This document provides information about programming and operating an Allen Bradley Powerflex 4M 400W adjustable frequency AC drive. It includes sections about wiring the drive, I/O wiring examples, and parameter organization. The parameter organization section describes numerous drive parameters including output frequency, commanded frequency, output current, drive status, and others. It also separates parameters into categories for display, program, and terminal parameters.
9. AB Powerflex 4M
Parameter Organization - Display
d001 â Output Frequency
Output frequency present at T1, T2 & T3 (U, V & W).
d002â Commanded Frequency
Value of the active frequency command. Displays the
commanded frequency even if the drive is not running.
d003 - Output Current
The output current present at T1, T2 & T3 (U, V & W).
d004 - Output Voltage
d006 â Drive Status
Present operating condition of the
drive.
The output voltage present at T1, T2 & T3 (U, V & W).
d005 â DC Bus Voltage
Present DC bus voltage level.
10. AB Powerflex 4M
Parameter Organization
d010 â Process Display
The output frequency scaled by A440 [Process Factor] or by A438 [Process Time Lo] and
A439 [Process Time Hi].
d012 â Control Source
Displays the active source of the Start
Command and Speed Command.
11. AB Powerflex 4M
Parameter Organization
d012 â Control In Status
Status of the control terminal block control inputs.
Important: Actual control commands may come from a source other than the control
terminal block.
d018 - Elapsed Run Time
Accumulated time drive is outputting power. Time is displayed in 10-hour increments.
12. AB Powerflex 4M
Parameter Organization
d020 - Analog In 0-10V
The present value of the voltage at I/O Terminal 13 (100.0% = 10 volts).
d021 - Analog In 4-20mA
The present value of the current at I/O Terminal 15 (0.0% = 4mA, 100.0% = 20mA).
d022 - Drive Temperature
Present operating temperature of the drive power section.
13. AB Powerflex 4M
Parameter Organization - Program
P101 â Motor NP Voltage
Stop drive before changing this parameter.
Set to the motor nameplate rated voltage.
P102 â Motor NP Hertz
Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
P103 â Motor OL Current
Set to the maximum allowable motor current.
P104 â Minimum Frequency
Sets the lowest frequency the drive will output
continuously. Min/Max: 0.0/400.0 Hz
P105 â Maximum Frequency
Sets the highest frequency the drive will output
continuously. Min/Max: 0.0/400.0 Hz
14. AB Powerflex 4M
Parameter Organization - Program
P106 â Start Source
Stop drive before changing this parameter.
Sets the control scheme used to start the drive.
P107 â Stop Mode
Active stop mode for all stop sources
0âRamp, CFâ(1) (Default)
Ramp to Stop. âStopâ command clears
active fault.
1âCoast, CFâ(1)
Coast to Stop. âStopâ command clears
active fault.
15. AB Powerflex 4M
Parameter Organization - Program
P108 â Speed Reference
Sets the source of the speed reference to the drive.
P109 â Acc. time
Sets the rate of acceleration for all speed increases.
16. AB Powerflex 4M
Parameter Organization - Program
P110 â Dec. Time
Sets the rate of deceleration for all speed decreases.
P112 â Reset to Default
Resets all parameter values to factory defaults.
17. AB Powerflex 4M
Parameter Organization - Terminal
t201 â Digital In1 Sel
(I/O Terminal 5)
T202 â Digital In2 Sel
(I/O Terminal 6)
18. AB Powerflex 4M
Parameter Organization - Terminal
t201 â Digital In1 Sel
(I/O Terminal 5)
T202 â Digital In2 Sel
(I/O Terminal 6)
19. AB Powerflex 4M
Parameter Organization - Terminal
t211 â Analog In 0 ~ 10 V Lo
Sets the analog input level that corresponds to P104 [Minimum Freq] if a 010V input is used by P108
Analog inversion can be accomplished by setting this value larger than
t212 [Anlg In 0-10V Hi] or by setting t201 - t202 [Digital Inx Sel] to option
15 âAnlg Invertâ.
t212 â Analog In 0 ~ 10 V Hi
Sets the analog input level that corresponds to P105 [Maximum Freq] if a 0-10V input is
used by P108 [Speed Reference].
Analog inversion can be accomplished by setting this value smaller than t211 [Anlg In 010V Lo] or by setting t201 - t202 [Digital Inx Sel] to option 15 âAnlg Invertâ.
20. AB Powerflex 4M
Parameter Organization - Terminal
t213 â Analog In 4 ~ 20mA Lo
Sets the analog input level that corresponds to P104 [Minimum Freq] if a 420mA input is used by P108 [Speed Reference].
Analog inversion can be accomplished by setting this value larger than t214
[Anlg In4-20mA Hi] or by setting t201 - t202 [Digital Inx Sel] to option 15
âAnlg Invertâ.
t214 â Analog In 4 ~ 20mA Hi
Sets the analog input level that corresponds to P105 [Maximum Freq] if a 420mA input is used by P108 [Speed Reference].
Analog inversion can be accomplished by setting this value smaller than
t213 [Anlg In4-20mA Lo] or by setting t201 - t202 [Digital Inx Sel] to option
15 âAnlg Invertâ.
21. AB Powerflex 4M
Parameter Organization - Terminal
t221 â Relay Out Selection
Sets the condition that changes the state of the output relay contacts.
22. AB Powerflex 4M
Parameter Organization - Terminal
t221 â Relay Out Selection
Sets the condition that changes the state of the output relay contacts.
t222 â Relay Out Level
Sets the trip point for the digital output relay if the value
of t221 [Relay Out Sel] is 6, 7, 8, 10 or 11.
23. 100+ Video Tutorials
Coupon Code
in $99 $49
https://www.udemy.com/nfi-plc-online-leaning/?couponCode=slideshare
Life time Access
Course Outline
Learn to Code | Code to Learn
nfi Learn 4 PLCâs in a Day
presents
PLC â Programmable Logic Controller
Delta DVP 14 SS + 16 SP
⢠100+ PLC Video Tutorials
Allen Bradley M1000
⢠Doubt Clearing Complementary LIVE Sessions on Team Viewer
Siemens S7 200
⢠Ladder Logic Programming
Schneider
⢠PLC Presentations, PLC Circuits, PLC Codes
Analog Cards Programming
⢠FREE PLC Simulation Software for Practice
04 AD â Analog to Digital
04DA- Digital to Analog
For more courses visit www.nfiautomation.org
24. PLC & VFD Advanced
Course
4 PLCâs Training
Platforms
$149
Course Link:
Course Highlights: http://www.wiziq.com/course/28882-plc-andac-drives-online-certificate-trainaing-course
⢠30 Live Practical Classes on PLC, Analog Cards & AC drives- VFD
⢠100+ PLC Video Tutorials with Lifetime Access & FREE PLC Simulator
⢠FREE Circuits Diagram
For more courses visit www.nfiautomation.org