet
Bently Nevada 3500 System Datasheet
 
Brooks Instrument Series GF40 Installation and Operation Manual
Brooks Instrument Series GF40 Installation and Operation ManualBrooks Instrument Series GF40 Installation and Operation Manual
Brooks Instrument Series GF40 Installation and Operation Manual
 
Solving Critical Process Applications for the Water and Wastewater Industry
Solving Critical Process Applications for the Water and Wastewater IndustrySolving Critical Process Applications for the Water and Wastewater Industry
Solving Critical Process Applications for the Water and Wastewater Industry
 
Campus & District BTU Energy Metering
Campus & District BTU Energy MeteringCampus & District BTU Energy Metering
Campus & District BTU Energy Metering
 
Fired Heater and Combustion eBook
Fired Heater and Combustion eBookFired Heater and Combustion eBook
Fired Heater and Combustion eBook
 
New Class of MFCs with Embedded Flow Diagnostics
New Class of MFCs with Embedded Flow DiagnosticsNew Class of MFCs with Embedded Flow Diagnostics
New Class of MFCs with Embedded Flow Diagnostics
 
Drager PointGard 2000 Series Gas Detection System
Drager PointGard 2000 Series Gas Detection SystemDrager PointGard 2000 Series Gas Detection System
Drager PointGard 2000 Series Gas Detection System
 
GE Advanced Modular Calibrator for Process Measurement Instruments
GE Advanced Modular Calibrator for Process Measurement InstrumentsGE Advanced Modular Calibrator for Process Measurement Instruments
GE Advanced Modular Calibrator for Process Measurement Instruments
 
Thermal dispersion switch for flow, level, interface, or temperature
Thermal dispersion switch for flow, level, interface, or temperatureThermal dispersion switch for flow, level, interface, or temperature
Thermal dispersion switch for flow, level, interface, or temperature
 
Turbine flow meters for gas service from Hoffer
Turbine flow meters for gas service from HofferTurbine flow meters for gas service from Hoffer
Turbine flow meters for gas service from Hoffer
 
Measuring Compressed Air Flow
Measuring Compressed Air FlowMeasuring Compressed Air Flow
Measuring Compressed Air Flow
 
Improve Process Control Security Using Annunciators as Watchers
Improve Process Control Security Using Annunciators as WatchersImprove Process Control Security Using Annunciators as Watchers
Improve Process Control Security Using Annunciators as Watchers
 
The Wafer Cone Flowmeter
The Wafer Cone FlowmeterThe Wafer Cone Flowmeter
The Wafer Cone Flowmeter
 
Reduce Unplanned Outages and Improve Profitability with Asset Condition Monit...
Reduce Unplanned Outages and Improve Profitability with Asset Condition Monit...Reduce Unplanned Outages and Improve Profitability with Asset Condition Monit...
Reduce Unplanned Outages and Improve Profitability with Asset Condition Monit...
 
List of Detectable Gasses and Vapors by CAS-Number 2015
List of Detectable Gasses and Vapors by CAS-Number 2015List of Detectable Gasses and Vapors by CAS-Number 2015
List of Detectable Gasses and Vapors by CAS-Number 2015
 
McCrometer V Cone Flowmeter Installation, Operations, Maintenace
McCrometer V Cone Flowmeter Installation, Operations, MaintenaceMcCrometer V Cone Flowmeter Installation, Operations, Maintenace
McCrometer V Cone Flowmeter Installation, Operations, Maintenace
 
Multivariable Transmitter for Mass Flow Measurement
Multivariable Transmitter for Mass Flow MeasurementMultivariable Transmitter for Mass Flow Measurement
Multivariable Transmitter for Mass Flow Measurement
 
Liquid Vaporizer Systems
Liquid Vaporizer SystemsLiquid Vaporizer Systems
Liquid Vaporizer Systems
 
Arc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC DrivesArc Flash as it Relates to AC Drives
Arc Flash as it Relates to AC Drives
 

Kürzlich hochgeladen

Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...soginsider
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaOmar Fathy
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projectssmsksolar
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VDineshKumar4165
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoordharasingh5698
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXssuser89054b
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayEpec Engineered Technologies
 

Kürzlich hochgeladen (20)

Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 

Electrical Ground Rules Part 2

  • 1. Acromag, Incorporated 30765 S Wixom Rd, Wixom, MI 48393 USA Tel: 248-295-0880 • Fax: 248-624-9234 • www.acromag.com Copyright © Acromag, Inc. April 2014 8501-020 White Paper: Electrical Ground Rules Best Practices for Grounding Your Electrical Equipment Examining our use of ground as protection, and how ground fault circuit interrupter devices operate to protect us from severe shock (Part 2 of 3)
  • 2. Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com 2 This paper is part two of a three part series that takes a look at grounding and its role in protecting personnel, protecting equipment, and ensuring the integrity of electrical signals. In this part, we will examine our use of ground as a means of protection from ground faults, and how ground fault circuit interrupter (GFCI) devices operate to protect us from severe shock. In part one of this series (8500-993) we looked at the concept of grounding, the AC power system and its use of ground, and gave three main reasons why we ground electrical equipment: for safety, to stabilize electrical signals, and to limit transient voltages and current. Part three of this series will review ground and its role as a voltage stabilizer and transient limiter. It will offer some tips on what you can do to improve your connection to ground to realize benefits to safety and signal integrity. GROUNDS AS A MEANS OF PROTECTION In Part 1 of this series, we said that one reason we connect to ground is for safety because it provides an alternative path for fault current to flow. The voltage in a circuit will force current to travel all available conductive paths back to the source. The majority of this current will follow the path of least resistance. We normally provide an earth ground connection as an alternative low-resistance path for this current flow to limit shock (as an alternative path to using your body to return current to AC neutral and earth ground). For AC powered circuits, a ground fault is any event that causes an imbalance in current flowing in the AC hot lead with current flowing in the AC neutral lead. The ground fault current refers to the difference in current flowing between AC hot and AC neutral, and it could be the current flowing in the earth ground lead or the current taking another path back to the AC source, like through a body to earth ground (because AC neutral and earth ground are tied together at the source). For AC powered devices, appliance manufacturers go to great lengths to make sure that you do not become the path of least resistance for a fault condition, which allows current to flow from AC hot back to AC neutral/earth ground via your body (Remember that AC neutral and earth ground are held in common at the source of the AC voltage). They do this by properly insulating their product and/or by providing a remote connection to earth ground at the product (via that third rounded conductor at your power outlet). That is, a conductive enclosure or housing of the device will typically connect to earth ground. Then if the AC hot or AC neutral wire to the device should fray or break, it could contact earth ground and complete the circuit, allowing the breaker to trip when its rated limit is reached, possibly preventing a fire, and hopefully without electrocuting yourself in the process. Of course, some appliances are constructed using insulating materials and do not connect their chassis to earth ground (they connect to AC using two-prong power cords). Under normal operation, the current to the device flows from between AC Hot and AC Neutral, through your load, and returns to your breaker box and utility meter power connection. The third wire, or earth ground wire, will become the return path for at least part of that current, should a fault occur at the powered device. Without this third conductor or alternate path held in reserve, your body could become the return path of least resistance to earth ground, and this could drive serious injury. Thus, for most 3-conductor AC wired equipment, its connection to earth ground is primarily to provide a safe path for current to flow in the event of a circuit fault, and normally, no current flows in the ground wire. By limiting current flow in the ground wire to only under certain conditions (ground faults), this helps to ensure that there will be no potential difference across this conductor, and it can better act like an extension of earth ground itself (i.e. nearly 0V).
  • 3. Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com 3 So what does a wired earth ground really protect you from? Does it protect you from electrocution? And what if your appliance does not include a connection to earth ground and you become the path of least resistance for some sort of ground fault? The answer to these questions is that a wired ground does not protect you from fatal shock. Rather, a GFCI can protect you from fatal shock. THE GFCI AND ITS USE OF GROUND AS A MEANS OF PROTECTION FROM GROUND FAULTS To further illustrate how earth ground works as a means of protection, let’s examine the behavior of a device that you may already be familiar with--the GFCI outlet. It looks similar to the picture at left, and usually includes a “Test” and “Reset” button. However, a GFCI protected outlet may look identical to a standard outlet if it happens to be connected downstream to the load side of a GFCI outlet. You probably have several of these in your home, perhaps in your kitchen, laundry room, basement, bathroom, garage, or at an outdoor outlet. You probably know that these outlets are used to help protect you from severe shock, and are generally required in “wet” areas, but you may not have given much thought to how this device actually works with ground to help protect you from harmful levels of shock. For example, as ground conducts current, a voltage difference will develop across it, forcing each connection to it to occur at a slightly different potential. So in practice, if all connections to ground were really made at 0V, we wouldn’t have ground faults or ground loops. And therein lies the problem with ground—your ability to mimic its idealized behavior as a reference connection to 0V really depends on how well you can minimize its effective impedance, chiefly its resistance and inductance. Generally at 50-60Hz power line frequencies, the resistive component of your connection to earth is more significant than the reactive component (inductance). At higher frequencies, the reactive component gains significance, as the inductance of your connection to ground raises its impedance to transient energy. The bottom line is that you need to minimize the effect both components have on raising ground impedance by keeping both the resistance and inductance of your connection to ground to a minimum. In addition to GFCI outlets, there are Ground Fault Circuit Interrupter (GFCI) Breakers similar to the examples shown at left. These act similar to GFCI outlets, but will protect an entire circuit from ground faults, while the GFCI outlet only protects at its outlet and any downstream outlets for daisy- chained “load” outlets. The advantage of a GFCI Breaker is that you do not need local GFCI outlets. GFCI Breakers are typically used on circuits where the likelihood of fatal shock is much higher (like a public swimming pool), and like a GFCI outlet, they can typically stop current flow within 25ms of detecting a ground fault condition on their branch circuit.
  • 4. Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com 4 As we noted in Part 1, the AC outlets in your home commonly provide 3-wires or conductors for connection to your appliance—a line hot connection (typically via a black insulated wire that connects to the shorter vertical slot of the outlet), a line neutral connection (typically via a white wire that connects to the taller vertical slot of the outlet), and a ground connection (typically via a green insulated or bare copper wire that connects to the round hole of the outlet at the top or bottom between the two vertical slots). In any circuit, current will seek all conductive paths back to its source, but most of this current will flow the path of least resistance. In your home, when you plug an appliance into an AC outlet, you give current a low-resistance path to flow through and power your appliance, and then return back via the outlet to its source. The source in this case is where your home or business connects to the power line, usually at your power meter and service entrance. Remember, although AC neutral and AC ground are separate conductors at your outlet, they do connect together at your service box and also connect to earth ground near this box, usually via one or more grounding rods driven into the earth. Load current normally flows out the line/load hot conductor, through your appliance, and returns to earth ground via the neutral conductor, and doesn’t normally flow in the ground conductor. GFCI refers to a type of power outlet called a Ground Fault Current Interrupter. The GFCI outlet will usually provide a second pair of screws for a load cable connection to allow it to connect to additional non-GFCI outlets in daisy-chain fashion, connecting them through itself to power (making it act like a GFCI breaker for downstream loads). This type of outlet can trip and quickly stop the flow of current through it and downstream from it to prevent serious injury if a Ground Fault occurs anywhere in the circuit. A Ground Fault would occur if the electricity (current) is allowed to take some other path back to the source, than neutral (including through a person’s body), as the source is where neutral and ground connect to the earth. A GFCI outlet works to protect you by measuring the amount of current flowing out the “Hot” wire circuit into the appliance, and monitoring the return current flowing out of the appliance back through the “Neutral” circuit. If the current returned in neutral does not match the current in the hot line, the GFCI will trip and interrupt the current flow out of the hot wire. Of course, the “lost” current doesn’t really go “missing”, but has temporarily found some other path back to the source, perhaps through your self to earth. This errant path is the ground fault we refer to and the GFCI feeding this circuit will trip very quickly to prevent serious shock or electrocution via current in this errant path. The figure at left depicts one example of a ground faulted circuit. It shows one phase of an AC line (like that sourced from a service panel) powering a hand drill through a GFCI outlet or breaker. The black AC hot wire to the hand drill makes contact with its metallic housing (causing a ground fault), and a workman standing on the ground and holding the drill completes a path to earth for a portion of the circuit current. Because this circuit was made through a GFCI outlet or breaker, the small leakage current triggers a relay in the black hot lead to the drill to open and stop the flow of current, protecting the workman from severe shock. It’s important to recognize that a GFCI does not protect against circuit overloads (too much load current), short circuits between hot and neutral, or minor electrical shocks. The man in the example above would still feel a small shock when he makes contact with the hand drill. And, even with a GFCI protected circuit, you can still be shocked if you touch bare wires while standing on an insulating surface, such as a
  • 5. Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com 5 wood floor, and you happen to complete the neutral current path. The GFCI only protects against current flow that does not completely follow its normal safe path along neutral to earth ground at your service panel, but uses some other errant path to reach the earth instead. The other path could be through a person’s body to earth ground, or even through the ground wire to earth (perhaps via a hot or neutral short to the grounded chassis of the load device, like in the example above). Because the GFCI outlet trips to interrupt current when it detects a ground fault (a mismatch in hot and neutral current), it also contains a reset button used to reset its trigger mechanism. This reset has a lockout feature that keeps it in reset for any of the following:  There is no power being supplied to the GFCI.  The GFCI has been miswired by reversing the line-in (source) and line-out (load) lead connections.  The GFCI fails an internal test, indicating that it may not be able to provide protection from a ground fault. The appliance that you plug into your AC outlet typically connects its other metal parts to the ground connection (any other conductive parts other than its AC hot and neutral circuits). It does this so that if its own AC Hot circuit was to break or fray and accidentally come in contact with another of its metal or conductive surfaces (like its shell or chassis), that surface would instead become a path to ground. This path to ground essentially shorts AC hot to AC ground and causes the circuit breaker or fuse to quickly overheat and open the circuit, interrupting the current flow. The normal level of current to cause a typical breaker to trip is 15A or 20A, but the amount of current that can put the human heart into fibrillation is less than 100mA. So even if a person handling that faulty appliance happened to be barefoot and standing on wet ground, a portion of that branch current would also flow through that person to ground and this could still be fatal. Generally, in a ground fault situation, the body path would provide a higher resistance path to earth than the grounded chassis and would only take a portion of this current. And just like two different resistive loads in a circuit, current is distributed along both resistive paths, but mostly along the path of least resistance. In the example of a grounded chassis, one path is through the ground wire and another through the body. But, even only a small portion of that 15A or 20A of branch current that flows just before the breaker trips is enough to stop the human heart. In the example of the hand drill, without GFCI protection, the workman may be killed. However, if the branch circuit happens to be passing through a GFCI protected outlet, the workman might still feel a momentary shock, but at a much lower current and of a shorter duration, as the GFCI will interrupt the hot current flow much more quickly than a circuit breaker alone. In fact, a GFCI protected outlet or breaker will trip if the measured difference in current between the “hot” and “neutral” conductors is as little as 4-6mA. Momentary contact with 120V at 6mA will shock you, but will not likely put your heart into fibrillation, as the GFCI typically trips within 1/30th of a second as soon as it detects a hot/neutral imbalance, a small enough duration to protect you from fatal levels of shock. Also note that for the purpose of discussion, we tend to think of and talk about AC current as flowing from the hot lead, through the device, and then returning on the neutral lead. However, AC current does not really flow in one direction or with respect to one polarity. Rather “AC” denotes Alternating Current, and alternating current actually flows back and forth through the load (alternating its polarity), 50-60 times a second.
  • 6. Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com 6 A GFCI outlet typically uses a differential or toroidal transformer to couple the line to the load, similar to the illustration at left. The current of the hot wire is magnetically coupled to the toroid and then passes to the load. The neutral wire from the load also passes through the toroid in the opposite direction and back to the service entrance of the house, where the line originates. These two wires are mutually coupled via the toroid or transformer magnetic material, such that for normal operation, the current that flows through the hot wire balances with the current that flows back through the neutral wire. But if these currents do not balance, this imbalance triggers a sensor circuit that drives relay contacts to open the Line hot circuit (black wire), interrupting its flow. Of course, the only way the hot and neutral line currents would not balance is if an external source is adding current to the circuit, or the line current is being leaked through some other external path (perhaps if line current is leaking to earth ground). A hot/neutral imbalance as small as 5mA is enough to quickly interrupt the flow of line current to the load, potentially protecting you from fatal levels of electric shock. In this way, the GFCI interrupts the flow of current much more quickly than the service entrance fuse or circuit breaker, in as quickly as one-thirtieth of a second. Do not be fooled into thinking that a fuse or breaker alone can protect you from electrical shock. Rather, it’s the purpose of a GFCI to protect you from electrical shock, while the purpose of a fuse or breaker is to protect its premises from electrical fire by limiting the maximum current and duration of excess current to a lower level, but not a low enough level to protect you from shock. Consider that there are many scenarios that could cause a hot wire to accidentally come in contact with the neutral or ground wire, causing a large amount of excess current to flow from hot to neutral. For example, an animal might chew through the wire insulation, a person might accidentally drive a nail or screw through the wire, or the cord connecting to an appliance might get chewed up after being pinched in a doorway or sucked up by a vacuum cleaner. The potential fault modes are endless and difficult to prevent. These faults will all cause excess current to flow and heat up the fuse or breaker and cause it to burn or break open, interrupting the flow of current, possibly preventing the wire from starting a fire. The problem with relying on a circuit breaker or fuse for shock protection is that they are tripped at much higher levels of current (15 or 20A typical), and after longer periods of time, both of which could be fatal if you happen to be in the path of this fault current. We started this discussion by trying to show how a GFCI outlet works with ground to protect yourself, but the reality is that a GFCI outlet would still protect you from electrical shock due to a ground fault, even without a hard-wired connection to earth ground. That is, if the GFCI happened to be wired using 2-wire AC cables (hot and neutral but no earth ground), it still provides ground fault protection. This is because a GFCI outlet monitors for current imbalances between hot and neutral, not ground. The only possible difference in a 2-wire GFCI powered application is the ground fault current along the errant path could potentially reach a higher level without the third wire ground path present, but the outlet would still detect the hot-neutral imbalance and break the hot wire connection in time to protect you from severe shock. We spent a lot of time talking about ground as a “safe” path for current, and this is because personal safety should be your number one priority, but we stated at the beginning of this paper that we have
  • 7. Tel: 248-295-0880  Fax: 248-624-1541  sales@acromag.com  www.acromag.com 7 two other important reasons for connecting to ground: to stabilize signals and to limit transient voltage and current. In Part 3 of this series, we will discuss the other two reasons we connect to ground and give some tips for improving your connection to ground to realize the benefits of increased safety and signal integrity for your wired equipment. ABOUT ACROMAG Acromag has designed and manufactured measurement and control products for more than 50 years. They are an AS9100 and ISO 9001-certified international corporation with a world headquarters near Detroit, Michigan and a global network of sales representatives and distributors. Acromag offers a complete line of industrial I/O products including a variety of process instruments, signal conditioners, and distributed fieldbus I/O modules that are available with a 2-year warranty. Industries served include chemical processing, manufacturing, defense, energy, and water services. For more information about Acromag products, call the Inside Sales Department at (248) 295-0880, FAX (248) 624-9234. E-mail sales@acromag.com or write Acromag at 30765 South Wixom Road, Wixom, MI 48393 USA. The web site is www.acromag.com. Electrical Grounding Rules Part 1 is available for download: www.acromag.com/page/white-paper-electrical-ground-rules