Building Integrated Photo Voltaic (BIPV) for multi-storied commercial buildings- how to perform QA/QC of the project has been described briefly in the slides.
5. WHY BIPV?
• LOWER COST
• IMPROVED ASTHETICS
• WIDER DISTRIBUTION
APPLICATION OF BIPV
• ROOFINGS
• SKYLIGHTS-CANOPIES
• CURTAIN WALLS- VERTICAL GLASS
• c-Si PV CELL COLORS
• DIFFERENT TYPES OF BIPV APPLICATIONS
6.
7. COMPONENTS OF BIPV ELECTRIC SYSTEMS
BIPV PANELS
SOLAR INVERTERS
SOLAR CABLES + CONNECTORS
MOUNTING RACKS
DISTRIBUTION PANEL
8. DESIGN CONSIDERATIONS
ROOF AREA AVAILABLE VISION GLASS APPLICATION
SPANDREL AREA INSTALLATION
TYPE OF PV CELLS & PANELS (SIZE, COLOR & SPACING)
TYPE & SPECIFICATION OF PCU (POWER CONDITIONING UNIT)
CABLES & CONNECTORS TYPE
ORIENTATION & ELEVATION
ANTICIPATED ENERGY PRODUCTION
9. CURTAIN WALL CONSIDERATIONS
ACCOMMODATE GLASS WITH END CONNECTORS
INCORPORATE WIRES & JUNCTION BOXES
COMPLY WITH BUILDNG CODES, IEC, IS & UL
GASKET & SEALANT COMPATIBILITY
AIR, WATER & THERMAL PERFORMANCE
ALLOW FOR FUTURE ACCESS TO WIRING
10. QUALITY CHECKING & DESIGN CONSIDERATION OF
BIPV CELLS & PANELS
Pv Cell Technology Has To Be Of 3rd Generation Based
Cell Efficiency Has To Be Greater Than 17%
Module Efficiency Must Be Greater Than 14%
NOCT Should Lie Between 56 to 62 C
Power Temperature Co-efficient Not More Than -0.47%/ C
At Irradiation 600w/sq.m/Day And At 25 C , Module’s Output Need To Be 55% Or
More Of It’s Rated Peak Power.
BIPV Modules Must Comply With IEC-61215 & IEC-61646
0
0
0
11.
12. DESIGN CONSIDERATION FOR
SOLAR INVERTERS
Micro Or String Type Inverters Can Be Used In Such Applications
Must Have 1 MPPT Per Inverter
Conversion Efficiency Has To Be Greater Than 95%
Should Operate At Unity P.F
Total Harmonic Distortion Should Be Less Than 2%
Must Comply With Anti-islanding Protection
Self Consumption Should Be Less Than 2%
Transformer less Topology Is Preferable
Grounding Arrangement Has To Be Included
Must Have A Surge Protection Device
Product Warranty Should Be At least 15 Years
Remote Monitoring & Data Acquisition Facility Is Preferable
Inverter Must Comply With UL-1741/ IEEE-1547
13. DESIGN CONSIDERATION FOR SOLAR CABLES
MUST WITHSTAND 120 C TEMPERATURE
RATED VOLTAGE HAS TO BE 0.9/1.8 KV DC
INSULATING MATERIAL SHOULD BE HALOGEN FREE CROSS-LINKED COMPUND
PRODUCT MUST COMPLY WITH IS-8130
0
14.
15. PV ARRAY TILT & ORIENTATION
TILT
TILT DEPENDS ON THE
LOCATION LATITUDES
e.g FOR DELHI, THE TILT
ANGLE WILL BE 28 (FIXED)
WHERE AS FOR KOLKATA
IT’LL BE 23
INSTALLATION OF BIPV
SHOULD BE DONE IN A WAY
TO OPTIMIZE THE TILT ANGLE
0
0
ORIENTATION
DEPENDS ON THE LOCATION’S
AZIMUTH
FOR INSTANCE, A SPV SYSTEM
AT DELHI SHOULD BE FACING
DIRECTLY TO SOUTH