Oscillography AnalysisOscillography Analysis
Oscillograph Analysis
IPSplot® PLUS Software
Features
Phasor & Time Domain Displays
Interpreting Data
Examples
Oscillography Analysis
Waveform Capture (Legend)
B C D
K NMLIG H
J
A
E
F
Oscillography Analysis
A) All analog traces. This
view shows peak values.
RMS values may also be
displayed.
B) Controls for going to the
beginning or end of a
record, as well as nudging
forward or backward in
time in a record.
C) Zoom controls
D) Display controls for analog
traces, RMS traces,
fundamental waveform
display, frequency trace,
power trace, power factor
trace, phasor diagram,
impedance diagram and
power diagram.
E) Marker #1
F) Marker #2
G) Time at Marker #1
H) Time at Marker #2
I) Control status input and
contact output traces
(discrete I/O)
J) Scaling for each analog
trace. This can be set
automatically or manually
adjusted.
K) Date and timestamp for
record
L) Time of trip command
M) Time at Marker #1
N) Time at Marker #2
Oscillography Analysis
Waveform Capture (Legend)
P
Q
R
O
S
Oscillography Analysis
O) Drop down window for view selection, diagram selection and
zoom.
P) Delta value between Marker #1 and Marker #2
Q) Value at Marker #1
R) Value at Marker #2
S) Scaling for each analog trace. This can be set automatically
or manually adjusted.
Oscillography Analysis
Waveform Capture (Phasor)
Oscillography Analysis
M-3311 Differential Function
Tripped when Generator
Breaker Closed
During Relay Commissioning
Oscillography Analysis
Oscillography Analysis
M-3311
Winding 3
Winding 2
Winding 1
Delta-ac
60:1
600:1
600:1
M3311 One Line
Oscillography Analysis
Target List
IPScom: Version V02.01.03
Relay: M3311/V01.05.00
Comments:
No. Date Time Event(s)
----------------------------------------------------------------------------------------------------
02-Jul-2005 09:37:08.000 1 (87T) Phase Differential Current - Phase B Operated
INPUTS: OUTPUTS: 1
W1 Currents: 1.36 A (A), 1.39 A (B), 1.44 A (C)
W2 Currents: 0.03 A (A), 0.05 A (B), 0.04 A (C), 0.00 A (N)
W3 Currents: 0.82 A (A), 0.81 A (B), 0.83 A (C), 0.01 A (N)
Oscillography Analysis
M-3311
Winding 3
Winding 2
Winding 1
Delta-ac
60:1
600:1
600:1
M3311 One Line
67.2MVA
230kV / 13.8kV
Wye / Delta-ac
Relay System Setup Screen
Wye connected CT's
Transformer Rating
Oscillography Analysis
87 Trip Oscillography
No rolled phases on Winding 1
No rolled phases on Winding 3
Currents are out of phase
Oscillography Analysis
87 Function Settings
CT Tap Settings
Oscillography Analysis
M-
3311
Winding 3
Winding 2
Winding 1
Delta-ac
60:1
600:1
600:1
M3311 One Line
Winding 1 Phase A Current = 1.36A
Per Unit Current = 1.36A / Winding 1 Tap
Per Unit Current = 1.36A / 4.7 = 0.29pu
Winding 3 Phase A Current = 0.82A
Per Unit Current = 0.82A / Winding 3 Tap
Per Unit Current = 0.82A / 2.81 = 0.29pu
67.2MVA
230kV / 13.8kV
Wye / Delta-ac
Winding 1 Tap Winding 3 TapWinding 2 Tap
CTR = 600:1 CTR = 600:1 CTR = 60:1
Tap1 = Tap3 =Tap2 =
x 600
Tap1 =
13.8 x 3
67.3 x 1000
x 60
Tap3 =
230 x 3
67.3 x 1000
x 600
Tap2 =
13.8 x 3
67.3 x 1000
4.69 4.69 2.81
Calculate Winding Tap Settings
Target List
IPScom: Version V02.01.03
Relay: M3311/V01.05.00
Comments:
No. Date Time Event(s)
----------------------------------------------------------------------------------------------------
02-Jul-2005 09:37:08.000 1 (87T) Phase Differential Current - Phase B Operated
INPUTS: OUTPUTS: 1
W1 Currents: 1.36 A (A), 1.39 A (B), 1.44 A (C)
W2 Currents: 0.03 A (A), 0.05 A (B), 0.04 A (C), 0.00 A (N)
W3 Currents: 0.82 A (A), 0.81 A (B), 0.83 A (C), 0.01 A (N)
Tap1 = 4.70
Tap2 = 4.70
Tap3 = 2.81
Oscillography Analysis
87 Trip Phasor Diagram
Winding 1
phase A current
Winding 3
phase A current
Winding 3 relay input current
Lags Winding 1 relay input
current by 210 degrees
Oscillography Analysis
67.2MVA
230kV / 13.8kV
M-3311
Winding 3
Winding 2
Winding 1
Delta-ac
60:1
600:1
600:1
M3311 One Line
All CT's are wye
Wye / Delta-ac Transformer
High side currents lead low side
currents by 30 degrees
Resulting relay currents taking CT
polaritiy into account,
Winding 3 currents lag Winding 1
currents by 150 degrees
IH
IL
IH
IL
IW3
IW1
M3311 Relay Application
IW3
IW1
150 degrees
Oscillography Analysis
IW3
IW1
150 degrees
Vector angle should
be 150 degrees
Vector angle is
210 degrees
Assume transformer is
actually a Delta -ab High
"LAGS" low by 30 degrees
IH
IL
30 degrees
IW3
IW1
210 degrees
Relay Currents
Oscillography Analysis
H1 X1
H2 X2
H3 X3
C
B
A a
b
c
IB
IA
Ic -Ia
Ib -Ic
Ia -Ib
Ia
Ib
Ic
W3A = 0.82A
W1A = 1.37A
W3C = 0.82A
Winding 1Winding 3
IA
IBIC Ic -Ia
Ib -Ic
Ia -Ib
W3C = 0.82A -60
W3A = 0.82A 180 W1A =1.37A 30
Actual Transformer 3-Line
Oscillography Analysis
W1A =1.37A 30
W3C = 0.82A -60
W3A = 0.82A 180
- W3C
W3A - W3C
0.82/2.81=0.29pu
0.82/2.81=0.29pu
IA-IC =
Convert to Per UnitW3A = 0.82A 180
W3C = 0.82A -60
180
-60
Convert to Delta-ac
1800.29pu -600.29pu-
3
150= 0.29pu
=
1.36/4.69=0.29pu 30
Convert to Per Unit
Calculate IDIFF & IRes
IDIFF= IAW1 +IAW2 +IAW3
1500.29pu 30 + 0 + 0.29pu=
0.29pu 90
M3311 with Delta-ac Configuration
IDIFF
W3A - W3C
W1A
W1A =1.37A 30
IDIFF =
IRES = IAW1 +IAW2 +IAW3
0.29pu + 0 + 0.29pu=
2
2
IRES = 0.29pu
M-3311
Oscillography Analysis
W1A =1.37A 30
W3B = 0.82A 60
W3A = 0.82A 180
- W3B
W3A - W3B
IDIFF = 0
W3A - W3B
W1A
W1A =1.37A 30
0.82/2.81=0.29pu
0.82/2.81=0.29pu
IA-IB =
Convert to Per UnitW3A = 0.82A 180
W3C = 0.82A 60
180
60
Convert to Delta-ab
1800.29pu 600.29pu-
3
210= 0.29pu
=
1.36/4.69=0.29pu 30
Convert to Per Unit
Calculate IDIFF
IDIFF= IAW1 +IAW2 +IAW3
2100.29pu 30 + 0 + 0.29pu=
0.0
M3311 with Delta-ab Configuration
IDIFF =
IRES = IAW1 +IAW2 +IAW3
0.29pu + 0 + 0.29pu=
2
2
IRES = 0.29pu
M-3311
Oscillography Analysis
Current was below 0.3 pu Pickup Setting
Was Trip Correct?
Why Only Phase B Differential?
Why not Phase A, B, and C?
Oscillography Analysis
M-3430
“40” Function Tripped Unit
Oscillography Analysis
M3430 Application One Line
1000:1
M-3430#1
M-3430#2
1000:1
120:1
M-3430#2 40
Function tripped
88MVA
13.2kV
Oscillography Analysis
Oscillography
Oscillography Analysis
Expanded Oscillography
Oscillography Analysis
Phasor Diagram
Oscillography Analysis
PQ Plot
Oscillography Analysis
Impedance Plot
Oscillography Analysis
M-3430 “40” Function Setting (both relays)
Oscillography Analysis
- 5
- 10
- 15
- 20
- 25
- 30
5 10 15
5
- 5
X
R
>
>
14.2
- j11.7
M-3430 Relay Loss of Field Operation40 Function Settings
Offset = -1.6 ohm
Zone 1 = 18 ohm, 5 cycle
Zone 2 = 30.2 ohm, 30 cycle
Impedance= 14.2 -j11.7
Oscillography Analysis
Was it a Correct Trip?
Zone 2 Time Delay was set at 30 cycles.
Why did it take 90 Cycles to Trip?
Why did only 1 Relay Trip?
M-3310 Differential Function
Tripped for
External Phase C Ground Fault
Oscillography Analysis
Oscillography Analysis
150/200/250MVA
352kV / 15kV
M-3310
Winding 1
Winding 2
Delta-ac
600:1
2400:1
All CT's are wye
IH
IL
IH
IL
IW1
IW2
M3310 Relay Application
IW1
IW2
150 degrees
Phase C-g Fault
Line Relay 67G also tripped
Oscillography Analysis
87 Trip Oscillography
Oscillography Analysis
Sequence Networks
XG1 XT1
X
XS1
XG2 XT2
X
XS2
XG0 XT0
X
XS0
VG VS
IT0 IS0
IS2IT2
IT1 IS1
Oscillography Analysis
Auto Scale & Voltages Removed
Oscillography Analysis
Phasor Pre fault
Oscillography Analysis
Phasor Post fault
Oscillography Analysis
System Setup Screen 87 Function Setup Screen
Oscillography Analysis
0.5
0.5
2.5
2.0
1.0
1.5
1.0 1.5 2.0 2.5 3.0
87 Slope Characteristic
ID
IR
BP = 1.0
Pickup = 0.27 pu
M1 = 27%
M2 = 60%
Phase A
Phase B
Phase C
IA Diff = W1(I a - I c) + W2I a
IC Diff = W1(I c - I b) + W2I c
IB Diff = W1(I b - I a) + W2I b
Oscillography Analysis
Expanded Phase A Scale
Waveshape Suspicious
Oscillography Analysis
Phasor Expanded Phase A Scale
Check Current Sum:IA + IB +IC = -IG
Oscillography Analysis
Check Current Sum:IA + IB +IC = -IG
Calculated IG = 15.19 -143.6 = 19.4 -147.0
IA + 1.97 11 12.66 43 - 19.4 -147+ =
IA 5.3 17.2=
Oscillography Analysis
Recalculated Differential Currents
IDIFF= IAW1(AC) +IAW2
571.38pu 240 + 1.34pu=
0.08 puIDIFF =
IRES = IAW1 (AC) + IAW2
1.38pu + 1.34pu=
2
2
IRES = 1.36pu
IDIFF= IBW1(BA) + IBW2
250.58pu -21.3 + 0.55pu=
0.04 puIDIFF =
IRES = IAW1(BA) +IAW2
0.58pu + 0 + 0.55pu=
2
2
IRES = 0.57pu
Phase A Phase B
Oscillography Analysis
0.5
0.5
2.5
2.0
1.0
1.5
1.0 1.5 2.0 2.5 3.0
87 Slope Characteristic
ID
IR
BP = 1.0
Pickup = 0.27 pu
M1 = 27%
M2 = 60%
Phase A
Phase B
Phase C
IA Diff = W1(I a - I c) + W2I a
IC Diff = W1(I c - I b) + W2I c
IB Diff = W1(I b - I a) + W2I b
With Calculated W1A
Phase A
Phase B
Oscillography Analysis
Customer Confirmed Problem
Phase A CT
©2008 Beckwith Electric Co., Inc.

More Related Content

What's hot

Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
michaeljmack
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
moiz89
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
Priten Vasa
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
Armstrong Okai Ababio
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
Power System Operation
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
Nageswar Rao
 

What's hot (20)

Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
FACTS DEVICES
FACTS DEVICESFACTS DEVICES
FACTS DEVICES
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Unit 1 Power System Stability
Unit 1 Power System Stability Unit 1 Power System Stability
Unit 1 Power System Stability
 
Fault Calculations
Fault CalculationsFault Calculations
Fault Calculations
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
 
Power System Stabilizer
Power System StabilizerPower System Stabilizer
Power System Stabilizer
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Basic protection and relaying
Basic protection and relayingBasic protection and relaying
Basic protection and relaying
 
Power system stability and control using facts devices
Power system stability and control using facts devicesPower system stability and control using facts devices
Power system stability and control using facts devices
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
Out of step
Out of stepOut of step
Out of step
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS) POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
POWER SYSTEM SIMULATION - 2 LAB MANUAL (ELECTRICAL ENGINEERING - POWER SYSTEMS)
 

Viewers also liked (9)

Circuit Breakers Interrupting Capacity and Short-Time Current Rating
Circuit Breakers Interrupting Capacity and Short-Time Current Rating Circuit Breakers Interrupting Capacity and Short-Time Current Rating
Circuit Breakers Interrupting Capacity and Short-Time Current Rating
 
Introduction to Oscilloscopes
Introduction to OscilloscopesIntroduction to Oscilloscopes
Introduction to Oscilloscopes
 
digita storage oscilloscope (dso)
digita storage oscilloscope (dso)digita storage oscilloscope (dso)
digita storage oscilloscope (dso)
 
Oscilloscope
OscilloscopeOscilloscope
Oscilloscope
 
Oscilloscope
OscilloscopeOscilloscope
Oscilloscope
 
cathode ray oscilloscope
cathode ray oscilloscopecathode ray oscilloscope
cathode ray oscilloscope
 
Cathode Ray Oscilloscope CRO
Cathode Ray Oscilloscope CROCathode Ray Oscilloscope CRO
Cathode Ray Oscilloscope CRO
 
Presentaion on dual trace oscilloscope
Presentaion on dual trace oscilloscopePresentaion on dual trace oscilloscope
Presentaion on dual trace oscilloscope
 
Presentation on cro
Presentation on croPresentation on cro
Presentation on cro
 

Similar to Oscillography analysis

Similar to Oscillography analysis (20)

Oscillography Analysis
Oscillography AnalysisOscillography Analysis
Oscillography Analysis
 
Presentació renovables
Presentació renovablesPresentació renovables
Presentació renovables
 
PPT FINAL (1)-1 (1).ppt
PPT FINAL (1)-1 (1).pptPPT FINAL (1)-1 (1).ppt
PPT FINAL (1)-1 (1).ppt
 
Original IGBT STGP6NC60HD 6N60 600V 15A TO-220 New STMicroelectronics
Original IGBT STGP6NC60HD 6N60 600V 15A TO-220 New STMicroelectronicsOriginal IGBT STGP6NC60HD 6N60 600V 15A TO-220 New STMicroelectronics
Original IGBT STGP6NC60HD 6N60 600V 15A TO-220 New STMicroelectronics
 
Original IGBT STGP6NC60HD GP6NC60 6N60 600V 15A TO-220 New STMicroelectronics
Original IGBT STGP6NC60HD GP6NC60 6N60 600V 15A TO-220 New STMicroelectronicsOriginal IGBT STGP6NC60HD GP6NC60 6N60 600V 15A TO-220 New STMicroelectronics
Original IGBT STGP6NC60HD GP6NC60 6N60 600V 15A TO-220 New STMicroelectronics
 
LED電源回路アプリケーションガイド 金沢プレゼン資料
LED電源回路アプリケーションガイド 金沢プレゼン資料LED電源回路アプリケーションガイド 金沢プレゼン資料
LED電源回路アプリケーションガイド 金沢プレゼン資料
 
Susol TS 1600 ÀF Reaflet 1010 LS
Susol TS 1600 ÀF Reaflet 1010 LSSusol TS 1600 ÀF Reaflet 1010 LS
Susol TS 1600 ÀF Reaflet 1010 LS
 
Dc circuit-breaker
Dc circuit-breakerDc circuit-breaker
Dc circuit-breaker
 
Catalog ls susol mccb denhathe.vn
Catalog ls susol mccb denhathe.vnCatalog ls susol mccb denhathe.vn
Catalog ls susol mccb denhathe.vn
 
Catalog ls susol mccb
Catalog ls susol mccbCatalog ls susol mccb
Catalog ls susol mccb
 
Jaquet multitasker
Jaquet multitaskerJaquet multitasker
Jaquet multitasker
 
Datasheet Metrel MI 3102BT. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Metrel MI 3102BT. Hubungi PT. Siwali Swantika 021-45850618Datasheet Metrel MI 3102BT. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Metrel MI 3102BT. Hubungi PT. Siwali Swantika 021-45850618
 
Line Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relayLine Differential - Test report for Alstom make Micom P546 relay
Line Differential - Test report for Alstom make Micom P546 relay
 
Design of CMOS operational Amplifiers using CADENCE
Design of CMOS operational Amplifiers using CADENCEDesign of CMOS operational Amplifiers using CADENCE
Design of CMOS operational Amplifiers using CADENCE
 
IMU General Introduction
IMU General IntroductionIMU General Introduction
IMU General Introduction
 
Original Digital Transistor KRC105 C105M C105 100mA 50V TO-92 New
Original Digital Transistor KRC105 C105M C105 100mA 50V TO-92 NewOriginal Digital Transistor KRC105 C105M C105 100mA 50V TO-92 New
Original Digital Transistor KRC105 C105M C105 100mA 50V TO-92 New
 
Original NPN Transistor KRC106M C106 106 TO-92 New KEC
Original NPN Transistor KRC106M C106 106 TO-92 New KECOriginal NPN Transistor KRC106M C106 106 TO-92 New KEC
Original NPN Transistor KRC106M C106 106 TO-92 New KEC
 
Datasheet Metrel MI 3100 SE. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Metrel MI 3100 SE. Hubungi PT. Siwali Swantika 021-45850618Datasheet Metrel MI 3100 SE. Hubungi PT. Siwali Swantika 021-45850618
Datasheet Metrel MI 3100 SE. Hubungi PT. Siwali Swantika 021-45850618
 
Catalogue ACB BT3 - Air Circuit Breaker BT3 Fuji - Beeteco.com
Catalogue ACB BT3 - Air Circuit Breaker BT3 Fuji - Beeteco.comCatalogue ACB BT3 - Air Circuit Breaker BT3 Fuji - Beeteco.com
Catalogue ACB BT3 - Air Circuit Breaker BT3 Fuji - Beeteco.com
 
RELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdfRELAY ETTING CALCULATION REV-A (DG-298).pdf
RELAY ETTING CALCULATION REV-A (DG-298).pdf
 

More from michaeljmack

Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
michaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
michaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
michaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
michaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
michaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
michaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
michaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
michaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
michaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 

Recently uploaded

Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Recently uploaded (20)

Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 

Oscillography analysis