Rittal – Aisle containment
Simple and efficient




Efficient cooling saves money
High-efficiency climate control concepts
from Rittal
Instead of flooding the room with cold air, this Rittal concept

routes the cold air directly to the equipment via the cold aisle.

Cold air is directed across the whole height of the enclosure

ensuring that there are no hot-spots and the hot air is

exhausted out of the system. Due to the cold aisle being

contained there is no chance of the hot exhaust air

mixing with the cold inlet air, therefore there is an

increase in system efficiency. The outstanding energy

efficiency of the Rittal cold aisle concept has a

simple explanation:

1. Intake air (cold) and waste air (hot) are unable to mix.
2. The system can be operated with a much higher aisle
     temperature level (reduction in hot-spots).
3. As a result of the increased temperature difference be-
     tween intake air and waste air, climate control units are
     operated at an optimum thermal difference (increased ΔT).

    Standard market concepts                    Rittal




    Hot air extraction using                    Rittal aisle containment (cold aisle)          Rittal aisle containment (cold aisle)
    a duct system                               with raised floor (CRAC)                       without raised floor (Inline Cooling)
    ● Complex and costly duct system.           ● Use of standard inexpensive air circu-       ● Direct connection of the liquid cooling
    ● Larger surface area and height              lation cooling units. Positioned outside       packages to an external cold water
      requirements.                               the server area.                               supply.
    ● Limitation of the raised floor height.    ● Even with low room heights, maximisation     ● Simple laying of pipework in the rack
    ● No uniform cooling air supply to the        of the raised floor height for cooling air     base/plinth.
      room area.                                  supply without flow losses.                  ● Homogeneous distribution of cooling air
    ● Cable management is more difficult.       ● Undisturbed and uniform air flow distri-       in the cold aisle guarantees a high level
    ● Limited rack positioning due to the air     bution of cooling air in the cold aisle        of efficiency.
      duct connection.                            guarantees high-efficiency.                  ● Favourable working conditions in the
    ● Extremely high presure loss on the air    ● Favourable working conditions in the cold      cold aisle due to low temperature,
      side, leading to increased energy           aisle due to low temperature, flow and         flow and noise load conditions.
      consumption of the fans.                    noise load conditions.                       ● Hardware racks not connected to the
                                                ● Hardware racks not connected to the            containment system do not impair
                                                  enclosure do not impair the cooling            cooling efficiency via the cold aisle.
                                                  efficiency of the cold aisle.                ● Room heights play only a minimal role.


2                                                                                                                      Rittal aisle containment
Three systems with a high level of efficiency
                                                Nowadays, servers are increasingly positioned in rooms that were not
 Rittal aisle containment (hot aisle)
                                                designed as data centres. As a result of hot air cushions below the
 without raised floor                           ceiling, in particular, hot-spots in hot-spot racks are not dissipated. In
 ● Simple assembly using the existing           order to consistently address this problem, Rittal has developed three
   components of Rittal aisle containment.      systems for aisle containment. In the two variants of cold aisle (CRAC
 ● Direct connection of the liquid cooling      and Inline Cooling), we are able to provide a solution that is independ-
   packages (LCP Inline) to an external cold    ent of whether there is a false floor available or not. Both provide cold
   water supply.
 ● Simple laying of pipework in the rack
                                                air to the aisle, where it is then absorbed by the server inlets. In the
   base/plinth.                                 third system, the hot air is extracted from the hot aisle, via the LCP
 ● Suitable for use with high heat losses.      Inline, without influencing the ambient temperatures, and then selec-
 ● Room-neutral dissipation of the heat loss.   tively re-emitted as cold air in the proximity of the equipment.
                                                The outcome is the same with all three systems: Increased reliability,
                                                greater cooling capacity and simultaneously improved energy effi-
                                                ciency.



Rittal aisle containment                                                                                                     3
Rittal cold aisle containment with
        CRAC system and sensors
                        5




            7


                                                                                                                            5

    5

                    5



                                                                                                                                 6
1


5               5                                                           4




                                                               5
                            2


            5                                                                      1 Rittal aisle containment
                                              3
                                                                                   2 CRAC systems
                                                                                   3 Water/water heat exchangers
                                                                                   4 IT chiller
                                                                                   5 Wireless temperature sensors
                                                                                   6 Administration
                                                                                   7 Wireless humidity sensors




                                By using Rittal aisle containment,          In conjunction with the LCP Inline, aisle
                                climate control of the room (in con-        containment is a further option for the
                                junction with the Rittal CRAC system)       efficient dissipation of high heat loads
                                may be optimised in terms of energy         from server racks.
                                efficiency and cooling output.
                                                                            ● A raised floor is not required for
                                ● High energy efficiency                        climate control
                                ● Increased cooling output per server       ● For increased heat loads per server
                                  rack                                          rack
                                ● Easily retro-fitted to existing systems   ● Redundancies easily achieved
                                ● Protection of your existing infra-        ● Direct supply of cold air to your
                                  structure                                     server and network components
                                ● The MTBF of existing systems can          ● Particularly suitable for use with
                                  be significantly extended                     low room heights



        4                                                                                             Rittal aisle containment
Aisle containment with
LCP Inline and sensors

                                   5


                           7                                                                                               5


             5


                                       5
                                                                                                                               6

                               2

     1


         5
                                                                                   4




                                                                    5


                                                                                             1 Rittal aisle containment
                                                3                                            2 LCP Inline
                                                                                             3 Water/water heat exchangers
                                                                                             4 IT chiller
                                                                                             5 Wireless temperature sensors
                                                                                             6 Administration
                                                                                             7 Wireless humidity sensors




                                           Innovative monitoring and control
                                           for even greater efficiency
With Rittal wireless sensors, all rele-
vant climate conditions may be meas-       In order to further enhance efficiency with the cooling of data
ured without any cabling whatsoever.       centres, the thermal parameters must be permanently moni-
                                           tored and adjusted for optimum performance.
This ensures that the optimum para-
meters for energy-efficient climate con-   Rittal wireless sensor technology is available for the fast log-
trol are available at all times.           ging and monitoring of these parameters. This technology
                                           supports simple, fast installation and commissioning at all
                                           key points in the data centre. Whether in the raised floor or
                                           under the ceiling, all measurements are wireless and can be
                                           processed directly using a controller.




Rittal aisle containment                                                                                                       5
Maximise potential savings!


    Know-how safeguards efficiency
                                                                                           The potential savings that can be made with the operating
                                                            Cooling output                 costs for a data centre are shown in the diagram opposite.
                                                                                           Despite considerable savings of energy and CO2, the oper-
                                                            Energy/electricity             ating temperature of the servers always remains within the
                                                                                           optimum range.
                                                            CO2                            We would like to prove this with some figures from our best
                                                                                           practice example, which demonstrates the benefits of coor-
                                                                                           dinated, intelligent regulation and control of all climate con-
                                                                                           trol components.




              Without
    aisle containment
                                          With
                            aisle containment
                                     Aisle containment with
                                          integrated control




        Rittal wireless sensor network
                                                                   7                       12                   13                  14                   15
                                           11
                 3




                                     LAN
                                                                   8


             4
                                                1
                                                                                                                          16



                                                                   9


            5

                                                                         0˚


                 PLC
                       X2




                                                                  10
                                                                                                                          17                   18

                               6

                                                                         0˚

                                            2
                                                                                           Wireless I/O unit
                                                                                           DK 7320.240
                                                                                           (as basic unit)
    1   Processing Unit II (PU II), the             5   RTT I/O unit                        9    Climate unit,                       12   Alternative external aerial
        nerve centre of the CMC-TC                      Up to 10 climate control devices         Fan Control System FCS                   DK 7320.241
        monitoring system                               with Comfort controller may              Fans are controlled via tempe-      13   Wireless measurement system
        The PU II is the coordinator                    be connected via one unit in             rature sensors. Airflow monitors         (must be available for commis-
        between the sensor unit and the                 master/slave mode.                       report any contamination of the          sioning)
        network. It is configured via the           6   Liquid Cooling Package LCP               filter mat, for example. The fan         DK 7320.242
        integral web server.                            The professional LCP water               speed is controlled and moni-
                                                                                                 tored via the FCS.                  14   Wireless humidity sensor
    2   Server shutdown function                        cooling system for data centres                                                   DK 7320.515
                                                        may be linked directly to the      10    Universal I/O unit
    3   Electronic systems with moni-                   Processing Unit II.                      This measurement and alarm          15   Wireless access sensor
        toring of temperatures, fans and                                                         module indicates motion, vibra-          DK 7320.535
                                                    7   I/O wireless unit
        DC voltages.                                    Up to 16 sensors may be wire-            tions, doors being opened, tem-     16   Wireless temperature sensor
    4   Active Power System Module                      lessly incorporated into the             peratures exceeded, and much             DK 7320.505
        PSM, Power Control Unit PCU                     CMC-TC system via this unit.             more besides. The sensors may
                                                                                                 be selected for the application.    17   IP protective cover (optional)
        The sockets may be activated                8   Access unit                                                                       DK 7320.245
        directly by the Processing Unit II              The doors of buildings, rooms
                                                                                            11   Video network IP camera
        (max. 4 x 4 x 8 sockets), com-
                                                                                                                                     18   Wireless digital input
                                                        and enclosures may be moni-                                                       DK 7320.585
        bined with an ammeter.                          tored, activated and opened via
                                                        the network.




6                                                                                                                                                    Rittal aisle containment
Easy with Rittal


 Step 1:
 Raise the water inlet temperature                                                                                             –26%
  Qtotal (Qsens.)              80 kW (80 kW) – 79.9 kW (79.9 kW)         The temperature in the cold aisle is precisely definable
  Tair; hot (rel. humidity)    26°C (45%) – 31°C (32%)                   and identical throughout, thanks to optimisation of the
  Tair; cold (rel. humidity)   15°C (89%) – 19.8°C (62.2%)               temperature distribution.
  Twater; inlet                10°C – 15°C                               ● Increasing the air intake temperature also increases
  Twater; return               15°C – 20°C                                   the waste air temperature.
  Pelectr. for cold water      190 MWh/a – 139 MWh/a                     ● Increasing the air intake temperature improves the
                                                                             performance of free cooling.
                                                                         Possible energy savings in cold water generation:
                                                                         up to 26%.



 Step 2:
 Reduce the volumetric airflow                                                                                                 –60%
  Qtotal (Qsens.)              79.9 kW (79.9 kW) – 88.4 kW (88.4 kW)     With a constant flow rate, the cooling output is increased
  Tair; hot (rel. humidity)    31°C (32%) – 36°C (25%)                   by raising the ΔT at the air end.
  Tair; cold (rel. humidity)   19.8°C (62.2%) – 19.7°C (64.6%)           ● By reducing the volumetric airflow, the waste air
  Vair (ext. press.)           22000 m3/h (80 Pa) – 17000 m3/h (20 Pa)       temperature and return temperature are increased.
  Pelectr. for UKS fan         3.6 kW – 1.5 kW
                                                                         Possible energy savings in the power consumption
                                                                         of the fans: up to 60%.




 Step 3:
 Reduce the throughput                                                                                                         –15%
  Qtotal (Qsens.)              88.4 kW (88.4 kW) – 80 kW (80 kW)         The pump output can be reduced due to a smaller through-
  Tair; hot (rel. humidity)    36°C (25%) – 36°C (25%)                   put required for the same cooling output, and the return
  Tair; cold (rel. humidity)   19.7°C (64.6%) – 21.3°C (54.2%)           temperature is increased.
  Twater; inlet                15°C – 15°C                               Potential saving in the power consumption of the pump:
  Twater; return               20.6°C – 23.5°C                           up to 14%.
  Vwater (Pelectr. )           13.6 m3/h (3 kW) – 8.1 m3/h (2.3 kW)      Potential saving in cold water generation:
  Pelectr. for cold water      143 MWh/a – 125 MWh/a                     up to 17%.




 Summary
                                                                                                                               –36%
  Qtotal (Qsens.)              80 kW (80 kW) – 80 kW (80 kW)             Energy saving:
  Tair; hot (rel. humidity)    26°C (45%) – 36°C (25%)                   ●   Fans: 19 MWh/a
  Tair; cold (rel. humidity)   15°C (89%) – 21.3°C (54.2%)               ●   Pumps: 6 MWh/a
  Vair (ext. press.)           22000 m³/h (80 Pa) – 17000 m³/h (20 Pa)   ●   Cold water production: 65 MWh/a
  Twater; inlet                10°C – 15°C                               ●   Overall: 90 MWh/a
  Twater; return               15°C – 23.5°C                             Cost saving with Rittal aisle containment:
  Vwater (Pelectr. )           13.8 m3/h (3 kW) – 8.09 m3/h (2.3 kW)     up to 36%.
  Pelectr. for UKS fan         3.6 kW – 1.5 kW
  Pelectr. for cold water      190 MWh/a – 125 MWh/a
  Pelectr. total               248 MWh/a – 158 MWh/a




Rittal aisle containment                                                                                                              7
Rittal – System solutions




From system to solution:                                Recooling systems for IT cooling
Comprehensively individual                              CRAC systems
However individual your business, you can               Aisle containment
be sure that all Rittal climate control systems
provide a comprehensive expert package:                 High-density cooling
●   Exemplary energy efficiency                         Piping systems
●   Plus special project engineering                    Monitoring
●   Plus permanent innovative strength
●   Plus typical Rittal high-quality production.
                                                        Free Cooling

Rittal never loses sight of a project’s particular
customer requirements. The aim is always the
same: to produce maximum benefits for the
customer.




                                                                                                          04/09 E593




Rittal GmbH & Co. KG Postfach 1662 D-35726 Herborn
Telephone: +49(0)2772 505-0 Telefax: +49(0)2772 505-2319 eMail: info@rittal.de www.rittal.com




                                                                                   Switch to perfection

More Related Content

What's hot

EvergreenCommBrochure
EvergreenCommBrochureEvergreenCommBrochure
EvergreenCommBrochureDavid King
 
Apc cooling solutions
Apc cooling solutionsApc cooling solutions
Apc cooling solutionspeperoca
 
VARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWVARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWRIDDHESH VARIK
 
Design, Installation and Testing of the VRF System
Design, Installation and Testing of the VRF SystemDesign, Installation and Testing of the VRF System
Design, Installation and Testing of the VRF SystemSocheat Veng
 
Data Centre Efficiency
Data Centre EfficiencyData Centre Efficiency
Data Centre Efficiencyemoclew
 
Compresor tornillo 75 a 100 HP
Compresor tornillo 75 a 100 HPCompresor tornillo 75 a 100 HP
Compresor tornillo 75 a 100 HPAlmacenes JJ S.A.
 
TRANE_Sintesis_Brochure
TRANE_Sintesis_BrochureTRANE_Sintesis_Brochure
TRANE_Sintesis_BrochureAngie Wolf
 
3 cf ch-006_hvac_systems
3 cf ch-006_hvac_systems3 cf ch-006_hvac_systems
3 cf ch-006_hvac_systemsbhattbhai
 
Introduction to VRF
Introduction to VRF Introduction to VRF
Introduction to VRF John Chavez
 
Heat Calculator for Chilled and Hot Water Systems
Heat Calculator for Chilled and Hot Water SystemsHeat Calculator for Chilled and Hot Water Systems
Heat Calculator for Chilled and Hot Water SystemsMiller Energy, Inc.
 
Life cycle analysis of hvac desining multi split vrf system
Life cycle analysis of hvac desining multi split vrf systemLife cycle analysis of hvac desining multi split vrf system
Life cycle analysis of hvac desining multi split vrf systemSYED KHURSHID ALAM ARZOO
 
Thermal Heat Pump final
Thermal Heat Pump finalThermal Heat Pump final
Thermal Heat Pump finalDrew Perryman
 
Scroll compressors for propane (R290)
Scroll compressors for propane (R290)Scroll compressors for propane (R290)
Scroll compressors for propane (R290)Venu Kandi
 

What's hot (20)

EvergreenCommBrochure
EvergreenCommBrochureEvergreenCommBrochure
EvergreenCommBrochure
 
Crac systems gb
Crac systems gbCrac systems gb
Crac systems gb
 
Apc cooling solutions
Apc cooling solutionsApc cooling solutions
Apc cooling solutions
 
G y un50_00
G y un50_00G y un50_00
G y un50_00
 
Comparison between vrv vrf brands & suppliers @ uae market-July 2017-by g...
Comparison between vrv vrf brands & suppliers @ uae market-July 2017-by g...Comparison between vrv vrf brands & suppliers @ uae market-July 2017-by g...
Comparison between vrv vrf brands & suppliers @ uae market-July 2017-by g...
 
VARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWVARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOW
 
Design, Installation and Testing of the VRF System
Design, Installation and Testing of the VRF SystemDesign, Installation and Testing of the VRF System
Design, Installation and Testing of the VRF System
 
Data Centre Efficiency
Data Centre EfficiencyData Centre Efficiency
Data Centre Efficiency
 
Compresor tornillo 75 a 100 HP
Compresor tornillo 75 a 100 HPCompresor tornillo 75 a 100 HP
Compresor tornillo 75 a 100 HP
 
My message to the 5th dc dialogue 2021 in dubai & true market opportunity...
My message to the 5th dc dialogue 2021 in dubai & true market opportunity...My message to the 5th dc dialogue 2021 in dubai & true market opportunity...
My message to the 5th dc dialogue 2021 in dubai & true market opportunity...
 
TRANE_Sintesis_Brochure
TRANE_Sintesis_BrochureTRANE_Sintesis_Brochure
TRANE_Sintesis_Brochure
 
CHILLER PLANT MANAGER
CHILLER PLANT MANAGERCHILLER PLANT MANAGER
CHILLER PLANT MANAGER
 
3 cf ch-006_hvac_systems
3 cf ch-006_hvac_systems3 cf ch-006_hvac_systems
3 cf ch-006_hvac_systems
 
Introduction to VRF
Introduction to VRF Introduction to VRF
Introduction to VRF
 
Heat Calculator for Chilled and Hot Water Systems
Heat Calculator for Chilled and Hot Water SystemsHeat Calculator for Chilled and Hot Water Systems
Heat Calculator for Chilled and Hot Water Systems
 
Data Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid CoolingData Center Cooling Study on Liquid Cooling
Data Center Cooling Study on Liquid Cooling
 
Life cycle analysis of hvac desining multi split vrf system
Life cycle analysis of hvac desining multi split vrf systemLife cycle analysis of hvac desining multi split vrf system
Life cycle analysis of hvac desining multi split vrf system
 
Thermal Heat Pump final
Thermal Heat Pump finalThermal Heat Pump final
Thermal Heat Pump final
 
Product manual hps
Product manual hpsProduct manual hps
Product manual hps
 
Scroll compressors for propane (R290)
Scroll compressors for propane (R290)Scroll compressors for propane (R290)
Scroll compressors for propane (R290)
 

Similar to Rittal aisle containment increases cooling efficiency

Sb in rack-ver.1.0_en
Sb in rack-ver.1.0_enSb in rack-ver.1.0_en
Sb in rack-ver.1.0_enYury Naumov
 
Ian wilson f mayer refrig evolution 4 4-16
Ian wilson f mayer refrig evolution 4 4-16Ian wilson f mayer refrig evolution 4 4-16
Ian wilson f mayer refrig evolution 4 4-16ARAaus
 
Ian wilson f mayer refrig evolution 4 4-16
Ian wilson f mayer refrig evolution 4 4-16Ian wilson f mayer refrig evolution 4 4-16
Ian wilson f mayer refrig evolution 4 4-16ARAaus
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationGreg Stover
 
Ppt4 exp leeds - alan real and jon summers ( university of leeds ) experien...
Ppt4   exp leeds - alan real and jon summers ( university of leeds ) experien...Ppt4   exp leeds - alan real and jon summers ( university of leeds ) experien...
Ppt4 exp leeds - alan real and jon summers ( university of leeds ) experien...JISC's Green ICT Programme
 
Critical design elements for high power density data centers
Critical design elements for high power density data centersCritical design elements for high power density data centers
Critical design elements for high power density data centersInternap
 
Integrating Radiant Cooling Systems for Energy Efficiency
Integrating Radiant Cooling Systems for Energy EfficiencyIntegrating Radiant Cooling Systems for Energy Efficiency
Integrating Radiant Cooling Systems for Energy EfficiencyCenter for Sustainable Energy
 
Sb ls scroll-uc-ii_ver.1.0_en
Sb ls scroll-uc-ii_ver.1.0_enSb ls scroll-uc-ii_ver.1.0_en
Sb ls scroll-uc-ii_ver.1.0_enYury Naumov
 
Eta lyra series reflow oven
Eta lyra series reflow ovenEta lyra series reflow oven
Eta lyra series reflow ovenCarrie Zhang
 
Underfloor heating
Underfloor heatingUnderfloor heating
Underfloor heatingTAQAMISR
 
Virtis bench top k series (brochure)
Virtis   bench top k series (brochure)Virtis   bench top k series (brochure)
Virtis bench top k series (brochure)amteclab
 
High Efficiency Solutions for process cooling
High Efficiency Solutions for process coolingHigh Efficiency Solutions for process cooling
High Efficiency Solutions for process coolingCAREL Industries S.p.A
 
Eta draco series reflow oven
Eta draco series reflow ovenEta draco series reflow oven
Eta draco series reflow ovenMark Tung
 
Eta draco series reflow oven
Eta draco series reflow ovenEta draco series reflow oven
Eta draco series reflow ovenLucy Xiao
 

Similar to Rittal aisle containment increases cooling efficiency (20)

Sb in rack-ver.1.0_en
Sb in rack-ver.1.0_enSb in rack-ver.1.0_en
Sb in rack-ver.1.0_en
 
Ian wilson f mayer refrig evolution 4 4-16
Ian wilson f mayer refrig evolution 4 4-16Ian wilson f mayer refrig evolution 4 4-16
Ian wilson f mayer refrig evolution 4 4-16
 
Ian wilson f mayer refrig evolution 4 4-16
Ian wilson f mayer refrig evolution 4 4-16Ian wilson f mayer refrig evolution 4 4-16
Ian wilson f mayer refrig evolution 4 4-16
 
Data Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure OptimizationData Center Cooling, Critical Facility and Infrastructure Optimization
Data Center Cooling, Critical Facility and Infrastructure Optimization
 
Ppt4 exp leeds - alan real and jon summers ( university of leeds ) experien...
Ppt4   exp leeds - alan real and jon summers ( university of leeds ) experien...Ppt4   exp leeds - alan real and jon summers ( university of leeds ) experien...
Ppt4 exp leeds - alan real and jon summers ( university of leeds ) experien...
 
Critical design elements for high power density data centers
Critical design elements for high power density data centersCritical design elements for high power density data centers
Critical design elements for high power density data centers
 
Integrating Radiant Cooling Systems for Energy Efficiency
Integrating Radiant Cooling Systems for Energy EfficiencyIntegrating Radiant Cooling Systems for Energy Efficiency
Integrating Radiant Cooling Systems for Energy Efficiency
 
Energy Efficiency in Offices
Energy Efficiency in OfficesEnergy Efficiency in Offices
Energy Efficiency in Offices
 
Sb ls scroll-uc-ii_ver.1.0_en
Sb ls scroll-uc-ii_ver.1.0_enSb ls scroll-uc-ii_ver.1.0_en
Sb ls scroll-uc-ii_ver.1.0_en
 
Eta lyra series reflow oven
Eta lyra series reflow ovenEta lyra series reflow oven
Eta lyra series reflow oven
 
Underfloor heating
Underfloor heatingUnderfloor heating
Underfloor heating
 
LogiCool Inrak Data Centre Cooling 10-60kW
LogiCool Inrak Data Centre Cooling 10-60kWLogiCool Inrak Data Centre Cooling 10-60kW
LogiCool Inrak Data Centre Cooling 10-60kW
 
Virtis bench top k series (brochure)
Virtis   bench top k series (brochure)Virtis   bench top k series (brochure)
Virtis bench top k series (brochure)
 
10 fn s35
10 fn s3510 fn s35
10 fn s35
 
10 fn s35
10 fn s3510 fn s35
10 fn s35
 
High Efficiency Solutions for process cooling
High Efficiency Solutions for process coolingHigh Efficiency Solutions for process cooling
High Efficiency Solutions for process cooling
 
Kazakistan references
Kazakistan referencesKazakistan references
Kazakistan references
 
Kazakistan references
Kazakistan references   Kazakistan references
Kazakistan references
 
Eta draco series reflow oven
Eta draco series reflow ovenEta draco series reflow oven
Eta draco series reflow oven
 
Eta draco series reflow oven
Eta draco series reflow ovenEta draco series reflow oven
Eta draco series reflow oven
 

More from erdinc klima

Tlc temperature-limit-controller
Tlc temperature-limit-controllerTlc temperature-limit-controller
Tlc temperature-limit-controllererdinc klima
 
T ex universal-controller
T ex universal-controllerT ex universal-controller
T ex universal-controllererdinc klima
 
Tcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloruTcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloruerdinc klima
 
Tcx 12062-universal-controller
Tcx 12062-universal-controllerTcx 12062-universal-controller
Tcx 12062-universal-controllererdinc klima
 
Tcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controllerTcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controllererdinc klima
 
Tci universal-controller
Tci universal-controllerTci universal-controller
Tci universal-controllererdinc klima
 
M6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controllerM6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controllererdinc klima
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controllererdinc klima
 
Ec 300-energy-controller
Ec 300-energy-controllerEc 300-energy-controller
Ec 300-energy-controllererdinc klima
 
Tcy3 universa-controller
Tcy3 universa-controllerTcy3 universa-controller
Tcy3 universa-controllererdinc klima
 
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalarKontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalarerdinc klima
 
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisiKontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisierdinc klima
 
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisiKontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisiKontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisiKontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisierdinc klima
 
Duyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostatDuyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostaterdinc klima
 
Duyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensorDuyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensorerdinc klima
 
Duyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorlerDuyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorlererdinc klima
 

More from erdinc klima (20)

Tlc temperature-limit-controller
Tlc temperature-limit-controllerTlc temperature-limit-controller
Tlc temperature-limit-controller
 
T ex universal-controller
T ex universal-controllerT ex universal-controller
T ex universal-controller
 
Tcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloruTcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloru
 
Tcx 12062-universal-controller
Tcx 12062-universal-controllerTcx 12062-universal-controller
Tcx 12062-universal-controller
 
Tcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controllerTcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controller
 
Tci universal-controller
Tci universal-controllerTci universal-controller
Tci universal-controller
 
M6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controllerM6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controller
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controller
 
Ec 300-energy-controller
Ec 300-energy-controllerEc 300-energy-controller
Ec 300-energy-controller
 
Tcy3 universa-controller
Tcy3 universa-controllerTcy3 universa-controller
Tcy3 universa-controller
 
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalarKontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
 
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisiKontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
 
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisiKontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
 
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisiKontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
 
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisiKontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
 
Duyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostatDuyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostat
 
Duyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensorDuyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensor
 
Duyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorlerDuyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorler
 

Recently uploaded

Marketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent ChirchirMarketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent Chirchirictsugar
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCRashishs7044
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Seta Wicaksana
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy Verified Accounts
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?Olivia Kresic
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africaictsugar
 
Market Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMarket Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMintel Group
 
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdfKhaled Al Awadi
 
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu MenzaYouth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menzaictsugar
 
2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis UsageNeil Kimberley
 
Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Kirill Klimov
 
Future Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted VersionFuture Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted VersionMintel Group
 
Innovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfInnovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfrichard876048
 
India Consumer 2024 Redacted Sample Report
India Consumer 2024 Redacted Sample ReportIndia Consumer 2024 Redacted Sample Report
India Consumer 2024 Redacted Sample ReportMintel Group
 
Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737Riya Pathan
 
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...ShrutiBose4
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Servicecallgirls2057
 

Recently uploaded (20)

Marketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent ChirchirMarketplace and Quality Assurance Presentation - Vincent Chirchir
Marketplace and Quality Assurance Presentation - Vincent Chirchir
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail Accounts
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?
 
Kenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby AfricaKenya’s Coconut Value Chain by Gatsby Africa
Kenya’s Coconut Value Chain by Gatsby Africa
 
Market Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMarket Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 Edition
 
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
 
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu MenzaYouth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
Youth Involvement in an Innovative Coconut Value Chain by Mwalimu Menza
 
2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage
 
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
No-1 Call Girls In Goa 93193 VIP 73153 Escort service In North Goa Panaji, Ca...
 
Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024
 
Call Us ➥9319373153▻Call Girls In North Goa
Call Us ➥9319373153▻Call Girls In North GoaCall Us ➥9319373153▻Call Girls In North Goa
Call Us ➥9319373153▻Call Girls In North Goa
 
Future Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted VersionFuture Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted Version
 
Innovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfInnovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdf
 
India Consumer 2024 Redacted Sample Report
India Consumer 2024 Redacted Sample ReportIndia Consumer 2024 Redacted Sample Report
India Consumer 2024 Redacted Sample Report
 
Corporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information TechnologyCorporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information Technology
 
Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737
 
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
Ms Motilal Padampat Sugar Mills vs. State of Uttar Pradesh & Ors. - A Milesto...
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
 

Rittal aisle containment increases cooling efficiency

  • 1. Rittal – Aisle containment Simple and efficient Efficient cooling saves money
  • 2. High-efficiency climate control concepts from Rittal Instead of flooding the room with cold air, this Rittal concept routes the cold air directly to the equipment via the cold aisle. Cold air is directed across the whole height of the enclosure ensuring that there are no hot-spots and the hot air is exhausted out of the system. Due to the cold aisle being contained there is no chance of the hot exhaust air mixing with the cold inlet air, therefore there is an increase in system efficiency. The outstanding energy efficiency of the Rittal cold aisle concept has a simple explanation: 1. Intake air (cold) and waste air (hot) are unable to mix. 2. The system can be operated with a much higher aisle temperature level (reduction in hot-spots). 3. As a result of the increased temperature difference be- tween intake air and waste air, climate control units are operated at an optimum thermal difference (increased ΔT). Standard market concepts Rittal Hot air extraction using Rittal aisle containment (cold aisle) Rittal aisle containment (cold aisle) a duct system with raised floor (CRAC) without raised floor (Inline Cooling) ● Complex and costly duct system. ● Use of standard inexpensive air circu- ● Direct connection of the liquid cooling ● Larger surface area and height lation cooling units. Positioned outside packages to an external cold water requirements. the server area. supply. ● Limitation of the raised floor height. ● Even with low room heights, maximisation ● Simple laying of pipework in the rack ● No uniform cooling air supply to the of the raised floor height for cooling air base/plinth. room area. supply without flow losses. ● Homogeneous distribution of cooling air ● Cable management is more difficult. ● Undisturbed and uniform air flow distri- in the cold aisle guarantees a high level ● Limited rack positioning due to the air bution of cooling air in the cold aisle of efficiency. duct connection. guarantees high-efficiency. ● Favourable working conditions in the ● Extremely high presure loss on the air ● Favourable working conditions in the cold cold aisle due to low temperature, side, leading to increased energy aisle due to low temperature, flow and flow and noise load conditions. consumption of the fans. noise load conditions. ● Hardware racks not connected to the ● Hardware racks not connected to the containment system do not impair enclosure do not impair the cooling cooling efficiency via the cold aisle. efficiency of the cold aisle. ● Room heights play only a minimal role. 2 Rittal aisle containment
  • 3. Three systems with a high level of efficiency Nowadays, servers are increasingly positioned in rooms that were not Rittal aisle containment (hot aisle) designed as data centres. As a result of hot air cushions below the without raised floor ceiling, in particular, hot-spots in hot-spot racks are not dissipated. In ● Simple assembly using the existing order to consistently address this problem, Rittal has developed three components of Rittal aisle containment. systems for aisle containment. In the two variants of cold aisle (CRAC ● Direct connection of the liquid cooling and Inline Cooling), we are able to provide a solution that is independ- packages (LCP Inline) to an external cold ent of whether there is a false floor available or not. Both provide cold water supply. ● Simple laying of pipework in the rack air to the aisle, where it is then absorbed by the server inlets. In the base/plinth. third system, the hot air is extracted from the hot aisle, via the LCP ● Suitable for use with high heat losses. Inline, without influencing the ambient temperatures, and then selec- ● Room-neutral dissipation of the heat loss. tively re-emitted as cold air in the proximity of the equipment. The outcome is the same with all three systems: Increased reliability, greater cooling capacity and simultaneously improved energy effi- ciency. Rittal aisle containment 3
  • 4. Rittal cold aisle containment with CRAC system and sensors 5 7 5 5 5 6 1 5 5 4 5 2 5 1 Rittal aisle containment 3 2 CRAC systems 3 Water/water heat exchangers 4 IT chiller 5 Wireless temperature sensors 6 Administration 7 Wireless humidity sensors By using Rittal aisle containment, In conjunction with the LCP Inline, aisle climate control of the room (in con- containment is a further option for the junction with the Rittal CRAC system) efficient dissipation of high heat loads may be optimised in terms of energy from server racks. efficiency and cooling output. ● A raised floor is not required for ● High energy efficiency climate control ● Increased cooling output per server ● For increased heat loads per server rack rack ● Easily retro-fitted to existing systems ● Redundancies easily achieved ● Protection of your existing infra- ● Direct supply of cold air to your structure server and network components ● The MTBF of existing systems can ● Particularly suitable for use with be significantly extended low room heights 4 Rittal aisle containment
  • 5. Aisle containment with LCP Inline and sensors 5 7 5 5 5 6 2 1 5 4 5 1 Rittal aisle containment 3 2 LCP Inline 3 Water/water heat exchangers 4 IT chiller 5 Wireless temperature sensors 6 Administration 7 Wireless humidity sensors Innovative monitoring and control for even greater efficiency With Rittal wireless sensors, all rele- vant climate conditions may be meas- In order to further enhance efficiency with the cooling of data ured without any cabling whatsoever. centres, the thermal parameters must be permanently moni- tored and adjusted for optimum performance. This ensures that the optimum para- meters for energy-efficient climate con- Rittal wireless sensor technology is available for the fast log- trol are available at all times. ging and monitoring of these parameters. This technology supports simple, fast installation and commissioning at all key points in the data centre. Whether in the raised floor or under the ceiling, all measurements are wireless and can be processed directly using a controller. Rittal aisle containment 5
  • 6. Maximise potential savings! Know-how safeguards efficiency The potential savings that can be made with the operating Cooling output costs for a data centre are shown in the diagram opposite. Despite considerable savings of energy and CO2, the oper- Energy/electricity ating temperature of the servers always remains within the optimum range. CO2 We would like to prove this with some figures from our best practice example, which demonstrates the benefits of coor- dinated, intelligent regulation and control of all climate con- trol components. Without aisle containment With aisle containment Aisle containment with integrated control Rittal wireless sensor network 7 12 13 14 15 11 3 LAN 8 4 1 16 9 5 0˚ PLC X2 10 17 18 6 0˚ 2 Wireless I/O unit DK 7320.240 (as basic unit) 1 Processing Unit II (PU II), the 5 RTT I/O unit 9 Climate unit, 12 Alternative external aerial nerve centre of the CMC-TC Up to 10 climate control devices Fan Control System FCS DK 7320.241 monitoring system with Comfort controller may Fans are controlled via tempe- 13 Wireless measurement system The PU II is the coordinator be connected via one unit in rature sensors. Airflow monitors (must be available for commis- between the sensor unit and the master/slave mode. report any contamination of the sioning) network. It is configured via the 6 Liquid Cooling Package LCP filter mat, for example. The fan DK 7320.242 integral web server. The professional LCP water speed is controlled and moni- tored via the FCS. 14 Wireless humidity sensor 2 Server shutdown function cooling system for data centres DK 7320.515 may be linked directly to the 10 Universal I/O unit 3 Electronic systems with moni- Processing Unit II. This measurement and alarm 15 Wireless access sensor toring of temperatures, fans and module indicates motion, vibra- DK 7320.535 7 I/O wireless unit DC voltages. Up to 16 sensors may be wire- tions, doors being opened, tem- 16 Wireless temperature sensor 4 Active Power System Module lessly incorporated into the peratures exceeded, and much DK 7320.505 PSM, Power Control Unit PCU CMC-TC system via this unit. more besides. The sensors may be selected for the application. 17 IP protective cover (optional) The sockets may be activated 8 Access unit DK 7320.245 directly by the Processing Unit II The doors of buildings, rooms 11 Video network IP camera (max. 4 x 4 x 8 sockets), com- 18 Wireless digital input and enclosures may be moni- DK 7320.585 bined with an ammeter. tored, activated and opened via the network. 6 Rittal aisle containment
  • 7. Easy with Rittal Step 1: Raise the water inlet temperature –26% Qtotal (Qsens.) 80 kW (80 kW) – 79.9 kW (79.9 kW) The temperature in the cold aisle is precisely definable Tair; hot (rel. humidity) 26°C (45%) – 31°C (32%) and identical throughout, thanks to optimisation of the Tair; cold (rel. humidity) 15°C (89%) – 19.8°C (62.2%) temperature distribution. Twater; inlet 10°C – 15°C ● Increasing the air intake temperature also increases Twater; return 15°C – 20°C the waste air temperature. Pelectr. for cold water 190 MWh/a – 139 MWh/a ● Increasing the air intake temperature improves the performance of free cooling. Possible energy savings in cold water generation: up to 26%. Step 2: Reduce the volumetric airflow –60% Qtotal (Qsens.) 79.9 kW (79.9 kW) – 88.4 kW (88.4 kW) With a constant flow rate, the cooling output is increased Tair; hot (rel. humidity) 31°C (32%) – 36°C (25%) by raising the ΔT at the air end. Tair; cold (rel. humidity) 19.8°C (62.2%) – 19.7°C (64.6%) ● By reducing the volumetric airflow, the waste air Vair (ext. press.) 22000 m3/h (80 Pa) – 17000 m3/h (20 Pa) temperature and return temperature are increased. Pelectr. for UKS fan 3.6 kW – 1.5 kW Possible energy savings in the power consumption of the fans: up to 60%. Step 3: Reduce the throughput –15% Qtotal (Qsens.) 88.4 kW (88.4 kW) – 80 kW (80 kW) The pump output can be reduced due to a smaller through- Tair; hot (rel. humidity) 36°C (25%) – 36°C (25%) put required for the same cooling output, and the return Tair; cold (rel. humidity) 19.7°C (64.6%) – 21.3°C (54.2%) temperature is increased. Twater; inlet 15°C – 15°C Potential saving in the power consumption of the pump: Twater; return 20.6°C – 23.5°C up to 14%. Vwater (Pelectr. ) 13.6 m3/h (3 kW) – 8.1 m3/h (2.3 kW) Potential saving in cold water generation: Pelectr. for cold water 143 MWh/a – 125 MWh/a up to 17%. Summary –36% Qtotal (Qsens.) 80 kW (80 kW) – 80 kW (80 kW) Energy saving: Tair; hot (rel. humidity) 26°C (45%) – 36°C (25%) ● Fans: 19 MWh/a Tair; cold (rel. humidity) 15°C (89%) – 21.3°C (54.2%) ● Pumps: 6 MWh/a Vair (ext. press.) 22000 m³/h (80 Pa) – 17000 m³/h (20 Pa) ● Cold water production: 65 MWh/a Twater; inlet 10°C – 15°C ● Overall: 90 MWh/a Twater; return 15°C – 23.5°C Cost saving with Rittal aisle containment: Vwater (Pelectr. ) 13.8 m3/h (3 kW) – 8.09 m3/h (2.3 kW) up to 36%. Pelectr. for UKS fan 3.6 kW – 1.5 kW Pelectr. for cold water 190 MWh/a – 125 MWh/a Pelectr. total 248 MWh/a – 158 MWh/a Rittal aisle containment 7
  • 8. Rittal – System solutions From system to solution: Recooling systems for IT cooling Comprehensively individual CRAC systems However individual your business, you can Aisle containment be sure that all Rittal climate control systems provide a comprehensive expert package: High-density cooling ● Exemplary energy efficiency Piping systems ● Plus special project engineering Monitoring ● Plus permanent innovative strength ● Plus typical Rittal high-quality production. Free Cooling Rittal never loses sight of a project’s particular customer requirements. The aim is always the same: to produce maximum benefits for the customer. 04/09 E593 Rittal GmbH & Co. KG Postfach 1662 D-35726 Herborn Telephone: +49(0)2772 505-0 Telefax: +49(0)2772 505-2319 eMail: info@rittal.de www.rittal.com Switch to perfection