Differential Protection Setting Calculations
Transformer Differential
Protection Setting
Calculations
Transformer Differential
Protection Setting
Calculations
Differential Protection Setting Calculations
Examine CT performance
Calculate winding “tap” values
Determine 87T pickup points
- Determine variable percentage slope breakpoints
- Determine harmonic restraint values
Determine 87H pick up
Determine 87GD pick up
Objectives
Differential Protection Setting Calculations
Class “C” CTs have established secondary
voltage/burden curves that are used to predict linear
performance
Operating a CT at values above the “kneepoint” on
the curve invite unfaithful replication of the primary
waveform and saturation
Unfaithful replication (including saturation) between
measurement CTs in a differential protection causes
misoperation
CT Performance
Differential Protection Setting Calculations
Class “C” CTs are designed to “faithfully” replicate
primary currents to within +/- 10%
Class designations designate maximum secondary CT
circuit voltage at standard burden that can be applied to
maintain accuracy
- Zrated = Voltage Class / 20 * Rated Secondary Current
- Zrated = C800 / 20 * 5A = 8 Ω, ∴ 800V at 8Ω burden
- Zrated = C200 / 20 * 5A = 2 Ω, ∴ 200V at 2Ω burden
Class “C” CTs
Differential Protection Setting Calculations
More than 100V secondary and you’re in trouble
Class “C” CT Performance Curve
Differential Protection Setting Calculations
1 pu 10 pu
10%
1%
0.1%
Accuracy curve for Class “C” 2000:5 multitap CT
CT Performance: +/- 10%
Differential Protection Setting Calculations
0
0
tt
ID= IP- IS
CT Secondary, IS CT Primary, IP
Comparison of primary to secondary waveforms with saturation
CT Performance
Differential Protection Setting Calculations
Use with Class “C” CTs
Determine maximum primary phase and ground
fault current
Calculate secondary current based on CTR and CT
connection type (wye or delta)
Determine secondary CT circuit burden
Determine maximum secondary voltage produced
from burden with secondary fault currents
Check maximum secondary voltage against CT
capability
CT Performance Calculation
Differential Protection Setting Calculations
For WYE connected CTs, to obtain secondary current,
use: (1X) I PRI / CTR = I SEC
Fault Types and Currents in Secondary
Circuits
Transformer Setting Calculations
Differential Protection Setting Calculations
For Delta connected CTs, to obtain secondary current,
use: (1.73) I PRI / CTR = I SEC
Fault Types and Currents in Secondary
Circuits
Differential Protection Setting Calculations
Determine all device burdens in secondary circuit
- Relays, meters, instrumentation
Determine lead burden
- Use wire tables (AWG @ ohms/ft)
Determine CT impedance
Use CT data sheet (typ. 0.4 ohm or less)
Burden Calculation
Differential Protection Setting Calculations
Where RCT is CT burden (internal)
RW total resistance of the ct secondary wiring.
RR is relay burden
VS = I (RCT + RW + RR)
Where I is the fault current and VS is the ct secondary voltage. In order to make sure that the
ct is in the linear range (to avoid ac saturation of the ct’s), VS should be less than the
knee-point voltage of the ct excitation characteristics. (See IEEE Guide for the
Application of Current Transformers Used for Protective Relaying Purposes C37.110-
1996).
VS
Equivalent circuit of the CT secondary wiring
RCT
RW
RR
Equivalent circuit of the CT Secondary wiring
Differential Protection Setting Calculations
Relay = 0.5VA @ 5 A
RR = VA/A2 , RR = 0.5/25 = 0.02 Ω
RW = 2 Ω (round trip)
RCT = 0.20 Ω
Total = 2.22 Ω
Burden Calculation
Example
Differential Protection Setting Calculations
Assume maximum secondary current of 90A and wye CTs
VS = I (RCT + RW + RR) * (FΔ-Υ)
- (FΔ-Υ) = delta or wye CT factor
- Use 1 for wye; use 1.73 for delta
VS = 90 x 2.22 * (1) = 199.8 V
Vs * 2 = 199.8 * 2 = 399.6 V
- The 2X factor accounts for full DC offset
Use at least a C400
Secondary CT Circuit Voltage
Differential Protection Setting Calculations
Used to determine current at rated transformer capacity
- Normally pick highest rating of multiple MVA rated
transformers
Allows “nominalization” of the transformer windings
Used to obtain “tap” that is digitally set
Itap = VA / [√3 * VLL] * CTR
This accommodates:
- Transformer winding ratios
- CT ratios
Power-Current Conversion
Differential Protection Setting Calculations
Use highest rating as basis for tap calculations
WyeWye
Calculating “Tap”
Differential Protection Setting Calculations
This nominalizes the current flow with respect to transformation ratios and
CT ratios
Rated power passing through any winding would yield these currents to the
protection system
Calculating “Tap”
Differential Protection Setting Calculations
From 3-Line Diagram, determine transformer and CT
winding arrangements
Example
- W1 = DAC, wye CTs
- W2 = DAC, wye CTs
- W3 = Wye, wye CTs
wye
Phase Shift Compensation
Differential Protection Setting Calculations
Trip Characteristic – 87T
Differential Protection Setting Calculations
87T Pickup
- Set above the magnetizing current and other CT inaccuracies
- 0.2 to 0.4 p.u. (typical setting)
Slope 1
- Set to accommodate +/- 10% CT inaccuracies
- LTC adds another +/- 10%
- Used for currents < 2X nominal
- Typically set for 25% to 30% (can be set lower for non LTC
transformers)
Slope 2 “breakpoint”
- Typically set at 2X rated current
- This setting assumes that any current over 2X rated is a fault
condition and is used to desensitize the element against
unfaithful replication of currents due to CT saturation
Trip Characteristic – 87T
Differential Protection Setting Calculations
Slope 2
- Typically set at 50% to 70%
- Prevents relay misoperation for though faults with CT
saturation.
Inrush Restraint (2nd and 4th harmonic)
- Typically set from 10-20%
- Employ cross phase averaging (harmonic sharing)
blocking for security – especially for modern
transformers where the harmonic content is low
Overexcitation Restraint (5th harmonic)
- Typically set at 30%
- Raise 87T pickup to 0.60 pu during overexcitation
- No cross phase averaging is needed, as the
magnetizing currents during overexcitation condition
are symmetrical
Trip Characteristic – 87T
Differential Protection Setting Calculations
87H Pickup
- Typically set at 8 to 12 pu rated current
- This value should be set to above the maximum
possible inrush current.
- Relay oscillograph analysis software can be used
determine the inrush current level and fine tune the
setting.
- Also, need to know if the high set element uses
fundamental component of current (typically the case)
or total RMS current and set the pickup appropriately.
Trip Characteristic – 87H
Differential Protection Setting Calculations
87GD Pickup
- Element normally uses directional comparison between
phase residual current (3I0) and measured ground current
(IG). The element becomes non-directional when the 3I0
current is small (example < 140 ma).
- Pickup of 0.2 to 0.5 A (5A rated CTs) can be applied when
using same ratio CTs on both phase and ground circuits.
- When CT correction factor higher than 1.0 is applied, the
pickup needs to be increased to account for noise
amplification due to high CT ratio correction.
- Use 6 cycle time delay to provide security against
misoperations during external phase-to-phase to ground
faults with CT saturation. The time delay must not be set
below 2 cycles.
Trip Characteristic – 87GD
Differential Protection Setting Calculations
WITHOUT GROUND DIFF. (87GD) THERE IS NO
HIGHSPEED PROTECTION FOR SEC. GND FAULTS
Typical Pickup of 87T:
O.3 pu pickup
Relay Tap set at Trans.
Rating (45MVA)
IFL138KV = 4.71 A
PU = 4.71A x 0.3 = 1.41A
Open
R
87T
2000/5
200/5
400A
13.8KV
138KV
I=0
400A
40A/1.73
40A/1.73*40/1=0.58A
45 MVA
Improved Ground Fault Sensitivity
Differential Protection Setting Calculations
DIGITAL TRANSFORMER
DIFFERENTIAL RELAY SETTING EXAMPLE
Differential Protection Setting Calculations
Sample Calculation – 87T
14,400/120
Differential Protection Setting Calculations
Transformer Size – MVA Rating
Voltage Taps – No Load
Transformer Connection
Current Transformer Ratios
Current Transformer Connection
Voltage Transformer Ratios
Voltage Transformer Connections
— L-G or L-L
LTC Tap Information
Calculating Differential Set Points and System Setup
87T Sample Calculation
Differential Protection Setting Calculations
Delta AB
14,400/120
87T Sample Calculation
Differential Protection Setting Calculations
COMMUNICATES
PHASING TO RELAY
COMMUNICATES
METERING DATA TO RELAY
87T Sample Calculation
Differential Protection Setting Calculations
COMMUNICATES
PHASING TO RELAY
COMMUNICATES
METERING DATA TO RELAY
87T Sample Calculation W-2 Delta CT’S
Differential Protection Setting Calculations
Step 1 -Check CT and Relay Input Ratings
Sample Transformer Ratings:
OA/FA/FA = 30/40/50 MVA
Short Time Rating of this transformer is
1.35 x 50 MVA = 67.5 MVA
Relay current input is rated at 2X Nominal Rating
i.e. 5A relay = 10 AMPS continuous
I67.5 MVA W-2 PRI
= 67.500 KVA/13.8KVx√3=2827A
I67.5 MVA W-2 SEC
= 2827/600/1 = 4.71 A
For Δ CTs relay gets
4.71x √3= 8.15A <10A Sec. Winding (W2) OK
I67.5 MVA W-1 PRI
= 67.500 KVA/70.35KVx√3=554.6A
I67.5 MVA W-1 SEC
= 554.6/120/1 = 4.62A <10A Pri. Winding (W1) OK
87T Sample Calculation
Differential Protection Setting Calculations
Step 2: Select W1 & W2 Tap Settings Balance at OA Rating
87T Sample Calculation
HandledBy
Relay
3
3
2.09 A
Differential Protection Setting Calculations
Step 2: Select W1 & W2 Tap Settings Balance at OA Rating
87T Sample Calculation
TAP VALUES
Differential Protection Setting Calculations
87T Sample Calculation
Step 3: Select minimum pickup of 87T
• Pick up should be set to prevent operation of 87T
due to transformer steady-state excitation current.
•Typical Transformer excitation current ~1% = .01 pu
•CT Error 10% =.10 pu
• LTC Error 10%= .10 pu
•Saftey Margin Typical 5% = .05 pu
26 % .26 pu
•Typical setting is 0.26 to 0.35 p.u.
Select p.u. at 0.3
Differential Protection Setting Calculations
87T Sample Calculation
Step 3: Select minimum pickup of 87T
MINIMUM
PICKUP
Differential Protection Setting Calculations
Step 4: Select Slope # 1 Setting
Slope 1
The setting of Slope #1 should be set according to various possible errors:
1. Tapchanger operations in the power transformer (worst case± 10%)
10%
2. CT mismatch due to ratio errors. Errors can be as high
as ± 10% 10%
3. Transformer excitation current (typical current of 1%) 1%
4. Relay measurement error 5%
Set Slope # 1 = 30%
Differential Protection Setting Calculations
Step 4: Select Slope # 1 Setting
SLOPE #1
SETTING
Differential Protection Setting Calculations
Step 5: Select slope #2 Setting
• Provides security for high fault current levels outside
the differential zone where CT inputs can saturate.
• Factors effecting CT saturation
- Residual magnetism in CT core
- CT characteristic mismatch
- CT circuit burden
• CT Burden Check
Differential Protection Setting Calculations
87T Sample Calculation
Step 5: Select Slope #2 Setting
Typical Slope #2 Settings is Twice
Slope #2
60%
Differential Protection Setting Calculations
87T Sample Calculation
Step 5: Select Slope #2 Setting
SLOPE #2
SETTING
Differential Protection Setting Calculations
87T Sample Calculation
Step 6: Select Break Point between Slope
1 and Slope 2
• Breakpoint is crossover from Slope 1 to Slope 2
Typical Breakpoint = 2.0
Differential Protection Setting Calculations
Step 6: Select Break Point between Slope
1 and Slope 2
BREAK POINT
BETWEEN SLOPES
1 AND 2
Differential Protection Setting Calculations
87T Sample Calculation
Step 7: Select Inrush Harmonic Restraint
• Relay uses 2nd and 4th harmonics
• Percent harmonics defined as –
• Amount of 2nd and 4th harmonics depend on:
- Magnetizing characteristics of transformer core
- Residual magnetism in core
• Typical Settings
-15% for most transformers
-can be 10% or lower on new transformers with low
core losses and steep magnetizing curves. Setting below 10%
risks blocking for internal faults.
Differential Protection Setting Calculations
87T Sample Calculation
Step 7: (continued)
Cross Phase Averaging (recommended)
- Inrush harmonic level different in each phase
- Cross phase averaging means each phase restrains on
harmonics in other phases. For example:
Differential Protection Setting Calculations
Step 7: Select Inrush Harmonic Restraint
INRUSH HARMONIC
RESTRAINT
Differential Protection Setting Calculations
87T Sample Calculation
Step 8: Select Overexcitation Harmonic Restraint
• M-3311 uses 5th harmonic.
• Overexcitation (V/Hz) produces high amounts of
5th harmonic current.
• 87T in M-3311 shifts minimum pickup to higher
value, typically 150 to 200% of normal 87T p.u.
Typical setting is 200% X 87T pickup, or 0.3 X
200% = 0.6 p.u.
Differential Protection Setting Calculations
87T Sample Calculation
Step 8: (continued)
• Amount of 5th harmonic depends on transformer
core magnetizing characteristics.
• No cross phase averaging – Overexcitation is
symmetrical.
Typical setting is 30%
Differential Protection Setting Calculations
87T Sample Calculation
Step 8: Select Overexcitation Harmonic Restraint
OVEREXCITATION
HARMONIC RESTRAINT
Differential Protection Setting Calculations
• 87H function is not blocked by any harmonic
restraint
• Pickup must be set above first peak of inrush
current
• 87H is used in almost all transformer differentials
to overcome restraint of 87T due to CT saturation for
high internal transformer faults
• Typical pickup setting is 8 to 12 p.u.
Set at 10 p.u.
Set delay at 1 cycle
Step 9: Setting 87H Unrestrained High Set
Differential
Differential Protection Setting Calculations
87T Sample Calculation
Step 9: Setting 87H Unrestrained High Set Differential
UNRESTRAINTED
HIGHSET DIFF.
©2008 Beckwith Electric Co., Inc.

More Related Content

What's hot

What's hot (20)

Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Motor Protection
Motor ProtectionMotor Protection
Motor Protection
 
Protection Of Generator
Protection Of GeneratorProtection Of Generator
Protection Of Generator
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Ppt of current transformer
Ppt of current transformerPpt of current transformer
Ppt of current transformer
 
Basic protection and relaying
Basic protection and relayingBasic protection and relaying
Basic protection and relaying
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Relays
RelaysRelays
Relays
 
Motor protection principles
Motor protection principlesMotor protection principles
Motor protection principles
 
Line to Line & Double Line to Ground Fault On Power System
Line to Line & Double Line to Ground Fault On Power SystemLine to Line & Double Line to Ground Fault On Power System
Line to Line & Double Line to Ground Fault On Power System
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 

Similar to Transformer differential protection

CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
Nageswar Rao
 
Ser2200 linpwrsuppyspecsappnote
Ser2200 linpwrsuppyspecsappnoteSer2200 linpwrsuppyspecsappnote
Ser2200 linpwrsuppyspecsappnote
Pawar Chander
 
fault location estimator in series compensator
fault location estimator in series compensatorfault location estimator in series compensator
fault location estimator in series compensator
ABHISHEK RAI
 

Similar to Transformer differential protection (20)

Get 8402
Get 8402Get 8402
Get 8402
 
CT design aspects - Nageswar-6
CT design aspects - Nageswar-6CT design aspects - Nageswar-6
CT design aspects - Nageswar-6
 
Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme Summary Presentation on PMU Based Transmission Line Protection Scheme
Summary Presentation on PMU Based Transmission Line Protection Scheme
 
CURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptxCURRENT TRANSFORMER.pptx
CURRENT TRANSFORMER.pptx
 
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
 
Brymen BM157 BM357 User's Manual
Brymen BM157 BM357 User's ManualBrymen BM157 BM357 User's Manual
Brymen BM157 BM357 User's Manual
 
Ser2200 linpwrsuppyspecsappnote
Ser2200 linpwrsuppyspecsappnoteSer2200 linpwrsuppyspecsappnote
Ser2200 linpwrsuppyspecsappnote
 
CHapter 4 -Signal Conditioning.pptxyyhhhj
CHapter 4 -Signal Conditioning.pptxyyhhhjCHapter 4 -Signal Conditioning.pptxyyhhhj
CHapter 4 -Signal Conditioning.pptxyyhhhj
 
Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detail
 
DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...
DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...
DESIGN, SIMULATION, IMPLEMENTATION AND CONTROL OF PLC BASED INTEGRAL CYCLE CO...
 
Ijaret 06 08_006
Ijaret 06 08_006Ijaret 06 08_006
Ijaret 06 08_006
 
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
 
Series2200 app note
Series2200 app noteSeries2200 app note
Series2200 app note
 
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
Locating Facts Devices in Optimized manner in Power System by Means of Sensit...
 
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
 
fault location estimator in series compensator
fault location estimator in series compensatorfault location estimator in series compensator
fault location estimator in series compensator
 
RGPV EX7102 UNIT II
RGPV EX7102 UNIT IIRGPV EX7102 UNIT II
RGPV EX7102 UNIT II
 
Current transformer (ct)
Current transformer (ct)Current transformer (ct)
Current transformer (ct)
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
 
K2917.pptx
K2917.pptxK2917.pptx
K2917.pptx
 

More from michaeljmack

Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
michaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
michaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
michaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
michaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
michaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
michaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
michaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
michaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
michaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 

Recently uploaded

Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 

Recently uploaded (20)

COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Learn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic MarksLearn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic Marks
 
Rums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdfRums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdf
 
Engineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planesEngineering Drawing focus on projection of planes
Engineering Drawing focus on projection of planes
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 

Transformer differential protection

  • 1. Differential Protection Setting Calculations Transformer Differential Protection Setting Calculations Transformer Differential Protection Setting Calculations
  • 2. Differential Protection Setting Calculations Examine CT performance Calculate winding “tap” values Determine 87T pickup points - Determine variable percentage slope breakpoints - Determine harmonic restraint values Determine 87H pick up Determine 87GD pick up Objectives
  • 3. Differential Protection Setting Calculations Class “C” CTs have established secondary voltage/burden curves that are used to predict linear performance Operating a CT at values above the “kneepoint” on the curve invite unfaithful replication of the primary waveform and saturation Unfaithful replication (including saturation) between measurement CTs in a differential protection causes misoperation CT Performance
  • 4. Differential Protection Setting Calculations Class “C” CTs are designed to “faithfully” replicate primary currents to within +/- 10% Class designations designate maximum secondary CT circuit voltage at standard burden that can be applied to maintain accuracy - Zrated = Voltage Class / 20 * Rated Secondary Current - Zrated = C800 / 20 * 5A = 8 Ω, ∴ 800V at 8Ω burden - Zrated = C200 / 20 * 5A = 2 Ω, ∴ 200V at 2Ω burden Class “C” CTs
  • 5. Differential Protection Setting Calculations More than 100V secondary and you’re in trouble Class “C” CT Performance Curve
  • 6. Differential Protection Setting Calculations 1 pu 10 pu 10% 1% 0.1% Accuracy curve for Class “C” 2000:5 multitap CT CT Performance: +/- 10%
  • 7. Differential Protection Setting Calculations 0 0 tt ID= IP- IS CT Secondary, IS CT Primary, IP Comparison of primary to secondary waveforms with saturation CT Performance
  • 8. Differential Protection Setting Calculations Use with Class “C” CTs Determine maximum primary phase and ground fault current Calculate secondary current based on CTR and CT connection type (wye or delta) Determine secondary CT circuit burden Determine maximum secondary voltage produced from burden with secondary fault currents Check maximum secondary voltage against CT capability CT Performance Calculation
  • 9. Differential Protection Setting Calculations For WYE connected CTs, to obtain secondary current, use: (1X) I PRI / CTR = I SEC Fault Types and Currents in Secondary Circuits Transformer Setting Calculations
  • 10. Differential Protection Setting Calculations For Delta connected CTs, to obtain secondary current, use: (1.73) I PRI / CTR = I SEC Fault Types and Currents in Secondary Circuits
  • 11. Differential Protection Setting Calculations Determine all device burdens in secondary circuit - Relays, meters, instrumentation Determine lead burden - Use wire tables (AWG @ ohms/ft) Determine CT impedance Use CT data sheet (typ. 0.4 ohm or less) Burden Calculation
  • 12. Differential Protection Setting Calculations Where RCT is CT burden (internal) RW total resistance of the ct secondary wiring. RR is relay burden VS = I (RCT + RW + RR) Where I is the fault current and VS is the ct secondary voltage. In order to make sure that the ct is in the linear range (to avoid ac saturation of the ct’s), VS should be less than the knee-point voltage of the ct excitation characteristics. (See IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes C37.110- 1996). VS Equivalent circuit of the CT secondary wiring RCT RW RR Equivalent circuit of the CT Secondary wiring
  • 13. Differential Protection Setting Calculations Relay = 0.5VA @ 5 A RR = VA/A2 , RR = 0.5/25 = 0.02 Ω RW = 2 Ω (round trip) RCT = 0.20 Ω Total = 2.22 Ω Burden Calculation Example
  • 14. Differential Protection Setting Calculations Assume maximum secondary current of 90A and wye CTs VS = I (RCT + RW + RR) * (FΔ-Υ) - (FΔ-Υ) = delta or wye CT factor - Use 1 for wye; use 1.73 for delta VS = 90 x 2.22 * (1) = 199.8 V Vs * 2 = 199.8 * 2 = 399.6 V - The 2X factor accounts for full DC offset Use at least a C400 Secondary CT Circuit Voltage
  • 15. Differential Protection Setting Calculations Used to determine current at rated transformer capacity - Normally pick highest rating of multiple MVA rated transformers Allows “nominalization” of the transformer windings Used to obtain “tap” that is digitally set Itap = VA / [√3 * VLL] * CTR This accommodates: - Transformer winding ratios - CT ratios Power-Current Conversion
  • 16. Differential Protection Setting Calculations Use highest rating as basis for tap calculations WyeWye Calculating “Tap”
  • 17. Differential Protection Setting Calculations This nominalizes the current flow with respect to transformation ratios and CT ratios Rated power passing through any winding would yield these currents to the protection system Calculating “Tap”
  • 18. Differential Protection Setting Calculations From 3-Line Diagram, determine transformer and CT winding arrangements Example - W1 = DAC, wye CTs - W2 = DAC, wye CTs - W3 = Wye, wye CTs wye Phase Shift Compensation
  • 19. Differential Protection Setting Calculations Trip Characteristic – 87T
  • 20. Differential Protection Setting Calculations 87T Pickup - Set above the magnetizing current and other CT inaccuracies - 0.2 to 0.4 p.u. (typical setting) Slope 1 - Set to accommodate +/- 10% CT inaccuracies - LTC adds another +/- 10% - Used for currents < 2X nominal - Typically set for 25% to 30% (can be set lower for non LTC transformers) Slope 2 “breakpoint” - Typically set at 2X rated current - This setting assumes that any current over 2X rated is a fault condition and is used to desensitize the element against unfaithful replication of currents due to CT saturation Trip Characteristic – 87T
  • 21. Differential Protection Setting Calculations Slope 2 - Typically set at 50% to 70% - Prevents relay misoperation for though faults with CT saturation. Inrush Restraint (2nd and 4th harmonic) - Typically set from 10-20% - Employ cross phase averaging (harmonic sharing) blocking for security – especially for modern transformers where the harmonic content is low Overexcitation Restraint (5th harmonic) - Typically set at 30% - Raise 87T pickup to 0.60 pu during overexcitation - No cross phase averaging is needed, as the magnetizing currents during overexcitation condition are symmetrical Trip Characteristic – 87T
  • 22. Differential Protection Setting Calculations 87H Pickup - Typically set at 8 to 12 pu rated current - This value should be set to above the maximum possible inrush current. - Relay oscillograph analysis software can be used determine the inrush current level and fine tune the setting. - Also, need to know if the high set element uses fundamental component of current (typically the case) or total RMS current and set the pickup appropriately. Trip Characteristic – 87H
  • 23. Differential Protection Setting Calculations 87GD Pickup - Element normally uses directional comparison between phase residual current (3I0) and measured ground current (IG). The element becomes non-directional when the 3I0 current is small (example < 140 ma). - Pickup of 0.2 to 0.5 A (5A rated CTs) can be applied when using same ratio CTs on both phase and ground circuits. - When CT correction factor higher than 1.0 is applied, the pickup needs to be increased to account for noise amplification due to high CT ratio correction. - Use 6 cycle time delay to provide security against misoperations during external phase-to-phase to ground faults with CT saturation. The time delay must not be set below 2 cycles. Trip Characteristic – 87GD
  • 24. Differential Protection Setting Calculations WITHOUT GROUND DIFF. (87GD) THERE IS NO HIGHSPEED PROTECTION FOR SEC. GND FAULTS Typical Pickup of 87T: O.3 pu pickup Relay Tap set at Trans. Rating (45MVA) IFL138KV = 4.71 A PU = 4.71A x 0.3 = 1.41A Open R 87T 2000/5 200/5 400A 13.8KV 138KV I=0 400A 40A/1.73 40A/1.73*40/1=0.58A 45 MVA Improved Ground Fault Sensitivity
  • 25. Differential Protection Setting Calculations DIGITAL TRANSFORMER DIFFERENTIAL RELAY SETTING EXAMPLE
  • 26. Differential Protection Setting Calculations Sample Calculation – 87T 14,400/120
  • 27. Differential Protection Setting Calculations Transformer Size – MVA Rating Voltage Taps – No Load Transformer Connection Current Transformer Ratios Current Transformer Connection Voltage Transformer Ratios Voltage Transformer Connections — L-G or L-L LTC Tap Information Calculating Differential Set Points and System Setup 87T Sample Calculation
  • 28. Differential Protection Setting Calculations Delta AB 14,400/120 87T Sample Calculation
  • 29. Differential Protection Setting Calculations COMMUNICATES PHASING TO RELAY COMMUNICATES METERING DATA TO RELAY 87T Sample Calculation
  • 30. Differential Protection Setting Calculations COMMUNICATES PHASING TO RELAY COMMUNICATES METERING DATA TO RELAY 87T Sample Calculation W-2 Delta CT’S
  • 31. Differential Protection Setting Calculations Step 1 -Check CT and Relay Input Ratings Sample Transformer Ratings: OA/FA/FA = 30/40/50 MVA Short Time Rating of this transformer is 1.35 x 50 MVA = 67.5 MVA Relay current input is rated at 2X Nominal Rating i.e. 5A relay = 10 AMPS continuous I67.5 MVA W-2 PRI = 67.500 KVA/13.8KVx√3=2827A I67.5 MVA W-2 SEC = 2827/600/1 = 4.71 A For Δ CTs relay gets 4.71x √3= 8.15A <10A Sec. Winding (W2) OK I67.5 MVA W-1 PRI = 67.500 KVA/70.35KVx√3=554.6A I67.5 MVA W-1 SEC = 554.6/120/1 = 4.62A <10A Pri. Winding (W1) OK 87T Sample Calculation
  • 32. Differential Protection Setting Calculations Step 2: Select W1 & W2 Tap Settings Balance at OA Rating 87T Sample Calculation HandledBy Relay 3 3 2.09 A
  • 33. Differential Protection Setting Calculations Step 2: Select W1 & W2 Tap Settings Balance at OA Rating 87T Sample Calculation TAP VALUES
  • 34. Differential Protection Setting Calculations 87T Sample Calculation Step 3: Select minimum pickup of 87T • Pick up should be set to prevent operation of 87T due to transformer steady-state excitation current. •Typical Transformer excitation current ~1% = .01 pu •CT Error 10% =.10 pu • LTC Error 10%= .10 pu •Saftey Margin Typical 5% = .05 pu 26 % .26 pu •Typical setting is 0.26 to 0.35 p.u. Select p.u. at 0.3
  • 35. Differential Protection Setting Calculations 87T Sample Calculation Step 3: Select minimum pickup of 87T MINIMUM PICKUP
  • 36. Differential Protection Setting Calculations Step 4: Select Slope # 1 Setting Slope 1 The setting of Slope #1 should be set according to various possible errors: 1. Tapchanger operations in the power transformer (worst case± 10%) 10% 2. CT mismatch due to ratio errors. Errors can be as high as ± 10% 10% 3. Transformer excitation current (typical current of 1%) 1% 4. Relay measurement error 5% Set Slope # 1 = 30%
  • 37. Differential Protection Setting Calculations Step 4: Select Slope # 1 Setting SLOPE #1 SETTING
  • 38. Differential Protection Setting Calculations Step 5: Select slope #2 Setting • Provides security for high fault current levels outside the differential zone where CT inputs can saturate. • Factors effecting CT saturation - Residual magnetism in CT core - CT characteristic mismatch - CT circuit burden • CT Burden Check
  • 39. Differential Protection Setting Calculations 87T Sample Calculation Step 5: Select Slope #2 Setting Typical Slope #2 Settings is Twice Slope #2 60%
  • 40. Differential Protection Setting Calculations 87T Sample Calculation Step 5: Select Slope #2 Setting SLOPE #2 SETTING
  • 41. Differential Protection Setting Calculations 87T Sample Calculation Step 6: Select Break Point between Slope 1 and Slope 2 • Breakpoint is crossover from Slope 1 to Slope 2 Typical Breakpoint = 2.0
  • 42. Differential Protection Setting Calculations Step 6: Select Break Point between Slope 1 and Slope 2 BREAK POINT BETWEEN SLOPES 1 AND 2
  • 43. Differential Protection Setting Calculations 87T Sample Calculation Step 7: Select Inrush Harmonic Restraint • Relay uses 2nd and 4th harmonics • Percent harmonics defined as – • Amount of 2nd and 4th harmonics depend on: - Magnetizing characteristics of transformer core - Residual magnetism in core • Typical Settings -15% for most transformers -can be 10% or lower on new transformers with low core losses and steep magnetizing curves. Setting below 10% risks blocking for internal faults.
  • 44. Differential Protection Setting Calculations 87T Sample Calculation Step 7: (continued) Cross Phase Averaging (recommended) - Inrush harmonic level different in each phase - Cross phase averaging means each phase restrains on harmonics in other phases. For example:
  • 45. Differential Protection Setting Calculations Step 7: Select Inrush Harmonic Restraint INRUSH HARMONIC RESTRAINT
  • 46. Differential Protection Setting Calculations 87T Sample Calculation Step 8: Select Overexcitation Harmonic Restraint • M-3311 uses 5th harmonic. • Overexcitation (V/Hz) produces high amounts of 5th harmonic current. • 87T in M-3311 shifts minimum pickup to higher value, typically 150 to 200% of normal 87T p.u. Typical setting is 200% X 87T pickup, or 0.3 X 200% = 0.6 p.u.
  • 47. Differential Protection Setting Calculations 87T Sample Calculation Step 8: (continued) • Amount of 5th harmonic depends on transformer core magnetizing characteristics. • No cross phase averaging – Overexcitation is symmetrical. Typical setting is 30%
  • 48. Differential Protection Setting Calculations 87T Sample Calculation Step 8: Select Overexcitation Harmonic Restraint OVEREXCITATION HARMONIC RESTRAINT
  • 49. Differential Protection Setting Calculations • 87H function is not blocked by any harmonic restraint • Pickup must be set above first peak of inrush current • 87H is used in almost all transformer differentials to overcome restraint of 87T due to CT saturation for high internal transformer faults • Typical pickup setting is 8 to 12 p.u. Set at 10 p.u. Set delay at 1 cycle Step 9: Setting 87H Unrestrained High Set Differential
  • 50. Differential Protection Setting Calculations 87T Sample Calculation Step 9: Setting 87H Unrestrained High Set Differential UNRESTRAINTED HIGHSET DIFF. ©2008 Beckwith Electric Co., Inc.