THEULTIMATESTABILISINGTARGETElectrodynamicvoltagestabilisers
Sterostab
Sterostab
THEULTIMATESTABILISINGTARGETElectrodynamicvoltagestabilisers
MinistabandSterostab.Theultimatestabilisingtarget
The wider use of equipment with non linear absorption
such as rectifiers, speed variators, drives, switching
power supplies, has caused, besides traditional and well
known voltage fluctuations, the spreading of a new
insidious type of electrical fault: harmonic distortion.
This fault “deceives” traditional stabilising systems that,
in its presence, read wrong input voltage values. As a
consequence a voltage is delivered with an efficient value
that differs from the rated one, becoming greater as the
harmonic distortion of the mains increases.
Ministab and Sterostab stabilisaers are IREM’s
technological and innovative answer to this problem,
permitting to supply electric users with a voltage
stabilised to the rated value they have been designed for
even in presence of strong harmonic distortions.
IRPower supply interferences
and failures
MinistabMinistabFailures on the distribution lines, atmospheric discharges,
continual load variations and disturbances generated by the
users make it impossible to guarantee always a steady voltage
within the tolerance bandwidth stipulated in the supply
contract with the electric energy producer.
Very often the tolerance is insufficient for more sensitive
facilities. Other times the mains voltage reaches levels
that exceed theforeseen rated value by 15, 20 or even
25%.
The voltage fluctuations are particularly treacherous
interferences since they are not seen and can only
be detected by using specific equipment. When such
interferences are present, the electrical equipment seems
to maintain correct operation but disguises serious
problems that at times are beyond repair. Even an
ordinary light bulb, if overpowered by 10%, continues to
give light, but halves its operating life.
The situation becomes much more serious in the case of
voltage variations on more complicated equipment.
• a computer may become damaged or make unexpected
errors;
• a laser cutting machine
undergoes changes in the
“laserbeam mode”, resulting
in cutting burrs or the
shutting off of the beam;
• a transmitter gives
signal distortion and its
components age more
quickly;
• an electric drive causes
undesired changes in the
speed of the powered motor
and damage to the data
storage and power terminals;
• an “electromedical” device
gives incorrect results,
wastes expensive reagents
and loses the samples to be
analysed.
a las
under
“laser
in cutt
shuttin
• a tra
signal
compo
quickl
• an e
undes
speed
and da
storag
• an “e
gives i
waste
and lo
analys
Applications
Sterostab
Sterostab
Ministab and Sterostab are registered names of two
series of electrodynamic voltage stabilisers that offer a
reliable and tested economic solution to inconveniences
caused by voltage fluctuation. To use Ministab and
Sterostab is a real investment because the elimination
of the inconveniences means a reduction in costs and an
increase in productivity. Very often it is only necessary to
avoid a few minutes machine downtime or just one failure
to repay the cost of the stabilisers. Ministab and Sterostab
are particularly suitable for applications that require:
• high reliability. For example they can be installed
in areas with difficult access, subject to critical
environment conditions due to cold, high temperatures,
humidity, atmospheric discharges.
• capability to compensate wide mains voltage variations
(both symmetrical up to ±25%, and asymmetrical from
-35% to +15%).
This is a typical requirement of equipment installed in
areas that are far from the distribution cabin and in fast
developing countries.
• high precision of the stabilised voltage. Ideal condition
for calibration and inspection stands, electric furnaces,
professional lighting systems.
• stabilising of high power services or with a strong inrush
current, such as: motors, air conditioners, compressors,
pumps.
• simple and limited maintenance.
Most important where it is difficult to find
qualified personnel for servicing.
professio
• stabilising
current, s
pum
MinistabMinistab
Ministab and Sterostab regulate through a series
transformer. A static control circuit drives the variable
autotransformer that supplies the required voltage to the
series transformer either in phase or phase opposition
to bring the mains to the rated value. The three-phase
stabilisers are available in two versions:
• T models which regulate on the average of the three
phases and are therefore suitable for balanced lines or
for a maximum load unbalance between the phases up
to 50%.
• Y models that, having three separate control circuits,
individually regulate each phase and are therefore
suitable for unbalanced lines and load unbalance
between phases up to 100%.
Operating principles
SINGLE-PHASE STABILISERS M
THREE-PHASE STABILISERS T
THREE-PHASE STABILISERS Y
T = series transformer
R = variable autotransformer
C = electronic control circuit
M = servomotor
Y
X
Z
T
RR2R3
T3
T2
R
S
T
C
M
R
S
T
R
C
Y
X
M
MMM
X
Y
Z
N
R
T
T 2
R
S
T
N
T3
R3 R2
C2C3
INPUT
INPUTINPUT
STABILISED
OUTPUT
STABILISED
OUTPUT
STABILISED
OUTPUT
C
General features
Accuracy
Ministab and Sterostab ensure the “true RMS value” of
the voltage with an accuracy range that varies according
to the model from ±0.5% to ±1.5%, even where strong
harmonic distortions are present on the line.
Fast response
The advanced electronic control circuit ensures a fast
response, from 11 to 50 ms/Volt according to the model.
A controlled deceleration minimises overshoots.
Overload capacity
A typical characteristic of the Ministab and Sterostab
regulation system. In fact, they can support without
damage overloads up to 10 times the rated current for
10 milliseconds, 5 times for 6 seconds and 2 times for 1
minute.
Efficiency
At full load the range is from 96% for small models to
98% for the larger units.
Unaffected by power factor and load
variations
The Ministab and Sterostab operating principle
ensures that the equipment accuracy and regulation
speed characteristics remain unaltered under any load
conditions, with inductive or capacitive loads.
Sterostab
Sterostab
Range
IREM voltage regulators are available in power rating from
1 kVA to 3300 kVA. Models up to 100 kVA can usually
be delivered ex stock. Upon request we can supply
stabilisers with the following characteristics:
• single-phase voltages: 100-110-115-120-127-200-220-
230-240-265-277 Volt. three-phase voltages: 208-220-
230-240-380-400-415-440-460-480-500 Volt
• Frequency: 50 or 60 Hz.
• Indoor versions (IP20, IP21, IP31, IP54), outdoor
versions (IP44, IP54), and open frame versions IP00.
• Special versions fitted with: ammeter, frequency meter,
multi-function meter, input or output circuit breaker
(with or without earth leakage), manual or automatic
by-pass, isolating transformer, surge arresters (lightning
protection), over/under voltage protection, thermal
relay, soft start, reversed phase sequence and phase
failure protection. Tropicalized versions.
MinistabMinistab
Unaffected by frequency variations
The servomotor control circuit operates correctly with
mains frequency variations up to ±5%.
Negligible waveform distortion
The high quality materials and their correct use ensure
that harmonic distortion is always less than 0.2% under
any working conditions.
Low intemal impedance
Installation of Ministab and Sterostab in already existing
systems does not require new calculations for protections
since their internal impedance varying from 0.52 to 0.015
ohm does not significantly affect the line impedance.
Operating temperature
Ministab and Sterostab have been designed to operate
correctly with a maximum environment temperature of
40°C under the worst conditions: continuous operation,
full load, minimum input voltage value.
Reliability
The continual improvements that the Ministab and
Sterostab have undergone in over 50 years of activity
during which IREM has manufactured over 230,000
stabilisers have obtained an exceptional MTBF for these
devices.
Conformity to standards
Ministab and Sterostab conform to the
requirements of the following standards: Electro
Magnetic Compatibility 89/336/EEC and following
amendments; Low Voltage Electrical Equipment
73/23/EEC and following amendments.
devices
C
M
r
M
a
7
L
I
s
s
o
O
M
c
4
f
IREM SpA - Via Abegg 75 - 10050 Borgone - Torino - ITALY
Tel. ++39 011 9648211 - Fax ++39 011 9648222
e-mail: irem@irem.it - www.irem.it
99533932.06
IREM is a leading company in the manufacture of electromechanical and electronic
equipment for the control of the mains power in the following sectors:
- powering of discharge lamps for professional applications;
- protection of electric users against line disturbances;
- luminous flux regulation in lighting plants;
- power generation by micro hydroelectric plants.
Since its foundation in 1947, IREM has gained wide recognition due to the reliability
and innovative content of its higt-tech products. A reliable company
deserving the Oscar-Award. In 1992, in Los Angeles,
Mario Celso - founder of IREM - was granted the
“Scientific-Technical Award” by the Academy of Motion Picture
Arts and Sciences.
Two production plants, a philosophy based on “quality upgranding”
as the company’s primary concern and direct export exceeding 50%
of the global turnover are a warranty of continuity and development.
Experience, quality and professional skill: these are the factors that
permitted IREM to achieve in 1993 the certification of its quality
system in compliance with UNI EN ISO 9001 standard, a further
confirmation of IREM commitment to constantim provement to
ensure the maximum satisfaction of the customer and its capacity to
guarantee:
• a constant quality standard
• precision and repeatability of all working processes
• dropping of acceptance control at the customer’s plant
• identification and traceability of a product through the years.
In year 2000, IREM obtained the certification of its environment management system
according to UNI EN ISO 14001 standard.This certification is a firm demonstration
of the company’s will to protect the environment not just through its products, but
also via precise patterns of behaviour.
IREM.ExperienceandQuality
www.think-adv.com
A
T
a
o
Ex
pe
sy
co
en

Weitere ähnliche Inhalte

Was ist angesagt?

Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Sourabh Ghosh
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
Partha Parida
 
Power quality harmonics and accuracy april 2013
Power quality harmonics and accuracy   april 2013Power quality harmonics and accuracy   april 2013
Power quality harmonics and accuracy april 2013
Hyteps B.V.
 
Design of a 400kv Transmission network
Design of a 400kv Transmission networkDesign of a 400kv Transmission network
Design of a 400kv Transmission network
Isaac Muyinza
 
FFC-MM Plantsite Power System Protection
FFC-MM Plantsite Power System ProtectionFFC-MM Plantsite Power System Protection
FFC-MM Plantsite Power System Protection
farazrafi87
 
Power Quality Issues _Literature Survey
Power Quality Issues _Literature SurveyPower Quality Issues _Literature Survey
Power Quality Issues _Literature Survey
Ketan Bhavsar
 

Was ist angesagt? (19)

Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.BhideFundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
Fundamentals of Power System protection by Y.G.Paithankar and S.R.Bhide
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Power quality harmonics and accuracy april 2013
Power quality harmonics and accuracy   april 2013Power quality harmonics and accuracy   april 2013
Power quality harmonics and accuracy april 2013
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
ppt on gss
ppt on gssppt on gss
ppt on gss
 
Design of a 400kv Transmission network
Design of a 400kv Transmission networkDesign of a 400kv Transmission network
Design of a 400kv Transmission network
 
General: Power Quality Presentation
General: Power Quality PresentationGeneral: Power Quality Presentation
General: Power Quality Presentation
 
MEDIUM VOLTAGE SWITCHGEAR
MEDIUM VOLTAGE SWITCHGEARMEDIUM VOLTAGE SWITCHGEAR
MEDIUM VOLTAGE SWITCHGEAR
 
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
 VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER... VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
VOLTAGE SAG AND SWELL ALLEVIATION IN DISTRIBUTION NETWORK USING CUSTOM POWER...
 
Power System Faults and Protection System
Power System Faults and Protection SystemPower System Faults and Protection System
Power System Faults and Protection System
 
FFC-MM Plantsite Power System Protection
FFC-MM Plantsite Power System ProtectionFFC-MM Plantsite Power System Protection
FFC-MM Plantsite Power System Protection
 
Power System Protection Technique: A Review
Power System Protection Technique: A ReviewPower System Protection Technique: A Review
Power System Protection Technique: A Review
 
Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
 
Differential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in SubstationDifferential Protection of Power Transformer in Substation
Differential Protection of Power Transformer in Substation
 
Power Quality Issues _Literature Survey
Power Quality Issues _Literature SurveyPower Quality Issues _Literature Survey
Power Quality Issues _Literature Survey
 
Switchyard design overview
Switchyard design overviewSwitchyard design overview
Switchyard design overview
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 

Andere mochten auch (15)

COPIA Y CERTIFICACION DE TITULO MARIA V. TABAR
COPIA Y CERTIFICACION DE TITULO MARIA V. TABARCOPIA Y CERTIFICACION DE TITULO MARIA V. TABAR
COPIA Y CERTIFICACION DE TITULO MARIA V. TABAR
 
Evaluation task 1 music video
Evaluation task 1   music videoEvaluation task 1   music video
Evaluation task 1 music video
 
G-Net-catalogue
G-Net-catalogueG-Net-catalogue
G-Net-catalogue
 
Fundamentos de Economia
Fundamentos de EconomiaFundamentos de Economia
Fundamentos de Economia
 
Propuesta pedagogica .modulo 3
Propuesta pedagogica .modulo 3Propuesta pedagogica .modulo 3
Propuesta pedagogica .modulo 3
 
акция открытого чтения. "Прочитай Рубцова"
акция открытого чтения. "Прочитай Рубцова"акция открытого чтения. "Прочитай Рубцова"
акция открытого чтения. "Прочитай Рубцова"
 
Abdul WORD CV completed
Abdul WORD CV completedAbdul WORD CV completed
Abdul WORD CV completed
 
ADT - Mesa
ADT - MesaADT - Mesa
ADT - Mesa
 
Shoop forms & conventions
Shoop forms & conventionsShoop forms & conventions
Shoop forms & conventions
 
éMil durkheim
éMil durkheiméMil durkheim
éMil durkheim
 
2014-AR-Foundation
2014-AR-Foundation2014-AR-Foundation
2014-AR-Foundation
 
Flash & Web Standards: Getting Along on the Playground
Flash & Web Standards: Getting Along on the PlaygroundFlash & Web Standards: Getting Along on the Playground
Flash & Web Standards: Getting Along on the Playground
 
на конкурс
на конкурсна конкурс
на конкурс
 
Talento 3.0. Biografías-2016
Talento 3.0. Biografías-2016Talento 3.0. Biografías-2016
Talento 3.0. Biografías-2016
 
Rehiyon III- Gitnang Luzon
Rehiyon III- Gitnang LuzonRehiyon III- Gitnang Luzon
Rehiyon III- Gitnang Luzon
 

Ähnlich wie Ministab Sterostab

powersystemprotectiondevices-161120193617 (1).pdf
powersystemprotectiondevices-161120193617 (1).pdfpowersystemprotectiondevices-161120193617 (1).pdf
powersystemprotectiondevices-161120193617 (1).pdf
MonalPandey1
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power System
vkmalik
 
Product technical brief
Product technical briefProduct technical brief
Product technical brief
Amol Chande
 

Ähnlich wie Ministab Sterostab (20)

ELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEFELECTRIC SUB-STATION IN BRIEF
ELECTRIC SUB-STATION IN BRIEF
 
powersystemprotectiondevices-161120193617 (1).pdf
powersystemprotectiondevices-161120193617 (1).pdfpowersystemprotectiondevices-161120193617 (1).pdf
powersystemprotectiondevices-161120193617 (1).pdf
 
Power system protection devices
Power system protection devicesPower system protection devices
Power system protection devices
 
Madan mohan malaviya
Madan mohan malaviyaMadan mohan malaviya
Madan mohan malaviya
 
UNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEMUNSYMMETRICAL FAULTS IN POWER SYSTEM
UNSYMMETRICAL FAULTS IN POWER SYSTEM
 
ABB Relay
ABB RelayABB Relay
ABB Relay
 
Wind Turbine programme
Wind Turbine programmeWind Turbine programme
Wind Turbine programme
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power System
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protection
 
63-pq.ppt
63-pq.ppt63-pq.ppt
63-pq.ppt
 
63-pq.ppt
63-pq.ppt63-pq.ppt
63-pq.ppt
 
1660034363151685.pptx
1660034363151685.pptx1660034363151685.pptx
1660034363151685.pptx
 
Product technical brief
Product technical briefProduct technical brief
Product technical brief
 
Power quality
Power qualityPower quality
Power quality
 
SICAM FPI - Fault Passage Indicator
SICAM FPI - Fault Passage IndicatorSICAM FPI - Fault Passage Indicator
SICAM FPI - Fault Passage Indicator
 
Switchgear and protection lecture 1
Switchgear and protection lecture 1Switchgear and protection lecture 1
Switchgear and protection lecture 1
 
Novatek Electro (India) Pvt. Ltd., Delhi, Microcontroller Based Devices
Novatek Electro (India) Pvt. Ltd., Delhi, Microcontroller Based Devices Novatek Electro (India) Pvt. Ltd., Delhi, Microcontroller Based Devices
Novatek Electro (India) Pvt. Ltd., Delhi, Microcontroller Based Devices
 
Cl novatek
Cl novatekCl novatek
Cl novatek
 
havells ppt
havells ppthavells ppt
havells ppt
 
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
220 kV GSS Mansarovar Jaipur (RVPNL) Training PPT SM54
 

Mehr von Bernadette Polintan

Mehr von Bernadette Polintan (12)

lm-opzs-emea-sa-asia-110412_english
lm-opzs-emea-sa-asia-110412_englishlm-opzs-emea-sa-asia-110412_english
lm-opzs-emea-sa-asia-110412_english
 
smg-12v-blocs-asia-131115_english
smg-12v-blocs-asia-131115_englishsmg-12v-blocs-asia-131115_english
smg-12v-blocs-asia-131115_english
 
Sunlight Traction Battery
Sunlight Traction BatterySunlight Traction Battery
Sunlight Traction Battery
 
smg-opzv-asia-131115_english-1-
smg-opzv-asia-131115_english-1-smg-opzv-asia-131115_english-1-
smg-opzv-asia-131115_english-1-
 
uPSSP-1009
uPSSP-1009uPSSP-1009
uPSSP-1009
 
Invertronic 110V englisch
Invertronic 110V englischInvertronic 110V englisch
Invertronic 110V englisch
 
lm-opzs-emea-sa-asia-110412_english
lm-opzs-emea-sa-asia-110412_englishlm-opzs-emea-sa-asia-110412_english
lm-opzs-emea-sa-asia-110412_english
 
HYBRID INDUSTRIAL BATTERY CHARGER
HYBRID INDUSTRIAL BATTERY CHARGERHYBRID INDUSTRIAL BATTERY CHARGER
HYBRID INDUSTRIAL BATTERY CHARGER
 
10027042_USV_Argument_gb
10027042_USV_Argument_gb10027042_USV_Argument_gb
10027042_USV_Argument_gb
 
784481_GLR_Indust_modu_gb
784481_GLR_Indust_modu_gb784481_GLR_Indust_modu_gb
784481_GLR_Indust_modu_gb
 
784323_Tebevert_dsp_gb
784323_Tebevert_dsp_gb784323_Tebevert_dsp_gb
784323_Tebevert_dsp_gb
 
GTI Product Presentation (Updated)
GTI Product Presentation (Updated)GTI Product Presentation (Updated)
GTI Product Presentation (Updated)
 

Ministab Sterostab

  • 2. Sterostab Sterostab THEULTIMATESTABILISINGTARGETElectrodynamicvoltagestabilisers MinistabandSterostab.Theultimatestabilisingtarget The wider use of equipment with non linear absorption such as rectifiers, speed variators, drives, switching power supplies, has caused, besides traditional and well known voltage fluctuations, the spreading of a new insidious type of electrical fault: harmonic distortion. This fault “deceives” traditional stabilising systems that, in its presence, read wrong input voltage values. As a consequence a voltage is delivered with an efficient value that differs from the rated one, becoming greater as the harmonic distortion of the mains increases. Ministab and Sterostab stabilisaers are IREM’s technological and innovative answer to this problem, permitting to supply electric users with a voltage stabilised to the rated value they have been designed for even in presence of strong harmonic distortions.
  • 3. IRPower supply interferences and failures MinistabMinistabFailures on the distribution lines, atmospheric discharges, continual load variations and disturbances generated by the users make it impossible to guarantee always a steady voltage within the tolerance bandwidth stipulated in the supply contract with the electric energy producer. Very often the tolerance is insufficient for more sensitive facilities. Other times the mains voltage reaches levels that exceed theforeseen rated value by 15, 20 or even 25%. The voltage fluctuations are particularly treacherous interferences since they are not seen and can only be detected by using specific equipment. When such interferences are present, the electrical equipment seems to maintain correct operation but disguises serious problems that at times are beyond repair. Even an ordinary light bulb, if overpowered by 10%, continues to give light, but halves its operating life. The situation becomes much more serious in the case of voltage variations on more complicated equipment. • a computer may become damaged or make unexpected errors; • a laser cutting machine undergoes changes in the “laserbeam mode”, resulting in cutting burrs or the shutting off of the beam; • a transmitter gives signal distortion and its components age more quickly; • an electric drive causes undesired changes in the speed of the powered motor and damage to the data storage and power terminals; • an “electromedical” device gives incorrect results, wastes expensive reagents and loses the samples to be analysed. a las under “laser in cutt shuttin • a tra signal compo quickl • an e undes speed and da storag • an “e gives i waste and lo analys
  • 4. Applications Sterostab Sterostab Ministab and Sterostab are registered names of two series of electrodynamic voltage stabilisers that offer a reliable and tested economic solution to inconveniences caused by voltage fluctuation. To use Ministab and Sterostab is a real investment because the elimination of the inconveniences means a reduction in costs and an increase in productivity. Very often it is only necessary to avoid a few minutes machine downtime or just one failure to repay the cost of the stabilisers. Ministab and Sterostab are particularly suitable for applications that require: • high reliability. For example they can be installed in areas with difficult access, subject to critical environment conditions due to cold, high temperatures, humidity, atmospheric discharges. • capability to compensate wide mains voltage variations (both symmetrical up to ±25%, and asymmetrical from -35% to +15%). This is a typical requirement of equipment installed in areas that are far from the distribution cabin and in fast developing countries. • high precision of the stabilised voltage. Ideal condition for calibration and inspection stands, electric furnaces, professional lighting systems. • stabilising of high power services or with a strong inrush current, such as: motors, air conditioners, compressors, pumps. • simple and limited maintenance. Most important where it is difficult to find qualified personnel for servicing. professio • stabilising current, s pum
  • 5. MinistabMinistab Ministab and Sterostab regulate through a series transformer. A static control circuit drives the variable autotransformer that supplies the required voltage to the series transformer either in phase or phase opposition to bring the mains to the rated value. The three-phase stabilisers are available in two versions: • T models which regulate on the average of the three phases and are therefore suitable for balanced lines or for a maximum load unbalance between the phases up to 50%. • Y models that, having three separate control circuits, individually regulate each phase and are therefore suitable for unbalanced lines and load unbalance between phases up to 100%. Operating principles SINGLE-PHASE STABILISERS M THREE-PHASE STABILISERS T THREE-PHASE STABILISERS Y T = series transformer R = variable autotransformer C = electronic control circuit M = servomotor Y X Z T RR2R3 T3 T2 R S T C M R S T R C Y X M MMM X Y Z N R T T 2 R S T N T3 R3 R2 C2C3 INPUT INPUTINPUT STABILISED OUTPUT STABILISED OUTPUT STABILISED OUTPUT C
  • 6. General features Accuracy Ministab and Sterostab ensure the “true RMS value” of the voltage with an accuracy range that varies according to the model from ±0.5% to ±1.5%, even where strong harmonic distortions are present on the line. Fast response The advanced electronic control circuit ensures a fast response, from 11 to 50 ms/Volt according to the model. A controlled deceleration minimises overshoots. Overload capacity A typical characteristic of the Ministab and Sterostab regulation system. In fact, they can support without damage overloads up to 10 times the rated current for 10 milliseconds, 5 times for 6 seconds and 2 times for 1 minute. Efficiency At full load the range is from 96% for small models to 98% for the larger units. Unaffected by power factor and load variations The Ministab and Sterostab operating principle ensures that the equipment accuracy and regulation speed characteristics remain unaltered under any load conditions, with inductive or capacitive loads. Sterostab Sterostab Range IREM voltage regulators are available in power rating from 1 kVA to 3300 kVA. Models up to 100 kVA can usually be delivered ex stock. Upon request we can supply stabilisers with the following characteristics: • single-phase voltages: 100-110-115-120-127-200-220- 230-240-265-277 Volt. three-phase voltages: 208-220- 230-240-380-400-415-440-460-480-500 Volt • Frequency: 50 or 60 Hz. • Indoor versions (IP20, IP21, IP31, IP54), outdoor versions (IP44, IP54), and open frame versions IP00. • Special versions fitted with: ammeter, frequency meter, multi-function meter, input or output circuit breaker (with or without earth leakage), manual or automatic by-pass, isolating transformer, surge arresters (lightning protection), over/under voltage protection, thermal relay, soft start, reversed phase sequence and phase failure protection. Tropicalized versions.
  • 7. MinistabMinistab Unaffected by frequency variations The servomotor control circuit operates correctly with mains frequency variations up to ±5%. Negligible waveform distortion The high quality materials and their correct use ensure that harmonic distortion is always less than 0.2% under any working conditions. Low intemal impedance Installation of Ministab and Sterostab in already existing systems does not require new calculations for protections since their internal impedance varying from 0.52 to 0.015 ohm does not significantly affect the line impedance. Operating temperature Ministab and Sterostab have been designed to operate correctly with a maximum environment temperature of 40°C under the worst conditions: continuous operation, full load, minimum input voltage value. Reliability The continual improvements that the Ministab and Sterostab have undergone in over 50 years of activity during which IREM has manufactured over 230,000 stabilisers have obtained an exceptional MTBF for these devices. Conformity to standards Ministab and Sterostab conform to the requirements of the following standards: Electro Magnetic Compatibility 89/336/EEC and following amendments; Low Voltage Electrical Equipment 73/23/EEC and following amendments. devices C M r M a 7 L I s s o O M c 4 f
  • 8. IREM SpA - Via Abegg 75 - 10050 Borgone - Torino - ITALY Tel. ++39 011 9648211 - Fax ++39 011 9648222 e-mail: irem@irem.it - www.irem.it 99533932.06 IREM is a leading company in the manufacture of electromechanical and electronic equipment for the control of the mains power in the following sectors: - powering of discharge lamps for professional applications; - protection of electric users against line disturbances; - luminous flux regulation in lighting plants; - power generation by micro hydroelectric plants. Since its foundation in 1947, IREM has gained wide recognition due to the reliability and innovative content of its higt-tech products. A reliable company deserving the Oscar-Award. In 1992, in Los Angeles, Mario Celso - founder of IREM - was granted the “Scientific-Technical Award” by the Academy of Motion Picture Arts and Sciences. Two production plants, a philosophy based on “quality upgranding” as the company’s primary concern and direct export exceeding 50% of the global turnover are a warranty of continuity and development. Experience, quality and professional skill: these are the factors that permitted IREM to achieve in 1993 the certification of its quality system in compliance with UNI EN ISO 9001 standard, a further confirmation of IREM commitment to constantim provement to ensure the maximum satisfaction of the customer and its capacity to guarantee: • a constant quality standard • precision and repeatability of all working processes • dropping of acceptance control at the customer’s plant • identification and traceability of a product through the years. In year 2000, IREM obtained the certification of its environment management system according to UNI EN ISO 14001 standard.This certification is a firm demonstration of the company’s will to protect the environment not just through its products, but also via precise patterns of behaviour. IREM.ExperienceandQuality www.think-adv.com A T a o Ex pe sy co en