INTRODUCTION

For any industry to be successful, it has become essential to identify the Hazards ,to assess the associated
risks and to bring the risks to tolerable level. Recognising this, IFFCO-AONLA is continuously putting efforts
for controlling the risks which are arising from various Hazards such that loss to Human life and property is
negligible or zero. Its continuous best efforts to identify the Hazards and to bring the risk levels to tolerable
level in the organization are recognised by several Government and safety regulating bodies. This paper
describes briefly about various types of Hazards and their associated risks, how they are being controlled
effectively through risk analysis at IFFCO – Aonla unit

In all plants, hazards and risk are identified time to time by using modern techniques. IFFCO Aonla unit is
OHSAS –18001 certified company. So in all departments /section risk and hazards are find out by proper risk
assessments. During this severity at various levels matched with probability level. And find out the case of
intolerable, substantial, moderate and tolerable risk. Accordingly control measures at the place checked.
Documentation done and records are maintained. .


At IFFCO Aonla unit, HAZOP, HAZAN study, Dow index, Risk Analysis, FMIA, Fault Tree Analysis are carried
out at its inception level..At IFFCO Aonla unit, various risk assessment procedures are followed. This has been
done by Dow Index method and Consequences methods. At the same time when any process modification
done/needed, then also proper HAZOP studies and any other risk analysis studies are carried out to assess
the risk due to the effect of modification.
Now as IFFCO Aonla unit is OHSAS –18001 certified company, in all sections/plants proper hazard and risk
assessment procedures and documentation done. Time to time, plant/section updates of this done and audited
by other sectional persons. And again compliance incorporated.


1.0.0   To effectively implement the safety systems , a structured approach has been drawn out to minimize
        the hazards and risks . This involves the following :


                     REPORTING/INVESTIGATING/ANALYSIS OF ACCIDENTS, DANGEROUS
                      OCCURRENCES AND NEAR MISSES.

        When any accident occurred in plant premise, the concern area shifts in-charge informed his higher
        officers as well as fire and safety section regarding this. Immediately accident/dangerous occurrence
        investigation committee consisting of senior officers from affected area, fire and safety section, factory
        safety officer and medical person set up. This committee starts immediately investigation without
        delay. It also preserves all facts and finding and reports of for future reference.

                                    IFFCO AONLA UNIT                                                         Y-AXIS ACCIDENT FREE MILLION HOURS
        Accident
        Free Man                                                                                                 16
                        947days
                                                                                                                          15.06
        days                                                          910 days( Cont.)
            1000                                                                                                 14
                                                                                                                                                                                13.00
                                    737days
                                                                                                                 12                   12.27
             800
                                                          600days                                                10
             600
                                                                                                                  8                                             7.83
             400                                                                         Accident Free Mandays    6
             200                              122days
                                                                                                                  4
               0                                                                                                  2                                  1.9                                    1
                   26.10.1997- 02.06.2000- 01.09.2002- 01.01.2003- 28.08.2004-                                    0   26.10.1997-   02.06.2000-   01.09.2002-   01.01.2003-   28.08.2004-
                   31.05.2000 08.06.2002 31.12.2002 22.08.2004 15.02.2006                                             31.05.2000    08.06.2002    31.12.2002    22.08.2004    15.02.2006

                                   Accident Free Period
IFFCO AONLA UNIT
                                                                                        Accident Free
   Y-AXIS –ACCIDENT FREE MAN DAYS                                                       Million Man
                                                                                        hours       15.06
                                                                                               16                                                    13
1000                                                                                           14                 12.27
                          947                                             910
                                                                                               12
  800                                                                                          10                                         7.83                    Accident free
                                  737                                                                                                                             Million Man-
                                                                                                8
                                                                                                                                                                  hours
  600                                                        700                                6
                                                                                                4                              1.90
  400                                                                                           2
                                                                                                0
  200                                            122
                                                                                                    26.10.1997- 02.06.2000- 01.09.2002- 01.01.2003- 28.08.2004-
                                                                                                    31.05.2000 08.06.2002 31.12.2002 22.08.2004 15.02.2006
       0    26.10.1997-         02.06.2000-   01.09.2002-   01.01.2003-   28.08.2004-                            Accident Free Period
            31.05.2000          08.06.2002    31.12.2002    22.08.2004    15.02.2006

           X-AXIS ACCDIENT FREE PERIOD


Now we see what type of risks and how they are being handled through some models of risk
analysis in IFFCO –AONLA unit.


           PROCESS & SAFETY–RELATED DATA FOR INDIVIDUAL PROCESS STAGES :

Physical and Health Occupational Hazards in any large scale Chemical /Hydrocarbon Processing
Industry (CPI/HPI) like our can be broadly classified into the following categories:

i.          Mechanical Risks
ii.         Electrical Risks
iii.        Fire/Explosion Risks
iv.         High /low Temperature Exposure Risks
v.          Toxic/Carcinogenic Chemicals Exposure Risks
vi.         Corrosive/Reactive/Radioactive Chemicals Exposure Risks

The first two types of risks are of universal nature associated with any industrial activity and not
specific to a particular plant or process. Mechanical risks which are generally encountered are
injuries to the head, Limbs, eyes, etc usually as a results of negligence on the part of
operating/maintenance personnel in the use of improper tools, bypassing prescribed safety
procedures neglect of personal protective wear and risks associated with rotating machinery as
well as risks associated with high-energy release from compressed gases. Electrical risks which
result in shock and/or burns are most often a consequence of poor maintenance, ingress of dust or
moisture, handling by unauthorized personnel and use of improper/substandard hardware.

Other categories of risks associated with specific plants are detailed here under.

Ammonia Plant :

The manufacture of anhydrous liquid ammonia involves processing of hydrocarbons under high
temperature, high pressure conditions in the presence of various catalysts, chemicals etc. Typical
risks are as follows:

  Fire /Explosion                                     Glands/seal leaks in valves, pumps, compressors handling hydrogen,
                                                       natural gas, naphtha, synthesis gas etc.
                                                      Hose/pipe failure, leakage from flanged joints carrying combustible
                                                       gases, vapours, liquids.
                                                      Fire box explosions in furnaces.
  High/Low     Temp.                                  Burns due to contact with hot surfaces of pipelines, equipments, etc.
  Exposure Risks                                       or leaking steam lines, process fluids at high temperature.
                                                      Frost bite due to contact with anhydrous liquid ammonia at -33 deg. C
                                                      Burns due to contact with pyrophoric catalyst.
  Toxic    Chemicals                                  Asphyxia due to inhalation of simple asphyxiants like CO2 , N2, H2,
  Exposure Risks                                       CH4, naphtha etc. and chemical asphyxiants like CO, NH3, Nickel
                                                       carbonyl, V2O5, Hydrazine, NOx, SOx, H2S etc.
                                                      Acute toxicity due to inhalation of catalyst dusts containing heavy
                                                       metals like Ni, Cr, CO, Mo, Fe, Zn, Alumina etc. and silica gel
                                                       molecular sieves, insulation fibers/dusts.



                                                                                                                                                                                  2
Urea Plant

The manufacture of urea involves reaction of Ammonia and Carbon dioxide under high
temperature & pressure and subsequent recovery and concentration of the solution at various
pressure stages. Typical risks are as follows :

 Fire / Explosion Risks         Ammonia leaks from glands / seals Risks involves, pumps or
                                 flanged joints piping resulting in formation explosive mixtures in
                                 air.

                                 Accumulation of H2 may take place in HP Section in case CO2
                                 purity from Ammonia Plant is not within allowable limits. Ignition
                                 of this accumulated H2 can occur due to dissipation of static
                                 charge.

 High      /     Low            Refer to risks in Ammonia Plant
 Temperature Exposure
 Risks

 Toxic       Chemicals          Asphyxia due to inhalation of simple Exposure Risks asphyxiants
 Exposure Risks                  like CO2 and N2 and chemical asphyxiant, NH3. Solution of
                                 Urea, Ammonium carbamate and ammonium carbonate
                                 containing high NH3 content.

                                Irritation due to inhalation of urea dust.

 Corrosive / Radioactive        Severe burns, damage to eyes, skin and body tissues due to
 Chemicals Exposure              contact with anhydrous ammonia, conc. Urea and Ammonium
 Risks                           carbamate solutions.



Power Plant

The captive Power Plant involves generation of steam in N.G./Naphtha-fired boilers and utilizing
the steam in Urea and Ammonia plants. Typical risks are as follows :

 Fire / Explosion Risks           Explosion and fire risks associated with storage and handling of
                                    B Class (Naphtha) and Natural gas handling pipelines (Refer
                                    off site Facilities).
                                  Fire Box explosion in Boiler


 Flammable Material          Lower         Upper                Temp. °C
 High / Low Temp.                Burns due to contact with hot surfaces of pipelines,
 Exposure Risks                    equipments, etc. or leaking steam lines.
 Toxic         Chemical          Asphyxia due to inhalation of SOX and Nox.
 Exposure Risk                   Irritation due to inflammation caused by inhalation of Natural
                                   gas and the Naphtha vapors.

The permissible exposure limits for cyclohexylamine coal dust / fly-ash are given below :


Offsite Facilities

The offsite facilities, as already described at the very outset, consist of integrated units for water
and effluent treatment, inert gas generation, cooling towers, storage of petroleum products and
ammonia, supply / distribution of utilities like compressed air, water, etc. Potential risks in the
above offsite facilities are essentially on account of handling of corrosive, toxic and reactive
chemicals as well as inflammable petroleum products.



                                                                                                    3
Fire / Explosion Risks    Gland / Seal leaks in valves, pumps, compressor, handling naphtha,
                            N.G., ammonia hydrogen, syngas etc.
                           Hose / pipe failure, leakage from flanged joints in pipes conveying
                            petroleum products, ammonia, hydrogen, syngas, etc.
                           Leakage of petroleum products during tanker unloading operations.
                           Overflow from storage tanks.
                           Overheating / pressurization of storage tanks.
                           Improper earthing / lightning protection of storage tanks and
                            pipelines.
                           Improper sealing of floating roof tanks.
                           In adequate / improper breather valves leading to tank failures.
                           Fire Box Explosion in cracker Furnace.

Critical data for flammable materials stored / handled in off sites has already been furnished under
Ammonia Plant and Power Plant.

 High / Low Temp.          Burns due to contact with hot surfaces of pipe lines, equipments, etc
 Exposure Risks             or leaking steam lines.
                           Heat radiation burns from high intensity flames from the flare stack.
                           Frost bite due to contact with anhydrous liquid ammonia at – 33 °C
 Toxic     Chemicals       Asphyxia due to inhalation of simple asphyxiants like N2, H2,
 Exposure Risks             Naphtha, etc. and Chemical asphyxiants like Cl2, NH3, NOx, Sox,
                            etc.
                           Toxicity due to inhalation of catalyst dust containing heavy metals like
                            Ni, Pd, Alumina etc. and perlite / insulation fibers, silica gel dust.

Data on Threshold Limit Values Limits for most of the above toxic Chemicals and dusts
encountered in off sites has already been furnished under Ammonia Plant. Data for Cl2 are as
follows :

 Corrosive          Chemicals      Severe burners, damage to eyes, skin & body tissues due to
 Exposure Risks                     contact with corrosive chemicals like anhydrous liquid
                                    Ammonia, Sulphuric acid, Hydrochloric acid, etc.

Bagging Plant

The bagging plant encompasses storage, packing, loading and dispatch activities for product urea
via road or rail. Typical risks in this plant are as follows :

 Fire Risks                        Fire hazards due to storage of bulk quantity of polyethylene –
                                    lined jute bags or HDPE bags which are easily combustible.
 Chemicals Exposure Risks          Irritation due to inhalation of urea dust and jute fibers.

 S.No    Name of Chemical         Form under normal condition              Expected    form    of
                                                                           Chemical         under
                                                                           abnormal condition
 1.      Ammonia                  Liquid state at – 33 °C temp. &          Vapour / Gaseous form.
                                  atmospheric pressure.
                                                                           Vapour / Gaseous form.
 2.      Chlorine                 Liquid at ambient temp. & 17.0
                                  Kg/cm² pressure.                         Vapour

 3.      Naphtha                  Liquid at ambient temp. & pressure.
                                                                           Acid fumes
                                  Liquid at ambient temp. & pressure.
 4.      Hydrochloric Acid        Liquid at ambient temp. & pressure.      Acid fumes
                                  Gaseous at ambient temp &
 5.      Sulphuric Acid           Pressure                                 Gaseous Form

 6.      Natural Gas




                                                                                                   4
        INFORMATION ON THE PRELIMINARY HAZARD ANALYSIS

Types of Accident

It is clear that during the course of Urea manufacture, furnaces, reactors, moving machineries,
material handling, cranes, chain, pulley blocks, wire ropes, chemicals, Rail wagons, etc. are
involved. Past reportable accidents are related to these agencies.
Type of personnel injuries indicates burn, cut, bone fracture burn injury etc. A brief resume of types
of accidents may happen are as follows ;-

1.       Burn injury due to handling cleaning of burners in furnaces.
2.       Fire accidents in furnaces leading to property damage.
3.       Burn injury accident due to attending electrical faults.
4.       Burn injury accidents due to handling of acids / alkalies.
5.       Hit / cut type accidents due to various maintenance jobs. For reference purposes and
         internal report titled “Safety Performance at a glance” is enclosed as Annexure 5.

System Elements or Events that can lead to a major Accident

All the section / plants of IFFCO Aonla unit are constructed and designed taking care of all relevant
safety measures possible. However the system elements such as Ammonia storage, Naphtha
storage, Chlorine tonners, Ammonia Plant area, Urea Plant HP section are some of them which
can lead to a major accident.

Although, Fire, explosion and release / leakage of toxic chemicals may lead to major accident, all
necessary safety measures have been duly incorporated in the plant design and regular up
gradation of safety appliances is carries out.

Hazards

Urea manufacturing process involves many chemicals such as NG, as feed stock, Ammonia as an
intermediate product and chlorine, hydrochloric / sulfuric acids, as water treatment chemicals.
Furnaces, High pressure vessels, Reactors, pipe lines, storage tanks are also involved in the
course of Urea and Ammonia manufacturing. Handling and storage of these Hazardous chemicals
and their use in the process may leak to a hazardous situation.


Failure Mode Analysis

There are various modes in which flammable and toxic chemicals can leak into atmosphere
causing adverse affects. It may be small leaks from gaskets of the flanged joints, or guillotine
failure of a pipeline of even catastrophic failure of the storage tank. Some typical modes of failures
and their possible causes are discussed below :

 S.No.      Failure Mode            Probable Cause               Remarks


 1.         Flange    /    Gasket   Incorrect gasket Incorrect   Attention to be paid during selection
            failure                 installation.                and installation of gaskets.

 2          Weld failure            It is normally due to poor   Welding to be done by certified
                                    quality of welds             welders with right quality of welding
                                                                 rods. Inspection and radiography
                                                                 must also be done.
 3          Pipe       corrosion    Some times fabrication or    Pipes material of construction
            erosion or failure      installation leaves stress   should be selected correctly.
            due to stress           in the pipes. Erosion or     Design should take care of erosion
                                    corrosion      also    are   effects. And installation of pipes
                                    sometimes the cause.         should not leave any stress.




                                                                                                     5
4         Over pressurization     Over pressurization can         Necessary procedures should be
           of pipeline             occur due to failure of         there to prevent.
                                   SRV        or       incorrect
                                   operation.
 5         Deficient               Pipes        design      and    It must be ensured that installation
           installation of pipes   installation is sometimes       is as per correct standards
                                   not as per appropriate          completely.
                                   standard.
 6         Leaks from valve        Leaks       from      glands,   Right selection of valves and their
                                   bonnets or failures valves      maintenance should be ensured.
                                   spindle is sometimes the
                                   cause.
 7         Instruments failure     Multifarious instruments        Reliability of instruments working
                                   are used for control of         must be ensured through proper
                                   process parameters. Any         selection and maintenance.
                                   such instrument failure
                                   can cause mishap.
 8         Failures          of    Protective system like          Reliability of protective system must
           protective system       SRV, bursting discs, vent       be    ensured       highest    through
                                   header, drain lines etc.        inspection and proper maintenance.
                                   are provided to take care
                                   of abnormal conditions.
 9         Operational effort      Plant            operational    Operating procedures must          be
                                   parameters should not be        complete and strictly followed.
                                   exceeded beyond the
                                   permissible limits.
 10        Other failures          There are external other        Design and operating philosophy
                                   reasons       causing     the   must consider all possible reasons.
                                   failures.

       INFORMATION ON THE HAZARD ASSESSMENT

Identification Of Hazards

The following main hazards may exist in the factory under the situations given below-
         High temperature and pressure.
         Fire & explosions (due to inflammable / combustible materials).
         Toxic and corrosive chemicals.
         Toxic and poisonous gases and dust.
         Electricity (Receiving / Clue ration / Distribution).
         Disposal of wastes.
         Work at heights.
         Work in confined spaces / vessels / tank etc.
         Specific jobs carried under highly hazards atmosphere (CO2, NH3, Naphtha vapours etc.).
         Non working of safety devices, inter locks, failure of high RPM machineries.
         Failure of boilers etc.
         Any other consequences due to leak of Ammonia, Chlorine gases.
         Hazards during heavy equipment handling (Crane, etc.)
         Road accidents

However, the threats posed to the aforesaid hazards may be on account of (i) Fire or (ii) explosion
or (iii) Release of toxic or corrosive liquid / gas from their confinement.

Causes Of Major Accidents

Following Major causes may lead to major accidents :-

1.      Release of Ammonia in huge quantity from storage tank.
2.      Release of chlorine due to leakage / rupture in chlorine toner or its valve failure of injection
        pipe failure feeding to cooling tower.
3.      Fire / explosion in Naphtha tanks due to leakage, unconfirmed clouds, or boil over, etc.
4.      Explosion in High pressure equipments, reactors in Ammonia / Urea Plants.

                                                                                                        6
5.       Fire / explosion in furnaces of Ammonia Plant and boilers in Power Plant.

Assessment Of Hazards According To Their Occurrence Frequency

Concurrency frequency (probability failure / year) for each selected failure case is given in table
9.c.1. For most of the cases the probability of failure occurrence is very less. Fire / explosion, sling
failure, safety rule failure, and injuries etc. are some cases which are considered as associated
hazards.

Assessment Of Accident Consequences

A major accident may cause severe danger to life and properties. The assessment will be based
on :

         Onsite losses.
         Offsite losses.

The first one will be loss of life, property damage and injuries to the scene of occurrence where the
people are working or combating with the accident control.
The offsite losses will include the loss of lives, injuries and properties damages of neighbor hood
bases on the affected area of accident or major event, if any.

Assessment Of The Possible Release Of Hazardous Chemicals Or Of Energy.

Technological Risks posed by this Fertiliser factory constitute threat to :

i) Its workers
ii) To a third party who may be present either in the factory or in its vicinity at the time of accident.
iii) Inhabitants living in the immediate neighborhood of the factory and their property.
iv) Environmental Conditions around the factory site.
The threats posed to the aforesaid entities may be on account of -
i) Fire,
ii) Explosion,
iii) Release of Toxic or corrosive liquids / gas from their confinement. The primary reason why
     such a disaster may occur, in spite of all precautionary measures is that major type of
     chemicals handled, are highly hazardous in nature and in substantial quantities, or
iv) A combination of more than one of such accidental phenomenon.

These risks may manifest due to accidental failures, break down or rupture of processing vessels,
equipments, storage tanks or pipelines. They may also arise due to undetected loss of
containment because of which liquid or gas contents gradually leak out in sufficient quantities to
create a hazardous situation. The loss of containment and associated hazards may be realized in
one of the following ways :

-    Large scale fire in naphtha storage area due to damage to the storage tank.
-    Naphtha leak from pipeline resulting into fire.
-    Flash fire due to leakage of flammable gas.
-    Equipment failure, pipeline failure, flange gasket failure, pump seal failure, safety relief valve
     failure etc. resulting in leakage of flammable, explosive and toxic material.
-    Accidents due to human errors.
-    Acts of nature like earthquake, enemy air attack during war, sabotage, act of terrorism etc.

When the scale of such accident is as to cause either –

a) Severe destruction of property.
b) Multiple fatalities and other casualties and cannot be contained within the premises, a Disaster
   Situation is said to prevail.

However the release of components listed below may cause hazards:-

a) Natural Gas, the feed stock for ammonia plant and
b) Hydrogen gas produced by reformation process for synthesizing Ammonia and



                                                                                                       7
c) Ammonia itself, generated as an intermediate product, constitute the gravest risks both from
   their nature of properties and the quantities involved.


Natural Gas is a highly flammable Gas equivalent to gasoline from fire and explosion hazard
angle, having a auto ignition temp. of 482 °C and a flammable range of 3.8 – 17 %.

Naphtha is also highly flammable liquid having flash point of -40o C and flammable range between
1 and 6%.

Ammonia is highly toxic gas its TLV being 25 ppm. It is also a combustible gas which can explode
under certain circumstances, although its lower explosive limit is rather high being of the order of
16%. It is true that two other highly flammable gases viz Carbon Monoxide and Methane are also
evolved in of the Ammonia plant. However, as these gases are immediately converted into non-
hazardous substances, they at best constitute transient risks. Besides the materials directly
involved in the manufacturing process, another extremely toxic gas viz Chlorine.

Chlorine (which has a TLV of 1 ppm) is used for treatment of water in the Cooling Towers. In-
spite of the fact, that quantity of chlorine held in the plant is almost insignificant, because of its
extremely high toxicity a leakage even in a „tonner‟ holding only 900 Kg of gas can endanger the
persons present inside the plant.

Assessment of risks posed by industrial accidents has two aspects viz.
 How frequently such accidents can occur and
 What could be their impact on people, property and environment.

Making a technically sound assessment of accident frequency for any individual plant is like
walking on treacherous grounds. It is true that there are various structured methods like HAZOP,
HAZAN, fault tree, Analysis Event tree Analysis etc. through which an estimate of such frequencies
can be attempted. However, no such methods can ensure that all potential accidents or top –
events would be identified, that all potential fault paths would be found and all common cause
failures covered. More-over, the adoption of such methods need use of Reliability Indices of
equipment and components of the system under study. These Reliability Indices are expected to
be furnished by the manufacturers, which is seldom the case in actual practice. No doubt generic
data could be used as a less preferable alternative. However, besides such data not being
available for every component, their use may give an entirely erroneous picture, as the real values
of such indices are greatly dependent on conditions of use, standards of maintenance etc. Even if
correct Reliability data were available, the results may not be quite accurate as accidents are
known to have taken place due to Human errors in operation and maintenance for which no
satisfactory models are yet available.
A statistical estimate of the risk could have been made if enough operating experience of the facts
was available. However, in the present case, the experience is not long enough to predict with any
degree of certainly of probability of accidents of different magnitudes, especially of that which may
cause Maximum credible loss, as such accidents are incidents of extremely low frequency. All that
can be stated with confidence is that since.

a)      The process carried out in the plant is well tested.
b)      The design and installation of the plant comply with recognized standards and codes of
        practice and
c)      All reasonable precautions are followed in respect of operation and maintenance, chances
        of a major accident is of low order.

HAZARDOUS AREAS OF THE PLANT

The following areas of the IFFCO Aonla Unit are hazardous with respect to nature of materials
handled and operating parameters.
  Ammonia Plant
  Urea Plant
  Ammonia storage
  Naphtha Storage and Handling
  Chlorine storage



                                                                                                    8
PLANT WISE HAZARDS

The plant wise hazards due to nature of materials handled there at are given below :

  Plant                                  Hazardous Material              Nature of Hazard

  Ammonia Plant               Natural Gas                                Fire
                              Naphtha                                    Fire
                              Process gas containing                     Fire
                              H2, CO, CH4                                Explosion
  Urea Plant                  Ammonia (liquid or gas)                    Toxic
  Ammonia storage             Ammonia Carbon dioxide                     Toxic Asphyxiant
  Naphtha Storage and         Ammonia                                    Toxic
  handling                    Naphtha                                    Fire
  D.M. Water plant            Hydrochloric acid caustic lye              Corrosive
  Cooling Tower               Chlorine                                   Toxic


ASSESSMENT OF THE POSSIBLE DISPERSION OF RELEASED CHEMICALS
STORAGE CAPACITY OF HAZARDOUS MATERIALS

The hazardous materials stored in the plant in substantial quantities. The detail of storage capacity
for each material is given below:

            Equipment                        Nos.        Material           Capacity
 Naphtha storage tank (old)                    2         Naphtha             6000 KL
 Naphtha storage tank (new)                    1         Naphtha            10000 KL
 Ammonia storage Tank                          2     Liquid Ammonia        10,000 Te *
 Chlorine Tonners                             16         Chlorine            900KG

* Though the capacities of Ammonia storage tanks are 10000 Te each , we normally store minimal
  quantity of liquid Ammonia in our Ammonia storage Tanks. The storage quantity at no times
  goes beyond 40% in the storage tanks. This conscious decision reduces the hazard potential.

FAILURE CASE LISTING

Keeping in view, the inventories of different hazardous material, plant process parameters etc.
following are the selected failure case which way be considered for consequence analysis. This
includes the worst case scenario i.e. catastrophic failure of Ammonia storage tanks and Naphtha
storage tanks, also leakage of ammonia from ammonia storage tank or from the system handling
ammonia, chlorine from tonners and fire in the naphtha tanks or from handling systems is identified
as the major accident hazards. This can occur as given below:


             Incident                                         Consequence
 Catastrophic       rupture       of   Refrigerated liquid ammonia or liquid ammonia spill and
 Ammonia storage tank or major         dispersion.
 leakage from the ammonia
 handling system.
 Chlorine leakages from the            Chlorine leakage and dispersion
 tonners due to valve getting
 sheared.
 Catastrophic failure of Naphtha/      Major fire.
 FO storage tanks and the
 leakage catching fire.
 Pipeline fracture / Nozzle failure    Liquid ammonia spills at hydraulic head or pump delivery
                                       pressure and dispersion.
                                       Chlorine leakage at tonners pressure and dispersion
                                       If the leakage due to pipeline fracture or nozzle failure in
                                       naphtha and catches fire- fire incident.



                                                                                                   9
Gasket failure                    Liquid ammonia spill and dispersion.
                                             Chlorine leakage and dispersion.
                                             Fire if the naphtha or FO leakage due to gasket failure and the
                                             leakage catch fire.

        System elements or events that can lead to major accident.

          a. Catastrophic rupture of Ammonia storage tank or major leakage from the ammonia handling
             system.
          b. Chlorine leakage from the tonners due to valve getting sheared.
          c. Catastrophic failure of Naphtha/FO / Diesel storage tanks or major leakage from the handling
             systems of these materials catching fire.
          d. Pipeline fracture / Nozzle failure.
          e. Gasket failure leading to flange leakages

Hazards
             Incident                Quantity Released
                                                                             Consequences
 1   Catastrophic rupture of              4000 MT             Ammonia Concentration upto 500 ppm in
     Ammonia storage tanks.                                   down-wind direction upto 11000 m
 2   Liquid ammonia line to                 40MT              Ammonia concentration upto 500 ppm in
     tank failure (20%)                                       down wind direction upto 4700ft downwind
                                                              & 8000ft cross wind.
 3   Chlorine leakage from                 900 kg             Chlorine Concentration upto 30 PPM in
     the tonners                                              down-wind direction upto 1247 m
                                                                          2
 4   Catastrophic failure of                                  12.5 KW/m heat radiation level at a
     Naphtha storage Tank         10000 KL                    distance of 56.35m
                                                              Burnpool radius : 150ft, Flame height:210ft,
                                                              Fatality radius upto distance 300ft, First
                                                              degree/Injury Zone radius upto
                                                              400ft(approx.)
 5   10000KL Naphtha tank                                     First degree burn upto 300 ft.
     outlet line failure (100%)                               Fatality radius upto 210ft
                                                              Burnpool radius: 100ft
                                                                          2
 6   Catastrophic failure of               7000KL             12.5 KW/m heat radiation level at a
     Naphtha storage Tanks                                    distance of 46.53m

                                                                         2
 7   Catastrophic failure of              1000 KL             12.5 KW/m heat radiation level at a
     Fuel Oil Storage tank.                                   distance of 43.5m
                                                                           2
 8   Leakage of synthesis                                     12.5 KW/m heat radiation due to flash fire
     gas from loop                                            extends up to 224.3 m
                                                                           2
                                                              12.5 KW/m radiation level due to jet flame
                                                              occur till 92.87 m
                                                              The over pressure of 0.2068 bar g is up to a
                                                              distance of 265.6m This over pressure may
                                                              result in extensive damage.

Note:     1. The IDLH of ammonia has been taken as 500ppm (NIOSH)
          2.The IDLH of chlorine has been taken as 30 ppm. (NIOSH)
          3. The weather is taken as 5 m/s D pasquill

Hydrogen

        Synthesis gas (which is hydrogen rich) is produced in the plant for conversion to Ammonia. There is
        no hydrogen gas holder for storage. Due to high pressure sufficient quantity is present in the
        process vessels and pipings to pose fire / explosion hazard. No off-site effect is envisaged for any
        synthesis gas fire explosion accidents.




                                                                                                             10
       CONSEQUENCE ANALYSIS

In case of release of toxic gas into the atmosphere the metrological factors play an important role
in transport, dispersion and diffusion in the atmosphere. The metrological data collected for the
IFFCO Aonla site was utilized for the purpose.

The mean annual speed is 3.5 km/hr. As regards the temperature in peak winter the mean daily
maximum temperature is around 18 degree C and minimum temperature is about 2 °C. In peak
summer the mean daily maximum temperature is about 31. °C and minimum temperature is 14 °C.

Fire hazard is generally experienced in the vessels where a large quantity of flammable material is
stored or when a major leak occurs. Fire hazard is a distinct possibility in Naphtha, FO and Diesel
storage tanks. The major fire risk rests on the storage tank having the maximum storage capacity
i.e. Naphtha storage tank having a capacity of 10000 KL+6000KL+6000KL but normal storage is to
the extent of 7000 KL. In case of catastrophic failure of the tank and the leakage catching fire, the
                                     2
critical radiation level of 12.5 KW/m will be felt at a distance of 56.35 m and the farthest distance
of flash fire at 229 m. If there is an explosion of the leaking naphtha vapour, over pressure of
0.2068 bar will extend up to 212.1 m. Since there is boundary wall, the effect of over pressure may
not be felt out side the factory premises. At the same time no population is residing in 800m radius
from tank area. The effects of explosion inside the factory premises may result in damage to
                                2
equipment. The 12.5 KW/m radiation level resulting from pool fire of Fuel Oil may extend up to
43.5 m.
                                                       3                                      3
The flow of gas in the synthesis loop is 685000m /hr, which corresponds to 39565 m /hr of
                                                                 2
hydrogen. The synthesis loop is at a pressure of 200 Kg/cm g. Assuming escape of the entire
                                                                                               2
quantity of gas through a 50mm hole and the escaping gas results in a jet flame with 12.5 KW/m
radiation level up to 92.87 m. The farthest extent of flash fire may affect up to 224.3 m. Over
pressure of 0.2068 bar due to explosion will be felt up to a distance of 265.6 m. As mentioned
above, the effects of over pressure may not be felt out side the factory premises.

Due to catastrophic rupture of ammonia storage tank, assuming the entire quantity of 4000
MTdisperses, the IDLH level of ammonia of 750 ppm at 1.35 m/s, D neutral weather conditions is
at a distance of 11000 m from the source of release. Similarly for chlorine release from a tonner
due to valve failure, the IDLH level of chlorine of 30 ppm at 1.35m/s D neutral weather conditions is
at a distance of 500m from the source of release.

       ASSESSMENT OF THE EFFECTS OF THE RELEASES (SIZE OF THE AFFECTED
        AREA, HEALTH EFFECTS, PROPERTY DAMAGE) :

Assessment of Risk impact is however, more important from the angle of On-site the Emergency
planning as primary concern of such planning is for creating preparedness and providing measures
for tackling major accidents.

Consequence analysis is basically quantitative study of the hazard with the help of internationally
accepted mathematical models, to determine the possible magnitude of damage effects and to
determine the distances up to which the damage may be affected for various failure scenarios.
The consequence analysis results in :
- To aid in better plant layout to reduce hazards.
- For evaluating damage potential for other plants and incorporating protection measures.
- To ascertain damage potential to public and evolve protection measures.
- For preparation of effective planning for both On – Site and off-site emergency.

The results of consequence analysis are useful for getting information about all known and
unknown effects that are of importance when some failure scenario occur and to get information
about how to deal with possible catastrophic events. It also gives the plant authorities, workers and
the public living outside in the vicinity of the plant an understanding of hazard potential and
remedial measures.

Bases on the result of consequences analysis, it may be concluded that in most of the cases the
effect would be limited to with-in plant boundary and there is no risk posed to neighborhood
because of this. But for scenarios involving Ammonia Gas leaks the effected zone goes beyond
the factory premises. The risk to the neighborhood of the project is therefore mainly be due to



                                                                                                  11
release of ammonia as described the different scenarios of Ammonia leakage. The probability of
such failure occurrence is extremely low in a order of 3 failure per ten lakh years duration.
It may be also concluded that catastrophic failure of Naphtha Storage Tank, Atmospheric storage
tanks, Let down vessels etc. may occur really and contribute small risk because of low frequency
of occurrence.

There are 5000 persons residing in our Township and details of surrounding villages within 5 km
circles and their population is around 10000.

       DESCRIPTION OF SAFETY RELEVANT UNITS, AMONG OTHERS SPECIAL DESIGN
        CRITERIA

Based on Preliminary hazard analysis the design criteria of system elements are as follows –

Ammonia Plant

Ammonia Plant is designed with a great deal of safety. The whole plant is open with proper lay out
of pipe lines, trenches, cables and flame proof lighting arrangements. A proper spacing between
the equipments, reactors, pumps, turbines, and compressors has been kept. Insulation of pipe
lines, vessels have been done wherever required. Proper marking, arrows, colour coding has
been done for convenience and statutory requirements. Control room with emergency doors and
safety equipments are established. Safety trip systems with alarms and trip relays (intrinsically
safe) have been provided to control and safe shut down of the plant during emergencies. Stacks
for furnaces and flare stack for burning of vent / excess gases of 30 M. height have been provided.
Safety valves, Rupture discs, explosion vents, vacuum breakers have been provided as extra
safety precautions other than automatic tripping of concerned equipment / unit in case of any
abnormality.

Urea Plant

This plant is safely designed to handle the process with safety valves, Rupture discs and automatic
tripping relays & alarms etc.

Power Plant

All safety measures have been adopted to ensure safe handling and operation of these plants.
Safety devices are of adequate sizes. Waste disposal being done with great care. The stack of
Power Plant is 120 mts. High and analysis of CO2 is being carried out regularly. SPM (Suspended
particulate matter) and SO2 are monitored on weekly basis. All the parameters are always well
with in the prescribed standard of U.P. Pollution control Board / Central Board.

Control and Alarms

Kick back antisurge valves on compressors to avoid surging in compressors.
Pressure controls at different points of the plants to control operating pressure automatically well
within the limits.
Flow controls to control and regulate flow of fluids automatically at desired level.
Temperature controls to control requisite temperature automatically.
Level controls to control level in various equipments automatically.
Likewise several alarms and trip circuits with automatic actuation are given in all the plants for safe
operation and process control.


Safety Relevant Components

The design and operating procedures has been so developed that it enables the safe handling,
operation and upkeep of plants. However, so far no major accident has taken place. The built in
Safety has been the prime factor while selecting the equipments, processes etc. Standards codes
of practices are being followed seriously during the erection, modification etc.
Some Safety relevant components are mentioned below :-

-   Use of relief valves, rupture discs, explosion vents of adequate sizes with proper testing.
    Checking of these safety relevant components are done in every annual shut down.


                                                                                                    12
-    Automatic control valves, solenoid operated quick shut off valves are installed to control any
     sort of emergencies.
-    Alarms, sensors, relays, trip systems have been provided.
-    Proper training, disclosure of information related to Safety rules / procedures have been given.
-    Appropriate operating procedures, manuals etc. are implemented since inception.
-    Flare stack for burning of vent gases like Ammonia, Natural Gas and Naphtha Vapours have
     been provided.
-    All the statutory requirements are being fulfilled and followed.

Setup Of Fire And Safety Section

All staff of Fire & Safety, Health and Environment sections and are of well qualified Engineers,
Fire& safety officers and Doctors.

EQUIPMENTS FOR FIRE FIGHTING
IFFCO-AONLA is well equipped with all fire & Safety appliances like Fire Tenders-3 with a pick up
van, all types of extinguishers like DCP,CO2,WATER CO2 Foam types in adequate numbers,
PPES like Breathing Apparatus of different types & capacities, Online Air masks at various
Hazardous areas ,Gas tight Suits, Alumnised Suits, Explosive meters, Portable Gas Detectors
,Chlorine Emergency Leakage Kit, Air compressor for air cylinders filling, PVC apron & suits, gum
boots, safety shoes, safety belts , Various types of hand gloves ,ladders, nylon life saving net,
Canisters, safety torches, dust pads etc.
 Fire Detection/ Alarm System for Plant Control Rooms, Administrative building, Cable Galleries,
Transformers are also provided. These are of Ionization, Optical & Heat sensing type.

Fixed Installations

         All Naphtha tanks are protected by installation of automatic fixed foam pouring system at
         their top which is checked periodically and record is maintained.
         There is a battery of CO2 cylinders installed for the turbo Generator sets GTG-I , GTG-II &
         GT in Ammonia-2, designed to come into operation in case of fire.
         In Bagging Plant including Empty bag Storages Fire hydrant system is well laid out &
         connected with Smoke detectors have been installed to work in case of any fire.
         Smoke detection system is provided at all the important buildings and control rooms.
         Well Laid under ground Fire Hydrant System Underground fire hydrant pipes has been
         laid throughout the premises as per the TAC guideline, keeping in mind area wise hazard
         categorization, based on which the distance of hydrant posts were provided. To maintain
         minimum hydrant pressure of 7 kg/cm2 fire pumps & auxiliary systems are provided at fire
         pump house near Raw water reservoir.
         At various places Eye wash showers have been installed where hazardous chemicals are
         being handled.
         Flame Proof fittings at the hydrocarbon storage and handling areas.
         Flame arrestors on moving equipments and Spark arrestors on various hazardous fixed
         installations.
         Bounding was done at various flanges to avoid static sparks at the critical hazardous
         installations

Safety Equipments

1.       Gas masks for use in leakage of Gases like Ammonia, Chlorine, etc. are available in all the
         Plant. Apart from this, breathing apparatus supplied by MSA, (USA) are available in all the
         control rooms and at Ammonia storage tank area.
2.       Air line systems are provided in Urea and Ammonia control rooms for which air is supplied
         from instrument air header. These can be used by the operators working in control room in
         case of Ammonia leak.
3.       Explosive meters supplied by M/s. MSA, (USA) and RESPO PRODUCTS .are available in
         all the plants for checking any leak of gases and testing the vessel and operating areas,
         before issue of hot work permit or permit for vessel entry etc.
4.       Personnel Protective appliances like safety helmet, safety goggles hand gloves etc., are
         issued to all the employees. Apart from this Eye wash showers, face shields, PVC suits
         etc. are installed in all sections of the plant.



                                                                                                  13
5.      Gas tight suits, chemical splash suits, Fire proximity suits and other suits are available to
              handle emergencies like toxic release, fire etc.
      6.      In order to create sense of safety consciousness safety section organises, various
              competitions every year like safety essay, slogan, debate and quiz competitions for regular
              employees and safety drawing competition for their children. Prizes are also given to the
              winners for motivation.

             TRAINING IN FIRE FIGHTING & SAFETY AND OHSAS-18001

      1.      Training of first aid fire fighting and accident prevention is imparted twice every year to all
              the employees, by the officers of fire and safety section. Sufficient numbers of employees
              have also been trained by St. John Ambulance Association on „First aid to the injured‟.
      2.      Twice in a year, Fire and safety section exercised Disaster ON-SITE Mock Drill with
              information to all Local authorities, for proper readiness in case of major disaster.
      3.      Emergency instructions are displayed at required places indicating actions to be taken in
              case of any leaks of Ammonia, Chlorine and Naphtha. Hoarding of hidden hazards are
              also displayed in different plants along with the control measures to be adopted while
              working there.
      4.      Wind socks are provided in Ammonia Plant, Ammonia Storage and handling area, Chorine
              handling area and other strategic locations to indicate wind direction in case of any toxic
              gas leak.
      5.      Portable oxygen meters and Explosive meters/Combustible Gas Indicators are also
              available in fire and safety section for checking the area or vessel, before entry and job to
              be carried out.
      6.      Periodic medical examination is being done for the employees
      7.      Proper hygiene and decontamination facilities have been provided and being done
              regularly
      8.      By putting the objectives and targets in OHSAS-18001like various trainings on Fire &
              Safety ,environment and health matters, periodic health check of the employees, training of
              Truck drivers and transporters and Importantly to contract and casual labour. and then
              follow up is being done rigorously to meet the objectives
      9.      All chemicals MSDS (Material Safety Data Sheet) are kept at easily available places to
              know about the properties and other values.
      10.     Each chemical antidotes are also kept available in the hospital and at van




                      Above : Leakage scenario of Ammonia from sample point.


Conclusion:   By effectively identifying the various types of Hazards ,doing the risk analysis and
              controlling the risk ,IFFCO-AONLA unit is maintaining the accident free atmosphere for
              both the humans and plant/property




                                                                                                          14

More Related Content

What's hot

HIRA TRAINING PPT.pptx
HIRA  TRAINING PPT.pptxHIRA  TRAINING PPT.pptx
HIRA TRAINING PPT.pptxMoolRaj3
 
Safety harness - fall protection - Wessam Atif
Safety harness - fall protection - Wessam AtifSafety harness - fall protection - Wessam Atif
Safety harness - fall protection - Wessam AtifWessam Atif
 
Working at heights training powerpoint
Working at heights training powerpointWorking at heights training powerpoint
Working at heights training powerpointJomish John
 
Working at-height
Working at-height Working at-height
Working at-height Reliance
 
Lock-Out Tag-Out (LOTO) Training
Lock-Out Tag-Out (LOTO) TrainingLock-Out Tag-Out (LOTO) Training
Lock-Out Tag-Out (LOTO) TrainingKJP Consulting
 
Risk Assessment Example.pdf
Risk Assessment Example.pdfRisk Assessment Example.pdf
Risk Assessment Example.pdfBalamuruganD26
 
Lone Worker Safety Training
Lone Worker Safety TrainingLone Worker Safety Training
Lone Worker Safety Trainingalijonker
 
Job safety analysis
Job safety analysis Job safety analysis
Job safety analysis soumenmakar
 
Moving equipment around the site
Moving equipment around the site Moving equipment around the site
Moving equipment around the site Larry Riley
 
2 fire risk assessment template risk assessment templates
2 fire risk assessment template risk assessment templates2 fire risk assessment template risk assessment templates
2 fire risk assessment template risk assessment templatesDwarika Bhushan Sharma
 
EMERGENCY RESPONSE TEAM (ERT).pptx
EMERGENCY RESPONSE TEAM (ERT).pptxEMERGENCY RESPONSE TEAM (ERT).pptx
EMERGENCY RESPONSE TEAM (ERT).pptxssuserd19c3e
 
BANKSMAN TRAINING.ppt
BANKSMAN TRAINING.pptBANKSMAN TRAINING.ppt
BANKSMAN TRAINING.pptKamran Zafar
 
Industrial safetY of height works
Industrial safetY of height worksIndustrial safetY of height works
Industrial safetY of height worksPavan Noel
 
20 use of suspended access cradles and platforms (temporary works) risk asses...
20 use of suspended access cradles and platforms (temporary works) risk asses...20 use of suspended access cradles and platforms (temporary works) risk asses...
20 use of suspended access cradles and platforms (temporary works) risk asses...Dwarika Bhushan Sharma
 
Machine Guarding Ppt
Machine Guarding PptMachine Guarding Ppt
Machine Guarding PptColleen True
 
CLASS Regulation 2013
CLASS Regulation 2013CLASS Regulation 2013
CLASS Regulation 2013Jau Robert
 

What's hot (20)

HIRA TRAINING PPT.pptx
HIRA  TRAINING PPT.pptxHIRA  TRAINING PPT.pptx
HIRA TRAINING PPT.pptx
 
Permit to Work Training
Permit to Work TrainingPermit to Work Training
Permit to Work Training
 
Safety harness - fall protection - Wessam Atif
Safety harness - fall protection - Wessam AtifSafety harness - fall protection - Wessam Atif
Safety harness - fall protection - Wessam Atif
 
Working at heights training powerpoint
Working at heights training powerpointWorking at heights training powerpoint
Working at heights training powerpoint
 
Working at-height
Working at-height Working at-height
Working at-height
 
Lock-Out Tag-Out (LOTO) Training
Lock-Out Tag-Out (LOTO) TrainingLock-Out Tag-Out (LOTO) Training
Lock-Out Tag-Out (LOTO) Training
 
Risk Assessment Example.pdf
Risk Assessment Example.pdfRisk Assessment Example.pdf
Risk Assessment Example.pdf
 
Hot Work
Hot WorkHot Work
Hot Work
 
Lone Worker Safety Training
Lone Worker Safety TrainingLone Worker Safety Training
Lone Worker Safety Training
 
Job safety analysis
Job safety analysis Job safety analysis
Job safety analysis
 
Moving equipment around the site
Moving equipment around the site Moving equipment around the site
Moving equipment around the site
 
2 fire risk assessment template risk assessment templates
2 fire risk assessment template risk assessment templates2 fire risk assessment template risk assessment templates
2 fire risk assessment template risk assessment templates
 
EMERGENCY RESPONSE TEAM (ERT).pptx
EMERGENCY RESPONSE TEAM (ERT).pptxEMERGENCY RESPONSE TEAM (ERT).pptx
EMERGENCY RESPONSE TEAM (ERT).pptx
 
BANKSMAN TRAINING.ppt
BANKSMAN TRAINING.pptBANKSMAN TRAINING.ppt
BANKSMAN TRAINING.ppt
 
Industrial safetY of height works
Industrial safetY of height worksIndustrial safetY of height works
Industrial safetY of height works
 
20 use of suspended access cradles and platforms (temporary works) risk asses...
20 use of suspended access cradles and platforms (temporary works) risk asses...20 use of suspended access cradles and platforms (temporary works) risk asses...
20 use of suspended access cradles and platforms (temporary works) risk asses...
 
Hirarc
HirarcHirarc
Hirarc
 
Machine Guarding Ppt
Machine Guarding PptMachine Guarding Ppt
Machine Guarding Ppt
 
CLASS Regulation 2013
CLASS Regulation 2013CLASS Regulation 2013
CLASS Regulation 2013
 
Working at height slides
Working at height slidesWorking at height slides
Working at height slides
 

Viewers also liked

Hazard Identification & Risk Analysis (HIRA)
Hazard Identification & Risk Analysis (HIRA)Hazard Identification & Risk Analysis (HIRA)
Hazard Identification & Risk Analysis (HIRA)Sudip Dey
 
OHSAS Hazard identification & Risk assessment
OHSAS Hazard identification & Risk assessmentOHSAS Hazard identification & Risk assessment
OHSAS Hazard identification & Risk assessmentTechnoSysCon
 
Powerpoint Risk Assessment
Powerpoint Risk AssessmentPowerpoint Risk Assessment
Powerpoint Risk AssessmentSteve Bishop
 
Risk assessment presentation
Risk assessment presentationRisk assessment presentation
Risk assessment presentationmmagario
 
Risk assessment principles and guidelines
Risk assessment principles and guidelinesRisk assessment principles and guidelines
Risk assessment principles and guidelinesHaris Tahir
 
Risk assessment
Risk assessmentRisk assessment
Risk assessmentdoogstone
 
Risk Assessment and Method Statement for Installation of Boardwalk in Dublin ...
Risk Assessment and Method Statement for Installation of Boardwalk in Dublin ...Risk Assessment and Method Statement for Installation of Boardwalk in Dublin ...
Risk Assessment and Method Statement for Installation of Boardwalk in Dublin ...pierdole
 
Risk assessment and management
Risk assessment and managementRisk assessment and management
Risk assessment and managementTaekHyeun Kim
 
Occupational Health and Safety Powerpoint Presentation
Occupational Health and Safety Powerpoint PresentationOccupational Health and Safety Powerpoint Presentation
Occupational Health and Safety Powerpoint PresentationJoLowe72
 
Hazard Identification and Risk Assessment HIRA
Hazard Identification and Risk Assessment HIRAHazard Identification and Risk Assessment HIRA
Hazard Identification and Risk Assessment HIRAYvonne Matlaupane Leshaba
 
Presentation HIRARC Sem 3
Presentation HIRARC Sem 3Presentation HIRARC Sem 3
Presentation HIRARC Sem 3consist college
 
Biological hazards overview
Biological hazards overviewBiological hazards overview
Biological hazards overviewmcivers1979
 
Hazard analysis(ppt)
Hazard analysis(ppt)Hazard analysis(ppt)
Hazard analysis(ppt)waiyin_lee
 
Health and safety plan generic
Health and safety plan genericHealth and safety plan generic
Health and safety plan genericfirstpick
 
Fmc close out repot hse dept. rev.000
Fmc close out repot hse dept. rev.000Fmc close out repot hse dept. rev.000
Fmc close out repot hse dept. rev.000Fitri Ifony
 

Viewers also liked (20)

Hazard Identification & Risk Analysis (HIRA)
Hazard Identification & Risk Analysis (HIRA)Hazard Identification & Risk Analysis (HIRA)
Hazard Identification & Risk Analysis (HIRA)
 
Hazard identification
Hazard identificationHazard identification
Hazard identification
 
OHSAS Hazard identification & Risk assessment
OHSAS Hazard identification & Risk assessmentOHSAS Hazard identification & Risk assessment
OHSAS Hazard identification & Risk assessment
 
Powerpoint Risk Assessment
Powerpoint Risk AssessmentPowerpoint Risk Assessment
Powerpoint Risk Assessment
 
Risk assessment presentation
Risk assessment presentationRisk assessment presentation
Risk assessment presentation
 
Risk assessment principles and guidelines
Risk assessment principles and guidelinesRisk assessment principles and guidelines
Risk assessment principles and guidelines
 
Risk assessment
Risk assessmentRisk assessment
Risk assessment
 
Risk Assessment and Method Statement for Installation of Boardwalk in Dublin ...
Risk Assessment and Method Statement for Installation of Boardwalk in Dublin ...Risk Assessment and Method Statement for Installation of Boardwalk in Dublin ...
Risk Assessment and Method Statement for Installation of Boardwalk in Dublin ...
 
Risk assessment and management
Risk assessment and managementRisk assessment and management
Risk assessment and management
 
Hirarc
HirarcHirarc
Hirarc
 
Occupational Health and Safety Powerpoint Presentation
Occupational Health and Safety Powerpoint PresentationOccupational Health and Safety Powerpoint Presentation
Occupational Health and Safety Powerpoint Presentation
 
Hazard Identification and Risk Assessment HIRA
Hazard Identification and Risk Assessment HIRAHazard Identification and Risk Assessment HIRA
Hazard Identification and Risk Assessment HIRA
 
Risk Assessment Presentation
Risk Assessment PresentationRisk Assessment Presentation
Risk Assessment Presentation
 
Presentation HIRARC Sem 3
Presentation HIRARC Sem 3Presentation HIRARC Sem 3
Presentation HIRARC Sem 3
 
Safety: Hazard Identification and Recognition Program
Safety: Hazard Identification and Recognition ProgramSafety: Hazard Identification and Recognition Program
Safety: Hazard Identification and Recognition Program
 
Biological hazards overview
Biological hazards overviewBiological hazards overview
Biological hazards overview
 
Hazard analysis(ppt)
Hazard analysis(ppt)Hazard analysis(ppt)
Hazard analysis(ppt)
 
Health and safety plan generic
Health and safety plan genericHealth and safety plan generic
Health and safety plan generic
 
Occupational hazards
Occupational hazardsOccupational hazards
Occupational hazards
 
Fmc close out repot hse dept. rev.000
Fmc close out repot hse dept. rev.000Fmc close out repot hse dept. rev.000
Fmc close out repot hse dept. rev.000
 

Recently uploaded

Long journey of Ruby standard library at RubyConf AU 2024
Long journey of Ruby standard library at RubyConf AU 2024Long journey of Ruby standard library at RubyConf AU 2024
Long journey of Ruby standard library at RubyConf AU 2024Hiroshi SHIBATA
 
Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Farhan Tariq
 
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...Wes McKinney
 
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024BookNet Canada
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.Curtis Poe
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersRaghuram Pandurangan
 
Time Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsTime Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsNathaniel Shimoni
 
From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .Alan Dix
 
Potential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsPotential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsRavi Sanghani
 
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...panagenda
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersNicole Novielli
 
A Framework for Development in the AI Age
A Framework for Development in the AI AgeA Framework for Development in the AI Age
A Framework for Development in the AI AgeCprime
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterMydbops
 
Rise of the Machines: Known As Drones...
Rise of the Machines: Known As Drones...Rise of the Machines: Known As Drones...
Rise of the Machines: Known As Drones...Rick Flair
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfMounikaPolabathina
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxLoriGlavin3
 
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentEmixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentPim van der Noll
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxLoriGlavin3
 
Take control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteTake control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteDianaGray10
 
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxPasskey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxLoriGlavin3
 

Recently uploaded (20)

Long journey of Ruby standard library at RubyConf AU 2024
Long journey of Ruby standard library at RubyConf AU 2024Long journey of Ruby standard library at RubyConf AU 2024
Long journey of Ruby standard library at RubyConf AU 2024
 
Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...Genislab builds better products and faster go-to-market with Lean project man...
Genislab builds better products and faster go-to-market with Lean project man...
 
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
The Future Roadmap for the Composable Data Stack - Wes McKinney - Data Counci...
 
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
New from BookNet Canada for 2024: Loan Stars - Tech Forum 2024
 
How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.How AI, OpenAI, and ChatGPT impact business and software.
How AI, OpenAI, and ChatGPT impact business and software.
 
Generative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information DevelopersGenerative AI for Technical Writer or Information Developers
Generative AI for Technical Writer or Information Developers
 
Time Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directionsTime Series Foundation Models - current state and future directions
Time Series Foundation Models - current state and future directions
 
From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .From Family Reminiscence to Scholarly Archive .
From Family Reminiscence to Scholarly Archive .
 
Potential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and InsightsPotential of AI (Generative AI) in Business: Learnings and Insights
Potential of AI (Generative AI) in Business: Learnings and Insights
 
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
Why device, WIFI, and ISP insights are crucial to supporting remote Microsoft...
 
A Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software DevelopersA Journey Into the Emotions of Software Developers
A Journey Into the Emotions of Software Developers
 
A Framework for Development in the AI Age
A Framework for Development in the AI AgeA Framework for Development in the AI Age
A Framework for Development in the AI Age
 
Scale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL RouterScale your database traffic with Read & Write split using MySQL Router
Scale your database traffic with Read & Write split using MySQL Router
 
Rise of the Machines: Known As Drones...
Rise of the Machines: Known As Drones...Rise of the Machines: Known As Drones...
Rise of the Machines: Known As Drones...
 
What is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdfWhat is DBT - The Ultimate Data Build Tool.pdf
What is DBT - The Ultimate Data Build Tool.pdf
 
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptxDigital Identity is Under Attack: FIDO Paris Seminar.pptx
Digital Identity is Under Attack: FIDO Paris Seminar.pptx
 
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native developmentEmixa Mendix Meetup 11 April 2024 about Mendix Native development
Emixa Mendix Meetup 11 April 2024 about Mendix Native development
 
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptxUse of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
Use of FIDO in the Payments and Identity Landscape: FIDO Paris Seminar.pptx
 
Take control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test SuiteTake control of your SAP testing with UiPath Test Suite
Take control of your SAP testing with UiPath Test Suite
 
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptxPasskey Providers and Enabling Portability: FIDO Paris Seminar.pptx
Passkey Providers and Enabling Portability: FIDO Paris Seminar.pptx
 

Hazard Identification And Risk Assessment

  • 1. Hazard Identification and Risk Assessment by N.P.Rao.(CHIEF MANAGER(F&S) PAPER PRESENTED IN ICQESMS(INDIAN CONGRESS ON QUALITY,ENERGY,ENVIRONMENT AND SAFETY MANAGEMENT SYSTEMS CONDUCTED BY JADHAVPUR UNIVERSITY AND CBWE AND GOT EXCELLENT AWARD INTRODUCTION For any industry to be successful, it has become essential to identify the Hazards ,to assess the associated risks and to bring the risks to tolerable level. Recognising this, IFFCO-AONLA is continuously putting efforts for controlling the risks which are arising from various Hazards such that loss to Human life and property is negligible or zero. Its continuous best efforts to identify the Hazards and to bring the risk levels to tolerable level in the organization are recognised by several Government and safety regulating bodies. This paper describes briefly about various types of Hazards and their associated risks, how they are being controlled effectively through risk analysis at IFFCO – Aonla unit In all plants, hazards and risk are identified time to time by using modern techniques. IFFCO Aonla unit is OHSAS –18001 certified company. So in all departments /section risk and hazards are find out by proper risk assessments. During this severity at various levels matched with probability level. And find out the case of intolerable, substantial, moderate and tolerable risk. Accordingly control measures at the place checked. Documentation done and records are maintained. . At IFFCO Aonla unit, HAZOP, HAZAN study, Dow index, Risk Analysis, FMIA, Fault Tree Analysis are carried out at its inception level..At IFFCO Aonla unit, various risk assessment procedures are followed. This has been done by Dow Index method and Consequences methods. At the same time when any process modification done/needed, then also proper HAZOP studies and any other risk analysis studies are carried out to assess the risk due to the effect of modification. Now as IFFCO Aonla unit is OHSAS –18001 certified company, in all sections/plants proper hazard and risk assessment procedures and documentation done. Time to time, plant/section updates of this done and audited by other sectional persons. And again compliance incorporated. 1.0.0 To effectively implement the safety systems , a structured approach has been drawn out to minimize the hazards and risks . This involves the following :  REPORTING/INVESTIGATING/ANALYSIS OF ACCIDENTS, DANGEROUS OCCURRENCES AND NEAR MISSES. When any accident occurred in plant premise, the concern area shifts in-charge informed his higher officers as well as fire and safety section regarding this. Immediately accident/dangerous occurrence investigation committee consisting of senior officers from affected area, fire and safety section, factory safety officer and medical person set up. This committee starts immediately investigation without delay. It also preserves all facts and finding and reports of for future reference. IFFCO AONLA UNIT Y-AXIS ACCIDENT FREE MILLION HOURS Accident Free Man 16 947days 15.06 days 910 days( Cont.) 1000 14 13.00 737days 12 12.27 800 600days 10 600 8 7.83 400 Accident Free Mandays 6 200 122days 4 0 2 1.9 1 26.10.1997- 02.06.2000- 01.09.2002- 01.01.2003- 28.08.2004- 0 26.10.1997- 02.06.2000- 01.09.2002- 01.01.2003- 28.08.2004- 31.05.2000 08.06.2002 31.12.2002 22.08.2004 15.02.2006 31.05.2000 08.06.2002 31.12.2002 22.08.2004 15.02.2006 Accident Free Period
  • 2. IFFCO AONLA UNIT Accident Free Y-AXIS –ACCIDENT FREE MAN DAYS Million Man hours 15.06 16 13 1000 14 12.27 947 910 12 800 10 7.83 Accident free 737 Million Man- 8 hours 600 700 6 4 1.90 400 2 0 200 122 26.10.1997- 02.06.2000- 01.09.2002- 01.01.2003- 28.08.2004- 31.05.2000 08.06.2002 31.12.2002 22.08.2004 15.02.2006 0 26.10.1997- 02.06.2000- 01.09.2002- 01.01.2003- 28.08.2004- Accident Free Period 31.05.2000 08.06.2002 31.12.2002 22.08.2004 15.02.2006 X-AXIS ACCDIENT FREE PERIOD Now we see what type of risks and how they are being handled through some models of risk analysis in IFFCO –AONLA unit.  PROCESS & SAFETY–RELATED DATA FOR INDIVIDUAL PROCESS STAGES : Physical and Health Occupational Hazards in any large scale Chemical /Hydrocarbon Processing Industry (CPI/HPI) like our can be broadly classified into the following categories: i. Mechanical Risks ii. Electrical Risks iii. Fire/Explosion Risks iv. High /low Temperature Exposure Risks v. Toxic/Carcinogenic Chemicals Exposure Risks vi. Corrosive/Reactive/Radioactive Chemicals Exposure Risks The first two types of risks are of universal nature associated with any industrial activity and not specific to a particular plant or process. Mechanical risks which are generally encountered are injuries to the head, Limbs, eyes, etc usually as a results of negligence on the part of operating/maintenance personnel in the use of improper tools, bypassing prescribed safety procedures neglect of personal protective wear and risks associated with rotating machinery as well as risks associated with high-energy release from compressed gases. Electrical risks which result in shock and/or burns are most often a consequence of poor maintenance, ingress of dust or moisture, handling by unauthorized personnel and use of improper/substandard hardware. Other categories of risks associated with specific plants are detailed here under. Ammonia Plant : The manufacture of anhydrous liquid ammonia involves processing of hydrocarbons under high temperature, high pressure conditions in the presence of various catalysts, chemicals etc. Typical risks are as follows: Fire /Explosion  Glands/seal leaks in valves, pumps, compressors handling hydrogen, natural gas, naphtha, synthesis gas etc.  Hose/pipe failure, leakage from flanged joints carrying combustible gases, vapours, liquids.  Fire box explosions in furnaces. High/Low Temp.  Burns due to contact with hot surfaces of pipelines, equipments, etc. Exposure Risks or leaking steam lines, process fluids at high temperature.  Frost bite due to contact with anhydrous liquid ammonia at -33 deg. C  Burns due to contact with pyrophoric catalyst. Toxic Chemicals  Asphyxia due to inhalation of simple asphyxiants like CO2 , N2, H2, Exposure Risks CH4, naphtha etc. and chemical asphyxiants like CO, NH3, Nickel carbonyl, V2O5, Hydrazine, NOx, SOx, H2S etc.  Acute toxicity due to inhalation of catalyst dusts containing heavy metals like Ni, Cr, CO, Mo, Fe, Zn, Alumina etc. and silica gel molecular sieves, insulation fibers/dusts. 2
  • 3. Urea Plant The manufacture of urea involves reaction of Ammonia and Carbon dioxide under high temperature & pressure and subsequent recovery and concentration of the solution at various pressure stages. Typical risks are as follows : Fire / Explosion Risks  Ammonia leaks from glands / seals Risks involves, pumps or flanged joints piping resulting in formation explosive mixtures in air. Accumulation of H2 may take place in HP Section in case CO2 purity from Ammonia Plant is not within allowable limits. Ignition of this accumulated H2 can occur due to dissipation of static charge. High / Low  Refer to risks in Ammonia Plant Temperature Exposure Risks Toxic Chemicals  Asphyxia due to inhalation of simple Exposure Risks asphyxiants Exposure Risks like CO2 and N2 and chemical asphyxiant, NH3. Solution of Urea, Ammonium carbamate and ammonium carbonate containing high NH3 content.  Irritation due to inhalation of urea dust. Corrosive / Radioactive  Severe burns, damage to eyes, skin and body tissues due to Chemicals Exposure contact with anhydrous ammonia, conc. Urea and Ammonium Risks carbamate solutions. Power Plant The captive Power Plant involves generation of steam in N.G./Naphtha-fired boilers and utilizing the steam in Urea and Ammonia plants. Typical risks are as follows : Fire / Explosion Risks  Explosion and fire risks associated with storage and handling of B Class (Naphtha) and Natural gas handling pipelines (Refer off site Facilities).  Fire Box explosion in Boiler Flammable Material Lower Upper Temp. °C High / Low Temp.  Burns due to contact with hot surfaces of pipelines, Exposure Risks equipments, etc. or leaking steam lines. Toxic Chemical  Asphyxia due to inhalation of SOX and Nox. Exposure Risk  Irritation due to inflammation caused by inhalation of Natural gas and the Naphtha vapors. The permissible exposure limits for cyclohexylamine coal dust / fly-ash are given below : Offsite Facilities The offsite facilities, as already described at the very outset, consist of integrated units for water and effluent treatment, inert gas generation, cooling towers, storage of petroleum products and ammonia, supply / distribution of utilities like compressed air, water, etc. Potential risks in the above offsite facilities are essentially on account of handling of corrosive, toxic and reactive chemicals as well as inflammable petroleum products. 3
  • 4. Fire / Explosion Risks  Gland / Seal leaks in valves, pumps, compressor, handling naphtha, N.G., ammonia hydrogen, syngas etc.  Hose / pipe failure, leakage from flanged joints in pipes conveying petroleum products, ammonia, hydrogen, syngas, etc.  Leakage of petroleum products during tanker unloading operations.  Overflow from storage tanks.  Overheating / pressurization of storage tanks.  Improper earthing / lightning protection of storage tanks and pipelines.  Improper sealing of floating roof tanks.  In adequate / improper breather valves leading to tank failures.  Fire Box Explosion in cracker Furnace. Critical data for flammable materials stored / handled in off sites has already been furnished under Ammonia Plant and Power Plant. High / Low Temp.  Burns due to contact with hot surfaces of pipe lines, equipments, etc Exposure Risks or leaking steam lines.  Heat radiation burns from high intensity flames from the flare stack.  Frost bite due to contact with anhydrous liquid ammonia at – 33 °C Toxic Chemicals  Asphyxia due to inhalation of simple asphyxiants like N2, H2, Exposure Risks Naphtha, etc. and Chemical asphyxiants like Cl2, NH3, NOx, Sox, etc.  Toxicity due to inhalation of catalyst dust containing heavy metals like Ni, Pd, Alumina etc. and perlite / insulation fibers, silica gel dust. Data on Threshold Limit Values Limits for most of the above toxic Chemicals and dusts encountered in off sites has already been furnished under Ammonia Plant. Data for Cl2 are as follows : Corrosive Chemicals  Severe burners, damage to eyes, skin & body tissues due to Exposure Risks contact with corrosive chemicals like anhydrous liquid Ammonia, Sulphuric acid, Hydrochloric acid, etc. Bagging Plant The bagging plant encompasses storage, packing, loading and dispatch activities for product urea via road or rail. Typical risks in this plant are as follows : Fire Risks  Fire hazards due to storage of bulk quantity of polyethylene – lined jute bags or HDPE bags which are easily combustible. Chemicals Exposure Risks  Irritation due to inhalation of urea dust and jute fibers. S.No Name of Chemical Form under normal condition Expected form of Chemical under abnormal condition 1. Ammonia Liquid state at – 33 °C temp. & Vapour / Gaseous form. atmospheric pressure. Vapour / Gaseous form. 2. Chlorine Liquid at ambient temp. & 17.0 Kg/cm² pressure. Vapour 3. Naphtha Liquid at ambient temp. & pressure. Acid fumes Liquid at ambient temp. & pressure. 4. Hydrochloric Acid Liquid at ambient temp. & pressure. Acid fumes Gaseous at ambient temp & 5. Sulphuric Acid Pressure Gaseous Form 6. Natural Gas 4
  • 5. INFORMATION ON THE PRELIMINARY HAZARD ANALYSIS Types of Accident It is clear that during the course of Urea manufacture, furnaces, reactors, moving machineries, material handling, cranes, chain, pulley blocks, wire ropes, chemicals, Rail wagons, etc. are involved. Past reportable accidents are related to these agencies. Type of personnel injuries indicates burn, cut, bone fracture burn injury etc. A brief resume of types of accidents may happen are as follows ;- 1. Burn injury due to handling cleaning of burners in furnaces. 2. Fire accidents in furnaces leading to property damage. 3. Burn injury accident due to attending electrical faults. 4. Burn injury accidents due to handling of acids / alkalies. 5. Hit / cut type accidents due to various maintenance jobs. For reference purposes and internal report titled “Safety Performance at a glance” is enclosed as Annexure 5. System Elements or Events that can lead to a major Accident All the section / plants of IFFCO Aonla unit are constructed and designed taking care of all relevant safety measures possible. However the system elements such as Ammonia storage, Naphtha storage, Chlorine tonners, Ammonia Plant area, Urea Plant HP section are some of them which can lead to a major accident. Although, Fire, explosion and release / leakage of toxic chemicals may lead to major accident, all necessary safety measures have been duly incorporated in the plant design and regular up gradation of safety appliances is carries out. Hazards Urea manufacturing process involves many chemicals such as NG, as feed stock, Ammonia as an intermediate product and chlorine, hydrochloric / sulfuric acids, as water treatment chemicals. Furnaces, High pressure vessels, Reactors, pipe lines, storage tanks are also involved in the course of Urea and Ammonia manufacturing. Handling and storage of these Hazardous chemicals and their use in the process may leak to a hazardous situation. Failure Mode Analysis There are various modes in which flammable and toxic chemicals can leak into atmosphere causing adverse affects. It may be small leaks from gaskets of the flanged joints, or guillotine failure of a pipeline of even catastrophic failure of the storage tank. Some typical modes of failures and their possible causes are discussed below : S.No. Failure Mode Probable Cause Remarks 1. Flange / Gasket Incorrect gasket Incorrect Attention to be paid during selection failure installation. and installation of gaskets. 2 Weld failure It is normally due to poor Welding to be done by certified quality of welds welders with right quality of welding rods. Inspection and radiography must also be done. 3 Pipe corrosion Some times fabrication or Pipes material of construction erosion or failure installation leaves stress should be selected correctly. due to stress in the pipes. Erosion or Design should take care of erosion corrosion also are effects. And installation of pipes sometimes the cause. should not leave any stress. 5
  • 6. 4 Over pressurization Over pressurization can Necessary procedures should be of pipeline occur due to failure of there to prevent. SRV or incorrect operation. 5 Deficient Pipes design and It must be ensured that installation installation of pipes installation is sometimes is as per correct standards not as per appropriate completely. standard. 6 Leaks from valve Leaks from glands, Right selection of valves and their bonnets or failures valves maintenance should be ensured. spindle is sometimes the cause. 7 Instruments failure Multifarious instruments Reliability of instruments working are used for control of must be ensured through proper process parameters. Any selection and maintenance. such instrument failure can cause mishap. 8 Failures of Protective system like Reliability of protective system must protective system SRV, bursting discs, vent be ensured highest through header, drain lines etc. inspection and proper maintenance. are provided to take care of abnormal conditions. 9 Operational effort Plant operational Operating procedures must be parameters should not be complete and strictly followed. exceeded beyond the permissible limits. 10 Other failures There are external other Design and operating philosophy reasons causing the must consider all possible reasons. failures.  INFORMATION ON THE HAZARD ASSESSMENT Identification Of Hazards The following main hazards may exist in the factory under the situations given below- High temperature and pressure. Fire & explosions (due to inflammable / combustible materials). Toxic and corrosive chemicals. Toxic and poisonous gases and dust. Electricity (Receiving / Clue ration / Distribution). Disposal of wastes. Work at heights. Work in confined spaces / vessels / tank etc. Specific jobs carried under highly hazards atmosphere (CO2, NH3, Naphtha vapours etc.). Non working of safety devices, inter locks, failure of high RPM machineries. Failure of boilers etc. Any other consequences due to leak of Ammonia, Chlorine gases. Hazards during heavy equipment handling (Crane, etc.) Road accidents However, the threats posed to the aforesaid hazards may be on account of (i) Fire or (ii) explosion or (iii) Release of toxic or corrosive liquid / gas from their confinement. Causes Of Major Accidents Following Major causes may lead to major accidents :- 1. Release of Ammonia in huge quantity from storage tank. 2. Release of chlorine due to leakage / rupture in chlorine toner or its valve failure of injection pipe failure feeding to cooling tower. 3. Fire / explosion in Naphtha tanks due to leakage, unconfirmed clouds, or boil over, etc. 4. Explosion in High pressure equipments, reactors in Ammonia / Urea Plants. 6
  • 7. 5. Fire / explosion in furnaces of Ammonia Plant and boilers in Power Plant. Assessment Of Hazards According To Their Occurrence Frequency Concurrency frequency (probability failure / year) for each selected failure case is given in table 9.c.1. For most of the cases the probability of failure occurrence is very less. Fire / explosion, sling failure, safety rule failure, and injuries etc. are some cases which are considered as associated hazards. Assessment Of Accident Consequences A major accident may cause severe danger to life and properties. The assessment will be based on : Onsite losses. Offsite losses. The first one will be loss of life, property damage and injuries to the scene of occurrence where the people are working or combating with the accident control. The offsite losses will include the loss of lives, injuries and properties damages of neighbor hood bases on the affected area of accident or major event, if any. Assessment Of The Possible Release Of Hazardous Chemicals Or Of Energy. Technological Risks posed by this Fertiliser factory constitute threat to : i) Its workers ii) To a third party who may be present either in the factory or in its vicinity at the time of accident. iii) Inhabitants living in the immediate neighborhood of the factory and their property. iv) Environmental Conditions around the factory site. The threats posed to the aforesaid entities may be on account of - i) Fire, ii) Explosion, iii) Release of Toxic or corrosive liquids / gas from their confinement. The primary reason why such a disaster may occur, in spite of all precautionary measures is that major type of chemicals handled, are highly hazardous in nature and in substantial quantities, or iv) A combination of more than one of such accidental phenomenon. These risks may manifest due to accidental failures, break down or rupture of processing vessels, equipments, storage tanks or pipelines. They may also arise due to undetected loss of containment because of which liquid or gas contents gradually leak out in sufficient quantities to create a hazardous situation. The loss of containment and associated hazards may be realized in one of the following ways : - Large scale fire in naphtha storage area due to damage to the storage tank. - Naphtha leak from pipeline resulting into fire. - Flash fire due to leakage of flammable gas. - Equipment failure, pipeline failure, flange gasket failure, pump seal failure, safety relief valve failure etc. resulting in leakage of flammable, explosive and toxic material. - Accidents due to human errors. - Acts of nature like earthquake, enemy air attack during war, sabotage, act of terrorism etc. When the scale of such accident is as to cause either – a) Severe destruction of property. b) Multiple fatalities and other casualties and cannot be contained within the premises, a Disaster Situation is said to prevail. However the release of components listed below may cause hazards:- a) Natural Gas, the feed stock for ammonia plant and b) Hydrogen gas produced by reformation process for synthesizing Ammonia and 7
  • 8. c) Ammonia itself, generated as an intermediate product, constitute the gravest risks both from their nature of properties and the quantities involved. Natural Gas is a highly flammable Gas equivalent to gasoline from fire and explosion hazard angle, having a auto ignition temp. of 482 °C and a flammable range of 3.8 – 17 %. Naphtha is also highly flammable liquid having flash point of -40o C and flammable range between 1 and 6%. Ammonia is highly toxic gas its TLV being 25 ppm. It is also a combustible gas which can explode under certain circumstances, although its lower explosive limit is rather high being of the order of 16%. It is true that two other highly flammable gases viz Carbon Monoxide and Methane are also evolved in of the Ammonia plant. However, as these gases are immediately converted into non- hazardous substances, they at best constitute transient risks. Besides the materials directly involved in the manufacturing process, another extremely toxic gas viz Chlorine. Chlorine (which has a TLV of 1 ppm) is used for treatment of water in the Cooling Towers. In- spite of the fact, that quantity of chlorine held in the plant is almost insignificant, because of its extremely high toxicity a leakage even in a „tonner‟ holding only 900 Kg of gas can endanger the persons present inside the plant. Assessment of risks posed by industrial accidents has two aspects viz. How frequently such accidents can occur and What could be their impact on people, property and environment. Making a technically sound assessment of accident frequency for any individual plant is like walking on treacherous grounds. It is true that there are various structured methods like HAZOP, HAZAN, fault tree, Analysis Event tree Analysis etc. through which an estimate of such frequencies can be attempted. However, no such methods can ensure that all potential accidents or top – events would be identified, that all potential fault paths would be found and all common cause failures covered. More-over, the adoption of such methods need use of Reliability Indices of equipment and components of the system under study. These Reliability Indices are expected to be furnished by the manufacturers, which is seldom the case in actual practice. No doubt generic data could be used as a less preferable alternative. However, besides such data not being available for every component, their use may give an entirely erroneous picture, as the real values of such indices are greatly dependent on conditions of use, standards of maintenance etc. Even if correct Reliability data were available, the results may not be quite accurate as accidents are known to have taken place due to Human errors in operation and maintenance for which no satisfactory models are yet available. A statistical estimate of the risk could have been made if enough operating experience of the facts was available. However, in the present case, the experience is not long enough to predict with any degree of certainly of probability of accidents of different magnitudes, especially of that which may cause Maximum credible loss, as such accidents are incidents of extremely low frequency. All that can be stated with confidence is that since. a) The process carried out in the plant is well tested. b) The design and installation of the plant comply with recognized standards and codes of practice and c) All reasonable precautions are followed in respect of operation and maintenance, chances of a major accident is of low order. HAZARDOUS AREAS OF THE PLANT The following areas of the IFFCO Aonla Unit are hazardous with respect to nature of materials handled and operating parameters. Ammonia Plant Urea Plant Ammonia storage Naphtha Storage and Handling Chlorine storage 8
  • 9. PLANT WISE HAZARDS The plant wise hazards due to nature of materials handled there at are given below : Plant Hazardous Material Nature of Hazard Ammonia Plant Natural Gas Fire Naphtha Fire Process gas containing Fire H2, CO, CH4 Explosion Urea Plant Ammonia (liquid or gas) Toxic Ammonia storage Ammonia Carbon dioxide Toxic Asphyxiant Naphtha Storage and Ammonia Toxic handling Naphtha Fire D.M. Water plant Hydrochloric acid caustic lye Corrosive Cooling Tower Chlorine Toxic ASSESSMENT OF THE POSSIBLE DISPERSION OF RELEASED CHEMICALS STORAGE CAPACITY OF HAZARDOUS MATERIALS The hazardous materials stored in the plant in substantial quantities. The detail of storage capacity for each material is given below: Equipment Nos. Material Capacity Naphtha storage tank (old) 2 Naphtha 6000 KL Naphtha storage tank (new) 1 Naphtha 10000 KL Ammonia storage Tank 2 Liquid Ammonia 10,000 Te * Chlorine Tonners 16 Chlorine 900KG * Though the capacities of Ammonia storage tanks are 10000 Te each , we normally store minimal quantity of liquid Ammonia in our Ammonia storage Tanks. The storage quantity at no times goes beyond 40% in the storage tanks. This conscious decision reduces the hazard potential. FAILURE CASE LISTING Keeping in view, the inventories of different hazardous material, plant process parameters etc. following are the selected failure case which way be considered for consequence analysis. This includes the worst case scenario i.e. catastrophic failure of Ammonia storage tanks and Naphtha storage tanks, also leakage of ammonia from ammonia storage tank or from the system handling ammonia, chlorine from tonners and fire in the naphtha tanks or from handling systems is identified as the major accident hazards. This can occur as given below: Incident Consequence Catastrophic rupture of Refrigerated liquid ammonia or liquid ammonia spill and Ammonia storage tank or major dispersion. leakage from the ammonia handling system. Chlorine leakages from the Chlorine leakage and dispersion tonners due to valve getting sheared. Catastrophic failure of Naphtha/ Major fire. FO storage tanks and the leakage catching fire. Pipeline fracture / Nozzle failure Liquid ammonia spills at hydraulic head or pump delivery pressure and dispersion. Chlorine leakage at tonners pressure and dispersion If the leakage due to pipeline fracture or nozzle failure in naphtha and catches fire- fire incident. 9
  • 10. Gasket failure Liquid ammonia spill and dispersion. Chlorine leakage and dispersion. Fire if the naphtha or FO leakage due to gasket failure and the leakage catch fire. System elements or events that can lead to major accident. a. Catastrophic rupture of Ammonia storage tank or major leakage from the ammonia handling system. b. Chlorine leakage from the tonners due to valve getting sheared. c. Catastrophic failure of Naphtha/FO / Diesel storage tanks or major leakage from the handling systems of these materials catching fire. d. Pipeline fracture / Nozzle failure. e. Gasket failure leading to flange leakages Hazards Incident Quantity Released Consequences 1 Catastrophic rupture of 4000 MT Ammonia Concentration upto 500 ppm in Ammonia storage tanks. down-wind direction upto 11000 m 2 Liquid ammonia line to 40MT Ammonia concentration upto 500 ppm in tank failure (20%) down wind direction upto 4700ft downwind & 8000ft cross wind. 3 Chlorine leakage from 900 kg Chlorine Concentration upto 30 PPM in the tonners down-wind direction upto 1247 m 2 4 Catastrophic failure of 12.5 KW/m heat radiation level at a Naphtha storage Tank 10000 KL distance of 56.35m Burnpool radius : 150ft, Flame height:210ft, Fatality radius upto distance 300ft, First degree/Injury Zone radius upto 400ft(approx.) 5 10000KL Naphtha tank First degree burn upto 300 ft. outlet line failure (100%) Fatality radius upto 210ft Burnpool radius: 100ft 2 6 Catastrophic failure of 7000KL 12.5 KW/m heat radiation level at a Naphtha storage Tanks distance of 46.53m 2 7 Catastrophic failure of 1000 KL 12.5 KW/m heat radiation level at a Fuel Oil Storage tank. distance of 43.5m 2 8 Leakage of synthesis 12.5 KW/m heat radiation due to flash fire gas from loop extends up to 224.3 m 2 12.5 KW/m radiation level due to jet flame occur till 92.87 m The over pressure of 0.2068 bar g is up to a distance of 265.6m This over pressure may result in extensive damage. Note: 1. The IDLH of ammonia has been taken as 500ppm (NIOSH) 2.The IDLH of chlorine has been taken as 30 ppm. (NIOSH) 3. The weather is taken as 5 m/s D pasquill Hydrogen Synthesis gas (which is hydrogen rich) is produced in the plant for conversion to Ammonia. There is no hydrogen gas holder for storage. Due to high pressure sufficient quantity is present in the process vessels and pipings to pose fire / explosion hazard. No off-site effect is envisaged for any synthesis gas fire explosion accidents. 10
  • 11. CONSEQUENCE ANALYSIS In case of release of toxic gas into the atmosphere the metrological factors play an important role in transport, dispersion and diffusion in the atmosphere. The metrological data collected for the IFFCO Aonla site was utilized for the purpose. The mean annual speed is 3.5 km/hr. As regards the temperature in peak winter the mean daily maximum temperature is around 18 degree C and minimum temperature is about 2 °C. In peak summer the mean daily maximum temperature is about 31. °C and minimum temperature is 14 °C. Fire hazard is generally experienced in the vessels where a large quantity of flammable material is stored or when a major leak occurs. Fire hazard is a distinct possibility in Naphtha, FO and Diesel storage tanks. The major fire risk rests on the storage tank having the maximum storage capacity i.e. Naphtha storage tank having a capacity of 10000 KL+6000KL+6000KL but normal storage is to the extent of 7000 KL. In case of catastrophic failure of the tank and the leakage catching fire, the 2 critical radiation level of 12.5 KW/m will be felt at a distance of 56.35 m and the farthest distance of flash fire at 229 m. If there is an explosion of the leaking naphtha vapour, over pressure of 0.2068 bar will extend up to 212.1 m. Since there is boundary wall, the effect of over pressure may not be felt out side the factory premises. At the same time no population is residing in 800m radius from tank area. The effects of explosion inside the factory premises may result in damage to 2 equipment. The 12.5 KW/m radiation level resulting from pool fire of Fuel Oil may extend up to 43.5 m. 3 3 The flow of gas in the synthesis loop is 685000m /hr, which corresponds to 39565 m /hr of 2 hydrogen. The synthesis loop is at a pressure of 200 Kg/cm g. Assuming escape of the entire 2 quantity of gas through a 50mm hole and the escaping gas results in a jet flame with 12.5 KW/m radiation level up to 92.87 m. The farthest extent of flash fire may affect up to 224.3 m. Over pressure of 0.2068 bar due to explosion will be felt up to a distance of 265.6 m. As mentioned above, the effects of over pressure may not be felt out side the factory premises. Due to catastrophic rupture of ammonia storage tank, assuming the entire quantity of 4000 MTdisperses, the IDLH level of ammonia of 750 ppm at 1.35 m/s, D neutral weather conditions is at a distance of 11000 m from the source of release. Similarly for chlorine release from a tonner due to valve failure, the IDLH level of chlorine of 30 ppm at 1.35m/s D neutral weather conditions is at a distance of 500m from the source of release.  ASSESSMENT OF THE EFFECTS OF THE RELEASES (SIZE OF THE AFFECTED AREA, HEALTH EFFECTS, PROPERTY DAMAGE) : Assessment of Risk impact is however, more important from the angle of On-site the Emergency planning as primary concern of such planning is for creating preparedness and providing measures for tackling major accidents. Consequence analysis is basically quantitative study of the hazard with the help of internationally accepted mathematical models, to determine the possible magnitude of damage effects and to determine the distances up to which the damage may be affected for various failure scenarios. The consequence analysis results in : - To aid in better plant layout to reduce hazards. - For evaluating damage potential for other plants and incorporating protection measures. - To ascertain damage potential to public and evolve protection measures. - For preparation of effective planning for both On – Site and off-site emergency. The results of consequence analysis are useful for getting information about all known and unknown effects that are of importance when some failure scenario occur and to get information about how to deal with possible catastrophic events. It also gives the plant authorities, workers and the public living outside in the vicinity of the plant an understanding of hazard potential and remedial measures. Bases on the result of consequences analysis, it may be concluded that in most of the cases the effect would be limited to with-in plant boundary and there is no risk posed to neighborhood because of this. But for scenarios involving Ammonia Gas leaks the effected zone goes beyond the factory premises. The risk to the neighborhood of the project is therefore mainly be due to 11
  • 12. release of ammonia as described the different scenarios of Ammonia leakage. The probability of such failure occurrence is extremely low in a order of 3 failure per ten lakh years duration. It may be also concluded that catastrophic failure of Naphtha Storage Tank, Atmospheric storage tanks, Let down vessels etc. may occur really and contribute small risk because of low frequency of occurrence. There are 5000 persons residing in our Township and details of surrounding villages within 5 km circles and their population is around 10000.  DESCRIPTION OF SAFETY RELEVANT UNITS, AMONG OTHERS SPECIAL DESIGN CRITERIA Based on Preliminary hazard analysis the design criteria of system elements are as follows – Ammonia Plant Ammonia Plant is designed with a great deal of safety. The whole plant is open with proper lay out of pipe lines, trenches, cables and flame proof lighting arrangements. A proper spacing between the equipments, reactors, pumps, turbines, and compressors has been kept. Insulation of pipe lines, vessels have been done wherever required. Proper marking, arrows, colour coding has been done for convenience and statutory requirements. Control room with emergency doors and safety equipments are established. Safety trip systems with alarms and trip relays (intrinsically safe) have been provided to control and safe shut down of the plant during emergencies. Stacks for furnaces and flare stack for burning of vent / excess gases of 30 M. height have been provided. Safety valves, Rupture discs, explosion vents, vacuum breakers have been provided as extra safety precautions other than automatic tripping of concerned equipment / unit in case of any abnormality. Urea Plant This plant is safely designed to handle the process with safety valves, Rupture discs and automatic tripping relays & alarms etc. Power Plant All safety measures have been adopted to ensure safe handling and operation of these plants. Safety devices are of adequate sizes. Waste disposal being done with great care. The stack of Power Plant is 120 mts. High and analysis of CO2 is being carried out regularly. SPM (Suspended particulate matter) and SO2 are monitored on weekly basis. All the parameters are always well with in the prescribed standard of U.P. Pollution control Board / Central Board. Control and Alarms Kick back antisurge valves on compressors to avoid surging in compressors. Pressure controls at different points of the plants to control operating pressure automatically well within the limits. Flow controls to control and regulate flow of fluids automatically at desired level. Temperature controls to control requisite temperature automatically. Level controls to control level in various equipments automatically. Likewise several alarms and trip circuits with automatic actuation are given in all the plants for safe operation and process control. Safety Relevant Components The design and operating procedures has been so developed that it enables the safe handling, operation and upkeep of plants. However, so far no major accident has taken place. The built in Safety has been the prime factor while selecting the equipments, processes etc. Standards codes of practices are being followed seriously during the erection, modification etc. Some Safety relevant components are mentioned below :- - Use of relief valves, rupture discs, explosion vents of adequate sizes with proper testing. Checking of these safety relevant components are done in every annual shut down. 12
  • 13. - Automatic control valves, solenoid operated quick shut off valves are installed to control any sort of emergencies. - Alarms, sensors, relays, trip systems have been provided. - Proper training, disclosure of information related to Safety rules / procedures have been given. - Appropriate operating procedures, manuals etc. are implemented since inception. - Flare stack for burning of vent gases like Ammonia, Natural Gas and Naphtha Vapours have been provided. - All the statutory requirements are being fulfilled and followed. Setup Of Fire And Safety Section All staff of Fire & Safety, Health and Environment sections and are of well qualified Engineers, Fire& safety officers and Doctors. EQUIPMENTS FOR FIRE FIGHTING IFFCO-AONLA is well equipped with all fire & Safety appliances like Fire Tenders-3 with a pick up van, all types of extinguishers like DCP,CO2,WATER CO2 Foam types in adequate numbers, PPES like Breathing Apparatus of different types & capacities, Online Air masks at various Hazardous areas ,Gas tight Suits, Alumnised Suits, Explosive meters, Portable Gas Detectors ,Chlorine Emergency Leakage Kit, Air compressor for air cylinders filling, PVC apron & suits, gum boots, safety shoes, safety belts , Various types of hand gloves ,ladders, nylon life saving net, Canisters, safety torches, dust pads etc. Fire Detection/ Alarm System for Plant Control Rooms, Administrative building, Cable Galleries, Transformers are also provided. These are of Ionization, Optical & Heat sensing type. Fixed Installations All Naphtha tanks are protected by installation of automatic fixed foam pouring system at their top which is checked periodically and record is maintained. There is a battery of CO2 cylinders installed for the turbo Generator sets GTG-I , GTG-II & GT in Ammonia-2, designed to come into operation in case of fire. In Bagging Plant including Empty bag Storages Fire hydrant system is well laid out & connected with Smoke detectors have been installed to work in case of any fire. Smoke detection system is provided at all the important buildings and control rooms. Well Laid under ground Fire Hydrant System Underground fire hydrant pipes has been laid throughout the premises as per the TAC guideline, keeping in mind area wise hazard categorization, based on which the distance of hydrant posts were provided. To maintain minimum hydrant pressure of 7 kg/cm2 fire pumps & auxiliary systems are provided at fire pump house near Raw water reservoir. At various places Eye wash showers have been installed where hazardous chemicals are being handled. Flame Proof fittings at the hydrocarbon storage and handling areas. Flame arrestors on moving equipments and Spark arrestors on various hazardous fixed installations. Bounding was done at various flanges to avoid static sparks at the critical hazardous installations Safety Equipments 1. Gas masks for use in leakage of Gases like Ammonia, Chlorine, etc. are available in all the Plant. Apart from this, breathing apparatus supplied by MSA, (USA) are available in all the control rooms and at Ammonia storage tank area. 2. Air line systems are provided in Urea and Ammonia control rooms for which air is supplied from instrument air header. These can be used by the operators working in control room in case of Ammonia leak. 3. Explosive meters supplied by M/s. MSA, (USA) and RESPO PRODUCTS .are available in all the plants for checking any leak of gases and testing the vessel and operating areas, before issue of hot work permit or permit for vessel entry etc. 4. Personnel Protective appliances like safety helmet, safety goggles hand gloves etc., are issued to all the employees. Apart from this Eye wash showers, face shields, PVC suits etc. are installed in all sections of the plant. 13
  • 14. 5. Gas tight suits, chemical splash suits, Fire proximity suits and other suits are available to handle emergencies like toxic release, fire etc. 6. In order to create sense of safety consciousness safety section organises, various competitions every year like safety essay, slogan, debate and quiz competitions for regular employees and safety drawing competition for their children. Prizes are also given to the winners for motivation.  TRAINING IN FIRE FIGHTING & SAFETY AND OHSAS-18001 1. Training of first aid fire fighting and accident prevention is imparted twice every year to all the employees, by the officers of fire and safety section. Sufficient numbers of employees have also been trained by St. John Ambulance Association on „First aid to the injured‟. 2. Twice in a year, Fire and safety section exercised Disaster ON-SITE Mock Drill with information to all Local authorities, for proper readiness in case of major disaster. 3. Emergency instructions are displayed at required places indicating actions to be taken in case of any leaks of Ammonia, Chlorine and Naphtha. Hoarding of hidden hazards are also displayed in different plants along with the control measures to be adopted while working there. 4. Wind socks are provided in Ammonia Plant, Ammonia Storage and handling area, Chorine handling area and other strategic locations to indicate wind direction in case of any toxic gas leak. 5. Portable oxygen meters and Explosive meters/Combustible Gas Indicators are also available in fire and safety section for checking the area or vessel, before entry and job to be carried out. 6. Periodic medical examination is being done for the employees 7. Proper hygiene and decontamination facilities have been provided and being done regularly 8. By putting the objectives and targets in OHSAS-18001like various trainings on Fire & Safety ,environment and health matters, periodic health check of the employees, training of Truck drivers and transporters and Importantly to contract and casual labour. and then follow up is being done rigorously to meet the objectives 9. All chemicals MSDS (Material Safety Data Sheet) are kept at easily available places to know about the properties and other values. 10. Each chemical antidotes are also kept available in the hospital and at van Above : Leakage scenario of Ammonia from sample point. Conclusion: By effectively identifying the various types of Hazards ,doing the risk analysis and controlling the risk ,IFFCO-AONLA unit is maintaining the accident free atmosphere for both the humans and plant/property 14