Diese Präsentation wurde erfolgreich gemeldet.
Wir verwenden Ihre LinkedIn Profilangaben und Informationen zu Ihren Aktivitäten, um Anzeigen zu personalisieren und Ihnen relevantere Inhalte anzuzeigen. Sie können Ihre Anzeigeneinstellungen jederzeit ändern.
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Description        Current allowance                                                         Demand
Circuit Load Group    ...
Nächste SlideShare
Wird geladen in …5
×

4.1.11 Light Demand 2 Table

790 Aufrufe

Veröffentlicht am

Veröffentlicht in: Technologie, Business
  • Als Erste(r) kommentieren

  • Gehören Sie zu den Ersten, denen das gefällt!

4.1.11 Light Demand 2 Table

  1. 1. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  2. 2. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  3. 3. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  4. 4. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  5. 5. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  6. 6. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  7. 7. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  8. 8. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  9. 9. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  10. 10. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05
  11. 11. Description Current allowance Demand Circuit Load Group of load per unit Calculation (Amps) No (column 1) (given list) (column 2) L1 L2 L3 1 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 2 12 twin A 36 W Full connected load 12 X 0.4 = 4.8 4.8 fluorescent 3 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 4 A 3 Highbay MV Full connected load 3 X 2.2 = 6.6 6.6 5 7 double 1000 W for 1st outlet + 750 each additional (1000 + (13 X 750)) B(i) 46.7 10 A outlets = 14 points outlet / 230 7 double (1000 + (13 X 750)) 6 B(i) 10 A outlets 1000 W for 1st + 750 each additional outlet 46.7 / 230 = 14 points 7 6 double (1000 + (11 X 750)) B(i) 1000 W for 1st + 750 each additional outlet 40.2 10 A outlets = 12 points / 230 8 2 x 15 A single phase B(iii) outlets 15 + (15 X 0.75) 26.25 Full current rating of highest outlet + 75% (x 9 2 x 15 A single phase 0.75) full current rating of remainder B(iii) 15 + (15 X 0.75) 26.25 outlets 10 This is the highest rated B(iii) 15 A three phase outlet 15.0 15.0 15.0 11 B(iii) 15 A three phase outlet 15 x 0.75 11.3 11.3 11.3 12 C Single phase range Full connected load current 26.7 6400 / 240 13 C Instant hot water heater Full connected load current 2400 / 240 10.0 14 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 15 D 4 kW three phase motor 8.5 x 0.5 = 4.3 4.3 4.3 4.3 16 D 4 kW three phase motor Full load of highest rated motor + 75% (x 8.5 x 0.5 = 4.3 4.3 4.3 4.3 17 D 5.5 kW three phase motor 0.75) of full load of second highest rated Highest rated motor 11.7 11.7 11.7 18 motor, + 50% of full load of remainder 0.75 x 11.7 = 8.8 D 5.5 kW three phase motor (second highest 8.8 8.8 8.8 rated motor) 19 D 5.5 kW three phase motor 0. 5 x 11.7 = 5.8 5.8 5.8 5.8 Total demand current per phase 143.8 153.25 145.05

×