Debugging of automatic fire alarm system
Source from https://www.vedard.com/blog
Before debugging the automatic fire alarm system, the
specifications, models, quantities and spare parts of the equipment
should be checked according to the requirements of the design
documents. The construction quality of the system shall be
checked according to the corresponding construction requirements,
and the problems arising in the construction shall be solved through
consultation with the relevant units, and written records shall be
provided. Inspect the system lines according to the requirements of
the corresponding construction, for the fault lines, open, empty
welding, the problem such as short circuit, insulation resistance is
less than 20 m Ω, corresponding treatment measures should be
taken.
Respectively electricity inspection for single machine is required for
fire alarm controller, fire linkage controller in the system, the
combustible gas alarm controller, electric fire monitor, gas (bubble),
fire extinguishing controller of electrical control equipment, fire
fighting equipment, emergency power, fire emergency
broadcasting equipment, fire special telephone, fire alarm
transmission equipment or user information transmission device,
fire control room graphic display device, fire, fire shutter controller,
electric actuator area monitors display panel (fire), fire emergency
lighting control, fire door monitor, fire alarm device.
Firstly, Fire Alarm Controller
Before debugging, all external control lines of the fire alarm
controller should be cut off, and the power should be switched on
after connecting the fire detector of any bus circuit and the manual
fire alarm button and other components on the bus circuit.
According to the relevant requirements of the fire Alarm Controller
standard, the following functions of the controller shall be checked
and recorded one by one by means of observation and instrument
measurement, which shall meet the following requirements:
1.Self-check function and operation level
Make the connection between the controller and the detector open
or short, and the controller should send fault signal within 100s
(except fire alarm signal in case of short circuit);In the fault state,
make the detector in any non-fault part send fire alarm signal, the
controller should send fire alarm signal within 1min, and record the
fire alarm time;Then make other detectors send fire alarm signal to
check the controller’s alarm function again.
2.Mute and reset functions
Make the connection between the controller and the standby power
cut off or short. The controller should send a fault signal within 100s.
3.Check shielding function
Short-circuit any point within the protection scope of the bus
isolator and check the isolation and protection function of the bus
isolator.
4.Make at least 10 fire detectors on any bus circuit in the state of
fire alarm at the same time to check the load function of the
controller.
5.The automatic conversion function of main and standby power
supplies, and the inspection of article 4 shall be repeated under the
condition of standby power supply.
6.Other functions specific to the alarm control panel
7.Connect the other loops to the fire alarm controller in turn and
repeat the inspection
Secondly, point type smoke and heat detector
1. Check the alarm function of each fire detector one by one by
using the special detection instrument or the method of simulating
fire. The detector should be able to send fire alarm signal.
For unrecoverable fire detector, simulated alarm method should be
adopted to check its alarm function one by one, and the detector
should be able to send fire alarm signal.When there are spare parts,
can sample check its alarm function.
2.The alarm function of each household fire detector shall be
checked one by one by means of special detection instruments, fire
simulation or pressing the detector alarm test button. The detector
shall be able to send sound and light alarm signals, and the
connected detector shall send sound alarm signals.
Thirdly, linear type heat detectors
Simulate fire alarm and fault on the unrecoverable detector, check
the fire alarm and fault alarm function of each fire detector one by
one, and the detector should be able to send fire alarm and fault
signal respectively.The recoverable detector can be made to send
fire alarm signals and simulate faults by means of special detection
instruments or fire simulation. The fire alarm and fault alarm
functions of each fire detector can be checked one by one. The
detector should be able to send fire alarm and fault signals
respectively.
Fourthly, linear beam smoke detector
Adjust the optical regulating device of the detector one by one, so
that the detector is in the normal monitoring state. Block the optical
path with the optical dimmer of 0.9dB, and the detector should not
send fire alarm signal. Block the optical path with a dimmer rate
(1.0dB ~ 10.0dB) set by the product manufacturer, and the detector
shall send fire alarm signal. Use a dimmer with a dimmer rate of
11.5dB to block the optical path, and the detector should send fault
signal or fire alarm signal. When selecting reflection-type detector,
the detector should be checked at 0.5m in front of the detector
according to the above requirements, and the detector should
respond correctly.
Fifthly, line sampling suction smoke fire detector
Add test smoke one by one into the sampling hole at the end of the
sampling tube (the most unfavorable place), and use stopwatch to
measure the alarm response time of the detector. The detector or
its control device should send fire alarm signal within 120s.
According to the product manual, the airflow of the sampling tube of
the detector is changed to make the detector in a fault state. A
stopwatch is used to measure the alarm response time of the
detector. The detector or its control device should send a fault
signal within 100s.
Sixthly, point fire detector and picture fire detector
The detector’s alarm function should be checked one by one in the
most unfavorable part of the detector’s monitoring area by special
detection instrument or fire simulation method, and the detector
should be able to respond correctly.
Seventhly, Manual fire alarm button
Apply appropriate thrust to the recoverable manual fire alarm
button to make it act, and the alarm button should send out fire
alarm signal. For the unrecoverable manual fire alarm button, the
method of simulating action should be adopted to make the alarm
button act (when there are spare parts, the action test can be
conducted by sampling), and the alarm button should send out the
fire alarm signal.

Weitere ähnliche Inhalte

Mehr von Vedard Security Alarm System Store

Security service equipment integrated CCTV and burglar fire alarm
Security service equipment integrated CCTV and burglar fire alarmSecurity service equipment integrated CCTV and burglar fire alarm
Security service equipment integrated CCTV and burglar fire alarmVedard Security Alarm System Store
 

Mehr von Vedard Security Alarm System Store (20)

addressable fire alarm system bus loop
addressable fire alarm system bus loopaddressable fire alarm system bus loop
addressable fire alarm system bus loop
 
fire alarm system types
fire alarm system typesfire alarm system types
fire alarm system types
 
fire alarm system fire graphic display device
fire alarm system fire graphic display devicefire alarm system fire graphic display device
fire alarm system fire graphic display device
 
overview of automatic fire-alarm systems
overview of automatic fire-alarm systemsoverview of automatic fire-alarm systems
overview of automatic fire-alarm systems
 
division of fire alarm areas
division of fire alarm areasdivision of fire alarm areas
division of fire alarm areas
 
addressable fire alarm bus short circuit isolator
addressable fire alarm bus short circuit isolatoraddressable fire alarm bus short circuit isolator
addressable fire alarm bus short circuit isolator
 
fire manual call and hydrant button
fire manual call and hydrant buttonfire manual call and hydrant button
fire manual call and hydrant button
 
addressable fire alarm system input module
addressable fire alarm system input moduleaddressable fire alarm system input module
addressable fire alarm system input module
 
carbon monoxide detection system
carbon monoxide detection systemcarbon monoxide detection system
carbon monoxide detection system
 
gas fire extinguish system
gas fire extinguish systemgas fire extinguish system
gas fire extinguish system
 
Residual current electrical fire detector
Residual current electrical fire detectorResidual current electrical fire detector
Residual current electrical fire detector
 
Linear infrared beam smoke detector
Linear infrared beam smoke detectorLinear infrared beam smoke detector
Linear infrared beam smoke detector
 
Security service equipment integrated CCTV and burglar fire alarm
Security service equipment integrated CCTV and burglar fire alarmSecurity service equipment integrated CCTV and burglar fire alarm
Security service equipment integrated CCTV and burglar fire alarm
 
FC-7664PRO alarm panel professional security system
FC-7664PRO alarm panel professional security systemFC-7664PRO alarm panel professional security system
FC-7664PRO alarm panel professional security system
 
MC-800DMT intrusion detector manual
MC-800DMT intrusion detector manualMC-800DMT intrusion detector manual
MC-800DMT intrusion detector manual
 
PB-503R Wireless alarm keypad
PB-503R Wireless alarm keypadPB-503R Wireless alarm keypad
PB-503R Wireless alarm keypad
 
Fire Alarm input module
Fire Alarm input moduleFire Alarm input module
Fire Alarm input module
 
Residual current electrical fire detector
Residual current electrical fire detectorResidual current electrical fire detector
Residual current electrical fire detector
 
gas fire extinguishing control system
gas fire extinguishing control systemgas fire extinguishing control system
gas fire extinguishing control system
 
gas fire extinguishing system instruction
gas fire extinguishing system instructiongas fire extinguishing system instruction
gas fire extinguishing system instruction
 

KĂĽrzlich hochgeladen

Steel Structures - Building technology.pptx
Steel Structures - Building technology.pptxSteel Structures - Building technology.pptx
Steel Structures - Building technology.pptxNikhil Raut
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionMebane Rash
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
Mine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptxMine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptxRomil Mishra
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxk795866
 
home automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasadhome automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasadaditya806802
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleAlluxio, Inc.
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating SystemRashmi Bhat
 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgsaravananr517913
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...asadnawaz62
 
welding defects observed during the welding
welding defects observed during the weldingwelding defects observed during the welding
welding defects observed during the weldingMuhammadUzairLiaqat
 
Internet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptxInternet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptxVelmuruganTECE
 
Industrial Safety Unit-IV workplace health and safety.ppt
Industrial Safety Unit-IV workplace health and safety.pptIndustrial Safety Unit-IV workplace health and safety.ppt
Industrial Safety Unit-IV workplace health and safety.pptNarmatha D
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHC Sai Kiran
 
Industrial Safety Unit-I SAFETY TERMINOLOGIES
Industrial Safety Unit-I SAFETY TERMINOLOGIESIndustrial Safety Unit-I SAFETY TERMINOLOGIES
Industrial Safety Unit-I SAFETY TERMINOLOGIESNarmatha D
 
Solving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.pptSolving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.pptJasonTagapanGulla
 

KĂĽrzlich hochgeladen (20)

Steel Structures - Building technology.pptx
Steel Structures - Building technology.pptxSteel Structures - Building technology.pptx
Steel Structures - Building technology.pptx
 
US Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of ActionUS Department of Education FAFSA Week of Action
US Department of Education FAFSA Week of Action
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
Mine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptxMine Environment II Lab_MI10448MI__________.pptx
Mine Environment II Lab_MI10448MI__________.pptx
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptx
 
home automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasadhome automation using Arduino by Aditya Prasad
home automation using Arduino by Aditya Prasad
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Correctly Loading Incremental Data at Scale
Correctly Loading Incremental Data at ScaleCorrectly Loading Incremental Data at Scale
Correctly Loading Incremental Data at Scale
 
Virtual memory management in Operating System
Virtual memory management in Operating SystemVirtual memory management in Operating System
Virtual memory management in Operating System
 
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfgUnit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
Unit7-DC_Motors nkkjnsdkfnfcdfknfdgfggfg
 
complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...complete construction, environmental and economics information of biomass com...
complete construction, environmental and economics information of biomass com...
 
welding defects observed during the welding
welding defects observed during the weldingwelding defects observed during the welding
welding defects observed during the welding
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
Internet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptxInternet of things -Arshdeep Bahga .pptx
Internet of things -Arshdeep Bahga .pptx
 
Industrial Safety Unit-IV workplace health and safety.ppt
Industrial Safety Unit-IV workplace health and safety.pptIndustrial Safety Unit-IV workplace health and safety.ppt
Industrial Safety Unit-IV workplace health and safety.ppt
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
 
Introduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECHIntroduction to Machine Learning Unit-3 for II MECH
Introduction to Machine Learning Unit-3 for II MECH
 
Industrial Safety Unit-I SAFETY TERMINOLOGIES
Industrial Safety Unit-I SAFETY TERMINOLOGIESIndustrial Safety Unit-I SAFETY TERMINOLOGIES
Industrial Safety Unit-I SAFETY TERMINOLOGIES
 
Solving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.pptSolving The Right Triangles PowerPoint 2.ppt
Solving The Right Triangles PowerPoint 2.ppt
 

Debugging of automatic fire alarm system

  • 1. Debugging of automatic fire alarm system Source from https://www.vedard.com/blog Before debugging the automatic fire alarm system, the specifications, models, quantities and spare parts of the equipment should be checked according to the requirements of the design documents. The construction quality of the system shall be checked according to the corresponding construction requirements, and the problems arising in the construction shall be solved through consultation with the relevant units, and written records shall be provided. Inspect the system lines according to the requirements of the corresponding construction, for the fault lines, open, empty welding, the problem such as short circuit, insulation resistance is less than 20 m Ω, corresponding treatment measures should be
  • 2. taken. Respectively electricity inspection for single machine is required for fire alarm controller, fire linkage controller in the system, the combustible gas alarm controller, electric fire monitor, gas (bubble), fire extinguishing controller of electrical control equipment, fire fighting equipment, emergency power, fire emergency broadcasting equipment, fire special telephone, fire alarm transmission equipment or user information transmission device, fire control room graphic display device, fire, fire shutter controller, electric actuator area monitors display panel (fire), fire emergency lighting control, fire door monitor, fire alarm device. Firstly, Fire Alarm Controller Before debugging, all external control lines of the fire alarm controller should be cut off, and the power should be switched on after connecting the fire detector of any bus circuit and the manual fire alarm button and other components on the bus circuit. According to the relevant requirements of the fire Alarm Controller standard, the following functions of the controller shall be checked and recorded one by one by means of observation and instrument measurement, which shall meet the following requirements:
  • 3. 1.Self-check function and operation level Make the connection between the controller and the detector open or short, and the controller should send fault signal within 100s (except fire alarm signal in case of short circuit);In the fault state, make the detector in any non-fault part send fire alarm signal, the controller should send fire alarm signal within 1min, and record the fire alarm time;Then make other detectors send fire alarm signal to check the controller’s alarm function again. 2.Mute and reset functions Make the connection between the controller and the standby power cut off or short. The controller should send a fault signal within 100s. 3.Check shielding function Short-circuit any point within the protection scope of the bus isolator and check the isolation and protection function of the bus isolator. 4.Make at least 10 fire detectors on any bus circuit in the state of fire alarm at the same time to check the load function of the controller. 5.The automatic conversion function of main and standby power supplies, and the inspection of article 4 shall be repeated under the condition of standby power supply. 6.Other functions specific to the alarm control panel
  • 4. 7.Connect the other loops to the fire alarm controller in turn and repeat the inspection Secondly, point type smoke and heat detector 1. Check the alarm function of each fire detector one by one by using the special detection instrument or the method of simulating fire. The detector should be able to send fire alarm signal. For unrecoverable fire detector, simulated alarm method should be adopted to check its alarm function one by one, and the detector should be able to send fire alarm signal.When there are spare parts, can sample check its alarm function. 2.The alarm function of each household fire detector shall be checked one by one by means of special detection instruments, fire simulation or pressing the detector alarm test button. The detector shall be able to send sound and light alarm signals, and the connected detector shall send sound alarm signals.
  • 5. Thirdly, linear type heat detectors Simulate fire alarm and fault on the unrecoverable detector, check the fire alarm and fault alarm function of each fire detector one by one, and the detector should be able to send fire alarm and fault signal respectively.The recoverable detector can be made to send fire alarm signals and simulate faults by means of special detection instruments or fire simulation. The fire alarm and fault alarm functions of each fire detector can be checked one by one. The detector should be able to send fire alarm and fault signals respectively. Fourthly, linear beam smoke detector Adjust the optical regulating device of the detector one by one, so that the detector is in the normal monitoring state. Block the optical path with the optical dimmer of 0.9dB, and the detector should not
  • 6. send fire alarm signal. Block the optical path with a dimmer rate (1.0dB ~ 10.0dB) set by the product manufacturer, and the detector shall send fire alarm signal. Use a dimmer with a dimmer rate of 11.5dB to block the optical path, and the detector should send fault signal or fire alarm signal. When selecting reflection-type detector, the detector should be checked at 0.5m in front of the detector according to the above requirements, and the detector should respond correctly. Fifthly, line sampling suction smoke fire detector Add test smoke one by one into the sampling hole at the end of the sampling tube (the most unfavorable place), and use stopwatch to measure the alarm response time of the detector. The detector or its control device should send fire alarm signal within 120s. According to the product manual, the airflow of the sampling tube of the detector is changed to make the detector in a fault state. A stopwatch is used to measure the alarm response time of the detector. The detector or its control device should send a fault signal within 100s. Sixthly, point fire detector and picture fire detector The detector’s alarm function should be checked one by one in the
  • 7. most unfavorable part of the detector’s monitoring area by special detection instrument or fire simulation method, and the detector should be able to respond correctly. Seventhly, Manual fire alarm button Apply appropriate thrust to the recoverable manual fire alarm button to make it act, and the alarm button should send out fire alarm signal. For the unrecoverable manual fire alarm button, the method of simulating action should be adopted to make the alarm button act (when there are spare parts, the action test can be conducted by sampling), and the alarm button should send out the fire alarm signal.