METAL ENCLOSED BUSDUCT
Metal enclosed busduct is an assembly of busbars with
associated connections, joints and insulator supports within
an earthed metal enclosure.
• Non-Segregated
• Phase Segregated
• Isolated Phase
Definition
Classification
• Connection between Generator and Generator
Transformer;
• Connection between Transformer and Switchgear;
• Connection between one Switchgear to another
Switchgear.
• Economical point of view: When the current rating
required is high and length is short.
Application
• Air is the only insulating medium between three
phases.
• Recommended up-to 660V systems with current
ratings up-to 4000A.
• Specifically use for connection between secondary side
of distribution transformer and LV switchgear.
Non-Segregated Phase Busduct
6.6kV, 2000A , 40KA for 3 Sec
6.6/0.433kV
2500 KVA
6.6/0.433kV
2500 KVA
415V, 4000A, 50KA for 1 Sec
NSPB
• Insulated phase barriers are provided;
• On high voltage systems up-to 6.6kV with current
ratings up-to 4000A.
• Specifically use for connection between secondary side
of Power / distribution transformer and MV
switchgear, tie between MV switchgear.
Phase-Segregated Busduct
• Separate enclosure for each;
• On systems 11kV and higher with current ratings over
4000A.
• Specially for generator leads (current>400A), IPBDs are
recommended.
Isolated Phase Busduct
IPBD
Continuous Non-Continuous
• Up-to 8000A rating may be left to the manufacturers of
busduct & the selection based on availability,
optimisation of capital cost & loss evaluation.
• Current rating over 8000A, only continuous type is
recommended to minimise the inductive heating of
supporting structures etc. & associated losses.
Typical arrangement of continuous type of Isolated Phase Bus Duct
Typical discontinuous type of Isolated Phase Bus Duct
6.6kV SWGR
ST-3
40/25/25 MVA
220/6.9/6.9kV
220kV Switchyard
R
SB-3A SB-3BUB-3A
220kV Switchyard
UB-3B
R
RR
UT-3
40/25/25 MVA
16.5/6.9/6.9kV
R
Generator
250 MW
16.5kV
GT-3
315 MVA
235/16.5kV
IPBD
SPBD
TO EXCT
TRAFO
Voltage class of the Busduct may be selected from one of the following
standard ratings and shall be at least equal to the maximum voltage
rating of the associated equipment:
0.66, 3.6, 7.2, 12, 24 and 36kV
Voltage Rating of the Busduct
Rated r.m.s. continuous current carrying capacity shall be at least equal
to the maximum current capability of the associated equipment (Which
may be higher than nominal rated current) rounded off to the nearest
higher standard current rating of the busduct.
Preferred standard current ratings are 100, 250, 400, 630, 800, 1250,
1600, 2000, 3150, 4000, 5000, 6300, 8000, 10000, 12500 and 15000A.
Continuous Current Rating
Rated r.m.s. short time current ratings of the busbar shall correspond to
the fault level of the system. The time shall take into consideration the
operating time of backup protective devices on the incoming side but
the duration shall not be less than 1 sec.
Momentary peak current rating shall be 2.55 times the short time r.m.s.
current rating of the busduct.
Short time Current Rating
Voltage The temperature rise of the conductor shall be as per IS-8084.
Also the temperature of the busduct shall not exceed 2500C while
carrying the specified short circuit current for 1 sec when fault occurs, at
the operating temperature.
Temperature rise
Busbar support insulators are enclosed, the creepage distances & height
of insulators shall be the highest feasible and shall not be less than those
for heavily polluted atmosphere as per IS:2544 & IS:5350 (Part-I)
respectively to allow for dust accumulation and moisture condensation
which can occur. Station/Post type insulator shall be used for supporting
buses in metal enclosed busduct.
Bus support Insulator
Flexible connections such as braided or laminated flexible joints for
conductors and rubber bellows for enclosures shall be used for
termination of busuct at the terminal of generator, transformer,
switchgear etc. and similar flexible connections for conductors and
metallic or rubber bellows with metallic shorting for enclosures shall be
used in the run of the busuct such that they allow for vibrations &
thermal expansion and do not impose any stress on terminal and
bushings.
Terminations
Busduct shall be normally natural cooled (AN). Forced cooling may be
considered beyond 10000A rating as per IS:8084.
Cooling
.
Material for Bus and Enclosure
• Bus bar shall be either of copper or aluminium
conductor.
• Copper conductor shall be of hard drawn (HD), high
conductivity conforming to IS:613.
• Aluminium conductors shall be of aluminium alloy
grade 63401WP conforming to IS:5082.
• Material of enclosure for segregated & non-segregated
type busduct shall be mild steel or aluminium.
• If the location where the busduct (Where mild steel
are used for enclosure ) is to be installed is having
corrosive atmosphere, it shall be galvanised after
fabrication or it shall be painted preferably with epoxy
based paint.
• For isolated phase type of busduct, the enclosure
material shall be of aluminium alloy grade 63401WP
conforming to IS:5082.
• Aluminium is cheaper to use than copper.
• Aluminium has les than one-third the density of
copper. Weight of aluminium bus bar only half as much
as copper bar of equal current capacity. The light
weight of aluminium is of advantage in other ways too:
for instance, it allows easier handling, transportation &
erection.
• Outstanding resistance to corrosion, thus permitting its
widespread use in electro-chemical & electroplating
process where the atmosphere is highly corrosive.
Popularity of Aluminium Busduct over copper busduct:
• “Self-stifling” property.
• Nevertheless, Aluminium is the cheapest Non-
magnetic metal. Hence suitable material for enclosure
also.
Busduct- Electrical Parameter
TABLE-III
BUSDUCTSUPPORTING INSULATOR & SEAL OFF BUSHING
(BASED ON IS:2544 & IS: 5350 PART I)
* Note: Not available for Seal off bushing
24
Reference
• TCE Design Guide
• INDAL Aluminium Bas bar
• IS: 8084-1976 (Specification for interconnecting
busbars for AC voltage above 1kV up to and including
36kV)
• ANSI-C37-20

Weitere ähnliche Inhalte

Was ist angesagt?

Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
Dinesh Sarda
 
MV MetalClad Switchgear
MV MetalClad SwitchgearMV MetalClad Switchgear
MV MetalClad Switchgear
michaeljmack
 

Was ist angesagt? (20)

Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Catalog busbar ls 06. busduct presentation e series rev 2
Catalog busbar ls 06. busduct presentation e series rev 2Catalog busbar ls 06. busduct presentation e series rev 2
Catalog busbar ls 06. busduct presentation e series rev 2
 
Substation Training presentation
Substation Training presentationSubstation Training presentation
Substation Training presentation
 
Fault Level Calculation
Fault Level CalculationFault Level Calculation
Fault Level Calculation
 
SWITCHGEAR
SWITCHGEARSWITCHGEAR
SWITCHGEAR
 
Electrostatic precipitator by rajeev saini
Electrostatic  precipitator  by rajeev sainiElectrostatic  precipitator  by rajeev saini
Electrostatic precipitator by rajeev saini
 
Lightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for InstrumentationLightning and Surge Protection Strategy for Instrumentation
Lightning and Surge Protection Strategy for Instrumentation
 
MV MetalClad Switchgear
MV MetalClad SwitchgearMV MetalClad Switchgear
MV MetalClad Switchgear
 
PPT ON CIM ,BHEL HARIDWAR
PPT ON CIM ,BHEL HARIDWARPPT ON CIM ,BHEL HARIDWAR
PPT ON CIM ,BHEL HARIDWAR
 
Substation overview
Substation overviewSubstation overview
Substation overview
 
2.components in a substation breaker
2.components in a substation   breaker2.components in a substation   breaker
2.components in a substation breaker
 
400 kv nelmangala
400 kv nelmangala400 kv nelmangala
400 kv nelmangala
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Power Supply System - Single Line Diagram
Power Supply System - Single Line DiagramPower Supply System - Single Line Diagram
Power Supply System - Single Line Diagram
 
Transformer maintenance
Transformer maintenance Transformer maintenance
Transformer maintenance
 
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...ABB Medium Voltage MV Indoor and Outdoor Current Transformers -  ABB CT's Cur...
ABB Medium Voltage MV Indoor and Outdoor Current Transformers - ABB CT's Cur...
 
Protection & switchgear
Protection & switchgear  Protection & switchgear
Protection & switchgear
 
GIS 400kv substation
GIS  400kv substationGIS  400kv substation
GIS 400kv substation
 
Switch yard & Protection
Switch yard & ProtectionSwitch yard & Protection
Switch yard & Protection
 
Equipments of power transmission
Equipments of power transmissionEquipments of power transmission
Equipments of power transmission
 

Ähnlich wie Metal enclosed busduct

NMML1 Power supply and traction Presentation.pptx
NMML1 Power supply and traction Presentation.pptxNMML1 Power supply and traction Presentation.pptx
NMML1 Power supply and traction Presentation.pptx
aj3456843
 
Bus duct fabrication
Bus duct fabricationBus duct fabrication
Bus duct fabrication
STUPIDPANDEY
 
Eaton-Product-Aid
Eaton-Product-AidEaton-Product-Aid
Eaton-Product-Aid
Joe Galuska
 

Ähnlich wie Metal enclosed busduct (20)

Ls busduct -tnhh kimxuan
Ls busduct -tnhh kimxuanLs busduct -tnhh kimxuan
Ls busduct -tnhh kimxuan
 
NMML1 Power supply and traction Presentation.pptx
NMML1 Power supply and traction Presentation.pptxNMML1 Power supply and traction Presentation.pptx
NMML1 Power supply and traction Presentation.pptx
 
220kv-switch-yard-ppt.pptx
220kv-switch-yard-ppt.pptx220kv-switch-yard-ppt.pptx
220kv-switch-yard-ppt.pptx
 
Dog Conductor
Dog ConductorDog Conductor
Dog Conductor
 
Elastimold - Cable Connectors, Joints, Terminations Catalogue
Elastimold - Cable Connectors, Joints, Terminations CatalogueElastimold - Cable Connectors, Joints, Terminations Catalogue
Elastimold - Cable Connectors, Joints, Terminations Catalogue
 
Aerial cables
Aerial cablesAerial cables
Aerial cables
 
Busduct___Busbar.pptx
Busduct___Busbar.pptxBusduct___Busbar.pptx
Busduct___Busbar.pptx
 
5 power house
5 power house5 power house
5 power house
 
Gis91
Gis91Gis91
Gis91
 
Electrical System Design
Electrical System Design Electrical System Design
Electrical System Design
 
Case study sterlite deadend grip
Case study  sterlite deadend gripCase study  sterlite deadend grip
Case study sterlite deadend grip
 
Bus duct fabrication
Bus duct fabricationBus duct fabrication
Bus duct fabrication
 
132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report132 KV Grid Station Intern ship training report
132 KV Grid Station Intern ship training report
 
Nexans high-voltage.pdf
Nexans high-voltage.pdfNexans high-voltage.pdf
Nexans high-voltage.pdf
 
Electrician club with cables
Electrician club with cablesElectrician club with cables
Electrician club with cables
 
Report on MCB
Report on MCBReport on MCB
Report on MCB
 
Xlpe insulated power cable
Xlpe insulated power cableXlpe insulated power cable
Xlpe insulated power cable
 
Chandu
ChanduChandu
Chandu
 
Eaton-Product-Aid
Eaton-Product-AidEaton-Product-Aid
Eaton-Product-Aid
 
the substation components study
the substation components study the substation components study
the substation components study
 

Kürzlich hochgeladen

Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
chumtiyababu
 

Kürzlich hochgeladen (20)

AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptx
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Moment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilMoment Distribution Method For Btech Civil
Moment Distribution Method For Btech Civil
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
PE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and propertiesPE 459 LECTURE 2- natural gas basic concepts and properties
PE 459 LECTURE 2- natural gas basic concepts and properties
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
Verification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptxVerification of thevenin's theorem for BEEE Lab (1).pptx
Verification of thevenin's theorem for BEEE Lab (1).pptx
 

Metal enclosed busduct

  • 2. Metal enclosed busduct is an assembly of busbars with associated connections, joints and insulator supports within an earthed metal enclosure. • Non-Segregated • Phase Segregated • Isolated Phase Definition Classification
  • 3. • Connection between Generator and Generator Transformer; • Connection between Transformer and Switchgear; • Connection between one Switchgear to another Switchgear. • Economical point of view: When the current rating required is high and length is short. Application
  • 4. • Air is the only insulating medium between three phases. • Recommended up-to 660V systems with current ratings up-to 4000A. • Specifically use for connection between secondary side of distribution transformer and LV switchgear. Non-Segregated Phase Busduct
  • 5.
  • 6. 6.6kV, 2000A , 40KA for 3 Sec 6.6/0.433kV 2500 KVA 6.6/0.433kV 2500 KVA 415V, 4000A, 50KA for 1 Sec NSPB
  • 7. • Insulated phase barriers are provided; • On high voltage systems up-to 6.6kV with current ratings up-to 4000A. • Specifically use for connection between secondary side of Power / distribution transformer and MV switchgear, tie between MV switchgear. Phase-Segregated Busduct
  • 8.
  • 9. • Separate enclosure for each; • On systems 11kV and higher with current ratings over 4000A. • Specially for generator leads (current>400A), IPBDs are recommended. Isolated Phase Busduct
  • 10. IPBD Continuous Non-Continuous • Up-to 8000A rating may be left to the manufacturers of busduct & the selection based on availability, optimisation of capital cost & loss evaluation. • Current rating over 8000A, only continuous type is recommended to minimise the inductive heating of supporting structures etc. & associated losses.
  • 11. Typical arrangement of continuous type of Isolated Phase Bus Duct
  • 12. Typical discontinuous type of Isolated Phase Bus Duct
  • 13. 6.6kV SWGR ST-3 40/25/25 MVA 220/6.9/6.9kV 220kV Switchyard R SB-3A SB-3BUB-3A 220kV Switchyard UB-3B R RR UT-3 40/25/25 MVA 16.5/6.9/6.9kV R Generator 250 MW 16.5kV GT-3 315 MVA 235/16.5kV IPBD SPBD TO EXCT TRAFO
  • 14. Voltage class of the Busduct may be selected from one of the following standard ratings and shall be at least equal to the maximum voltage rating of the associated equipment: 0.66, 3.6, 7.2, 12, 24 and 36kV Voltage Rating of the Busduct Rated r.m.s. continuous current carrying capacity shall be at least equal to the maximum current capability of the associated equipment (Which may be higher than nominal rated current) rounded off to the nearest higher standard current rating of the busduct. Preferred standard current ratings are 100, 250, 400, 630, 800, 1250, 1600, 2000, 3150, 4000, 5000, 6300, 8000, 10000, 12500 and 15000A. Continuous Current Rating
  • 15. Rated r.m.s. short time current ratings of the busbar shall correspond to the fault level of the system. The time shall take into consideration the operating time of backup protective devices on the incoming side but the duration shall not be less than 1 sec. Momentary peak current rating shall be 2.55 times the short time r.m.s. current rating of the busduct. Short time Current Rating Voltage The temperature rise of the conductor shall be as per IS-8084. Also the temperature of the busduct shall not exceed 2500C while carrying the specified short circuit current for 1 sec when fault occurs, at the operating temperature. Temperature rise
  • 16. Busbar support insulators are enclosed, the creepage distances & height of insulators shall be the highest feasible and shall not be less than those for heavily polluted atmosphere as per IS:2544 & IS:5350 (Part-I) respectively to allow for dust accumulation and moisture condensation which can occur. Station/Post type insulator shall be used for supporting buses in metal enclosed busduct. Bus support Insulator Flexible connections such as braided or laminated flexible joints for conductors and rubber bellows for enclosures shall be used for termination of busuct at the terminal of generator, transformer, switchgear etc. and similar flexible connections for conductors and metallic or rubber bellows with metallic shorting for enclosures shall be used in the run of the busuct such that they allow for vibrations & thermal expansion and do not impose any stress on terminal and bushings. Terminations
  • 17. Busduct shall be normally natural cooled (AN). Forced cooling may be considered beyond 10000A rating as per IS:8084. Cooling . Material for Bus and Enclosure • Bus bar shall be either of copper or aluminium conductor. • Copper conductor shall be of hard drawn (HD), high conductivity conforming to IS:613. • Aluminium conductors shall be of aluminium alloy grade 63401WP conforming to IS:5082.
  • 18. • Material of enclosure for segregated & non-segregated type busduct shall be mild steel or aluminium. • If the location where the busduct (Where mild steel are used for enclosure ) is to be installed is having corrosive atmosphere, it shall be galvanised after fabrication or it shall be painted preferably with epoxy based paint. • For isolated phase type of busduct, the enclosure material shall be of aluminium alloy grade 63401WP conforming to IS:5082.
  • 19. • Aluminium is cheaper to use than copper. • Aluminium has les than one-third the density of copper. Weight of aluminium bus bar only half as much as copper bar of equal current capacity. The light weight of aluminium is of advantage in other ways too: for instance, it allows easier handling, transportation & erection. • Outstanding resistance to corrosion, thus permitting its widespread use in electro-chemical & electroplating process where the atmosphere is highly corrosive. Popularity of Aluminium Busduct over copper busduct:
  • 20. • “Self-stifling” property. • Nevertheless, Aluminium is the cheapest Non- magnetic metal. Hence suitable material for enclosure also.
  • 22.
  • 23. TABLE-III BUSDUCTSUPPORTING INSULATOR & SEAL OFF BUSHING (BASED ON IS:2544 & IS: 5350 PART I) * Note: Not available for Seal off bushing
  • 24. 24 Reference • TCE Design Guide • INDAL Aluminium Bas bar • IS: 8084-1976 (Specification for interconnecting busbars for AC voltage above 1kV up to and including 36kV) • ANSI-C37-20