Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317

RESEARCH ARTICLE

OPEN ACCESS

Emergency Control Using Multifunctional DVR for Distribution
Systems
Salava V Satyanarayana1, A Tejasri M.Tech2
M.TECH Scholar, Dept of EEE, GIET College Rajahmundry, AP
Assistant Professor, Dept. of EEE, GIET College Rajahmundry, AP India

Abstract
This paper discusses a new multifunctional dynamic voltage restorer (DVR) and closed loop controller using the
Posicast and P+Resonant controllers. The closed loop controller using the Posicast and P+Resonant controllers
is proposed in order to improve the transient response and eliminate the steady-state error in DVR response,
respectively. The proposed algorithm is applied to some disturbances in load voltage caused by induction
motors starting, and a three-phase short circuit fault. Also, the capability of the proposed DVR has been tested to
limit the downstream fault current. The current limitation will restore the point of common coupling (PCC) (the
bus to which all feeders under study are connected) voltage and protect the DVR itself. The innovation here is
that the DVR acts as virtual impedance with the main aim of protecting the PCC voltage during downstream
fault without any problem in real power injection into the DVR. Results of the simulation studies in the
MATLAB/SIMULINK software environment indicate that the proposed control scheme with faults and
induction motor under multifunctional DVR.

I.

Introduction

Electric power quality is capacity of an
electric power system to supply electric energy of a
load in an acceptable quality. Power distribution
system should provide with an uninterrupted flow of
energy at smooth sinusoidal voltage at the contracted
magnitude level and frequency to their customers.
Power systems especially distribution systems, have
numerous non linear loads, which significantly affect
the quality of power. Apart from non linear loads like
capacitor switching, motor starting and unusual faults
could also inflict power quality problems. Many
problems can result from poor power quality (PQ),
especially in today’s complex power system, such as
the false operation of modern control systems.
Voltage sag is an important PQ problem because of
sensitive loads growth. Worldwide experience has
showed that short circuit faults are the main origin of
voltage sag; therefore there is a loss of voltage quality
[1]-[2].
Voltage sag is defined as a sudden reduction
in supply voltage to between 90% and 10% of the
nominal value, followed by a recovery after a short
interval (the standard duration of sag is between 10
milliseconds and 1 minute). The most common
compensator for voltage sag is the dynamic voltage
restorer (DVR). The basic operation of the DVR is
based on injection of a compensation voltage with
required magnitude, phase angle and frequency in
series with the sensitive electric distribution feeder.
Previous works have been done on different
aspects of DVR performance, and different control
www.ijera.com

strategies have been found. These methods mostly
depend on the purpose of using DVR. In some
methods, the main purpose is to detect and
compensate for the voltage sag with minimum DVR
active power injection [4], [5]. Also, the in-phase
compensation method can be used for sag and swell
mitigation [6]. The multiline DVR can be used for
eliminating the battery in the DVR structure and
controlling more than one line [7], [14]. Moreover,
research has been made on using the DVR in medium
level voltage [8]. Harmonic mitigation [9] and control
of DVR under frequency variation [10] are also in the
area of research. The closed-loop control with load
voltage and current feedback is introduced as a simple
method to control the DVR in [15]. Also, Posicast and
P+Resonant controllers can be used to improve the
transient response and eliminate the steady-state error
in DVR. The Posicast controller is a kind of step
function with two parts and is used to improve the
damping of the transient oscillations initiated at the
start instant from the voltage sag. The P+Resonant
controller consists of a proportional function plus a
resonant function and it eliminates the steady-state
voltage tracking error [6]. The state feed forward and
feedback methods [7], symmetrical components
estimation [8], robust control [10], and wavelet
transform [12] have also been proposed as different
methods of controlling the DVR.
The basis of the proposed control strategy in
this paper is that when the fault current does not pass
through the DVR, an outer feedback loop of the load
voltage with an inner feedback loop of the filter
312 | P a g e
Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317
capacitor current will be used. Also, a feed forward
loop will be used to improve the dynamic response of
the load voltage. Moreover, to improve the transient
response, the Posicast controller and to eliminate the
steady-state error, the P+Resonant controller are used.
But in case the fault current passes through the DVR,
using the flux control algorithm [11], the series
voltage is injected in the opposite direction and,
therefore, the DVR acts like series variable
impedance.

II.

disturbance compensation process. In particular, if
capacitors are used as energy storage, the DC-link
voltage will decrease with the dwindling storage
energy during compensation.

Dynamic Voltage Restorer

Dynamic voltage restorer was originally
proposed to compensate for voltage disturbances on
distribution systems. A typical DVR scheme is shown
in Fig. 1. The restoration is based on injecting AC
voltages in series with the incoming three-phase
network, the purpose of which is to improve voltage
quality by adjustment in voltage magnitude, waveshape, and phase shift. As shown in Fig. 1, the DVR
essentially consists of a series-connected injection
transformer Ti, a voltage-source inverter (VSI), a
harmonic filter, and an energy storage device [4],
[13]. Meanwhile, a parallel switch is used to bypass
and protect the DVR, when a downstream fault is
detected [14], [15]. As shown in Fig. 1, the line-side
harmonic filter topology [11] consists of the leakage
inductance of the injection transformer and the filter
capacitor. Meanwhile, denotes the dc-link capacitor.
The series injected voltage of the DVR,
Vdvr, is synthesized by modulating pulse widths of
the inverter-bridge switches. The injection of an
appropriate Vdvr in the face of an up-stream voltage
disturbance requires a certain amount of real and
reactive power supply from the DVR. The reactive
power requirement is generated by the inverter.

Fig. 2; Vector Diagram of Voltage Injection Method
The
corresponding
phasor
diagram
describing the electrical conditions during voltage sag
is depicted, where only the affected phase is shown
for clarity. Let the voltage quantities Il, φ, δ and α
represent the load current, load power factor angle,
supply voltage phase angle and load voltage advance
angle respectively. Although there is a phase
advancement of α in the load voltage with respect to
the pre-sag voltage in Fig. 2, only in-phase
compensation where the injected voltage is in phase
with the supply voltage (α = δ) is considered.
By mounting the battery in DC link of the
centralized inverter, the DC/DC converter for battery
can be saved as shown in Figure 1(b) [1], [2].
Different from the centralized inverters in Figure 1(a)
and (b), the separate grid inverters are used by the two
PV systems in Figure 1(c). Thus, the power rating of
each inverter becomes smaller, and the inverter is
intended to be modular design as well as mass
production.

III.

Fig. 1: schematic diagram of the DVR with line side
harmonic filter

Proposed Multifunctional DVR

In addition to the aforementioned
capabilities of DVR, it can be used in the mediumvoltage level as in Fig. 2 to protect a group of
consumers when the cause of disturbance is in the
downstream of the DVR’s feeder and the large fault
current passes through the DVR itself. In this case,
the equipment can limit the fault current and protect
the loads in parallel feeders until the breaker works
and disconnects the faulted feeder.

Widely used in present DVR control is the
so-called in phase voltage injection technique where
the load voltage V2 is assumed to be in-phase with
the pre-sag voltage. As the DVR is required to inject
active power into the distribution line during the
period of compensation, the capacity of the energy
storage unit can become a limiting factor in the
www.ijera.com

313 | P a g e
Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317

Fig. 2: A multifunctional DVR connected in a
medium-voltage level power system.
The large fault current will cause the PCC
voltage to drop and the loads on the other feeders
connected to this bus will be affected. Furthermore, if
not controlled properly, the DVR might also
contribute to this PCC voltage sag in the process of
compensating the missing voltage, hence further
worsening the fault situation [11].
To limit the fault current, a flux-charge
model has been proposed and used to make DVR act
like a pure virtual inductance which does not take any
real power from the external system and, therefore,
protects the dc-link capacitor and battery as shown in
Fig. 1 [11]. But in this model, the value of the virtual
inductance of DVR is a fixed one and the reference of
the control loop is the flux of the injection
transformer winding, and the PCC voltage is not
mentioned in the control loop. In this paper, the PCC
voltage is used as the main reference signal and the
DVR acts like variable impedance. For this reason,
the absorption of real power is harmful for the battery
and dc-link capacitor. To solve this problem,
impedance including a resistance and an inductance
will be connected in parallel with the dc-link
capacitor. This capacitor will be separated from the
circuit, and the battery will be connected in series
with a diode just when the downstream fault occurs so
that the power does not enter the battery and the dclink capacitor. It should be noted here that the
inductance is used mainly to prevent large oscillations
in the current. The active power mentioned is,
therefore, absorbed by the impedance.
3.1 Proposed control scheme for using Flux charge
model
In this part, an algorithm is proposed for the
DVR to restore the PCC voltage, limit the fault
current, and, therefore, protect the DVR components.
The flux-charge model here is used in a way so that
the DVR acts as a virtual inductance with a variable
value in series with the distribution feeder. To do this,
the DVR must be controlled in a way to inject a
proper voltage having the opposite polarity with
www.ijera.com

respect to usual cases. It should be noted that over
current tripping is not possible in this case, unless
additional communication between the DVR and the
downstream side over current circuit breaker (CB) is
available. If it is necessary operate the over current
CB at PCC, communication between the DVR and the
PCC breaker might have to be made and this can be
easily done by sending a signal to the breaker when
the DVR is in the fault-current limiting mode as the
DVR is just located after PCC [11]. The proposed
DVR control method is illustrated in Fig. 8. It should
also be noted that the reference flux (𝜙 𝑟𝑒𝑓 ) is derived
by integration of the subtraction of the PCC reference
voltage (𝑉 ∗ ) and the DVR load-side voltage. This
𝑃𝐶𝐶
control strategy, the control variable used for the
outer flux model is the inverter-filtered terminal flux
defined as:
(1)
Where 𝑉 𝑜𝑑𝑣𝑟 is the filter capacitor voltage of the DVR
(at the DVR power converter side of the injection
transformer). The flux error is then fed to the flux
regulator, which is a P+Resonant controller, with a
transfer function given in (1). On the other hand, it
can be shown that a single flux-model would not
damp out the resonant peak of the LC filter connected
to the output of the inverter.

Fig. 3: Proposed method.
To stabilize the system, an inner charge
model is therefore considered. In this loop, the filter
inductor charge, which is derived by integration of its
current, tracks the reference charge output of the flux
regulator. The calculated charge error is then fed to
the charge regulator with the transfer function

This is actually a practical form of the
derivative controller. In this transfer function, the
regulator gain is limited to N at high frequencies to
prevent noise amplification. The derivative term in
𝑆 + 𝑆 neutralizes the effects of voltage and
1
𝑁
current integrations at the inputs of the flux-charge
model, resulting in the proposed algorithm having the
same regulation performance as the multiloop
voltage-current feedback control, with the only
difference being the presence of an additional low–
pass filter in the flux control loop in the form of
1 + 𝑆 . The bandwidth of this low–pass filter is
𝑆
𝑁
314 | P a g e
Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317
tuned (through varying N) with consideration for
measurement noise attenuation, DVR LC-filter
transient resonance attenuation, and system stability
margins.

4.1 Fault Current Limiting

Fig. 4: Multi-loop control using the Posicast and
P+Resonant controller
Theoretically, the resonant controller
compensates by introducing an infinite gain at the
resonant frequency of 50 Hz to force the steady-state
voltage error to zero. The ideal resonant controller,
however, acts like a network with an infinite quality
factor, which is not realizable in practice. A more
practical (nonideal) compensator is therefore used
here, and is expressed as

Where 𝑤 𝑐𝑢𝑡 is the compensator cutoff frequency
which is 1 rad/s in this application.

Fig. 5: Open loop control using the Posicast controller
To improve the damping, as shown in Fig. 4,
the Posicast controller can be used just before
transferring the signal to the PWM inverter of the
DVR. The transfer function of the controller can be
described as follows:

Where 𝛿 and 𝑇 𝑑 are the step response overshoot and
the period of damped response signal, respectively. It
should be noted that the Posicast controller has
limited high-frequency gain; hence, low sensitivity to
noise.

IV.

Fig. 6: SIMULINK Model of Proposed a
Multifunctional DVR under Three Phase Fault
condition.
MATLAB/simulink model of proposed
multifunctional DVR under three phase fault in
figure.6; The last simulation is run for a symmetrical
downstream fault, and the capability of the DVR to
reduce the fault current and restore the PCC voltage is
tested.
For the simulation with DVR compensation,
the three-phase fault is applied at t = 205 ms and then
removed after 0.1 s. Also, a breaker will remove the
faulted bus from the entire system at t = 300 ms. Fig.
13 shows the DVR operation during the fault. As can
be seen, the rms load bus voltage reaches zero during
the fault, and as the enlarged figure shows, in about
half a cycle, the
DVR has succeeded in restoring the PCC
voltage wave shape to the normal condition. It should
be noted that the amount and shape of the oscillations
depend on the time of applying the fault. As Fig. 13
shows, at this time, the voltage value of phase B is
nearly zero; this

MATLAB/Simulink modelling and
results

In this section, the proposed DVR topology
and control algorithm will be used for emergency
control during the voltage sag. The three-phase short
circuit and the start of a three-phase large induction
motor will be considered as the cause of distortion in
the simulations.

www.ijera.com

315 | P a g e
Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317

Fig. 8: SIMULINK model of proposed a
multifunctional DVR with Induction Motor.
During this period, the PCC bus is under
voltage sag. From t = 1.4 s, as the speed approaches
nominal, the voltage also approaches the normal
condition. However, during all of these events, the
DVR keeps the load bus voltage at the normal
condition. The DVR has succeeded in restoring the
load voltage in half a cycle from the instant of the
motor starting.

Fig. 7: Fault current limiting by DVR. (a) Threephase PCC voltages. (b) Three-phase load voltages.
(c) RMS voltages of the PCC and load. (d) Threephase currents.
4.2 Induction Motor
The large motor starting current will cause
the PCC voltage to drop. The simulation results in the
case of using the DVR are shown in Fig. 9. In this
simulation, the motor is started at t = 405 ms. As can
be seen in Fig. 11, at this time, the PCC rms voltage
drops to about 0.8 p.u. The motor speed reaches the
nominal value in about 1 s. MATLAB/simlink model
of proposed multifunctional DVR with induction
motor in figure8;

Fig. 9: Starting of an induction motor and the DVR
compensation. (a) Three phase PCC voltages. (b)
Three-phase load voltages. (c) RMS voltages of PCC
and load.

www.ijera.com

316 | P a g e
Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com
ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317
V.

CONCLUSION

In this paper, a multifunctional DVR is
proposed, and a closed-loop control system is used for
its control to improve the damping of the DVR
response. Also, for further improving the transient
response and eliminating the steady-state error, the
Posicast and P+Resonant controllers are used. As the
second function of this DVR, using the flux-charge
model, the equipment is controlled so that it limits the
downstream fault currents and protects the PCC
voltage during these faults by acting as variable
impedance. The problem of absorbed active power is
solved by entering impedance just at the start of this
kind of fault in parallel with the dc-link capacitor and
the battery being connected in series with a diode so
that the power does not enter it. The simulation
results verify the effectiveness and capability of the
proposed DVR in compensating for the voltage sags
caused by short circuits and the large induction motor
starting and limiting the downstream fault currents
and protecting the PCC voltage.

[8]

[9]

[10]

[11]

[12]

REFERENCE
[1]

[2]

[3]

[4]

[5]

[6]

[7]

A. K. Jindal, A. Ghosh, and A. Joshi,
―Critical load bus voltage control using DVR
under system frequency variation,‖ Elect.
Power Syst. Res., vol. 78, no. 2, pp. 255–
263, Feb. 2008.
J. A. Martinez and J. Martin-Arnedo,
―Voltage sag studies in distribution
networks- part II: Voltage sag assessment,‖
IEEE Trans. Power Del., vol. 21, no. 3, pp.
1679–1688, Jul. 2006.
S. S. Choi, B. H. Li, and D. M.
Vilathgamuwa,
―Dynamic
voltage
restoration with minimum energy injection,‖
IEEE Trans. Power Syst., vol. 15, no. 1, pp.
51–57, Feb. 2000.
C. Fitzer, M. Barnes, and P. Green, ―Voltage
sag detection technique for a dynamic
voltage restore,‖ IEEE Trans. Ind. Appl., vol.
2, no. 1, pp. 203–212, Jan./Feb. 2004.
Y. W. Li, D. M. Vilathgamuwa, F.
Blaabjerg, and P. C. Loh, ―A robust control
scheme
for
medium-voltage-levelDVR
implementation,‖
IEEE
Trans.
Ind.
Electron., vol. 54, no. 4, pp. 2249–2261,
Aug. 2007.
M. Vilathgamuwa, A. A. D. R. Perera, and
S. S. Choi, ―Performance improvement of
the dynamic voltage restorer with closedloop load voltage and current-mode control,‖
IEEE Trans. Power Electron., vol. 17, no. 5,
pp. 824–834, Sep. 2002.
M. J. Newman, D. G. Holmes, J. G. Nielsen,
and F. Blaabjerg, ―A dynamic voltage
restorer (DVR) with selective harmonic

www.ijera.com

[13]

[14]

[15]

[16]

compensation at medium voltage level,‖
IEEE Trans. Ind. Appl., vol. 41, no. 6, pp.
1744–1753, Nov./Dec. 2005.
M. H. Rashid, Power Electronics-Circuits,
Devices and Applications, 3rd ed. India:
Prentice-Hall of India, Aug. 2006.
S. S. Choi, B. H. Li, and D. M.
Vilathgamuwa,
―Dynamic
voltage
restoration with minimum energy injection,‖
IEEE Trans. Power Syst., vol. 15, no. 1, pp.
51–57, Feb. 2000.
H. Awad, J. Svensson, and M. Bollen,
―Mitigation of unbalanced voltage dips using
static series compensator,‖ IEEE Trans.
Power Electron., vol. 1, no. 3, pp. 837–846,
May 2004.
B. Delfino, F. Fornari, and R. Procopio, ―An
effective SSC control scheme for voltage sag
compensation,‖ IEEE Trans. Power Del.,
vol. 20, no. 3, pp. 2100–2107, Jul. 2005.
S. S. Choi, T. X. Wang, and D. M.
Vilathgamuwa, ―A series compensator with
fault current limiting function,‖ IEEE Trans.
Power Del., vol. 20, no. 3, pp. 2248–2256,
Jul. 2005.
V. K. Ramachandaramurthy, C. Fitzer, A.
Arulampalam, C. Zhan, M. Barnes, and N.
Jankins, ―Control of a battery supported
dynamic voltage restorer,‖ Proc. Inst. Elect.
Eng., Gen. Transm. Distrib., vol. 149, no. 5,
pp. 533–542, Sep. 2002.
D. M. Vilathgamuwa, H. M. Wijekoon, and
S. S. Choi, ―A novel technique to
compensate voltage sags in multiline
distribution system—the interline dynamic
voltage restorer,‖ IEEE Trans. Ind.
Electron., vol. 53, no. 5, pp. 1603–1611,
Oct. 2006.
N. G. Hingorani, ―Introducing custom
power,‖ IEEE Spectr., vol. 32, no. 6, pp. 41–
48, Jun. 1995.
B. H. Li, S. S. Choi, and D. M.
Vilathgamuwa, ―Design considerations on
the line-side filter used in the dynamic
voltage restorer,‖ Proc. Inst. Elect. Eng.,
Gen. Transm. Distrib., vol. 148, no. 1, pp. 1–
7, Jan. 2001.

317 | P a g e

Weitere ähnliche Inhalte

Was ist angesagt?

Iaetsd minimization of voltage sags and swells using dvr
Iaetsd minimization of voltage sags and swells using dvrIaetsd minimization of voltage sags and swells using dvr
Iaetsd minimization of voltage sags and swells using dvrIaetsd Iaetsd
 
IRJET- Dynamic Voltage Restorer for Voltage Sag/Swell Mitigation
IRJET- Dynamic Voltage Restorer for Voltage Sag/Swell MitigationIRJET- Dynamic Voltage Restorer for Voltage Sag/Swell Mitigation
IRJET- Dynamic Voltage Restorer for Voltage Sag/Swell MitigationIRJET Journal
 
A Three Phase D-STATCOM to Compensate AC and DC loads by using Fuzzy Logic DC...
A Three Phase D-STATCOM to Compensate AC and DC loads by using Fuzzy Logic DC...A Three Phase D-STATCOM to Compensate AC and DC loads by using Fuzzy Logic DC...
A Three Phase D-STATCOM to Compensate AC and DC loads by using Fuzzy Logic DC...IJMTST Journal
 
Sag/Swell Compensation by using BES DVR in Industrial Drives Applications
Sag/Swell Compensation by using BES DVR in Industrial Drives ApplicationsSag/Swell Compensation by using BES DVR in Industrial Drives Applications
Sag/Swell Compensation by using BES DVR in Industrial Drives ApplicationsIRJET Journal
 
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET Journal
 
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...IJERA Editor
 
Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)
Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)
Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)IJERA Editor
 
ijre paper
ijre paperijre paper
ijre paperNithin S
 
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...IAES-IJPEDS
 
Dvr Based Power Quality Improvement In Distribution System
Dvr Based Power Quality Improvement In Distribution SystemDvr Based Power Quality Improvement In Distribution System
Dvr Based Power Quality Improvement In Distribution Systeminventionjournals
 
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...IRJET Journal
 
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...Dr. Sudhir Kumar Srivastava
 

Was ist angesagt? (18)

Iaetsd minimization of voltage sags and swells using dvr
Iaetsd minimization of voltage sags and swells using dvrIaetsd minimization of voltage sags and swells using dvr
Iaetsd minimization of voltage sags and swells using dvr
 
IRJET- Dynamic Voltage Restorer for Voltage Sag/Swell Mitigation
IRJET- Dynamic Voltage Restorer for Voltage Sag/Swell MitigationIRJET- Dynamic Voltage Restorer for Voltage Sag/Swell Mitigation
IRJET- Dynamic Voltage Restorer for Voltage Sag/Swell Mitigation
 
A Three Phase D-STATCOM to Compensate AC and DC loads by using Fuzzy Logic DC...
A Three Phase D-STATCOM to Compensate AC and DC loads by using Fuzzy Logic DC...A Three Phase D-STATCOM to Compensate AC and DC loads by using Fuzzy Logic DC...
A Three Phase D-STATCOM to Compensate AC and DC loads by using Fuzzy Logic DC...
 
Hd3413181323
Hd3413181323Hd3413181323
Hd3413181323
 
Sag/Swell Compensation by using BES DVR in Industrial Drives Applications
Sag/Swell Compensation by using BES DVR in Industrial Drives ApplicationsSag/Swell Compensation by using BES DVR in Industrial Drives Applications
Sag/Swell Compensation by using BES DVR in Industrial Drives Applications
 
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
 
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
Analysis of Total Harmonic Distortion (THD) Level of Distribution Network Usi...
 
H011125457
H011125457H011125457
H011125457
 
Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)
Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)
Sag mitigation in distribution system by using Dynamic voltage Restorer (DVR)
 
ijre paper
ijre paperijre paper
ijre paper
 
Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
 
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
Fuzzy Bang-Bang Control Scheme of USSC for Voltage Sag Mitigation due to Shor...
 
Bo36390397
Bo36390397Bo36390397
Bo36390397
 
F01233345
F01233345F01233345
F01233345
 
Dvr Based Power Quality Improvement In Distribution System
Dvr Based Power Quality Improvement In Distribution SystemDvr Based Power Quality Improvement In Distribution System
Dvr Based Power Quality Improvement In Distribution System
 
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
To Diminish the Voltage Sag Replaced DVR with Generalized Modulation Strategy...
 
Enhanced decoupled current control with voltage compensation for modular mult...
Enhanced decoupled current control with voltage compensation for modular mult...Enhanced decoupled current control with voltage compensation for modular mult...
Enhanced decoupled current control with voltage compensation for modular mult...
 
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
Power Quality Enhancement in Power Distribution System by Using Fuzzy Logic C...
 

Andere mochten auch

AndreaColzani-CertificatoLaurea (1)
AndreaColzani-CertificatoLaurea (1)AndreaColzani-CertificatoLaurea (1)
AndreaColzani-CertificatoLaurea (1)andrea colzani
 
Hh31 08 15 gravidez na adolescência e doenças sexualmente transmissíveis
Hh31 08 15 gravidez na adolescência e doenças sexualmente transmissíveisHh31 08 15 gravidez na adolescência e doenças sexualmente transmissíveis
Hh31 08 15 gravidez na adolescência e doenças sexualmente transmissíveiseduvania
 
eforea_AmericanSpa_June2011
eforea_AmericanSpa_June2011eforea_AmericanSpa_June2011
eforea_AmericanSpa_June2011Tyra Lowman
 
Project 2 Drawings.pdf
Project 2 Drawings.pdfProject 2 Drawings.pdf
Project 2 Drawings.pdfEave0222
 
A verdade sobre a Pós-Graduação versão Tarantino
A verdade sobre a Pós-Graduação versão TarantinoA verdade sobre a Pós-Graduação versão Tarantino
A verdade sobre a Pós-Graduação versão TarantinoJosiane Cruz
 

Andere mochten auch (6)

AndreaColzani-CertificatoLaurea (1)
AndreaColzani-CertificatoLaurea (1)AndreaColzani-CertificatoLaurea (1)
AndreaColzani-CertificatoLaurea (1)
 
Hh31 08 15 gravidez na adolescência e doenças sexualmente transmissíveis
Hh31 08 15 gravidez na adolescência e doenças sexualmente transmissíveisHh31 08 15 gravidez na adolescência e doenças sexualmente transmissíveis
Hh31 08 15 gravidez na adolescência e doenças sexualmente transmissíveis
 
Daniel Bergmann
Daniel BergmannDaniel Bergmann
Daniel Bergmann
 
eforea_AmericanSpa_June2011
eforea_AmericanSpa_June2011eforea_AmericanSpa_June2011
eforea_AmericanSpa_June2011
 
Project 2 Drawings.pdf
Project 2 Drawings.pdfProject 2 Drawings.pdf
Project 2 Drawings.pdf
 
A verdade sobre a Pós-Graduação versão Tarantino
A verdade sobre a Pós-Graduação versão TarantinoA verdade sobre a Pós-Graduação versão Tarantino
A verdade sobre a Pós-Graduação versão Tarantino
 

Ähnlich wie Bc4101312317

A Versatile Control Scheme For Dynamic Voltage Restorer To Limit Downstream F...
A Versatile Control Scheme For Dynamic Voltage Restorer To Limit Downstream F...A Versatile Control Scheme For Dynamic Voltage Restorer To Limit Downstream F...
A Versatile Control Scheme For Dynamic Voltage Restorer To Limit Downstream F...IJERA Editor
 
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...IRJET Journal
 
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...IJERD Editor
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorIRJET Journal
 
IRJET-Power Quality Improvement by using CHB Inverter based DVR
IRJET-Power Quality Improvement by using CHB Inverter based DVRIRJET-Power Quality Improvement by using CHB Inverter based DVR
IRJET-Power Quality Improvement by using CHB Inverter based DVRIRJET Journal
 
Compensation of Sag and Swell Voltage by using Dynamic Voltage Restorer
Compensation of Sag and Swell Voltage by using Dynamic Voltage RestorerCompensation of Sag and Swell Voltage by using Dynamic Voltage Restorer
Compensation of Sag and Swell Voltage by using Dynamic Voltage Restorerijtsrd
 
Power Quality Enhancement in Power Distribution system using Artificial intel...
Power Quality Enhancement in Power Distribution system using Artificial intel...Power Quality Enhancement in Power Distribution system using Artificial intel...
Power Quality Enhancement in Power Distribution system using Artificial intel...sundar balan
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)theijes
 
DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)
DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)
DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)Journal For Research
 
DVR with Artificial Intelligent Controller for Voltage Sag Mitigation
DVR with Artificial Intelligent Controller for Voltage Sag MitigationDVR with Artificial Intelligent Controller for Voltage Sag Mitigation
DVR with Artificial Intelligent Controller for Voltage Sag MitigationMohamed Khaleeel
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Scienceresearchinventy
 
Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...
Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...
Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...IJAPEJOURNAL
 
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...Wireilla
 
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...ijfls
 

Ähnlich wie Bc4101312317 (20)

Ke2517881796
Ke2517881796Ke2517881796
Ke2517881796
 
A Versatile Control Scheme For Dynamic Voltage Restorer To Limit Downstream F...
A Versatile Control Scheme For Dynamic Voltage Restorer To Limit Downstream F...A Versatile Control Scheme For Dynamic Voltage Restorer To Limit Downstream F...
A Versatile Control Scheme For Dynamic Voltage Restorer To Limit Downstream F...
 
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
 
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
Power Quality Enhancement through Dynamic Voltage Restorer using SRF Theory f...
 
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra CapacitorSimulation of DVR for power Quality Improvement by using Ultra Capacitor
Simulation of DVR for power Quality Improvement by using Ultra Capacitor
 
Gr3412151231
Gr3412151231Gr3412151231
Gr3412151231
 
IRJET-Power Quality Improvement by using CHB Inverter based DVR
IRJET-Power Quality Improvement by using CHB Inverter based DVRIRJET-Power Quality Improvement by using CHB Inverter based DVR
IRJET-Power Quality Improvement by using CHB Inverter based DVR
 
Compensation of Sag and Swell Voltage by using Dynamic Voltage Restorer
Compensation of Sag and Swell Voltage by using Dynamic Voltage RestorerCompensation of Sag and Swell Voltage by using Dynamic Voltage Restorer
Compensation of Sag and Swell Voltage by using Dynamic Voltage Restorer
 
Fm3110901095
Fm3110901095Fm3110901095
Fm3110901095
 
Power Quality Enhancement in Power Distribution system using Artificial intel...
Power Quality Enhancement in Power Distribution system using Artificial intel...Power Quality Enhancement in Power Distribution system using Artificial intel...
Power Quality Enhancement in Power Distribution system using Artificial intel...
 
Energy efficiency enhancement using dynamic voltage restorer (DVR)
Energy efficiency enhancement using dynamic voltage restorer (DVR)Energy efficiency enhancement using dynamic voltage restorer (DVR)
Energy efficiency enhancement using dynamic voltage restorer (DVR)
 
F010344049
F010344049F010344049
F010344049
 
The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)The International Journal of Engineering and Science (The IJES)
The International Journal of Engineering and Science (The IJES)
 
DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)
DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)
DESIGN AND SIMULATION OF DYNAMIC VOLTAGE RESTORER (DVR)
 
DVR with Artificial Intelligent Controller for Voltage Sag Mitigation
DVR with Artificial Intelligent Controller for Voltage Sag MitigationDVR with Artificial Intelligent Controller for Voltage Sag Mitigation
DVR with Artificial Intelligent Controller for Voltage Sag Mitigation
 
Research Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and ScienceResearch Inventy : International Journal of Engineering and Science
Research Inventy : International Journal of Engineering and Science
 
Power Quality Enhancement in Power System Network using DSTACOM
Power Quality Enhancement in Power System Network using DSTACOMPower Quality Enhancement in Power System Network using DSTACOM
Power Quality Enhancement in Power System Network using DSTACOM
 
Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...
Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...
Compensation of Single-Phase and Three-Phase Voltage Sag and Swell Using Dyna...
 
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
IMPLEMENTATION OF FUZZY CONTROLLED PHOTO VOLTAIC FED DYNAMIC VOLTAGE RESTORER...
 
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
Implementation of Fuzzy Controlled Photo Voltaic Fed Dynamic Voltage Restorer...
 

Kürzlich hochgeladen

The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024Rafal Los
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityPrincipled Technologies
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...Neo4j
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Enterprise Knowledge
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘RTylerCroy
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdfhans926745
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...Martijn de Jong
 
Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Allon Mureinik
 
CNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of ServiceCNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of Servicegiselly40
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Scriptwesley chun
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024Results
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationSafe Software
 
Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101Paola De la Torre
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptxHampshireHUG
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsEnterprise Knowledge
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonAnna Loughnan Colquhoun
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc
 

Kürzlich hochgeladen (20)

The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024The 7 Things I Know About Cyber Security After 25 Years | April 2024
The 7 Things I Know About Cyber Security After 25 Years | April 2024
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...Workshop - Best of Both Worlds_ Combine  KG and Vector search for  enhanced R...
Workshop - Best of Both Worlds_ Combine KG and Vector search for enhanced R...
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...Driving Behavioral Change for Information Management through Data-Driven Gree...
Driving Behavioral Change for Information Management through Data-Driven Gree...
 
🐬 The future of MySQL is Postgres 🐘
🐬  The future of MySQL is Postgres   🐘🐬  The future of MySQL is Postgres   🐘
🐬 The future of MySQL is Postgres 🐘
 
[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf[2024]Digital Global Overview Report 2024 Meltwater.pdf
[2024]Digital Global Overview Report 2024 Meltwater.pdf
 
2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...2024: Domino Containers - The Next Step. News from the Domino Container commu...
2024: Domino Containers - The Next Step. News from the Domino Container commu...
 
Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)
 
CNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of ServiceCNv6 Instructor Chapter 6 Quality of Service
CNv6 Instructor Chapter 6 Quality of Service
 
Automating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps ScriptAutomating Google Workspace (GWS) & more with Apps Script
Automating Google Workspace (GWS) & more with Apps Script
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time AutomationFrom Event to Action: Accelerate Your Decision Making with Real-Time Automation
From Event to Action: Accelerate Your Decision Making with Real-Time Automation
 
Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101Salesforce Community Group Quito, Salesforce 101
Salesforce Community Group Quito, Salesforce 101
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
 
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
04-2024-HHUG-Sales-and-Marketing-Alignment.pptx
 
IAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI SolutionsIAC 2024 - IA Fast Track to Search Focused AI Solutions
IAC 2024 - IA Fast Track to Search Focused AI Solutions
 
Data Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt RobisonData Cloud, More than a CDP by Matt Robison
Data Cloud, More than a CDP by Matt Robison
 
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law DevelopmentsTrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
TrustArc Webinar - Stay Ahead of US State Data Privacy Law Developments
 

Bc4101312317

  • 1. Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317 RESEARCH ARTICLE OPEN ACCESS Emergency Control Using Multifunctional DVR for Distribution Systems Salava V Satyanarayana1, A Tejasri M.Tech2 M.TECH Scholar, Dept of EEE, GIET College Rajahmundry, AP Assistant Professor, Dept. of EEE, GIET College Rajahmundry, AP India Abstract This paper discusses a new multifunctional dynamic voltage restorer (DVR) and closed loop controller using the Posicast and P+Resonant controllers. The closed loop controller using the Posicast and P+Resonant controllers is proposed in order to improve the transient response and eliminate the steady-state error in DVR response, respectively. The proposed algorithm is applied to some disturbances in load voltage caused by induction motors starting, and a three-phase short circuit fault. Also, the capability of the proposed DVR has been tested to limit the downstream fault current. The current limitation will restore the point of common coupling (PCC) (the bus to which all feeders under study are connected) voltage and protect the DVR itself. The innovation here is that the DVR acts as virtual impedance with the main aim of protecting the PCC voltage during downstream fault without any problem in real power injection into the DVR. Results of the simulation studies in the MATLAB/SIMULINK software environment indicate that the proposed control scheme with faults and induction motor under multifunctional DVR. I. Introduction Electric power quality is capacity of an electric power system to supply electric energy of a load in an acceptable quality. Power distribution system should provide with an uninterrupted flow of energy at smooth sinusoidal voltage at the contracted magnitude level and frequency to their customers. Power systems especially distribution systems, have numerous non linear loads, which significantly affect the quality of power. Apart from non linear loads like capacitor switching, motor starting and unusual faults could also inflict power quality problems. Many problems can result from poor power quality (PQ), especially in today’s complex power system, such as the false operation of modern control systems. Voltage sag is an important PQ problem because of sensitive loads growth. Worldwide experience has showed that short circuit faults are the main origin of voltage sag; therefore there is a loss of voltage quality [1]-[2]. Voltage sag is defined as a sudden reduction in supply voltage to between 90% and 10% of the nominal value, followed by a recovery after a short interval (the standard duration of sag is between 10 milliseconds and 1 minute). The most common compensator for voltage sag is the dynamic voltage restorer (DVR). The basic operation of the DVR is based on injection of a compensation voltage with required magnitude, phase angle and frequency in series with the sensitive electric distribution feeder. Previous works have been done on different aspects of DVR performance, and different control www.ijera.com strategies have been found. These methods mostly depend on the purpose of using DVR. In some methods, the main purpose is to detect and compensate for the voltage sag with minimum DVR active power injection [4], [5]. Also, the in-phase compensation method can be used for sag and swell mitigation [6]. The multiline DVR can be used for eliminating the battery in the DVR structure and controlling more than one line [7], [14]. Moreover, research has been made on using the DVR in medium level voltage [8]. Harmonic mitigation [9] and control of DVR under frequency variation [10] are also in the area of research. The closed-loop control with load voltage and current feedback is introduced as a simple method to control the DVR in [15]. Also, Posicast and P+Resonant controllers can be used to improve the transient response and eliminate the steady-state error in DVR. The Posicast controller is a kind of step function with two parts and is used to improve the damping of the transient oscillations initiated at the start instant from the voltage sag. The P+Resonant controller consists of a proportional function plus a resonant function and it eliminates the steady-state voltage tracking error [6]. The state feed forward and feedback methods [7], symmetrical components estimation [8], robust control [10], and wavelet transform [12] have also been proposed as different methods of controlling the DVR. The basis of the proposed control strategy in this paper is that when the fault current does not pass through the DVR, an outer feedback loop of the load voltage with an inner feedback loop of the filter 312 | P a g e
  • 2. Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317 capacitor current will be used. Also, a feed forward loop will be used to improve the dynamic response of the load voltage. Moreover, to improve the transient response, the Posicast controller and to eliminate the steady-state error, the P+Resonant controller are used. But in case the fault current passes through the DVR, using the flux control algorithm [11], the series voltage is injected in the opposite direction and, therefore, the DVR acts like series variable impedance. II. disturbance compensation process. In particular, if capacitors are used as energy storage, the DC-link voltage will decrease with the dwindling storage energy during compensation. Dynamic Voltage Restorer Dynamic voltage restorer was originally proposed to compensate for voltage disturbances on distribution systems. A typical DVR scheme is shown in Fig. 1. The restoration is based on injecting AC voltages in series with the incoming three-phase network, the purpose of which is to improve voltage quality by adjustment in voltage magnitude, waveshape, and phase shift. As shown in Fig. 1, the DVR essentially consists of a series-connected injection transformer Ti, a voltage-source inverter (VSI), a harmonic filter, and an energy storage device [4], [13]. Meanwhile, a parallel switch is used to bypass and protect the DVR, when a downstream fault is detected [14], [15]. As shown in Fig. 1, the line-side harmonic filter topology [11] consists of the leakage inductance of the injection transformer and the filter capacitor. Meanwhile, denotes the dc-link capacitor. The series injected voltage of the DVR, Vdvr, is synthesized by modulating pulse widths of the inverter-bridge switches. The injection of an appropriate Vdvr in the face of an up-stream voltage disturbance requires a certain amount of real and reactive power supply from the DVR. The reactive power requirement is generated by the inverter. Fig. 2; Vector Diagram of Voltage Injection Method The corresponding phasor diagram describing the electrical conditions during voltage sag is depicted, where only the affected phase is shown for clarity. Let the voltage quantities Il, φ, δ and α represent the load current, load power factor angle, supply voltage phase angle and load voltage advance angle respectively. Although there is a phase advancement of α in the load voltage with respect to the pre-sag voltage in Fig. 2, only in-phase compensation where the injected voltage is in phase with the supply voltage (α = δ) is considered. By mounting the battery in DC link of the centralized inverter, the DC/DC converter for battery can be saved as shown in Figure 1(b) [1], [2]. Different from the centralized inverters in Figure 1(a) and (b), the separate grid inverters are used by the two PV systems in Figure 1(c). Thus, the power rating of each inverter becomes smaller, and the inverter is intended to be modular design as well as mass production. III. Fig. 1: schematic diagram of the DVR with line side harmonic filter Proposed Multifunctional DVR In addition to the aforementioned capabilities of DVR, it can be used in the mediumvoltage level as in Fig. 2 to protect a group of consumers when the cause of disturbance is in the downstream of the DVR’s feeder and the large fault current passes through the DVR itself. In this case, the equipment can limit the fault current and protect the loads in parallel feeders until the breaker works and disconnects the faulted feeder. Widely used in present DVR control is the so-called in phase voltage injection technique where the load voltage V2 is assumed to be in-phase with the pre-sag voltage. As the DVR is required to inject active power into the distribution line during the period of compensation, the capacity of the energy storage unit can become a limiting factor in the www.ijera.com 313 | P a g e
  • 3. Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317 Fig. 2: A multifunctional DVR connected in a medium-voltage level power system. The large fault current will cause the PCC voltage to drop and the loads on the other feeders connected to this bus will be affected. Furthermore, if not controlled properly, the DVR might also contribute to this PCC voltage sag in the process of compensating the missing voltage, hence further worsening the fault situation [11]. To limit the fault current, a flux-charge model has been proposed and used to make DVR act like a pure virtual inductance which does not take any real power from the external system and, therefore, protects the dc-link capacitor and battery as shown in Fig. 1 [11]. But in this model, the value of the virtual inductance of DVR is a fixed one and the reference of the control loop is the flux of the injection transformer winding, and the PCC voltage is not mentioned in the control loop. In this paper, the PCC voltage is used as the main reference signal and the DVR acts like variable impedance. For this reason, the absorption of real power is harmful for the battery and dc-link capacitor. To solve this problem, impedance including a resistance and an inductance will be connected in parallel with the dc-link capacitor. This capacitor will be separated from the circuit, and the battery will be connected in series with a diode just when the downstream fault occurs so that the power does not enter the battery and the dclink capacitor. It should be noted here that the inductance is used mainly to prevent large oscillations in the current. The active power mentioned is, therefore, absorbed by the impedance. 3.1 Proposed control scheme for using Flux charge model In this part, an algorithm is proposed for the DVR to restore the PCC voltage, limit the fault current, and, therefore, protect the DVR components. The flux-charge model here is used in a way so that the DVR acts as a virtual inductance with a variable value in series with the distribution feeder. To do this, the DVR must be controlled in a way to inject a proper voltage having the opposite polarity with www.ijera.com respect to usual cases. It should be noted that over current tripping is not possible in this case, unless additional communication between the DVR and the downstream side over current circuit breaker (CB) is available. If it is necessary operate the over current CB at PCC, communication between the DVR and the PCC breaker might have to be made and this can be easily done by sending a signal to the breaker when the DVR is in the fault-current limiting mode as the DVR is just located after PCC [11]. The proposed DVR control method is illustrated in Fig. 8. It should also be noted that the reference flux (𝜙 𝑟𝑒𝑓 ) is derived by integration of the subtraction of the PCC reference voltage (𝑉 ∗ ) and the DVR load-side voltage. This 𝑃𝐶𝐶 control strategy, the control variable used for the outer flux model is the inverter-filtered terminal flux defined as: (1) Where 𝑉 𝑜𝑑𝑣𝑟 is the filter capacitor voltage of the DVR (at the DVR power converter side of the injection transformer). The flux error is then fed to the flux regulator, which is a P+Resonant controller, with a transfer function given in (1). On the other hand, it can be shown that a single flux-model would not damp out the resonant peak of the LC filter connected to the output of the inverter. Fig. 3: Proposed method. To stabilize the system, an inner charge model is therefore considered. In this loop, the filter inductor charge, which is derived by integration of its current, tracks the reference charge output of the flux regulator. The calculated charge error is then fed to the charge regulator with the transfer function This is actually a practical form of the derivative controller. In this transfer function, the regulator gain is limited to N at high frequencies to prevent noise amplification. The derivative term in 𝑆 + 𝑆 neutralizes the effects of voltage and 1 𝑁 current integrations at the inputs of the flux-charge model, resulting in the proposed algorithm having the same regulation performance as the multiloop voltage-current feedback control, with the only difference being the presence of an additional low– pass filter in the flux control loop in the form of 1 + 𝑆 . The bandwidth of this low–pass filter is 𝑆 𝑁 314 | P a g e
  • 4. Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317 tuned (through varying N) with consideration for measurement noise attenuation, DVR LC-filter transient resonance attenuation, and system stability margins. 4.1 Fault Current Limiting Fig. 4: Multi-loop control using the Posicast and P+Resonant controller Theoretically, the resonant controller compensates by introducing an infinite gain at the resonant frequency of 50 Hz to force the steady-state voltage error to zero. The ideal resonant controller, however, acts like a network with an infinite quality factor, which is not realizable in practice. A more practical (nonideal) compensator is therefore used here, and is expressed as Where 𝑤 𝑐𝑢𝑡 is the compensator cutoff frequency which is 1 rad/s in this application. Fig. 5: Open loop control using the Posicast controller To improve the damping, as shown in Fig. 4, the Posicast controller can be used just before transferring the signal to the PWM inverter of the DVR. The transfer function of the controller can be described as follows: Where 𝛿 and 𝑇 𝑑 are the step response overshoot and the period of damped response signal, respectively. It should be noted that the Posicast controller has limited high-frequency gain; hence, low sensitivity to noise. IV. Fig. 6: SIMULINK Model of Proposed a Multifunctional DVR under Three Phase Fault condition. MATLAB/simulink model of proposed multifunctional DVR under three phase fault in figure.6; The last simulation is run for a symmetrical downstream fault, and the capability of the DVR to reduce the fault current and restore the PCC voltage is tested. For the simulation with DVR compensation, the three-phase fault is applied at t = 205 ms and then removed after 0.1 s. Also, a breaker will remove the faulted bus from the entire system at t = 300 ms. Fig. 13 shows the DVR operation during the fault. As can be seen, the rms load bus voltage reaches zero during the fault, and as the enlarged figure shows, in about half a cycle, the DVR has succeeded in restoring the PCC voltage wave shape to the normal condition. It should be noted that the amount and shape of the oscillations depend on the time of applying the fault. As Fig. 13 shows, at this time, the voltage value of phase B is nearly zero; this MATLAB/Simulink modelling and results In this section, the proposed DVR topology and control algorithm will be used for emergency control during the voltage sag. The three-phase short circuit and the start of a three-phase large induction motor will be considered as the cause of distortion in the simulations. www.ijera.com 315 | P a g e
  • 5. Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317 Fig. 8: SIMULINK model of proposed a multifunctional DVR with Induction Motor. During this period, the PCC bus is under voltage sag. From t = 1.4 s, as the speed approaches nominal, the voltage also approaches the normal condition. However, during all of these events, the DVR keeps the load bus voltage at the normal condition. The DVR has succeeded in restoring the load voltage in half a cycle from the instant of the motor starting. Fig. 7: Fault current limiting by DVR. (a) Threephase PCC voltages. (b) Three-phase load voltages. (c) RMS voltages of the PCC and load. (d) Threephase currents. 4.2 Induction Motor The large motor starting current will cause the PCC voltage to drop. The simulation results in the case of using the DVR are shown in Fig. 9. In this simulation, the motor is started at t = 405 ms. As can be seen in Fig. 11, at this time, the PCC rms voltage drops to about 0.8 p.u. The motor speed reaches the nominal value in about 1 s. MATLAB/simlink model of proposed multifunctional DVR with induction motor in figure8; Fig. 9: Starting of an induction motor and the DVR compensation. (a) Three phase PCC voltages. (b) Three-phase load voltages. (c) RMS voltages of PCC and load. www.ijera.com 316 | P a g e
  • 6. Salava V Satyanarayana et al Int. Journal of Engineering Research and Applications www.ijera.com ISSN : 2248-9622, Vol. 4, Issue 1( Version 1), January 2014, pp.312-317 V. CONCLUSION In this paper, a multifunctional DVR is proposed, and a closed-loop control system is used for its control to improve the damping of the DVR response. Also, for further improving the transient response and eliminating the steady-state error, the Posicast and P+Resonant controllers are used. As the second function of this DVR, using the flux-charge model, the equipment is controlled so that it limits the downstream fault currents and protects the PCC voltage during these faults by acting as variable impedance. The problem of absorbed active power is solved by entering impedance just at the start of this kind of fault in parallel with the dc-link capacitor and the battery being connected in series with a diode so that the power does not enter it. The simulation results verify the effectiveness and capability of the proposed DVR in compensating for the voltage sags caused by short circuits and the large induction motor starting and limiting the downstream fault currents and protecting the PCC voltage. [8] [9] [10] [11] [12] REFERENCE [1] [2] [3] [4] [5] [6] [7] A. K. Jindal, A. Ghosh, and A. Joshi, ―Critical load bus voltage control using DVR under system frequency variation,‖ Elect. Power Syst. Res., vol. 78, no. 2, pp. 255– 263, Feb. 2008. J. A. Martinez and J. Martin-Arnedo, ―Voltage sag studies in distribution networks- part II: Voltage sag assessment,‖ IEEE Trans. Power Del., vol. 21, no. 3, pp. 1679–1688, Jul. 2006. S. S. Choi, B. H. Li, and D. M. Vilathgamuwa, ―Dynamic voltage restoration with minimum energy injection,‖ IEEE Trans. Power Syst., vol. 15, no. 1, pp. 51–57, Feb. 2000. C. Fitzer, M. Barnes, and P. Green, ―Voltage sag detection technique for a dynamic voltage restore,‖ IEEE Trans. Ind. Appl., vol. 2, no. 1, pp. 203–212, Jan./Feb. 2004. Y. W. Li, D. M. Vilathgamuwa, F. Blaabjerg, and P. C. Loh, ―A robust control scheme for medium-voltage-levelDVR implementation,‖ IEEE Trans. Ind. Electron., vol. 54, no. 4, pp. 2249–2261, Aug. 2007. M. Vilathgamuwa, A. A. D. R. Perera, and S. S. Choi, ―Performance improvement of the dynamic voltage restorer with closedloop load voltage and current-mode control,‖ IEEE Trans. Power Electron., vol. 17, no. 5, pp. 824–834, Sep. 2002. M. J. Newman, D. G. Holmes, J. G. Nielsen, and F. Blaabjerg, ―A dynamic voltage restorer (DVR) with selective harmonic www.ijera.com [13] [14] [15] [16] compensation at medium voltage level,‖ IEEE Trans. Ind. Appl., vol. 41, no. 6, pp. 1744–1753, Nov./Dec. 2005. M. H. Rashid, Power Electronics-Circuits, Devices and Applications, 3rd ed. India: Prentice-Hall of India, Aug. 2006. S. S. Choi, B. H. Li, and D. M. Vilathgamuwa, ―Dynamic voltage restoration with minimum energy injection,‖ IEEE Trans. Power Syst., vol. 15, no. 1, pp. 51–57, Feb. 2000. H. Awad, J. Svensson, and M. Bollen, ―Mitigation of unbalanced voltage dips using static series compensator,‖ IEEE Trans. Power Electron., vol. 1, no. 3, pp. 837–846, May 2004. B. Delfino, F. Fornari, and R. Procopio, ―An effective SSC control scheme for voltage sag compensation,‖ IEEE Trans. Power Del., vol. 20, no. 3, pp. 2100–2107, Jul. 2005. S. S. Choi, T. X. Wang, and D. M. Vilathgamuwa, ―A series compensator with fault current limiting function,‖ IEEE Trans. Power Del., vol. 20, no. 3, pp. 2248–2256, Jul. 2005. V. K. Ramachandaramurthy, C. Fitzer, A. Arulampalam, C. Zhan, M. Barnes, and N. Jankins, ―Control of a battery supported dynamic voltage restorer,‖ Proc. Inst. Elect. Eng., Gen. Transm. Distrib., vol. 149, no. 5, pp. 533–542, Sep. 2002. D. M. Vilathgamuwa, H. M. Wijekoon, and S. S. Choi, ―A novel technique to compensate voltage sags in multiline distribution system—the interline dynamic voltage restorer,‖ IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 1603–1611, Oct. 2006. N. G. Hingorani, ―Introducing custom power,‖ IEEE Spectr., vol. 32, no. 6, pp. 41– 48, Jun. 1995. B. H. Li, S. S. Choi, and D. M. Vilathgamuwa, ―Design considerations on the line-side filter used in the dynamic voltage restorer,‖ Proc. Inst. Elect. Eng., Gen. Transm. Distrib., vol. 148, no. 1, pp. 1– 7, Jan. 2001. 317 | P a g e