Remember that good insulation has high resistance; poor insulation, relatively low resistance. The actual resistance
values can be higher or lower, depending upon such factors as the temperature or moisture content of the insulation
(resistance decreases in temperature or moisture).
Edvard
Megger Insulation Resistance Test
Good
Insulation Resistance?
As you know good insulation has high resistance; poor insulation, relatively low resistance. The actual
resistance values can be higher or lower, depending upon such f actors as the temperature or moisture content
of the insulation (resistance decreases in temperature or moisture).
With a little record-keeping and common sense, however, you can get a good picture of the insulation
condition f rom values that are only relative.
The Megger insulation tester is a small, portable instrument that gives you a direct reading of insulation
resistance in ohms or megohms. For good insulation, the resistance usually reads in the megohm range.
The Megger insulation tester is essentially a high-range resistance meter (ohmmeter) with a built-in direct-
current generator. This meter is of special construction with both current and voltage coils, enabling true ohms
to be read directly, independent of the actual voltage applied.
This method is non-destructive; that is, it does not cause deterioration of the insulation.
Figure 2 - Typical Megger test instrument hook-up to measure insulation resistance.
Figure 1 - Comparison of water flow (a) with electric current (b)
The generator can be hand-
cranked or line-operated to
develop a high DC voltage which
causes a small current through
and over surf aces of the
insulation being tested (Fig. 2).
This current (usually at an applied
voltage of 500 volts or more) is
measured by the ohmmeter, which
has an indicating scale.
Fig. 3 shows a typical scale,
which reads increasing resistance
values f rom lef t up to inf inity, or a resistance too high to be measured.
What is “Good” Insulation?
Every electric wire in your plant – whether it’s in a motor, generator, cable, switch, transf ormer, etc. – is
caref ully covered with some f orm of electrical insulation. The wire itself is usually copper or aluminum, which is
known to be a good conductor of the electric current that powers your equipment. The insulation must be just
the opposite f rom a conductor: it should resist current and keep the current in its path along the conductor.
To understand insulation testing you really don’t need to go into the mathematics of electricity, but one
simple equation – ohm’s law – can be very helpf ul in appreciating many aspects. even if you’ve been exposed
to this law bef ore, it may be a good idea to review it in the light of insulation testing.
Purpose of megger test
The purpose of insulation around a conductor is much like that of a pipe carrying water , and ohm’s law of
electricity can be more easily understood by a comparison with water f low. In Figure 1 we show this
comparison. Pressure on water f rom a pump causes f low along the pipe (Fig. 1a). If the pipe were to spring a
leak, you’d waste water and lose some water pressure. With electricity, voltage is like the pump pressure,
causing electricity to f low along the copper wire (Fig. 1b).
As in a water pipe, there is some resistance to f low, but it is much less along the wire than it is through the
insulation.
Common sense
tells us that the
more voltage we
have, the more
current there’ll
be. Also, the
lower the
resistance of
the wire, the
more current f or
the same
voltage. Actually, this is ohm’s law, which is expressed this way in equation f orm:
e = I x R
where,
e = voltage in volts
I = current in amperes
R = resistance in ohms
Note, however, that no insulation is perf ect (that is, has inf inite resistance) so some electricity does f low
along the insulation or through it to ground. Such a current may only be a millionth of an ampere (one
microampere) but it is the basis of insulation testing equipment. note also that a higher voltage tends to cause
more current through the insulation.
This small amount of current would not, of course, harm good insulation but would be a problem if the
insulation has deteriorated. now, to sum up our answer to the question “what is ‘good’ insulation?”
We have seen that, essentially, “good” means a relatively high resistance to current. Used to describe an
insulation material, “good” would also mean “the ability to keep a high resistance.” So, a suitable way of
measuring resistance can tell you how “good” the insulation is. Also, if you take measurements at regular
periods, you can check trends toward its deterioration (more on this later).
What Makes Insulation Go Bad?
When your plant electrical system and equipment are new, the electrical insulation should be in top notch
shape. Furthermore, manuf acturers of wire, cable, motors, and so on have continually improved their
insulations f or services in industry. nevertheless, even today, insulation is subject to many ef f ects which can
cause it to f ail – mechanical damage, vibration, excessive heat or cold, dirt, oil, corrosive vapors, moisture
f rom processes, or just the humidity on a muggy day.
In various degrees, these enemies of insulation are at work as time goes on – combined with the electrical
stresses that exist. As pin holes or cracks develop, moisture and f oreign matter penetrate the surf aces of the
insulation, providing a low resistance path f or leakage current.
Once started, the dif f erent enemies tend to aid each other, permitting excessive current through the
insulation. Sometimes the drop in insulation resistance is sudden, as when equipment is f looded. Usually,
however, it drops gradually, giving plenty of warning, if checked periodically. Such checks permit planned
reconditioning bef ore service f ailure.
If there are no checks, a motor with poor insulation, f or example, may not only be dangerous to touch when
voltage is applied, but also be subject to burn out. What was good insulation has become a partial conductor.
Advertisement
Resource: Megger handbook

More Related Content

What's hot

Ppt part 6 passive component
Ppt part 6 passive componentPpt part 6 passive component
Ppt part 6 passive component
Ahmad Omar
 
Resistors and resistance.ppt
Resistors and resistance.pptResistors and resistance.ppt
Resistors and resistance.ppt
mrmeredith
 

What's hot (19)

resistor
resistorresistor
resistor
 
Resistors
ResistorsResistors
Resistors
 
Resistors
ResistorsResistors
Resistors
 
Resistors - Electrical Engineering
Resistors - Electrical EngineeringResistors - Electrical Engineering
Resistors - Electrical Engineering
 
Types of Resistor
Types of ResistorTypes of Resistor
Types of Resistor
 
Resistors
ResistorsResistors
Resistors
 
Plugs
PlugsPlugs
Plugs
 
Resistor and its types
Resistor and its typesResistor and its types
Resistor and its types
 
ResistorS
ResistorSResistorS
ResistorS
 
Resistor
ResistorResistor
Resistor
 
Components used in electrical installations
Components used in electrical installationsComponents used in electrical installations
Components used in electrical installations
 
Potential divider
Potential divider Potential divider
Potential divider
 
Ppt part 6 passive component
Ppt part 6 passive componentPpt part 6 passive component
Ppt part 6 passive component
 
Resistors and resistance.ppt
Resistors and resistance.pptResistors and resistance.ppt
Resistors and resistance.ppt
 
Topic 3 resistor
Topic  3 resistorTopic  3 resistor
Topic 3 resistor
 
resistors
resistorsresistors
resistors
 
Electricity
Electricity Electricity
Electricity
 
Resistance In Circuits
Resistance In CircuitsResistance In Circuits
Resistance In Circuits
 
surge diverters
surge diverterssurge diverters
surge diverters
 

Similar to Megger insulation resistance_test

Chapter6 electronic-components
Chapter6 electronic-componentsChapter6 electronic-components
Chapter6 electronic-components
Vin Voro
 
Electrical Safety
Electrical SafetyElectrical Safety
Electrical Safety
mrmackenzie
 
Basic principles of electrical safety
Basic principles of electrical safetyBasic principles of electrical safety
Basic principles of electrical safety
Muthurv Venkatachalam
 
Common Fuse Box Problems.docx
Common Fuse Box Problems.docxCommon Fuse Box Problems.docx
Common Fuse Box Problems.docx
Gary Crilly, RCDD/OSP
 

Similar to Megger insulation resistance_test (20)

Chapter6 electronic-components
Chapter6 electronic-componentsChapter6 electronic-components
Chapter6 electronic-components
 
Hipot cable-testing
Hipot cable-testingHipot cable-testing
Hipot cable-testing
 
Partial Discharge Techniques For Measuring Condition Of MV & HV Switchgear
Partial Discharge Techniques For Measuring Condition Of MV & HV SwitchgearPartial Discharge Techniques For Measuring Condition Of MV & HV Switchgear
Partial Discharge Techniques For Measuring Condition Of MV & HV Switchgear
 
Electrical Safety
Electrical SafetyElectrical Safety
Electrical Safety
 
Basic principles of electrical safety
Basic principles of electrical safetyBasic principles of electrical safety
Basic principles of electrical safety
 
Basic Principles of Electrical Safety.ppt
Basic Principles of Electrical Safety.pptBasic Principles of Electrical Safety.ppt
Basic Principles of Electrical Safety.ppt
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Common Fuse Box Problems.docx
Common Fuse Box Problems.docxCommon Fuse Box Problems.docx
Common Fuse Box Problems.docx
 
CH4 Insulating materials.pptx
CH4 Insulating materials.pptxCH4 Insulating materials.pptx
CH4 Insulating materials.pptx
 
CH4 Insulating materials.pptx
CH4 Insulating materials.pptxCH4 Insulating materials.pptx
CH4 Insulating materials.pptx
 
CH4 Insulating materialss.pptx
CH4 Insulating materialss.pptxCH4 Insulating materialss.pptx
CH4 Insulating materialss.pptx
 
CH4 Insulating materials.pptx
CH4 Insulating materials.pptxCH4 Insulating materials.pptx
CH4 Insulating materials.pptx
 
ch4.pdf
ch4.pdfch4.pdf
ch4.pdf
 
Electricity 1
Electricity 1Electricity 1
Electricity 1
 
Physics 31 - Dangers of electricity.pptx
Physics 31 - Dangers of electricity.pptxPhysics 31 - Dangers of electricity.pptx
Physics 31 - Dangers of electricity.pptx
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Unit I.pdf
Unit I.pdfUnit I.pdf
Unit I.pdf
 
Arc Flash Hazards In The Workplace
Arc Flash Hazards In The WorkplaceArc Flash Hazards In The Workplace
Arc Flash Hazards In The Workplace
 
Flashover Tests
Flashover TestsFlashover Tests
Flashover Tests
 
Amin
AminAmin
Amin
 

Recently uploaded

Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
dharasingh5698
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 

Recently uploaded (20)

Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Unit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdfUnit 2- Effective stress & Permeability.pdf
Unit 2- Effective stress & Permeability.pdf
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 

Megger insulation resistance_test

  • 1. elect rical-engineering-port al.com http://electrical-engineering-portal.com/megger-insulation-resistance-test#.UoVTXiKHa2g.facebook Remember that good insulation has high resistance; poor insulation, relatively low resistance. The actual resistance values can be higher or lower, depending upon such factors as the temperature or moisture content of the insulation (resistance decreases in temperature or moisture). Edvard Megger Insulation Resistance Test Good Insulation Resistance? As you know good insulation has high resistance; poor insulation, relatively low resistance. The actual resistance values can be higher or lower, depending upon such f actors as the temperature or moisture content of the insulation (resistance decreases in temperature or moisture). With a little record-keeping and common sense, however, you can get a good picture of the insulation condition f rom values that are only relative. The Megger insulation tester is a small, portable instrument that gives you a direct reading of insulation resistance in ohms or megohms. For good insulation, the resistance usually reads in the megohm range. The Megger insulation tester is essentially a high-range resistance meter (ohmmeter) with a built-in direct- current generator. This meter is of special construction with both current and voltage coils, enabling true ohms to be read directly, independent of the actual voltage applied. This method is non-destructive; that is, it does not cause deterioration of the insulation.
  • 2. Figure 2 - Typical Megger test instrument hook-up to measure insulation resistance. Figure 1 - Comparison of water flow (a) with electric current (b) The generator can be hand- cranked or line-operated to develop a high DC voltage which causes a small current through and over surf aces of the insulation being tested (Fig. 2). This current (usually at an applied voltage of 500 volts or more) is measured by the ohmmeter, which has an indicating scale. Fig. 3 shows a typical scale, which reads increasing resistance values f rom lef t up to inf inity, or a resistance too high to be measured. What is “Good” Insulation? Every electric wire in your plant – whether it’s in a motor, generator, cable, switch, transf ormer, etc. – is caref ully covered with some f orm of electrical insulation. The wire itself is usually copper or aluminum, which is known to be a good conductor of the electric current that powers your equipment. The insulation must be just the opposite f rom a conductor: it should resist current and keep the current in its path along the conductor. To understand insulation testing you really don’t need to go into the mathematics of electricity, but one simple equation – ohm’s law – can be very helpf ul in appreciating many aspects. even if you’ve been exposed to this law bef ore, it may be a good idea to review it in the light of insulation testing. Purpose of megger test The purpose of insulation around a conductor is much like that of a pipe carrying water , and ohm’s law of electricity can be more easily understood by a comparison with water f low. In Figure 1 we show this comparison. Pressure on water f rom a pump causes f low along the pipe (Fig. 1a). If the pipe were to spring a leak, you’d waste water and lose some water pressure. With electricity, voltage is like the pump pressure, causing electricity to f low along the copper wire (Fig. 1b). As in a water pipe, there is some resistance to f low, but it is much less along the wire than it is through the insulation. Common sense tells us that the more voltage we have, the more current there’ll be. Also, the lower the resistance of the wire, the more current f or the same voltage. Actually, this is ohm’s law, which is expressed this way in equation f orm:
  • 3. e = I x R where, e = voltage in volts I = current in amperes R = resistance in ohms Note, however, that no insulation is perf ect (that is, has inf inite resistance) so some electricity does f low along the insulation or through it to ground. Such a current may only be a millionth of an ampere (one microampere) but it is the basis of insulation testing equipment. note also that a higher voltage tends to cause more current through the insulation. This small amount of current would not, of course, harm good insulation but would be a problem if the insulation has deteriorated. now, to sum up our answer to the question “what is ‘good’ insulation?” We have seen that, essentially, “good” means a relatively high resistance to current. Used to describe an insulation material, “good” would also mean “the ability to keep a high resistance.” So, a suitable way of measuring resistance can tell you how “good” the insulation is. Also, if you take measurements at regular periods, you can check trends toward its deterioration (more on this later). What Makes Insulation Go Bad? When your plant electrical system and equipment are new, the electrical insulation should be in top notch shape. Furthermore, manuf acturers of wire, cable, motors, and so on have continually improved their insulations f or services in industry. nevertheless, even today, insulation is subject to many ef f ects which can cause it to f ail – mechanical damage, vibration, excessive heat or cold, dirt, oil, corrosive vapors, moisture f rom processes, or just the humidity on a muggy day. In various degrees, these enemies of insulation are at work as time goes on – combined with the electrical stresses that exist. As pin holes or cracks develop, moisture and f oreign matter penetrate the surf aces of the insulation, providing a low resistance path f or leakage current. Once started, the dif f erent enemies tend to aid each other, permitting excessive current through the insulation. Sometimes the drop in insulation resistance is sudden, as when equipment is f looded. Usually, however, it drops gradually, giving plenty of warning, if checked periodically. Such checks permit planned reconditioning bef ore service f ailure. If there are no checks, a motor with poor insulation, f or example, may not only be dangerous to touch when voltage is applied, but also be subject to burn out. What was good insulation has become a partial conductor. Advertisement Resource: Megger handbook