Kalman Filter Estimation of Impedance Parameters for Medium Transmission Line
Optimal Control Theory
1. Identification & Tracking of Harmonic Sources in a Power System using a Kalman Filter Optimal Control Theory II (ECGR 6116) Prof. Dr. Kakad Nikhil Kulkarni (Student ID 800696839) Adly A. Girgis, Fellow, IEEE Dept. of Elect & CompEngg. Clemson University Clemson, SC 29634 Haili Ma, Student Member, IEEE Illinois Institute of Technology Chicago, IL 60616
2.
3. Mathematical Formulation Bus injection current expressed as c(t) = I cos(wt + θ) = I coswtcos θ- I sinwt sin θ Let the state variable XR be Icos θand XI be I sin θ Then 2 state variable equation for injection of current may be expressed as
4. For powers system with n buses, all bus current injections are treated as state variable, Vector W is process noise which represents the random variation of the state variable. Bus voltages are related to bus injection current by Z matrix.
6. We assume that m measuring meters are available and that the measured quantities are sampled values of bus voltage and injection current waveforms at m buses. The final measurement equation at the frequency w is given as
7. A harmonic injection current i(t) which includes rharmonics may be represented by For an n-bus power system, the state equation representation of the harmonic injection current is
8. The system harmonic measurement equation is A 3 phase Z bus matrix is considered in the equation. Also last 2 equations together gives mathematical model on which Kalman Filtering is based.
9. A Kalman Filter Algorithm For simplicity mathematical model is rewritten in following form State Equation: Measurment Equation: System covariance matrices are assumed for Wkand Vk are assumed as Initial variable is assumed to be zero Initial covariance matrix is
11. Optimal Metering Locations From recursive Kalman Filter Equations, the error covariance matrix Pk is independent of the measurements,thus Pk+1 can be explicitly expressed as a function of Pk. Advantage of Kalman filter method when used for optimal metering locations is that it accounts for the Measurement noise variance Rk and system covariance matrix Qk. These parameters may change the arrangements of harmonic metering locations up to some extend. Hence, method is suitable for Stochastic & Deterministic variations. Optimal metering locations are based on error covariance analysis of the harmonic injection. Optimal metering locations in power system are arranged so that trace[Pk] = minimal
13. Power system brief Capacitors are considered as out of service. 6 pulse drive is major source of harmonic. Actual 3 phase harmonic measurement data on the system is used to test the method 3 phase bus voltage waveforms were observed on October 15, 1993. All signals were sampled at 7680 Hz i.e. 128 samples/cycle
14. Initial covariance estimation Measurement error vi is unknown for specific measurement, but for stable measurement system, errors in number of measurement have certain statistical feature of normal distribution. Standard deviation of error is assumed to know. In this study, based of actual field measurement standard deviation is taken as 5%. P0(-) is denoted by σ1=3.8, σ4=1.1, σ5=3, σ6=1, σ7=2.5, σ9= 1.5. These initial parameters model the possibilities of occurrences of harmonic sources at these buses, and are determined by average load levels & prior information about harmonic sources. For buses without loads σ is chosen as 0.1 Diagonal elements of Qk taken as 0.05 (p.u.)
15. Optimal Arrangements of Harmonic Meters 3 harmonic meters are assumed to be available Steady state value of trace[Pk] depends on location of meters
16.
17. Identification and Tracking of Harmonic Sources Based on results in table I meters are placed at buses 4,5,7. Actual voltage waveform at buses 4,5,7 are sampled. No current injection were observed, i.e. load levels are low during sampling. Recursive Kalman Filter equations are used to estimate harmonic injection at all buses. Estimates of harmonic injections at all buses are very small except Bus no. 9
18.
19. Phase A harmonic injection at bus 9 with harmonic meters placed at 2,3,4.