Microsoft word ms11 chapter 2 equipment selection-tcm135-60924

MS11 Split inverter course

Daikin Europe NV

2

Equipment selection

What is in this chapter?

Introduction

Selecting the right unit for the right application can prevent a lot of problems.
In this chapter we would like to introduce you to information which will help
you select the correct unit. However, even with the right unit, there will still
be some points of attention, which will have to be taken into account.

Overview

This chapter covers the following topics
Topic

See Page

2.1 Selection specifications
2.2 Combination possibilities
2.3 Installation specifications
2.4 Application precautions

CHAPTER 2: Equipment selection

2- 1
MS11 Split inverter course

Daikin Europe NV

2.1 Selection specifications

Overview

This chapter covers the following topics

2.1.1
2.1.2
2.1.3
2.1.4
2.1.5

Topic
Non inverters
Inverters
Correction factors
Capacity tables
Attention points in selection

CHAPTER 2: Equipment selection

See Page

2- 2
MS11 Split inverter course

Daikin Europe NV

2.1.1 Non inverters

Introduction

You should select a unit by comparing the (maximum possible) heat load of a
room to the nominal capacity of a unit.
If your heat load is much larger than your nominal capacity, you will have
capacity shortage complaints.
If your heat load is much smaller than the nominal capacity, your unit will
switch on/off a lot, which has a negative effect on the lifetime of a unit.

Capacity table

Global Mini Split
Unit

FT(Y)N50EV1B
FT(Y)N60EV1B

Mode

Cooling
Heating
Cooling
Heating

CHAPTER 2: Equipment selection

Nominal Capacity [kW]

5.0
5.8
6.0
7.0

2- 3
MS11 Split inverter course

Daikin Europe NV

2.1.2 Inverters (DC inverter)

Introduction

When selecting an inverter controlled A/C unit, it is of the up most
importance to select a unit with a nominal capacity as close as possible to the
heat load of the room. When selecting a unit, which is too small, the
compressor will operate continuously on its maximum frequency like a non
inverter. If you select a unit that has too much capacity, the minimum
frequency of the compressor can still generate too much capacity and switch
the compressor on/off like a non inverter. You can see that in both these
cases an inverter has no added value compared to a non inverter which is a lot
cheaper.

Minimum
capacity

When the unit is in thermostat ON, there is a minimum compressor frequency
and a minimum expansion valve opening. If the required capacity is below
the minimum capacity of the compressor, the unit will switch ON-OFF.

Maximum
capacity

When a unit runs at its maximum frequency and the expansion valve is
opened to the maximum the unit will give its maximum capacity. (For the
mentioned indoor/outdoor and accordingly to the installation conditions.)
However it is very important that you realize that this will not always be
the case, even when the capacity demand is high. The unit is controlled by
a micro-controller and the micro-controller will take all factors into account
(capacity demand, safeties, efficiency, sensors, etc. …) and then decide the
best frequency. If you combine this together with piping length losses, it is
very likely that when you select a unit on the maximum capacity you will
have complaints of capacity shortage.
Continued on the next page

CHAPTER 2: Equipment selection

2- 4
MS11 Split inverter course

Daikin Europe NV

2.1.2 Inverters (DC inverter), continued

Capacity table

Global Mini Split
Unit

Mode
Minimum

FTK/XS50EV1B
FTK/XS60EV1B
FTK/XS71EV1B
FTXG25EV1BW/S
FTXG35EV1BW/S
CTXG50EV1BW/S
ATXG25EV1B
ATXG35EV1B
ATXG50E2V1B
FDK/XS25EVMB
FDK/XS35EVMB
ATK/XS20E2V1B
ATK/XS25E2V1B
ATK/XS35E2V1B
ATXS50E2V1B

Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating
Cooling
Heating

2.0
2.0
2.0
2.0
4.0
4.0
1.3
1.3
1.4
1.4
?
?
?
?
?
?
?
?
1.3
1.3
1.4
1.4
1.3
1.3
1.3
1.3
1.4
1.4
2.0
2.0

Capacity [kW]
Nominal Maximum
5.0
5.8
6.0
7.0
7.1
8.2
2.5
3.4
3.5
4.2
?
?
?
?
?
?
?
?
2.4
3.2
3.4
4.1
2.0
2.7
2.5
3.4
3.4
4.0
5.0
5.8

6.0
7.7
6.7
8.0
8.5
10.0
3.0
4.5
4.8
5.0
?
?
?
?
?
?
?
?
3.0
4.5
3.8
5.0
2.6
4.1
3.0
4.5
3.8
5.0
5.2
6.0

Continued on the next page

CHAPTER 2: Equipment selection

2- 5
MS11 Split inverter course

Daikin Europe NV

2.1.3 Correction factors

Correction factors

When the piping exceeds a certain length, a correction factor has to be
multiplied with the rated capacity.
The cooling and the heating capacity of the unit have to be corrected in
accordance with the length of the refrigerant piping. (The distance between
the indoor unit and the outdoor unit)

Fig.:

CHAPTER 2: Equipment selection

2- 6
MS11 Split inverter course

Daikin Europe NV

2.1.4 Capacity tables

Introduction

For the Multi outdoor units, when your connection ratio goes above 100%,
the minimum, nominal and maximum capacities will lower (only when the
capacity demand of the indoor units is greater than the outdoor unit can
deliver). What your minimum, nominal and maximum capacity will be when
this happens, you can read out on the capacity tables. (Engineering Databook)
The maximum allowed connection ratios are
Modelname
2(A)MXS52EV1B
3MKS50E2V1B
3(A)MXS52E2V1B
4MKS58E2V1B
4MXS68E2V1B
4MKS75E2V1B
4MXS80E7V3B
5MKS90E7V3B
5MXS90E7V3B

Max. connectable
capacity (kW)
8.5
9.5
9.0
10.0
11.0
13.5
14.5
15.6
15.6

For the C/O units, there’s an additional function programmed that will limit
the operation of units when you connect more than the allowed capacity.
When an indoor unit is switched on, over sizing the allowed operational
capacity of a C/O multi, the last unit which is turned ON will go into stand-by
mode (slowly blinking indoor operation LED). It will only resume operation
once operation in the other rooms (or one room) has stopped.
This function has been added to prevent the compressor from overheating
(overload clixon).

CHAPTER 2: Equipment selection

2- 7
MS11 Split inverter course

Daikin Europe NV

2.1.5 Selection attention points

Introduction

When selecting a model there are some points of attention. You should
select your type of unit and installation place carefully.

Selection
according to
room type.

Living room

Bedroom

Selection
according to air
circulation for
different room
types.

Selection
according to air
circulation
distinctive to the
different air
conditioning
types.

Rectangular
rooms
Long rooms,
Odd shaped
rooms
Wall mounted
type

Floor type

Ceiling hung
type

this is often used from morning to night,
an energy saving unit would be
recommended
It is important to select an air conditioner,
which is quiet and does not blow (draft)
directly onto the occupants.
Install the unit so it blows into the length
of the room.
Install separate units to blow air through
the room.
Install separate units to prevent air
accumulation in one place.
This type of unit allows great air
circulation in cooling, this due to its high
position. This position is however a
disadvantage for heating, as heat rises,
stratification is possible.

This type of unit is more suitable for
heating applications than cooling
applications. Since hot air rises there are
few temperature differences between
heights.
This type of unit can be put in a central
position in the room, allowing a good air
circulation.

CHAPTER 2: Equipment selection

2- 8
MS11 Split inverter course

Daikin Europe NV

2.2 Combination possibilities

Introduction

On the following page you will find our combination table. These pictograms
point out the possibilities as well as the limitations of the combinations. Also
a file which is named FAQ (Frequently Asked Questions) is added. This will
give you some more clarification why certain specific combinations are not
possible.

CHAPTER 2: Equipment selection

2- 9
MS11 Split inverter course

Daikin Europe NV

2.3 Installation specifications

Introduction

This chapter gives a summary of the basic technical specifications concerning
piping which are essential to a decent installation. All this information can be
found back in the installation manual of the specific unit.

Overview

Topic

See Page

RYN50/60E2V1B
(A)RK/XS50/60/71E2V1B
(A)RXG25/35E(2)V1B
ARK/XS20/25/35E2V1B
2(A)MXS52E2V1B, 3(A)MK/XS50/52E2V1/MB,
4MKS58E2V1B
4MK/X58/68E2V1B
5MK/XS90E7V3B, 4MXS80E7V3B
Additional explanation on installation comments

CHAPTER 2: Equipment selection

2- 10
MS11 Split inverter course

Daikin Europe NV

RYN50/60E2V1B

Pipe sizes

The table below shows the available piping connections.

Liquid line
Gas line

RYN50/60E2V1B
6.4 mm
12.7 mm

Table : piping dimensions

Piping lengths

The table below shows the maximum allowed piping lengths.

Total length
Level difference

RYN50/60E2V1B
30 m
20 m

Table: piping lengths

Additional
refrigerant
charge

For the RYN50/60E2V1B add 20 g/m when piping exceeds 10 m.

Fuses

Daikin recommends using a 20A safety breaker.

Continued on the next page

CHAPTER 2: Equipment selection

2- 11
MS11 Split inverter course

Daikin Europe NV

RYN50/60E2V1B, continued

Installation
space

Fig.: Outdoor unit positioning

CHAPTER 2: Equipment selection

2- 12
MS11 Split inverter course

Daikin Europe NV

(A)RK/XS50/60/71E2V1B

Pipe sizes

The tables below show the available piping connections

Liquid line (mm)
Gas line (mm)

(A)RK/XS50/60E2V1B RK/XS71E2V1B
6.4 mm
12.7 mm
15.9 mm

Table : Piping dimensions

Piping lengths

The table below shows the maximum allowed piping lengths.

Total length
Level difference

(A)RK/XS20/25/35DVMB
30 m
20 m

Table: Piping lengths

Additional
refrigerant
charge

Add 20 g/m when piping length exceeds 10 m.

Fuses

Daikin recommends using a 20 A safety breaker.
Continued on the next page

CHAPTER 2: Equipment selection

2- 13
MS11 Split inverter course

Daikin Europe NV

(A)RK/XS50/60/71E2V1B, continued

Installation
space

Fig.: Outdoor unit positioning

CHAPTER 2: Equipment selection

2- 14
MS11 Split inverter course

Daikin Europe NV

(A)RXG25/35E(2)V1B

Pipe sizes

The tables below show the available piping connections

Liquid line (mm)
Gas line (mm)

Piping lengths

(A)RXG25/35E(2)V1B
6.4 mm
9.5 mm

The table below shows the maximum allowed piping lengths.

Total length
Level difference

(A)RXG25/35E(2)V1B
20 m
15

Table: Piping lengths

Additional
refrigerant
charge

Add 20 g/m when piping length exceeds 10 m.

Fuses

Daikin recommends using a 16 A safety breaker.
Continued on next page

CHAPTER 2: Equipment selection

2- 15
MS11 Split inverter course

Daikin Europe NV

(A)RXG25/35E(2)V1B, Continued

Installation
space

CHAPTER 2: Equipment selection

2- 16
MS11 Split inverter course

Daikin Europe NV

ARK/XS20/25/35E2V1B

Pipe sizes

The tables below show the available piping connections

Liquid line (mm)
Gas line (mm)

Piping lengths

ARK/XS20/25/35E2V1B
6.4 mm
9.5 mm

The table below shows the maximum allowed piping lengths.

Total length
Level difference

(A)RXG25/35E(2)V1B
20 m
15

Table: Piping lengths

Additional
refrigerant
charge

Add 20 g/m when piping length exceeds 10 m.

Fuses

Daikin recommends using a 16 A safety breaker.
Continued on next page

CHAPTER 2: Equipment selection

2- 17
MS11 Split inverter course

Daikin Europe NV

ARK/XS20/25/35E2V1B, Continued

Installation
space

CHAPTER 2: Equipment selection

2- 18
MS11 Split inverter course

Daikin Europe NV

2(A)MXS52E2V1B, 3MXS52E2V1B, 3(A)MKS50E2V1B,
4MKS58E2V1B.

Pipe sizes

The tables below show the available piping connections
2(A)MXS52E2V1B/3MXS52E2V1B/3(A)MK
S50E2V1B/4MKS58E2V1B
Liquid line
Gas line

6.4 – 9.5 – 12.7 – 15.9

Table : Piping dimensions

Piping lengths

The table below shows the maximum allowed piping lengths.
2(A)MXS52E2V1B/3MXS52E2V1B/3(A)
MKS50E2V1B/4MKS58E2V1B
Piping to each indoor
25 m
Total piping
50 m
Min piping length to each indoor
3m
Max. level difference between 2
7.5 m
indoors if the outdoor is
positioned higher than all the
indoors
Max. level difference between 2
15 m
indoor units if the outdoor is
lower than 1 or more indoors
Max level difference between
7.5 m
indoor/outdoor if the outdoor is
lower than 1 or more indoors
Table: Piping lengths

Additional
refrigerant
charge

Add 20 g/m when total piping length exceeds 30 m.

Fuses

Daikin recommends using a ? A safety breaker. (2MK/XS40DVMB)

Continued on the next page

CHAPTER 2: Equipment selection

2- 19
MS11 Split inverter course

Daikin Europe NV

2(A)MXS52E2V1B, 3MXS52E2V1B, 3(A)MKS50E2V1B,
4MKS58E2V1B., continued

Installation
space

Fig.: Outdoor unit positioning

CHAPTER 2: Equipment selection

2- 20
MS11 Split inverter course

Daikin Europe NV

4MXS68E2V1B, 4MKS58E2V1B,

Pipe sizes

The tables below show the available piping connections.

Liquid line(mm)
Gas line (mm)

4MKS58D
6.4 / 6.4 / 6.4 / 6.4
9.5 / 9.5 / 12.7 / 12.7

4MXS68D
6.4 / 6.4 / 6.4 / 6.4
9.5 / 9.5 / 12.7 / 12.7

Table : Piping dimensions

Piping lengths

The table below shows the maximum allowed piping lengths.
4MKS58D
Max. piping to each indoor
Max. level difference between 2
indoors if the outdoor is positioned
higher than all the indoors
Max. level difference between 2 indoor
units if the outdoor is lower than 1 or
more indoors
Max
level
difference
between
indoor/outdoor if the outdoor is lower
than 1 or more indoors
Total length of piping

4MXS68D
25
7.5

15 m

7.5 m

60

Table: Piping lengths

Additional
refrigerant
charge

Add 20 g/m when total piping length exceeds 30 m.
Cooling only units are chargeless! There is no need for additional refrigerant!

Fuses

Daikin recommends using a ?? A safety breaker.
Continued on next page

CHAPTER 2: Equipment selection

2- 21
MS11 Split inverter course

Daikin Europe NV

4MXS68E2V1B, 4MKS58E2V1B,, Continued

Installation
space

Fig.: Outdoor unit positioning

CHAPTER 2: Equipment selection

2- 22
MS11 Split inverter course

Daikin Europe NV

5MKS90E7V3B, 5MXS90E7V3B, 4MXS80 E7V3B,

Pipe sizes

The tables below show the available piping connections

Liquid line (mm)
Gas line (mm)

5MKS90E7V3B, 5MXS90E7V3B,
4MXS80 E7V3B
6.4
9.5 / 9.5 / 12.7 / 15.9 (/ 15.9)

Table : Piping dimensions

Piping lengths

The table below shows the maximum allowed piping lengths.
4MXS80 E7V3B
Max. piping to each indoor
Max. level difference between 2
indoors if the outdoor is positioned
higher than all the indoors
Max. level difference between 2
indoor units if the outdoor is lower
than 1 or more indoors
Max level difference between
indoor/outdoor if the outdoor is lower
than 1 or more indoors
Total length of piping
Min piping length to one indoor unit

25 m
7.5 m

5MKS90E7V3B,
5MXS90E7V3B
25 m
7.5 m

15 m

15 m

7.5 m

7.5 m

70 m
3m

75 m
3m

Table: Piping lengths

Additional
comments

•
•

Always connect a minimum of 2 rooms for heat pump systems.
The shortest allowable length per room is 3 m.

Additional
refrigerant
charge

•
•

Add 20 g/m when total piping length exceeds 30 m.
For cooling only models, there’s no need to additionally charge. ???(see
installation manual)
Continued on the next page

CHAPTER 2: Equipment selection

2- 23
MS11 Split inverter course

Daikin Europe NV

4MKS90DVMB, 4MXS80DVMB, continued

Fuse

Daikin recommends a 20 A fuse

Installation
space

Fig.: Outdoor unit positioning

CHAPTER 2: Equipment selection

2- 24
MS11 Split inverter course

Daikin Europe NV

Additional comments on installation specifications

Installation
Manual

Additional refrigerant is necessary when the piping exceeds a certain
length. For the multi units however you don’t need to add any
refrigerant for C/O units.

Explanation

The evaporator regulates the superheat (SH), the larger your evaporating
capability (fan speed, size heat exchanger, heat exchanging capability) the
larger your SH will be.
The condenser regulates your subcool (SC), which is needed for the
expansion valve to work properly.
In cooling the evaporator is the indoor coil and the condenser the outdoor
coil. This changes when the unit is in heating, so the sizes of the H/E can
change.
In heating on small loads the unit will have a small SC (low condensing
capability). When refrigerant is added the SC goes up. Adding refrigerant
also means that the SH will go down but in heating there’s a large evaporator
which can handle this surplus of refrigerant.

Installation
Manual

Always connect at least 2 rooms to a Multi.

Explanation

(Strictly speaking, for heat pump models only.)
If you connect only 1 indoor unit you will have compressor damage due to the
following reasons:
1. Abnormal high pressure
Surplus refrigerant is accumulated in the indoor unit during heating operation,
at that point, the heat exchanger thermistor is in sub cooling area and it can
not sense the saturated temperature. Therefore the safety (peak cut operation)
can not function leaving the unit prone to high pressures.
However, surplus refrigerant is accumulated in the non operating unit whilst
one unit is operating in a two unit connection in heating mode.
2. Poor lubrication by refrigerant oil
When you connect only 1 indoor unit to a multi, surplus refrigerant is
accumulated in the indoor unit or accumulator. In case the refrigerant is
accumulated in the accumulator, you’ll have wet operation and poor
lubrication and this will lead to compressor damage.
Continued on the next page

CHAPTER 2: Equipment selection

2- 25

Recomendados

Sb delta dx-dc-ver.4.0_en von
Sb delta dx-dc-ver.4.0_enSb delta dx-dc-ver.4.0_en
Sb delta dx-dc-ver.4.0_enYury Naumov
37 views4 Folien
cooling systems of transformers von
cooling systems of transformerscooling systems of transformers
cooling systems of transformersMalik Armughan
3.6K views28 Folien
VRV IV von
VRV IVVRV IV
VRV IVBENRY APRIANTO HUTAPEA
1.9K views36 Folien
Sb compact dx_ver.1.0_en von
Sb compact dx_ver.1.0_enSb compact dx_ver.1.0_en
Sb compact dx_ver.1.0_enYury Naumov
19 views4 Folien
VRF II VRV von
VRF II VRVVRF II VRV
VRF II VRVAshutosh
6K views13 Folien
Transformer_Cooling 2015 Doble LOAT Conference von
Transformer_Cooling 2015 Doble LOAT ConferenceTransformer_Cooling 2015 Doble LOAT Conference
Transformer_Cooling 2015 Doble LOAT ConferenceKevin Riley
3.5K views51 Folien

Más contenido relacionado

Was ist angesagt?

VARIABLE REFRIGERATE FLOW von
VARIABLE REFRIGERATE FLOWVARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWRIDDHESH VARIK
841 views11 Folien
Cooling of power transformer von
Cooling of power transformerCooling of power transformer
Cooling of power transformerBiswajit Pratihari
32.5K views29 Folien
Comparison between Systems von
Comparison between SystemsComparison between Systems
Comparison between SystemsVictor Ashkenazy
638 views9 Folien
Wrl hp y-na60_00 von
Wrl hp y-na60_00Wrl hp y-na60_00
Wrl hp y-na60_00Oliverh Kalprit
94 views4 Folien
Plumbing von
PlumbingPlumbing
Plumbingnickgee
980 views11 Folien
Mac 050 von
Mac 050Mac 050
Mac 050Carlos Hernandez
1.5K views53 Folien

Was ist angesagt?(20)

Plumbing von nickgee
PlumbingPlumbing
Plumbing
nickgee980 views
Method of cooling transformer by Aditya bindal von AdityaBindal6
Method of cooling transformer by Aditya bindalMethod of cooling transformer by Aditya bindal
Method of cooling transformer by Aditya bindal
AdityaBindal6166 views
Temperature Controlled DC fan using Thermistor von Zaheer Basha
Temperature Controlled DC fan using ThermistorTemperature Controlled DC fan using Thermistor
Temperature Controlled DC fan using Thermistor
Zaheer Basha24.2K views
Heat sink von Sv Anand
Heat sinkHeat sink
Heat sink
Sv Anand66 views
VARIABLE REFRIGERANT FLOW(VRF) ppt von Ezhil Raj s
VARIABLE REFRIGERANT FLOW(VRF)  pptVARIABLE REFRIGERANT FLOW(VRF)  ppt
VARIABLE REFRIGERANT FLOW(VRF) ppt
Ezhil Raj s21.3K views
Sb delta cw-cwu-ver.3.0_en von Yury Naumov
Sb delta cw-cwu-ver.3.0_enSb delta cw-cwu-ver.3.0_en
Sb delta cw-cwu-ver.3.0_en
Yury Naumov32 views
Automatic temperature based exhaust fan controller von Ecwayt
Automatic temperature based exhaust fan controllerAutomatic temperature based exhaust fan controller
Automatic temperature based exhaust fan controller
Ecwayt156 views
Presentation DCP(revised) von Daniel udau
Presentation DCP(revised)Presentation DCP(revised)
Presentation DCP(revised)
Daniel udau951 views
Blue star package units von Kumar Ramaiah
Blue star package unitsBlue star package units
Blue star package units
Kumar Ramaiah35.1K views
Rio LLC District Cooling von guestba4f28
Rio LLC  District CoolingRio LLC  District Cooling
Rio LLC District Cooling
guestba4f282.6K views
Topic 3 District Cooling System von pnnazz
Topic 3 District Cooling SystemTopic 3 District Cooling System
Topic 3 District Cooling System
pnnazz25.8K views

Destacado

University of Essex, Colchester Campus von
University of Essex, Colchester CampusUniversity of Essex, Colchester Campus
University of Essex, Colchester CampusUniversity of Essex
1.4K views65 Folien
Three Reasons Why A Ranking Drop Might Occur von
Three Reasons Why A Ranking Drop Might OccurThree Reasons Why A Ranking Drop Might Occur
Three Reasons Why A Ranking Drop Might OccurSpider India
575 views1 Folie
Bai 04 bai toan va thuat toan (t1) von
Bai 04 bai toan va thuat toan (t1)Bai 04 bai toan va thuat toan (t1)
Bai 04 bai toan va thuat toan (t1)quangaxa
866 views18 Folien
Things to consider while choosing ac dc module von
Things to consider while choosing ac  dc module Things to consider while choosing ac  dc module
Things to consider while choosing ac dc module 779061702
288 views3 Folien
Contents page analysis von
Contents page analysisContents page analysis
Contents page analysisal04929284
194 views12 Folien
Ryan air von
Ryan airRyan air
Ryan airmelisandenoelmba2
320 views11 Folien

Destacado(16)

Three Reasons Why A Ranking Drop Might Occur von Spider India
Three Reasons Why A Ranking Drop Might OccurThree Reasons Why A Ranking Drop Might Occur
Three Reasons Why A Ranking Drop Might Occur
Spider India575 views
Bai 04 bai toan va thuat toan (t1) von quangaxa
Bai 04 bai toan va thuat toan (t1)Bai 04 bai toan va thuat toan (t1)
Bai 04 bai toan va thuat toan (t1)
quangaxa866 views
Things to consider while choosing ac dc module von 779061702
Things to consider while choosing ac  dc module Things to consider while choosing ac  dc module
Things to consider while choosing ac dc module
779061702288 views
Contents page analysis von al04929284
Contents page analysisContents page analysis
Contents page analysis
al04929284194 views
Everything DiSC 363 for Leaders Sample report- Download Now! von Strengthscape
Everything DiSC 363 for Leaders Sample report-  Download Now!Everything DiSC 363 for Leaders Sample report-  Download Now!
Everything DiSC 363 for Leaders Sample report- Download Now!
Strengthscape361 views
Care IQ presentation at Big Data Expo - healthcare session von Andre van Est
Care IQ presentation at Big Data Expo - healthcare sessionCare IQ presentation at Big Data Expo - healthcare session
Care IQ presentation at Big Data Expo - healthcare session
Andre van Est572 views
Emerging Technologies von Dawn Boone
Emerging TechnologiesEmerging Technologies
Emerging Technologies
Dawn Boone364 views
Researching the market place von al04929284
Researching the market placeResearching the market place
Researching the market place
al04929284180 views
GR hart Maatschappijleer Thema multiculturele samenleving von evymaatschappijleer
GR hart Maatschappijleer Thema multiculturele samenleving GR hart Maatschappijleer Thema multiculturele samenleving
GR hart Maatschappijleer Thema multiculturele samenleving
evymaatschappijleer1.3K views
My inspirations with examples von willharold9
My inspirations with examplesMy inspirations with examples
My inspirations with examples
willharold9197 views

Similar a Microsoft word ms11 chapter 2 equipment selection-tcm135-60924

Fuji tu dong hoa catalog frenic-hvac-dienhathe.org von
Fuji tu dong hoa catalog frenic-hvac-dienhathe.orgFuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.orgDien Ha The
43 views25 Folien
VRV-A-DIDVA1808B.pdf von
VRV-A-DIDVA1808B.pdfVRV-A-DIDVA1808B.pdf
VRV-A-DIDVA1808B.pdfRahmanOde
33 views14 Folien
Điều hòa âm trần LG 36000BTU von
Điều hòa âm trần LG 36000BTUĐiều hòa âm trần LG 36000BTU
Điều hòa âm trần LG 36000BTUMyravn1
1.7K views23 Folien
Rtx 17-23 y-un50_00 von
Rtx 17-23 y-un50_00Rtx 17-23 y-un50_00
Rtx 17-23 y-un50_00Oliverh Kalprit
86 views4 Folien
04 V4- K TSM 380V 50Hz.pdf von
04 V4- K TSM 380V 50Hz.pdf04 V4- K TSM 380V 50Hz.pdf
04 V4- K TSM 380V 50Hz.pdfAirconDoctor
11 views169 Folien
Ecs 5M Manual von
Ecs 5M ManualEcs 5M Manual
Ecs 5M ManualPig Farm Solution
278 views52 Folien

Similar a Microsoft word ms11 chapter 2 equipment selection-tcm135-60924(20)

Fuji tu dong hoa catalog frenic-hvac-dienhathe.org von Dien Ha The
Fuji tu dong hoa catalog frenic-hvac-dienhathe.orgFuji tu dong hoa catalog frenic-hvac-dienhathe.org
Fuji tu dong hoa catalog frenic-hvac-dienhathe.org
Dien Ha The43 views
VRV-A-DIDVA1808B.pdf von RahmanOde
VRV-A-DIDVA1808B.pdfVRV-A-DIDVA1808B.pdf
VRV-A-DIDVA1808B.pdf
RahmanOde33 views
Điều hòa âm trần LG 36000BTU von Myravn1
Điều hòa âm trần LG 36000BTUĐiều hòa âm trần LG 36000BTU
Điều hòa âm trần LG 36000BTU
Myravn11.7K views
04 V4- K TSM 380V 50Hz.pdf von AirconDoctor
04 V4- K TSM 380V 50Hz.pdf04 V4- K TSM 380V 50Hz.pdf
04 V4- K TSM 380V 50Hz.pdf
AirconDoctor11 views
Sb ls scroll-uc_ver.3.0_en von Yury Naumov
Sb ls scroll-uc_ver.3.0_enSb ls scroll-uc_ver.3.0_en
Sb ls scroll-uc_ver.3.0_en
Yury Naumov20 views
Sb ls scroll_ver.3.0_en von Yury Naumov
Sb ls scroll_ver.3.0_enSb ls scroll_ver.3.0_en
Sb ls scroll_ver.3.0_en
Yury Naumov27 views
Catalog Biến tần Frenic-HVAC (Fuji Electric) von Beeteco
Catalog Biến tần Frenic-HVAC (Fuji Electric)Catalog Biến tần Frenic-HVAC (Fuji Electric)
Catalog Biến tần Frenic-HVAC (Fuji Electric)
Beeteco815 views
Sb ls screw-fixed-speed_ver.3.0_en von Yury Naumov
Sb ls screw-fixed-speed_ver.3.0_enSb ls screw-fixed-speed_ver.3.0_en
Sb ls screw-fixed-speed_ver.3.0_en
Yury Naumov26 views
Sb ls screw-inverter_ver.3.0_en von Yury Naumov
Sb ls screw-inverter_ver.3.0_enSb ls screw-inverter_ver.3.0_en
Sb ls screw-inverter_ver.3.0_en
Yury Naumov28 views
Ventilation von Dantherm
VentilationVentilation
Ventilation
Dantherm1.6K views
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb... von Ingeteam Wind Energy
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...
PES Wind Magazine - New-generation DFIG power converters for 6-8 MW wind turb...
Estrategias para ahorro de energía en applicaciones de misión crítica de IT von Data Center Consultores
Estrategias para ahorro de energía en applicaciones de misión crítica de ITEstrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de IT
Wiring diagram krisbow 26 13 von -
Wiring diagram krisbow 26 13Wiring diagram krisbow 26 13
Wiring diagram krisbow 26 13
-7.7K views

Último

Super Solar Mounting Solutions 20230509(1).pdf von
Super Solar Mounting Solutions 20230509(1).pdfSuper Solar Mounting Solutions 20230509(1).pdf
Super Solar Mounting Solutions 20230509(1).pdfcarrie55bradshaw
15 views25 Folien
Cohen_Summit 2023-FINAL.pptx von
Cohen_Summit 2023-FINAL.pptxCohen_Summit 2023-FINAL.pptx
Cohen_Summit 2023-FINAL.pptxbradgallagher6
52 views45 Folien
auto dialer aegis.pdf von
auto dialer aegis.pdfauto dialer aegis.pdf
auto dialer aegis.pdfVoiceLogger1
17 views1 Folie
Integrating Talent Management Practices von
Integrating Talent Management PracticesIntegrating Talent Management Practices
Integrating Talent Management PracticesSeta Wicaksana
161 views29 Folien
Steele_D&O Summit Keynote.pptx von
Steele_D&O Summit Keynote.pptxSteele_D&O Summit Keynote.pptx
Steele_D&O Summit Keynote.pptxbradgallagher6
13 views16 Folien
port23_2023121_resize2.pdf von
port23_2023121_resize2.pdfport23_2023121_resize2.pdf
port23_2023121_resize2.pdfSivaphan Wuttingam
38 views64 Folien

Último(20)

Super Solar Mounting Solutions 20230509(1).pdf von carrie55bradshaw
Super Solar Mounting Solutions 20230509(1).pdfSuper Solar Mounting Solutions 20230509(1).pdf
Super Solar Mounting Solutions 20230509(1).pdf
carrie55bradshaw15 views
Integrating Talent Management Practices von Seta Wicaksana
Integrating Talent Management PracticesIntegrating Talent Management Practices
Integrating Talent Management Practices
Seta Wicaksana161 views
Nevigating Sucess.pdf von TEWMAGAZINE
Nevigating Sucess.pdfNevigating Sucess.pdf
Nevigating Sucess.pdf
TEWMAGAZINE29 views
Navigating the Complexity of Derivatives Valuation 📈 von ValAdvisor
Navigating the Complexity of Derivatives Valuation 📈Navigating the Complexity of Derivatives Valuation 📈
Navigating the Complexity of Derivatives Valuation 📈
ValAdvisor18 views
Navigating EUDR Compliance within the Coffee Industry von Peter Horsten
Navigating EUDR Compliance within the Coffee IndustryNavigating EUDR Compliance within the Coffee Industry
Navigating EUDR Compliance within the Coffee Industry
Peter Horsten82 views
[1Slide] Event Report AWS ReInvent 2023 - Q stands out von Holger Mueller
[1Slide] Event Report AWS ReInvent 2023 - Q stands out[1Slide] Event Report AWS ReInvent 2023 - Q stands out
[1Slide] Event Report AWS ReInvent 2023 - Q stands out
Holger Mueller15 views
Hoole_Summit 2023 - Opening Remarks.pptx von bradgallagher6
Hoole_Summit 2023 - Opening Remarks.pptxHoole_Summit 2023 - Opening Remarks.pptx
Hoole_Summit 2023 - Opening Remarks.pptx
bradgallagher614 views
2023 Tracking Volunteers in Bloomerang.pdf von Bloomerang
2023 Tracking Volunteers in Bloomerang.pdf2023 Tracking Volunteers in Bloomerang.pdf
2023 Tracking Volunteers in Bloomerang.pdf
Bloomerang26 views
SplitMetrics at APS Berlin von VikaVlasova1
SplitMetrics at APS BerlinSplitMetrics at APS Berlin
SplitMetrics at APS Berlin
VikaVlasova135 views
Learning from Failure_ Lessons from Failed Startups.pptx von Codeventures
Learning from Failure_ Lessons from Failed Startups.pptxLearning from Failure_ Lessons from Failed Startups.pptx
Learning from Failure_ Lessons from Failed Startups.pptx
Codeventures19 views
Engaging Senior Leaders to Accelerate Your Continuous Improvement Program von KaiNexus
Engaging Senior Leaders to Accelerate Your Continuous Improvement ProgramEngaging Senior Leaders to Accelerate Your Continuous Improvement Program
Engaging Senior Leaders to Accelerate Your Continuous Improvement Program
KaiNexus97 views
Gross_TownHall_Summit Conf 2023 BRC Intro slides.pptx von bradgallagher6
Gross_TownHall_Summit Conf 2023 BRC Intro slides.pptxGross_TownHall_Summit Conf 2023 BRC Intro slides.pptx
Gross_TownHall_Summit Conf 2023 BRC Intro slides.pptx
bradgallagher648 views

Microsoft word ms11 chapter 2 equipment selection-tcm135-60924

  • 1. MS11 Split inverter course Daikin Europe NV 2 Equipment selection What is in this chapter? Introduction Selecting the right unit for the right application can prevent a lot of problems. In this chapter we would like to introduce you to information which will help you select the correct unit. However, even with the right unit, there will still be some points of attention, which will have to be taken into account. Overview This chapter covers the following topics Topic See Page 2.1 Selection specifications 2.2 Combination possibilities 2.3 Installation specifications 2.4 Application precautions CHAPTER 2: Equipment selection 2- 1
  • 2. MS11 Split inverter course Daikin Europe NV 2.1 Selection specifications Overview This chapter covers the following topics 2.1.1 2.1.2 2.1.3 2.1.4 2.1.5 Topic Non inverters Inverters Correction factors Capacity tables Attention points in selection CHAPTER 2: Equipment selection See Page 2- 2
  • 3. MS11 Split inverter course Daikin Europe NV 2.1.1 Non inverters Introduction You should select a unit by comparing the (maximum possible) heat load of a room to the nominal capacity of a unit. If your heat load is much larger than your nominal capacity, you will have capacity shortage complaints. If your heat load is much smaller than the nominal capacity, your unit will switch on/off a lot, which has a negative effect on the lifetime of a unit. Capacity table Global Mini Split Unit FT(Y)N50EV1B FT(Y)N60EV1B Mode Cooling Heating Cooling Heating CHAPTER 2: Equipment selection Nominal Capacity [kW] 5.0 5.8 6.0 7.0 2- 3
  • 4. MS11 Split inverter course Daikin Europe NV 2.1.2 Inverters (DC inverter) Introduction When selecting an inverter controlled A/C unit, it is of the up most importance to select a unit with a nominal capacity as close as possible to the heat load of the room. When selecting a unit, which is too small, the compressor will operate continuously on its maximum frequency like a non inverter. If you select a unit that has too much capacity, the minimum frequency of the compressor can still generate too much capacity and switch the compressor on/off like a non inverter. You can see that in both these cases an inverter has no added value compared to a non inverter which is a lot cheaper. Minimum capacity When the unit is in thermostat ON, there is a minimum compressor frequency and a minimum expansion valve opening. If the required capacity is below the minimum capacity of the compressor, the unit will switch ON-OFF. Maximum capacity When a unit runs at its maximum frequency and the expansion valve is opened to the maximum the unit will give its maximum capacity. (For the mentioned indoor/outdoor and accordingly to the installation conditions.) However it is very important that you realize that this will not always be the case, even when the capacity demand is high. The unit is controlled by a micro-controller and the micro-controller will take all factors into account (capacity demand, safeties, efficiency, sensors, etc. …) and then decide the best frequency. If you combine this together with piping length losses, it is very likely that when you select a unit on the maximum capacity you will have complaints of capacity shortage. Continued on the next page CHAPTER 2: Equipment selection 2- 4
  • 5. MS11 Split inverter course Daikin Europe NV 2.1.2 Inverters (DC inverter), continued Capacity table Global Mini Split Unit Mode Minimum FTK/XS50EV1B FTK/XS60EV1B FTK/XS71EV1B FTXG25EV1BW/S FTXG35EV1BW/S CTXG50EV1BW/S ATXG25EV1B ATXG35EV1B ATXG50E2V1B FDK/XS25EVMB FDK/XS35EVMB ATK/XS20E2V1B ATK/XS25E2V1B ATK/XS35E2V1B ATXS50E2V1B Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating 2.0 2.0 2.0 2.0 4.0 4.0 1.3 1.3 1.4 1.4 ? ? ? ? ? ? ? ? 1.3 1.3 1.4 1.4 1.3 1.3 1.3 1.3 1.4 1.4 2.0 2.0 Capacity [kW] Nominal Maximum 5.0 5.8 6.0 7.0 7.1 8.2 2.5 3.4 3.5 4.2 ? ? ? ? ? ? ? ? 2.4 3.2 3.4 4.1 2.0 2.7 2.5 3.4 3.4 4.0 5.0 5.8 6.0 7.7 6.7 8.0 8.5 10.0 3.0 4.5 4.8 5.0 ? ? ? ? ? ? ? ? 3.0 4.5 3.8 5.0 2.6 4.1 3.0 4.5 3.8 5.0 5.2 6.0 Continued on the next page CHAPTER 2: Equipment selection 2- 5
  • 6. MS11 Split inverter course Daikin Europe NV 2.1.3 Correction factors Correction factors When the piping exceeds a certain length, a correction factor has to be multiplied with the rated capacity. The cooling and the heating capacity of the unit have to be corrected in accordance with the length of the refrigerant piping. (The distance between the indoor unit and the outdoor unit) Fig.: CHAPTER 2: Equipment selection 2- 6
  • 7. MS11 Split inverter course Daikin Europe NV 2.1.4 Capacity tables Introduction For the Multi outdoor units, when your connection ratio goes above 100%, the minimum, nominal and maximum capacities will lower (only when the capacity demand of the indoor units is greater than the outdoor unit can deliver). What your minimum, nominal and maximum capacity will be when this happens, you can read out on the capacity tables. (Engineering Databook) The maximum allowed connection ratios are Modelname 2(A)MXS52EV1B 3MKS50E2V1B 3(A)MXS52E2V1B 4MKS58E2V1B 4MXS68E2V1B 4MKS75E2V1B 4MXS80E7V3B 5MKS90E7V3B 5MXS90E7V3B Max. connectable capacity (kW) 8.5 9.5 9.0 10.0 11.0 13.5 14.5 15.6 15.6 For the C/O units, there’s an additional function programmed that will limit the operation of units when you connect more than the allowed capacity. When an indoor unit is switched on, over sizing the allowed operational capacity of a C/O multi, the last unit which is turned ON will go into stand-by mode (slowly blinking indoor operation LED). It will only resume operation once operation in the other rooms (or one room) has stopped. This function has been added to prevent the compressor from overheating (overload clixon). CHAPTER 2: Equipment selection 2- 7
  • 8. MS11 Split inverter course Daikin Europe NV 2.1.5 Selection attention points Introduction When selecting a model there are some points of attention. You should select your type of unit and installation place carefully. Selection according to room type. Living room Bedroom Selection according to air circulation for different room types. Selection according to air circulation distinctive to the different air conditioning types. Rectangular rooms Long rooms, Odd shaped rooms Wall mounted type Floor type Ceiling hung type this is often used from morning to night, an energy saving unit would be recommended It is important to select an air conditioner, which is quiet and does not blow (draft) directly onto the occupants. Install the unit so it blows into the length of the room. Install separate units to blow air through the room. Install separate units to prevent air accumulation in one place. This type of unit allows great air circulation in cooling, this due to its high position. This position is however a disadvantage for heating, as heat rises, stratification is possible. This type of unit is more suitable for heating applications than cooling applications. Since hot air rises there are few temperature differences between heights. This type of unit can be put in a central position in the room, allowing a good air circulation. CHAPTER 2: Equipment selection 2- 8
  • 9. MS11 Split inverter course Daikin Europe NV 2.2 Combination possibilities Introduction On the following page you will find our combination table. These pictograms point out the possibilities as well as the limitations of the combinations. Also a file which is named FAQ (Frequently Asked Questions) is added. This will give you some more clarification why certain specific combinations are not possible. CHAPTER 2: Equipment selection 2- 9
  • 10. MS11 Split inverter course Daikin Europe NV 2.3 Installation specifications Introduction This chapter gives a summary of the basic technical specifications concerning piping which are essential to a decent installation. All this information can be found back in the installation manual of the specific unit. Overview Topic See Page RYN50/60E2V1B (A)RK/XS50/60/71E2V1B (A)RXG25/35E(2)V1B ARK/XS20/25/35E2V1B 2(A)MXS52E2V1B, 3(A)MK/XS50/52E2V1/MB, 4MKS58E2V1B 4MK/X58/68E2V1B 5MK/XS90E7V3B, 4MXS80E7V3B Additional explanation on installation comments CHAPTER 2: Equipment selection 2- 10
  • 11. MS11 Split inverter course Daikin Europe NV RYN50/60E2V1B Pipe sizes The table below shows the available piping connections. Liquid line Gas line RYN50/60E2V1B 6.4 mm 12.7 mm Table : piping dimensions Piping lengths The table below shows the maximum allowed piping lengths. Total length Level difference RYN50/60E2V1B 30 m 20 m Table: piping lengths Additional refrigerant charge For the RYN50/60E2V1B add 20 g/m when piping exceeds 10 m. Fuses Daikin recommends using a 20A safety breaker. Continued on the next page CHAPTER 2: Equipment selection 2- 11
  • 12. MS11 Split inverter course Daikin Europe NV RYN50/60E2V1B, continued Installation space Fig.: Outdoor unit positioning CHAPTER 2: Equipment selection 2- 12
  • 13. MS11 Split inverter course Daikin Europe NV (A)RK/XS50/60/71E2V1B Pipe sizes The tables below show the available piping connections Liquid line (mm) Gas line (mm) (A)RK/XS50/60E2V1B RK/XS71E2V1B 6.4 mm 12.7 mm 15.9 mm Table : Piping dimensions Piping lengths The table below shows the maximum allowed piping lengths. Total length Level difference (A)RK/XS20/25/35DVMB 30 m 20 m Table: Piping lengths Additional refrigerant charge Add 20 g/m when piping length exceeds 10 m. Fuses Daikin recommends using a 20 A safety breaker. Continued on the next page CHAPTER 2: Equipment selection 2- 13
  • 14. MS11 Split inverter course Daikin Europe NV (A)RK/XS50/60/71E2V1B, continued Installation space Fig.: Outdoor unit positioning CHAPTER 2: Equipment selection 2- 14
  • 15. MS11 Split inverter course Daikin Europe NV (A)RXG25/35E(2)V1B Pipe sizes The tables below show the available piping connections Liquid line (mm) Gas line (mm) Piping lengths (A)RXG25/35E(2)V1B 6.4 mm 9.5 mm The table below shows the maximum allowed piping lengths. Total length Level difference (A)RXG25/35E(2)V1B 20 m 15 Table: Piping lengths Additional refrigerant charge Add 20 g/m when piping length exceeds 10 m. Fuses Daikin recommends using a 16 A safety breaker. Continued on next page CHAPTER 2: Equipment selection 2- 15
  • 16. MS11 Split inverter course Daikin Europe NV (A)RXG25/35E(2)V1B, Continued Installation space CHAPTER 2: Equipment selection 2- 16
  • 17. MS11 Split inverter course Daikin Europe NV ARK/XS20/25/35E2V1B Pipe sizes The tables below show the available piping connections Liquid line (mm) Gas line (mm) Piping lengths ARK/XS20/25/35E2V1B 6.4 mm 9.5 mm The table below shows the maximum allowed piping lengths. Total length Level difference (A)RXG25/35E(2)V1B 20 m 15 Table: Piping lengths Additional refrigerant charge Add 20 g/m when piping length exceeds 10 m. Fuses Daikin recommends using a 16 A safety breaker. Continued on next page CHAPTER 2: Equipment selection 2- 17
  • 18. MS11 Split inverter course Daikin Europe NV ARK/XS20/25/35E2V1B, Continued Installation space CHAPTER 2: Equipment selection 2- 18
  • 19. MS11 Split inverter course Daikin Europe NV 2(A)MXS52E2V1B, 3MXS52E2V1B, 3(A)MKS50E2V1B, 4MKS58E2V1B. Pipe sizes The tables below show the available piping connections 2(A)MXS52E2V1B/3MXS52E2V1B/3(A)MK S50E2V1B/4MKS58E2V1B Liquid line Gas line 6.4 – 9.5 – 12.7 – 15.9 Table : Piping dimensions Piping lengths The table below shows the maximum allowed piping lengths. 2(A)MXS52E2V1B/3MXS52E2V1B/3(A) MKS50E2V1B/4MKS58E2V1B Piping to each indoor 25 m Total piping 50 m Min piping length to each indoor 3m Max. level difference between 2 7.5 m indoors if the outdoor is positioned higher than all the indoors Max. level difference between 2 15 m indoor units if the outdoor is lower than 1 or more indoors Max level difference between 7.5 m indoor/outdoor if the outdoor is lower than 1 or more indoors Table: Piping lengths Additional refrigerant charge Add 20 g/m when total piping length exceeds 30 m. Fuses Daikin recommends using a ? A safety breaker. (2MK/XS40DVMB) Continued on the next page CHAPTER 2: Equipment selection 2- 19
  • 20. MS11 Split inverter course Daikin Europe NV 2(A)MXS52E2V1B, 3MXS52E2V1B, 3(A)MKS50E2V1B, 4MKS58E2V1B., continued Installation space Fig.: Outdoor unit positioning CHAPTER 2: Equipment selection 2- 20
  • 21. MS11 Split inverter course Daikin Europe NV 4MXS68E2V1B, 4MKS58E2V1B, Pipe sizes The tables below show the available piping connections. Liquid line(mm) Gas line (mm) 4MKS58D 6.4 / 6.4 / 6.4 / 6.4 9.5 / 9.5 / 12.7 / 12.7 4MXS68D 6.4 / 6.4 / 6.4 / 6.4 9.5 / 9.5 / 12.7 / 12.7 Table : Piping dimensions Piping lengths The table below shows the maximum allowed piping lengths. 4MKS58D Max. piping to each indoor Max. level difference between 2 indoors if the outdoor is positioned higher than all the indoors Max. level difference between 2 indoor units if the outdoor is lower than 1 or more indoors Max level difference between indoor/outdoor if the outdoor is lower than 1 or more indoors Total length of piping 4MXS68D 25 7.5 15 m 7.5 m 60 Table: Piping lengths Additional refrigerant charge Add 20 g/m when total piping length exceeds 30 m. Cooling only units are chargeless! There is no need for additional refrigerant! Fuses Daikin recommends using a ?? A safety breaker. Continued on next page CHAPTER 2: Equipment selection 2- 21
  • 22. MS11 Split inverter course Daikin Europe NV 4MXS68E2V1B, 4MKS58E2V1B,, Continued Installation space Fig.: Outdoor unit positioning CHAPTER 2: Equipment selection 2- 22
  • 23. MS11 Split inverter course Daikin Europe NV 5MKS90E7V3B, 5MXS90E7V3B, 4MXS80 E7V3B, Pipe sizes The tables below show the available piping connections Liquid line (mm) Gas line (mm) 5MKS90E7V3B, 5MXS90E7V3B, 4MXS80 E7V3B 6.4 9.5 / 9.5 / 12.7 / 15.9 (/ 15.9) Table : Piping dimensions Piping lengths The table below shows the maximum allowed piping lengths. 4MXS80 E7V3B Max. piping to each indoor Max. level difference between 2 indoors if the outdoor is positioned higher than all the indoors Max. level difference between 2 indoor units if the outdoor is lower than 1 or more indoors Max level difference between indoor/outdoor if the outdoor is lower than 1 or more indoors Total length of piping Min piping length to one indoor unit 25 m 7.5 m 5MKS90E7V3B, 5MXS90E7V3B 25 m 7.5 m 15 m 15 m 7.5 m 7.5 m 70 m 3m 75 m 3m Table: Piping lengths Additional comments • • Always connect a minimum of 2 rooms for heat pump systems. The shortest allowable length per room is 3 m. Additional refrigerant charge • • Add 20 g/m when total piping length exceeds 30 m. For cooling only models, there’s no need to additionally charge. ???(see installation manual) Continued on the next page CHAPTER 2: Equipment selection 2- 23
  • 24. MS11 Split inverter course Daikin Europe NV 4MKS90DVMB, 4MXS80DVMB, continued Fuse Daikin recommends a 20 A fuse Installation space Fig.: Outdoor unit positioning CHAPTER 2: Equipment selection 2- 24
  • 25. MS11 Split inverter course Daikin Europe NV Additional comments on installation specifications Installation Manual Additional refrigerant is necessary when the piping exceeds a certain length. For the multi units however you don’t need to add any refrigerant for C/O units. Explanation The evaporator regulates the superheat (SH), the larger your evaporating capability (fan speed, size heat exchanger, heat exchanging capability) the larger your SH will be. The condenser regulates your subcool (SC), which is needed for the expansion valve to work properly. In cooling the evaporator is the indoor coil and the condenser the outdoor coil. This changes when the unit is in heating, so the sizes of the H/E can change. In heating on small loads the unit will have a small SC (low condensing capability). When refrigerant is added the SC goes up. Adding refrigerant also means that the SH will go down but in heating there’s a large evaporator which can handle this surplus of refrigerant. Installation Manual Always connect at least 2 rooms to a Multi. Explanation (Strictly speaking, for heat pump models only.) If you connect only 1 indoor unit you will have compressor damage due to the following reasons: 1. Abnormal high pressure Surplus refrigerant is accumulated in the indoor unit during heating operation, at that point, the heat exchanger thermistor is in sub cooling area and it can not sense the saturated temperature. Therefore the safety (peak cut operation) can not function leaving the unit prone to high pressures. However, surplus refrigerant is accumulated in the non operating unit whilst one unit is operating in a two unit connection in heating mode. 2. Poor lubrication by refrigerant oil When you connect only 1 indoor unit to a multi, surplus refrigerant is accumulated in the indoor unit or accumulator. In case the refrigerant is accumulated in the accumulator, you’ll have wet operation and poor lubrication and this will lead to compressor damage. Continued on the next page CHAPTER 2: Equipment selection 2- 25