Energy Modeling of Dedicated
Outdoor Air Systems for a Small
Commercial Pilot Project
BUILDING ENERGY SIMULATION FORUM, AUGUST 17, 2016
AMY MONTGOMERY, MASc, P.Eng.
 Pilot project: energy efficient
replacement options for end-of-life
packaged rooftop units on small
commercial buildings
 Dedicated Outdoor Air Systems (DOAS) with
Heat Recovery Ventilation (HRV)
 Energy modeling as a tool to quantify
savings
 Share progress and lessons learned
Overview
Pilot Project Overview
 Target Building Sector:
 Small commercial (< 25,000 ft2)
 Includes small office, retail, schools, restaurants, small
assembly
 Makes up approx. half of the commercial building floor
area in the Pacific Northwest.
 Smaller HVAC systems; typically not engineered.
Pilot Project Overview
Ventilation +
Heating (or Cooling)
Outdoor
Air
Return Air
Exhaust
Air
Packaged Rooftop Unit
Controls space
temperature
Ventilation +
Heating (or Cooling)
Pilot Project Overview
Provides fresh air
for occupants
Pilot Project Overview
Dedicated Outdoor Air System
Outdoor Air
Ventilation Exhaust
Air
Heat Recovery
Exhaust Air
Heat Pump
Zone-Level
Heating (or
Cooling)
Pilot Project Overview
 Dedicated Outdoor Air System (DOAS) with Heat
Recovery in Small Commercial Building Sector
 Successful DOAS conversion depends on several
factors, including:
› Reduction in ventilation air volumes; demand controlled
ventilation (DCV)
› Very low ventilation fan power (0.5 Watts/cfm or less)
› Very high ventilation heat/energy recovery
efficiency
 Minimal uptake due to lack of a cost-effective high
efficiency ventilation solution
Pilot Project Overview
 Early pilot work funded by the Northwest Energy
Efficiency Alliance (NEEA)
 New high efficiency Heat Recovery Ventilation (HRV) unit
 Vertical mounting for existing RTU ductwork
 1000 cfm max flow
 Greater than 80% sensible heat recovery efficiency
Pilot Project Overview
 PART 1: Establish Baseline Conditions
 PART 2: Calibrated Baseline Energy Model
 PART 3: DOAS Conversion
 PART 4: Establish Post-Conversion Conditions
 PART 5: Calibrated Post-Conversion Energy Model
Savings
Pilot Project Overview
 PART 1: Establish Baseline Conditions
 Site Review
 Baseline Air Leakage Testing
 Installation of Monitoring Equipment
Pilot Project Overview
 PART 2: Calibrated Baseline Energy Model
 Actual Operating Conditions (occupancy, schedules,
heating and cooling setpoints, etc.)
 Baseline Air Tightness
 Monitoring Data
 Historic Utility Data
Pilot Project Overview
 PART 3: DOAS Conversion
 New HRV unit
 Zone-level heating and cooling
 Local design teams and contractors
Pilot Project Overview
 PART 4: Establish Post-Conversion Conditions
 Site Review
 Post-Conversion Air Leakage Testing
 Additional Monitoring Equipment
Pilot Project Overview
 PART 5: Calibrated Post-Conversion Energy Model
 Maintain Baseline Operating Conditions
 Post-Conversion Air Tightness
 Monitoring Data
 1 Year Post Conversion Utility Data
Pilot Project Overview
 Project timeline: Year 1
Recruiting Pilot Project Participants
Prototype Modeling
PART 1: Establish Baseline Conditions
PART 2: Calibrated Baseline Energy Model
PART 3: HRV Conversion
PART 4: Establish Post-
Conversion Conditions
Pilot Project Overview
 Project timeline: Year 2
PART 1: Baseline
PART 2: Baseline Model
PART 3: HRV Conversion
PART 4: Establish Post-Conversion Conditions
PART 5: Calibrated Post-Conversion Energy Model
Prototype Modeling
Prototype Modeling
 Perform energy modeling of small commercial building
prototypes to demonstrate savings potential
 Prototype buildings
› Office
› Retail
› School
› Restaurant
 Climate zones
› CZ4C Portland OR
› CZ5B Boise ID
› CZ6B Helena MT
4C 5B 6B
Prototype Modeling
 A few notes on prototypes:
 Geometry and majority of operating inputs from DOE
Commercial Prototype Building Models
Prototype Modeling
 A few notes on prototypes:
 How to reflect existing small commercial building stock?
› DOE Pre-1980s Building enclosure inputs (4C/5B/6B)
» R-5/R-6/R-7 walls
» R-11/R-14/R-17 roof
» U-0.55 windows
› Downgraded baseline equipment efficiencies by 10%
› No motorized damper controls on baseline rooftop units
» Fixed damper position at 20%
Prototype Modeling
 Office Building
 5,500 ft2
 Defined as perimeter (70%) and core (30%) areas
Perimeter
Core
Prototype Modeling
 Rooftop Unit (RTU) with Gas-Fired Heating and DX Cooling
Office Baseline
Prototype Modeling
 Dedicated Outdoor Air System (DOAS) with Heat Recovery
Ventilation (HRV) and Zone-Level Heat Pumps
Office Conversion
Prototype Modeling
 Office Prototype Results
Annual Energy Consumption Profile Annual Energy Consumption Profile
Baseline Conversion
Whole building modeled EUI of 55
kBtu/ft2.
Whole building modeled EUI of 33
kBtu/ft2. Results in 22 kBtu/ft2 energy
savings over the baseline model.
Prototype Modeling
 Office Prototype Results
Baseline Conversion
HVAC systems represent 57% or
32 kBtu/ft2 of the overall energy use.
HVAC systems represent 29% or
10 kBtu/ft2 of the overall energy use.
Annual Energy Consumption Profile Annual Energy Consumption Profile
Prototype Modeling
 Office Prototype Results
Climate
Zone
Baseline EUI
(kBtu/ft2)
Conversion EUI
(kBtu/ft2)
Savings
(kBtu/ft2)
CZ4C
Portland OR 55 33 22
CZ5B
Boise ID 61 34 27
CZ6B
Helena MT 69 39 30
Prototype Modeling
 Sit-Down Restaurant
 5,500 ft2 floor area
 Includes dining area (73%) and kitchen (27%)
Kitchen
Dining
Prototype Modeling
 Rooftop Unit (RTU) with Gas-Fired Heating and DX Cooling;
Kitchen Exhaust with 100% Outdoor Air Make-up
Sit-Down Restaurant Baseline
Prototype Modeling
 Dedicated Outdoor Air System (DOAS) with Heat Recovery
Ventilation (HRV) and Zone-Level Heat Pumps; Kitchen Exhaust
Heat Recovery
Sit-Down Restaurant Conversion
Prototype Modeling
 Sit-Down Restaurant Prototype Results
Annual Energy Consumption Profile Annual Energy Consumption Profile
Baseline Conversion
Whole building modeled EUI of
435 kBtu/ft2.
Whole building modeled EUI of 307
kBtu/ft2. Results in 128 kBtu/ft2 energy
savings over the baseline model.
Prototype Modeling
 Sit-Down Restaurant Prototype Results
Baseline Conversion
HVAC systems represent 39% or
169 kBtu/ft2 of the overall energy use.
HVAC systems represent 13% or
41 kBtu/ft2 of the overall energy use.
Annual Energy Consumption Profile Annual Energy Consumption Profile
Prototype Modeling
 Sit-Down Restaurant Prototype Results
Climate
Zone
Baseline EUI
(kBtu/ft2)
Conversion EUI
(kBtu/ft2)
Savings
(kBtu/ft2)
CZ4C
Portland OR 435 307 128
CZ5B
Boise ID 469 321 148
CZ6B
Helena MT 523 342 181
Prototype Modeling
 Retail
 3,750 ft2
 End unit of strip mall
 100% retail space
Retail
Prototype Modeling
 Rooftop Unit (RTU) with Gas-Fired Heating and DX Cooling
Retail Baseline
Prototype Modeling
 Dedicated Outdoor Air System (DOAS) with Heat Recovery
Ventilation (HRV) and Zone-Level Heat Pumps
Retail Conversion
Prototype Modeling
 Retail Prototype Results
Annual Energy Consumption Profile Annual Energy Consumption Profile
Baseline Conversion
Whole building modeled EUI of 71
kBtu/ft2.
Whole building modeled EUI of 44
kBtu/ft2. Results in 27 kBtu/ft2 energy
savings over the baseline model.
Prototype Modeling
 Retail Prototype Results
Baseline Conversion
HVAC systems represent 52% or
37 kBtu/ft2 of the overall energy use.
HVAC systems represent 22% or
10 kBtu/ft2 of the overall energy use.
Annual Energy Consumption Profile Annual Energy Consumption Profile
Prototype Modeling
 Retail Prototype Results
Climate
Zone
Baseline EUI
(kBtu/ft2)
Conversion EUI
(kBtu/ft2)
Savings
(kBtu/ft2)
CZ4C
Portland OR 61 41 20
CZ5B
Boise ID 66 43 23
CZ6B
Helena MT 74 46 28
Prototype Modeling
 Primary School
 74,600 ft2
 Includes classrooms (50%), office & amenity (27%), and
circulation and service areas (23%)
Circulation
Classroom
Office &
Amenity
Prototype Modeling
 Gas-Fired Boiler, Rooftop Unit (RTU) with Hydronic Heating
and DX Cooling, and Zone-Level Hydronic Re-Heating
Primary School Baseline
Prototype Modeling
 Dedicated Outdoor Air System (DOAS) with Heat Recovery
Ventilation (HRV) and Zone-Level Heat Pumps
Primary School Conversion
Prototype Modeling
 Primary School Prototype Results
Annual Energy Consumption Profile Annual Energy Consumption Profile
Baseline Conversion
Whole building modeled EUI of 61
kBtu/ft2.
Whole building modeled EUI of 41
kBtu/ft2. Results in 20 kBtu/ft2 energy
savings over the baseline model.
Prototype Modeling
 Primary School Prototype Results
Baseline Conversion
HVAC systems represent 42% or
26 kBtu/ft2 of the overall energy use.
HVAC systems represent 14% or
6 kBtu/ft2 of the overall energy use.
Annual Energy Consumption Profile Annual Energy Consumption Profile
Prototype Modeling
 Primary School Prototype Results
Climate
Zone
Baseline EUI
(kBtu/ft2)
Conversion EUI
(kBtu/ft2)
Savings
(kBtu/ft2)
CZ4C
Portland OR 61 41 20
CZ5B
Boise ID 66 43 23
CZ6B
Helena MT 74 46 28
Prototype Modeling
 30% to 40% predicted whole building savings for DOAS
conversion
Pilot Projects
Pilot Projects
 10 pilot projects to date
Office #3
Libby MTOffice #6
Seattle WA
Other #1
Darby MT
Office #1
Portland OR
Restaurant #1
Corvallis OR
Office #5
Salem OR
Office #7
McMinnville OR Office #4
Portland OR
Restaurant #2
Portland OR
Office #2
Corvallis OR
Pilot Projects
 Highlight first pilot projects
 Office 1, Portland OR
 Office 2, Corvallis, OR
 Office 3, Libby, MT
 Restaurant 1, Corvallis, OR
 Progress report
 General lessons learned to reconcile energy model and
in-service energy performance
Pilot Projects
Office #1
Portland OR
Pilot Projects
 Office 1
 Existing heritage building
 Second floor of a 2 storey
building
 Private offices
 Intermittent occupancy in
meeting and conference
rooms
 Monday through Friday
day time operation
Pilot Project
Pilot Project
 Office 1
 Baseline
 9 RTUs, total 35 tons cooling,
650,000 Btu/h heating
 Conversion
 4 HRVs
 8 zone-level VRF fan coil units,
tons cooling, 215,000 Btu/h
heating
Pilot Project
Pilot Project
 Office 1
 Pre-Conversion Air Leakage Testing
 Air Leakage Test Result: 0.616 cfm/ft2 at 75 Pa
› Air leakage noted at operable windows, HVAC dampers, and
mechanical chases between floors.
Pilot Project
 Office 1
 Preliminary baseline
modeling results
 EUI 51 kBtu/ft2
Pilot Project
 Office 1
 Post-Conversion Air Leakage Testing
 Air Leakage Test Result: 0.506 cfm/ft2 at 75 Pa
Pilot Project
 Office 1
 Preliminary DOAS
conversion modeling
results
 EUI 30 kBtu/ft2
 ~ 40% savings
Pilot Project
 Office 1
 Preliminary Monitoring Data
Outdoor Air
Temperature
Heat Pump
Energy
(Cooling Mode)
Pilot Project
 Office 1
 Preliminary Monitoring Data
Outdoor Air
Temperature
VRF Fan Coil Units
HRV Fans
Pilot Project
 Office 1
 Preliminary Monitoring Data
Outdoor Air
Temperature
Space
Temperatures
???
???
Pilot Project
 Office 1
 What’s next?
 Fine tuning DOAS conversion
 Collect more utility data and
monitoring data
 Calibrate DOAS conversion model
 General “lessons learned” for
reconciling metered and modeled
energy performance:
 Commissioning matters!
 Expect and mitigate anomalies in
monitoring data
Pilot Projects
Office #2
Corvallis OR
Pilot Projects
 Office 2
 Single storey office
building
 Private offices, conference
room, storage & library
 Monday through Friday
day time operation
 DOAS conversion for 2
out of 5 zones
Pilot Projects
Pilot Project
 Office 2
 Baseline
 5 RTUs, total 20 tons cooling,
227,000 Btu/h heating
 Conversion
 3 RTUs remain, total 14 tons
cooling, 152,000 Btu/h heating
 1 HRV
 2 zone-level multi-split indoor
units and 1 outdoor unit, 4
tons cooling, 54,000 Btu/h
heating
Pilot Project
 Office 2
 Pre-Conversion Air Leakage Testing
 Air Leakage Test Result: 0.295 cfm/ft2 at 75 Pa
› Air leakage noted at office entry doors, operable windows,
exhaust fans with gravity dampers (under positive pressure).
Pilot Projects
 Office 2
 Preliminary baseline
modeling results
 EUI 60 kBtu/ft2
Pilot Projects
 Office 2
 DOAS conversion in spring/summer 2016
Pilot Project
 Office 2
 Post-Conversion Air Leakage Testing
 Air Leakage Test Result: 0.266 cfm/ft2 at 75 Pa
Pilot Projects
 Office 2
 Preliminary DOAS
conversion modeling
results
 EUI 50 kBtu/ft2
Pilot Projects
 Office 2
 Preliminary Monitoring Data
24 hour period
showing time averaged
difference between
post-conversion CO2
levels and pre-
conversion CO2 levels.
Pilot Project
 Office 2
 What’s next?
 Collect more utility data and
monitoring data
 Calibrate DOAS conversion model
 General “lessons learned” for
using energy modeling as a tool
to evaluate performance:
 Modeling evaluates energy
consumption; don’t forget the
non-energy benefits.
Pilot Projects
Office #3
Libby MT
Pilot Projects
 Office 3
 Single storey office with
attached garage + shop
area
 Monday through Friday
day time schedule
Pilot Projects
Pilot Project
 Office 3
 Baseline
 1 RTU, total 7 tons cooling,
76,000 Btu/h heating
 Hydronic heating (electric)
 Conversion
 1 HRV
 9 zone-level multi-split indoor
units and 2 outdoor units,
4 tons cooling, 54,000 Btu/h
heating
Pilot Projects
Pilot Project
 Office 3
 Pre-Conversion Air Leakage Testing
 Air Leakage Test Result: 0.746 cfm/ft2 at 75 Pa
› Air leakage noted at roof to wall joints in garage, operable
windows and overhead sectional doors in garage, ductwork.
Pilot Projects
 Office 3
 Preliminary baseline
modeling results
 EUI 79 kBtu/ft2
Pilot Projects
 Office 3
 DOAS conversion scheduled for summer 2016
Pilot Projects
 Office 3
 Preliminary DOAS
conversion modeling
results
 EUI 67 kBtu/ft2
Pilot Projects
 Office 3
 Preliminary Monitoring Data Electric boiler energy
consumption
(secondary axis)
IT room heat pump
(primary axis)
RTU???
Pilot Projects
 Office 3
 Preliminary Monitoring Data
Actual electricity consumption
and modeled electricity
consumption per month for
the year 2013.
Pilot Project
 Office 2
 What’s next?
 Install DOAS conversion
 Post-conversion air leakage testing
and monitoring equipment install
 Collect more utility data and
monitoring data
 Calibrate DOAS conversion model
 General “lessons learned” for
reconciling metered and modeled
energy performance :
 Expect and incorporate seasonal and
other building-specific operating
characteristics.
Pilot Projects
Restaurant #1
Corvallis OR
Pilot Projects
 Restaurant 1
 Busy sit-in & take-out restaurant
 Dining area, kitchen, basement
storage
 Operating hours from 9AM to
midnight, daily
Pilot Project
Pilot Project
 Restaurant 1
 Baseline
 Dining area:
› Previously had 1 RTU, 7.5 tons
cooling, 88,000 Btu/h heating
› Currently no ventilation
› Ductless split heat pumps for
heating and cooling
 Conversion
 Dining area:
› Install 1 HRV to reinstate
ventilation at low energy penalty
› Use existing ductless split heat
pumps for heat and cooling
Pilot Project
 Restaurant 1
 Pre-Conversion Air Leakage Testing
 Air Leakage Test Result: 1.634 cfm/ft2 at 75 Pa
› Air leakage noted at existing RTU supply and return registers,
around doorway to basement, exhaust fans.
Pilot Project
 Restaurant 1
 Preliminary baseline
modeling results
 EUI 651 kBtu/ft2
Pilot Project
 Restaurant 1
 Post-Conversion Air Leakage Testing
 Air Leakage Test Result: 1.644 cfm/ft2 at 75 Pa
Pilot Project
 Restaurant 1
 Preliminary Monitoring Data
Interior Air
Temperature
(front and back)
Outdoor Air
Temperature
Pilot Project
 Restaurant 1
 Preliminary Monitoring Data
Interior Air Temperatures ≠
Temperature at HRV Exhaust Inlet
Duct Leakage in
Unconditioned Attic
Pilot Project
 Restaurant 1
 What’s next?
 Collect more utility data and
monitoring data
 Create and calibrate DOAS
conversion model
 General “lessons learned” for
reconciling metered and modeled
energy performance:
 Expect and mitigate system losses.
Summary and Next Steps
Summary and Next Steps
 Summary – progress thus far
Summary and Next Steps
 Project timeline: Year 1
Recruiting Pilot Project Participants
Prototype Modeling
PART 1: Establish Baseline Conditions
PART 2: Calibrated Baseline Energy Model
PART 3: HRV Conversion
PART 4: Establish Post-
Conversion Conditions
Summary and Next Steps
 Summary – some early lessons
learned for connecting modeled
energy performance with in-service
building performance
 Commissioning matters!
 Expect and mitigate anomalies in
monitoring data.
 Expect and incorporate building-
specific and seasonal operational
schedules.
 Expect and mitigate system
losses.
 Also, don’t forget the non-energy
benefits.
Summary and Next Steps
 Project timeline: Year 2
PART 1: Baseline
PART 2: Baseline Model
PART 3: HRV Conversion
PART 4: Establish Post-Conversion Conditions
PART 5: Calibrated Post-Conversion Energy Model
Summary and Next Steps
 PART 1: Establish Baseline Conditions
 PART 2: Calibrated Baseline Energy Model
 PART 3: DOAS Conversion
 PART 4: Establish Post-Conversion Conditions
 PART 5: Calibrated Post-Conversion Energy Model
Reliably
Estimate
and
Validate
Savings
Market Transformation
 rdh.com | buildingsciencelabs.com
RDH Building Engineering Ltd. and Building Science Consulting Inc. have merged. Effective November 1, 2015, we now operate as
one integrated firm. The merger brings two of the leading building science firms in North America together to provide a
combination of cutting-edge research with leading design and implementation capabilities. The result is a unique offering for our
clients–an ability to explore new and innovative ideas based on science and our practical knowledge of what can be built. We are
excited about the possibilities as we launch the new firm.
Discussion + Questions
FOR FURTHER INFORMATION PLEASE VISIT

More Related Content

What's hot

3.17.15 commercial solar_design_training
3.17.15 commercial solar_design_training3.17.15 commercial solar_design_training
3.17.15 commercial solar_design_training
melanie_bissonnette
 
Standard 90.1-2010 Update
Standard 90.1-2010 UpdateStandard 90.1-2010 Update
Standard 90.1-2010 Update
Illinois ASHRAE
 

What's hot (20)

Besf building renewal_021815
Besf building renewal_021815Besf building renewal_021815
Besf building renewal_021815
 
Mechanical Engineering Seminar 2017_3
Mechanical Engineering Seminar 2017_3Mechanical Engineering Seminar 2017_3
Mechanical Engineering Seminar 2017_3
 
Building EQ
Building EQBuilding EQ
Building EQ
 
ASHRAE Standard 100
ASHRAE Standard 100ASHRAE Standard 100
ASHRAE Standard 100
 
Energy Trust New Buildings: Technical Updates for Modelers and Engineers
Energy Trust New Buildings: Technical Updates for Modelers and EngineersEnergy Trust New Buildings: Technical Updates for Modelers and Engineers
Energy Trust New Buildings: Technical Updates for Modelers and Engineers
 
Team IES - 2016 ASHRAE Lowdown Showdown
Team IES - 2016 ASHRAE Lowdown ShowdownTeam IES - 2016 ASHRAE Lowdown Showdown
Team IES - 2016 ASHRAE Lowdown Showdown
 
3.17.15 commercial solar_design_training
3.17.15 commercial solar_design_training3.17.15 commercial solar_design_training
3.17.15 commercial solar_design_training
 
equest ppt
equest pptequest ppt
equest ppt
 
Standard 90.1-2010 Update
Standard 90.1-2010 UpdateStandard 90.1-2010 Update
Standard 90.1-2010 Update
 
Optimizing Existing Rooftop Unit Energy Efficiency
Optimizing Existing Rooftop Unit Energy EfficiencyOptimizing Existing Rooftop Unit Energy Efficiency
Optimizing Existing Rooftop Unit Energy Efficiency
 
Measurement & Verification
Measurement & VerificationMeasurement & Verification
Measurement & Verification
 
2014 energy modeling
2014 energy modeling2014 energy modeling
2014 energy modeling
 
Modelling Natural Ventilation in IES-VE: Case studies & Research Outlook
Modelling Natural Ventilation in IES-VE: Case studies & Research OutlookModelling Natural Ventilation in IES-VE: Case studies & Research Outlook
Modelling Natural Ventilation in IES-VE: Case studies & Research Outlook
 
Building performance analysis system IES VE main features overview
Building performance analysis system IES VE main features overviewBuilding performance analysis system IES VE main features overview
Building performance analysis system IES VE main features overview
 
SESG Seminar Presentation
SESG Seminar PresentationSESG Seminar Presentation
SESG Seminar Presentation
 
Assessing Your Building Energy Costs: Benefits of Energy Modeling to Owners
Assessing Your Building Energy Costs:  Benefits of Energy Modeling to OwnersAssessing Your Building Energy Costs:  Benefits of Energy Modeling to Owners
Assessing Your Building Energy Costs: Benefits of Energy Modeling to Owners
 
Modelling Natural Ventilation in IES-VE: Case studies & Research Outlook
Modelling Natural Ventilation in IES-VE: Case studies & Research OutlookModelling Natural Ventilation in IES-VE: Case studies & Research Outlook
Modelling Natural Ventilation in IES-VE: Case studies & Research Outlook
 
Modeling, It's Not Just For Calendars and Energy
Modeling, It's Not Just For Calendars and EnergyModeling, It's Not Just For Calendars and Energy
Modeling, It's Not Just For Calendars and Energy
 
Energy Modeling with ASHRAE 90.1-2016
Energy Modeling with ASHRAE 90.1-2016Energy Modeling with ASHRAE 90.1-2016
Energy Modeling with ASHRAE 90.1-2016
 
The role of delivered performance june2009
The role of delivered performance june2009The role of delivered performance june2009
The role of delivered performance june2009
 

Viewers also liked

Case Study: Challenges of Insulating Existing Masonry Buildings in the Common...
Case Study: Challenges of Insulating Existing Masonry Buildings in the Common...Case Study: Challenges of Insulating Existing Masonry Buildings in the Common...
Case Study: Challenges of Insulating Existing Masonry Buildings in the Common...
Sustainable Performance Institute
 
Internal Wall Insulation - Valentina marincioni, ktp associate
Internal Wall Insulation - Valentina marincioni, ktp associateInternal Wall Insulation - Valentina marincioni, ktp associate
Internal Wall Insulation - Valentina marincioni, ktp associate
sustainableCoRE
 

Viewers also liked (20)

Stay Ahead of Advancing Energy Codes with the Advanced Buildings New Construc...
Stay Ahead of Advancing Energy Codes with the Advanced Buildings New Construc...Stay Ahead of Advancing Energy Codes with the Advanced Buildings New Construc...
Stay Ahead of Advancing Energy Codes with the Advanced Buildings New Construc...
 
High Performance Design in Oregon, Two Regional Case Studies
High Performance Design in Oregon, Two Regional Case StudiesHigh Performance Design in Oregon, Two Regional Case Studies
High Performance Design in Oregon, Two Regional Case Studies
 
Building enclosure design presentation 1
Building enclosure design presentation 1Building enclosure design presentation 1
Building enclosure design presentation 1
 
Aesthetics in a High-Performing Building How Beauty Blends with Energy Savings
Aesthetics in a High-Performing Building How Beauty Blends with Energy SavingsAesthetics in a High-Performing Building How Beauty Blends with Energy Savings
Aesthetics in a High-Performing Building How Beauty Blends with Energy Savings
 
Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...Energy and comfort modeling for the net zero rocky mountain institute headqua...
Energy and comfort modeling for the net zero rocky mountain institute headqua...
 
Oregon Zoo Elephant Lands
Oregon Zoo Elephant LandsOregon Zoo Elephant Lands
Oregon Zoo Elephant Lands
 
Allies for efficiency training chemeketa final locked
Allies for efficiency training   chemeketa final lockedAllies for efficiency training   chemeketa final locked
Allies for efficiency training chemeketa final locked
 
Efficient and Affordable: Applying the Passive House Standard to Low-income, ...
Efficient and Affordable: Applying the Passive House Standard to Low-income, ...Efficient and Affordable: Applying the Passive House Standard to Low-income, ...
Efficient and Affordable: Applying the Passive House Standard to Low-income, ...
 
A User's Perspective on IES Modeling
A User's Perspective on IES ModelingA User's Perspective on IES Modeling
A User's Perspective on IES Modeling
 
Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian
Calibrated Modeling - How Well Does My Building Perform? by Eveline KillianCalibrated Modeling - How Well Does My Building Perform? by Eveline Killian
Calibrated Modeling - How Well Does My Building Perform? by Eveline Killian
 
Capacity Building and Energy-Economic Modeling
Capacity Building and Energy-Economic ModelingCapacity Building and Energy-Economic Modeling
Capacity Building and Energy-Economic Modeling
 
2015.10 wufi passive-manual-en
2015.10 wufi passive-manual-en2015.10 wufi passive-manual-en
2015.10 wufi passive-manual-en
 
Developing an Open Source Hourly Building Energy Modelling Software Tool
Developing an Open Source Hourly Building Energy Modelling Software ToolDeveloping an Open Source Hourly Building Energy Modelling Software Tool
Developing an Open Source Hourly Building Energy Modelling Software Tool
 
Insulation Technologies and Materials: Technologies, Systems and Tools in the...
Insulation Technologies and Materials: Technologies, Systems and Tools in the...Insulation Technologies and Materials: Technologies, Systems and Tools in the...
Insulation Technologies and Materials: Technologies, Systems and Tools in the...
 
Integrated Energy Presentation
Integrated Energy PresentationIntegrated Energy Presentation
Integrated Energy Presentation
 
Case Study: Challenges of Insulating Existing Masonry Buildings in the Common...
Case Study: Challenges of Insulating Existing Masonry Buildings in the Common...Case Study: Challenges of Insulating Existing Masonry Buildings in the Common...
Case Study: Challenges of Insulating Existing Masonry Buildings in the Common...
 
Energy Modeling 2009 Presentation
Energy Modeling 2009 PresentationEnergy Modeling 2009 Presentation
Energy Modeling 2009 Presentation
 
High Performing Collaboration
High Performing CollaborationHigh Performing Collaboration
High Performing Collaboration
 
Cowhorn Vineyard + Garden Tasting Room
Cowhorn Vineyard + Garden Tasting RoomCowhorn Vineyard + Garden Tasting Room
Cowhorn Vineyard + Garden Tasting Room
 
Internal Wall Insulation - Valentina marincioni, ktp associate
Internal Wall Insulation - Valentina marincioni, ktp associateInternal Wall Insulation - Valentina marincioni, ktp associate
Internal Wall Insulation - Valentina marincioni, ktp associate
 

Similar to Energy Modeling of Dedicated Outdoor Air System, DOAS, for a Small Commercial Pilot Project

Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
RDH Building Science
 
Energy efficiency in buildings
Energy efficiency in buildingsEnergy efficiency in buildings
Energy efficiency in buildings
D.Pawan Kumar
 
Parmenter, Brady, Poster
Parmenter, Brady, PosterParmenter, Brady, Poster
Parmenter, Brady, Poster
Brady Parmenter
 
Carbon Accounting Buildings | Sue Roaf
Carbon Accounting Buildings | Sue Roaf Carbon Accounting Buildings | Sue Roaf
Carbon Accounting Buildings | Sue Roaf
icarb
 
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
Koeppen Halvart
 
Chilled Water Plant Optimization
Chilled Water Plant OptimizationChilled Water Plant Optimization
Chilled Water Plant Optimization
JoePessa
 
Sez presentation-6
Sez presentation-6Sez presentation-6
Sez presentation-6
domsr
 

Similar to Energy Modeling of Dedicated Outdoor Air System, DOAS, for a Small Commercial Pilot Project (20)

Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
Energy and Indoor Air Quality Impacts of DOAS Retrofits in Small Commercial B...
 
Energy efficiency in buildings
Energy efficiency in buildingsEnergy efficiency in buildings
Energy efficiency in buildings
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for Cooling
 
Gard analytics DOE energy modeling
Gard analytics DOE energy modelingGard analytics DOE energy modeling
Gard analytics DOE energy modeling
 
Appa
AppaAppa
Appa
 
Kapileshwari and Robison- Gulf Coast Green 2010
Kapileshwari and Robison- Gulf Coast Green 2010Kapileshwari and Robison- Gulf Coast Green 2010
Kapileshwari and Robison- Gulf Coast Green 2010
 
Commercial Condensing Boiler Optimization
Commercial Condensing Boiler OptimizationCommercial Condensing Boiler Optimization
Commercial Condensing Boiler Optimization
 
Energy modeling 101 (public)
Energy modeling 101 (public)Energy modeling 101 (public)
Energy modeling 101 (public)
 
Unit 1.pptx
Unit 1.pptxUnit 1.pptx
Unit 1.pptx
 
Parmenter, Brady, Poster
Parmenter, Brady, PosterParmenter, Brady, Poster
Parmenter, Brady, Poster
 
Leed Modeling
Leed ModelingLeed Modeling
Leed Modeling
 
VGBC Online Series, Module 5: Các tiêu chí về Năng lượng trong LOTUS NC v3
VGBC Online Series, Module 5: Các tiêu chí về Năng lượng trong LOTUS NC v3VGBC Online Series, Module 5: Các tiêu chí về Năng lượng trong LOTUS NC v3
VGBC Online Series, Module 5: Các tiêu chí về Năng lượng trong LOTUS NC v3
 
Carbon Accounting Buildings | Sue Roaf
Carbon Accounting Buildings | Sue Roaf Carbon Accounting Buildings | Sue Roaf
Carbon Accounting Buildings | Sue Roaf
 
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
 
Chilled Water Plant Optimization
Chilled Water Plant OptimizationChilled Water Plant Optimization
Chilled Water Plant Optimization
 
NZEB Office Building including renewable energy ratio calculation orla coyle
NZEB Office Building including renewable energy ratio calculation  orla coyleNZEB Office Building including renewable energy ratio calculation  orla coyle
NZEB Office Building including renewable energy ratio calculation orla coyle
 
Comparative Analysis of HVAC System Based on Life Cycle Cost Analysis
Comparative Analysis of HVAC System Based on Life Cycle Cost AnalysisComparative Analysis of HVAC System Based on Life Cycle Cost Analysis
Comparative Analysis of HVAC System Based on Life Cycle Cost Analysis
 
EC Fans Efficiency / Upgrade Projects
EC Fans Efficiency / Upgrade ProjectsEC Fans Efficiency / Upgrade Projects
EC Fans Efficiency / Upgrade Projects
 
5 Steps to Achieve More CostEffective Aminebased Carbon Capture Processes at ...
5 Steps to Achieve More CostEffective Aminebased Carbon Capture Processes at ...5 Steps to Achieve More CostEffective Aminebased Carbon Capture Processes at ...
5 Steps to Achieve More CostEffective Aminebased Carbon Capture Processes at ...
 
Sez presentation-6
Sez presentation-6Sez presentation-6
Sez presentation-6
 

Recently uploaded

Clinico-mycological profile of isolates of superficial fungal infection: A st...
Clinico-mycological profile of isolates of superficial fungal infection: A st...Clinico-mycological profile of isolates of superficial fungal infection: A st...
Clinico-mycological profile of isolates of superficial fungal infection: A st...
Open Access Research Paper
 
High Profile Escort in Abu Dhabi 0524076003 Abu Dhabi Escorts
High Profile Escort in Abu Dhabi 0524076003 Abu Dhabi EscortsHigh Profile Escort in Abu Dhabi 0524076003 Abu Dhabi Escorts
High Profile Escort in Abu Dhabi 0524076003 Abu Dhabi Escorts
Monica Sydney
 
Training Of Trainers FAI Eng. Basel Tilapia Welfare.pdf
Training Of Trainers FAI Eng. Basel Tilapia Welfare.pdfTraining Of Trainers FAI Eng. Basel Tilapia Welfare.pdf
Training Of Trainers FAI Eng. Basel Tilapia Welfare.pdf
Basel Ahmed
 
Principle of erosion control- Introduction to contouring,strip cropping,conto...
Principle of erosion control- Introduction to contouring,strip cropping,conto...Principle of erosion control- Introduction to contouring,strip cropping,conto...
Principle of erosion control- Introduction to contouring,strip cropping,conto...
ZAPPAC1
 

Recently uploaded (20)

Role of Copper and Zinc Nanoparticles in Plant Disease Management
Role of Copper and Zinc Nanoparticles in Plant Disease ManagementRole of Copper and Zinc Nanoparticles in Plant Disease Management
Role of Copper and Zinc Nanoparticles in Plant Disease Management
 
Clinico-mycological profile of isolates of superficial fungal infection: A st...
Clinico-mycological profile of isolates of superficial fungal infection: A st...Clinico-mycological profile of isolates of superficial fungal infection: A st...
Clinico-mycological profile of isolates of superficial fungal infection: A st...
 
Enhancing forest data transparency for climate action
Enhancing forest data transparency for climate actionEnhancing forest data transparency for climate action
Enhancing forest data transparency for climate action
 
Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...
Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...
Faridabad Call Girl ₹7.5k Pick Up & Drop With Cash Payment 8168257667 Badarpu...
 
RA 7942:vThe Philippine Mining Act of 1995
RA 7942:vThe Philippine Mining Act of 1995RA 7942:vThe Philippine Mining Act of 1995
RA 7942:vThe Philippine Mining Act of 1995
 
Introduction to heat waves and Heatwaves in Bangladesh.pptx
Introduction to heat waves and Heatwaves in Bangladesh.pptxIntroduction to heat waves and Heatwaves in Bangladesh.pptx
Introduction to heat waves and Heatwaves in Bangladesh.pptx
 
Russian Call girls in Dubai 0508644382 Dubai Call girls
Russian Call girls in Dubai 0508644382 Dubai Call girlsRussian Call girls in Dubai 0508644382 Dubai Call girls
Russian Call girls in Dubai 0508644382 Dubai Call girls
 
Sustainable Recovery and Reconstruction Framework (SURRF)(1).pdf
Sustainable Recovery and Reconstruction Framework  (SURRF)(1).pdfSustainable Recovery and Reconstruction Framework  (SURRF)(1).pdf
Sustainable Recovery and Reconstruction Framework (SURRF)(1).pdf
 
Yil Me Hu Summer 2023 Edition - Nisqually Salmon Recovery Newsletter
Yil Me Hu Summer 2023 Edition - Nisqually Salmon Recovery NewsletterYil Me Hu Summer 2023 Edition - Nisqually Salmon Recovery Newsletter
Yil Me Hu Summer 2023 Edition - Nisqually Salmon Recovery Newsletter
 
High Profile Escort in Abu Dhabi 0524076003 Abu Dhabi Escorts
High Profile Escort in Abu Dhabi 0524076003 Abu Dhabi EscortsHigh Profile Escort in Abu Dhabi 0524076003 Abu Dhabi Escorts
High Profile Escort in Abu Dhabi 0524076003 Abu Dhabi Escorts
 
Training Of Trainers FAI Eng. Basel Tilapia Welfare.pdf
Training Of Trainers FAI Eng. Basel Tilapia Welfare.pdfTraining Of Trainers FAI Eng. Basel Tilapia Welfare.pdf
Training Of Trainers FAI Eng. Basel Tilapia Welfare.pdf
 
FYP1 FINAL PRESENTATION POLITEKNIK MALAYSIA
FYP1 FINAL PRESENTATION POLITEKNIK MALAYSIAFYP1 FINAL PRESENTATION POLITEKNIK MALAYSIA
FYP1 FINAL PRESENTATION POLITEKNIK MALAYSIA
 
Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...Presentation: Farmer-led climate adaptation - Project launch and overview by ...
Presentation: Farmer-led climate adaptation - Project launch and overview by ...
 
Principle of erosion control- Introduction to contouring,strip cropping,conto...
Principle of erosion control- Introduction to contouring,strip cropping,conto...Principle of erosion control- Introduction to contouring,strip cropping,conto...
Principle of erosion control- Introduction to contouring,strip cropping,conto...
 
Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.Cyclone Case Study Odisha 1999 Super Cyclone in India.
Cyclone Case Study Odisha 1999 Super Cyclone in India.
 
Climate Change
Climate ChangeClimate Change
Climate Change
 
Green Marketing
Green MarketingGreen Marketing
Green Marketing
 
Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...
Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...
Sensual Call Girls in Surajpur { 9332606886 } VVIP NISHA Call Girls Near 5 St...
 
Hook Up Call Girls Rajgir 9332606886 High Profile Call Girls You Can Get T...
Hook Up Call Girls Rajgir   9332606886  High Profile Call Girls You Can Get T...Hook Up Call Girls Rajgir   9332606886  High Profile Call Girls You Can Get T...
Hook Up Call Girls Rajgir 9332606886 High Profile Call Girls You Can Get T...
 
Russian Call girl Dubai 0503464457 Dubai Call girls
Russian Call girl Dubai 0503464457 Dubai Call girlsRussian Call girl Dubai 0503464457 Dubai Call girls
Russian Call girl Dubai 0503464457 Dubai Call girls
 

Energy Modeling of Dedicated Outdoor Air System, DOAS, for a Small Commercial Pilot Project

  • 1. Energy Modeling of Dedicated Outdoor Air Systems for a Small Commercial Pilot Project BUILDING ENERGY SIMULATION FORUM, AUGUST 17, 2016 AMY MONTGOMERY, MASc, P.Eng.
  • 2.  Pilot project: energy efficient replacement options for end-of-life packaged rooftop units on small commercial buildings  Dedicated Outdoor Air Systems (DOAS) with Heat Recovery Ventilation (HRV)  Energy modeling as a tool to quantify savings  Share progress and lessons learned Overview
  • 3. Pilot Project Overview  Target Building Sector:  Small commercial (< 25,000 ft2)  Includes small office, retail, schools, restaurants, small assembly  Makes up approx. half of the commercial building floor area in the Pacific Northwest.  Smaller HVAC systems; typically not engineered.
  • 4. Pilot Project Overview Ventilation + Heating (or Cooling) Outdoor Air Return Air Exhaust Air Packaged Rooftop Unit
  • 5. Controls space temperature Ventilation + Heating (or Cooling) Pilot Project Overview Provides fresh air for occupants
  • 6. Pilot Project Overview Dedicated Outdoor Air System Outdoor Air Ventilation Exhaust Air Heat Recovery Exhaust Air Heat Pump Zone-Level Heating (or Cooling)
  • 7. Pilot Project Overview  Dedicated Outdoor Air System (DOAS) with Heat Recovery in Small Commercial Building Sector  Successful DOAS conversion depends on several factors, including: › Reduction in ventilation air volumes; demand controlled ventilation (DCV) › Very low ventilation fan power (0.5 Watts/cfm or less) › Very high ventilation heat/energy recovery efficiency  Minimal uptake due to lack of a cost-effective high efficiency ventilation solution
  • 8. Pilot Project Overview  Early pilot work funded by the Northwest Energy Efficiency Alliance (NEEA)  New high efficiency Heat Recovery Ventilation (HRV) unit  Vertical mounting for existing RTU ductwork  1000 cfm max flow  Greater than 80% sensible heat recovery efficiency
  • 9. Pilot Project Overview  PART 1: Establish Baseline Conditions  PART 2: Calibrated Baseline Energy Model  PART 3: DOAS Conversion  PART 4: Establish Post-Conversion Conditions  PART 5: Calibrated Post-Conversion Energy Model Savings
  • 10. Pilot Project Overview  PART 1: Establish Baseline Conditions  Site Review  Baseline Air Leakage Testing  Installation of Monitoring Equipment
  • 11. Pilot Project Overview  PART 2: Calibrated Baseline Energy Model  Actual Operating Conditions (occupancy, schedules, heating and cooling setpoints, etc.)  Baseline Air Tightness  Monitoring Data  Historic Utility Data
  • 12. Pilot Project Overview  PART 3: DOAS Conversion  New HRV unit  Zone-level heating and cooling  Local design teams and contractors
  • 13. Pilot Project Overview  PART 4: Establish Post-Conversion Conditions  Site Review  Post-Conversion Air Leakage Testing  Additional Monitoring Equipment
  • 14. Pilot Project Overview  PART 5: Calibrated Post-Conversion Energy Model  Maintain Baseline Operating Conditions  Post-Conversion Air Tightness  Monitoring Data  1 Year Post Conversion Utility Data
  • 15. Pilot Project Overview  Project timeline: Year 1 Recruiting Pilot Project Participants Prototype Modeling PART 1: Establish Baseline Conditions PART 2: Calibrated Baseline Energy Model PART 3: HRV Conversion PART 4: Establish Post- Conversion Conditions
  • 16. Pilot Project Overview  Project timeline: Year 2 PART 1: Baseline PART 2: Baseline Model PART 3: HRV Conversion PART 4: Establish Post-Conversion Conditions PART 5: Calibrated Post-Conversion Energy Model
  • 18. Prototype Modeling  Perform energy modeling of small commercial building prototypes to demonstrate savings potential  Prototype buildings › Office › Retail › School › Restaurant  Climate zones › CZ4C Portland OR › CZ5B Boise ID › CZ6B Helena MT 4C 5B 6B
  • 19. Prototype Modeling  A few notes on prototypes:  Geometry and majority of operating inputs from DOE Commercial Prototype Building Models
  • 20. Prototype Modeling  A few notes on prototypes:  How to reflect existing small commercial building stock? › DOE Pre-1980s Building enclosure inputs (4C/5B/6B) » R-5/R-6/R-7 walls » R-11/R-14/R-17 roof » U-0.55 windows › Downgraded baseline equipment efficiencies by 10% › No motorized damper controls on baseline rooftop units » Fixed damper position at 20%
  • 21. Prototype Modeling  Office Building  5,500 ft2  Defined as perimeter (70%) and core (30%) areas Perimeter Core
  • 22. Prototype Modeling  Rooftop Unit (RTU) with Gas-Fired Heating and DX Cooling Office Baseline
  • 23. Prototype Modeling  Dedicated Outdoor Air System (DOAS) with Heat Recovery Ventilation (HRV) and Zone-Level Heat Pumps Office Conversion
  • 24. Prototype Modeling  Office Prototype Results Annual Energy Consumption Profile Annual Energy Consumption Profile Baseline Conversion Whole building modeled EUI of 55 kBtu/ft2. Whole building modeled EUI of 33 kBtu/ft2. Results in 22 kBtu/ft2 energy savings over the baseline model.
  • 25. Prototype Modeling  Office Prototype Results Baseline Conversion HVAC systems represent 57% or 32 kBtu/ft2 of the overall energy use. HVAC systems represent 29% or 10 kBtu/ft2 of the overall energy use. Annual Energy Consumption Profile Annual Energy Consumption Profile
  • 26. Prototype Modeling  Office Prototype Results Climate Zone Baseline EUI (kBtu/ft2) Conversion EUI (kBtu/ft2) Savings (kBtu/ft2) CZ4C Portland OR 55 33 22 CZ5B Boise ID 61 34 27 CZ6B Helena MT 69 39 30
  • 27. Prototype Modeling  Sit-Down Restaurant  5,500 ft2 floor area  Includes dining area (73%) and kitchen (27%) Kitchen Dining
  • 28. Prototype Modeling  Rooftop Unit (RTU) with Gas-Fired Heating and DX Cooling; Kitchen Exhaust with 100% Outdoor Air Make-up Sit-Down Restaurant Baseline
  • 29. Prototype Modeling  Dedicated Outdoor Air System (DOAS) with Heat Recovery Ventilation (HRV) and Zone-Level Heat Pumps; Kitchen Exhaust Heat Recovery Sit-Down Restaurant Conversion
  • 30. Prototype Modeling  Sit-Down Restaurant Prototype Results Annual Energy Consumption Profile Annual Energy Consumption Profile Baseline Conversion Whole building modeled EUI of 435 kBtu/ft2. Whole building modeled EUI of 307 kBtu/ft2. Results in 128 kBtu/ft2 energy savings over the baseline model.
  • 31. Prototype Modeling  Sit-Down Restaurant Prototype Results Baseline Conversion HVAC systems represent 39% or 169 kBtu/ft2 of the overall energy use. HVAC systems represent 13% or 41 kBtu/ft2 of the overall energy use. Annual Energy Consumption Profile Annual Energy Consumption Profile
  • 32. Prototype Modeling  Sit-Down Restaurant Prototype Results Climate Zone Baseline EUI (kBtu/ft2) Conversion EUI (kBtu/ft2) Savings (kBtu/ft2) CZ4C Portland OR 435 307 128 CZ5B Boise ID 469 321 148 CZ6B Helena MT 523 342 181
  • 33. Prototype Modeling  Retail  3,750 ft2  End unit of strip mall  100% retail space Retail
  • 34. Prototype Modeling  Rooftop Unit (RTU) with Gas-Fired Heating and DX Cooling Retail Baseline
  • 35. Prototype Modeling  Dedicated Outdoor Air System (DOAS) with Heat Recovery Ventilation (HRV) and Zone-Level Heat Pumps Retail Conversion
  • 36. Prototype Modeling  Retail Prototype Results Annual Energy Consumption Profile Annual Energy Consumption Profile Baseline Conversion Whole building modeled EUI of 71 kBtu/ft2. Whole building modeled EUI of 44 kBtu/ft2. Results in 27 kBtu/ft2 energy savings over the baseline model.
  • 37. Prototype Modeling  Retail Prototype Results Baseline Conversion HVAC systems represent 52% or 37 kBtu/ft2 of the overall energy use. HVAC systems represent 22% or 10 kBtu/ft2 of the overall energy use. Annual Energy Consumption Profile Annual Energy Consumption Profile
  • 38. Prototype Modeling  Retail Prototype Results Climate Zone Baseline EUI (kBtu/ft2) Conversion EUI (kBtu/ft2) Savings (kBtu/ft2) CZ4C Portland OR 61 41 20 CZ5B Boise ID 66 43 23 CZ6B Helena MT 74 46 28
  • 39. Prototype Modeling  Primary School  74,600 ft2  Includes classrooms (50%), office & amenity (27%), and circulation and service areas (23%) Circulation Classroom Office & Amenity
  • 40. Prototype Modeling  Gas-Fired Boiler, Rooftop Unit (RTU) with Hydronic Heating and DX Cooling, and Zone-Level Hydronic Re-Heating Primary School Baseline
  • 41. Prototype Modeling  Dedicated Outdoor Air System (DOAS) with Heat Recovery Ventilation (HRV) and Zone-Level Heat Pumps Primary School Conversion
  • 42. Prototype Modeling  Primary School Prototype Results Annual Energy Consumption Profile Annual Energy Consumption Profile Baseline Conversion Whole building modeled EUI of 61 kBtu/ft2. Whole building modeled EUI of 41 kBtu/ft2. Results in 20 kBtu/ft2 energy savings over the baseline model.
  • 43. Prototype Modeling  Primary School Prototype Results Baseline Conversion HVAC systems represent 42% or 26 kBtu/ft2 of the overall energy use. HVAC systems represent 14% or 6 kBtu/ft2 of the overall energy use. Annual Energy Consumption Profile Annual Energy Consumption Profile
  • 44. Prototype Modeling  Primary School Prototype Results Climate Zone Baseline EUI (kBtu/ft2) Conversion EUI (kBtu/ft2) Savings (kBtu/ft2) CZ4C Portland OR 61 41 20 CZ5B Boise ID 66 43 23 CZ6B Helena MT 74 46 28
  • 45. Prototype Modeling  30% to 40% predicted whole building savings for DOAS conversion
  • 47. Pilot Projects  10 pilot projects to date Office #3 Libby MTOffice #6 Seattle WA Other #1 Darby MT Office #1 Portland OR Restaurant #1 Corvallis OR Office #5 Salem OR Office #7 McMinnville OR Office #4 Portland OR Restaurant #2 Portland OR Office #2 Corvallis OR
  • 48. Pilot Projects  Highlight first pilot projects  Office 1, Portland OR  Office 2, Corvallis, OR  Office 3, Libby, MT  Restaurant 1, Corvallis, OR  Progress report  General lessons learned to reconcile energy model and in-service energy performance
  • 50. Pilot Projects  Office 1  Existing heritage building  Second floor of a 2 storey building  Private offices  Intermittent occupancy in meeting and conference rooms  Monday through Friday day time operation
  • 52. Pilot Project  Office 1  Baseline  9 RTUs, total 35 tons cooling, 650,000 Btu/h heating  Conversion  4 HRVs  8 zone-level VRF fan coil units, tons cooling, 215,000 Btu/h heating
  • 54. Pilot Project  Office 1  Pre-Conversion Air Leakage Testing  Air Leakage Test Result: 0.616 cfm/ft2 at 75 Pa › Air leakage noted at operable windows, HVAC dampers, and mechanical chases between floors.
  • 55. Pilot Project  Office 1  Preliminary baseline modeling results  EUI 51 kBtu/ft2
  • 56.
  • 57. Pilot Project  Office 1  Post-Conversion Air Leakage Testing  Air Leakage Test Result: 0.506 cfm/ft2 at 75 Pa
  • 58. Pilot Project  Office 1  Preliminary DOAS conversion modeling results  EUI 30 kBtu/ft2  ~ 40% savings
  • 59. Pilot Project  Office 1  Preliminary Monitoring Data Outdoor Air Temperature Heat Pump Energy (Cooling Mode)
  • 60. Pilot Project  Office 1  Preliminary Monitoring Data Outdoor Air Temperature VRF Fan Coil Units HRV Fans
  • 61. Pilot Project  Office 1  Preliminary Monitoring Data Outdoor Air Temperature Space Temperatures ??? ???
  • 62. Pilot Project  Office 1  What’s next?  Fine tuning DOAS conversion  Collect more utility data and monitoring data  Calibrate DOAS conversion model  General “lessons learned” for reconciling metered and modeled energy performance:  Commissioning matters!  Expect and mitigate anomalies in monitoring data
  • 64. Pilot Projects  Office 2  Single storey office building  Private offices, conference room, storage & library  Monday through Friday day time operation  DOAS conversion for 2 out of 5 zones
  • 66. Pilot Project  Office 2  Baseline  5 RTUs, total 20 tons cooling, 227,000 Btu/h heating  Conversion  3 RTUs remain, total 14 tons cooling, 152,000 Btu/h heating  1 HRV  2 zone-level multi-split indoor units and 1 outdoor unit, 4 tons cooling, 54,000 Btu/h heating
  • 67.
  • 68. Pilot Project  Office 2  Pre-Conversion Air Leakage Testing  Air Leakage Test Result: 0.295 cfm/ft2 at 75 Pa › Air leakage noted at office entry doors, operable windows, exhaust fans with gravity dampers (under positive pressure).
  • 69. Pilot Projects  Office 2  Preliminary baseline modeling results  EUI 60 kBtu/ft2
  • 70. Pilot Projects  Office 2  DOAS conversion in spring/summer 2016
  • 71. Pilot Project  Office 2  Post-Conversion Air Leakage Testing  Air Leakage Test Result: 0.266 cfm/ft2 at 75 Pa
  • 72. Pilot Projects  Office 2  Preliminary DOAS conversion modeling results  EUI 50 kBtu/ft2
  • 73. Pilot Projects  Office 2  Preliminary Monitoring Data 24 hour period showing time averaged difference between post-conversion CO2 levels and pre- conversion CO2 levels.
  • 74. Pilot Project  Office 2  What’s next?  Collect more utility data and monitoring data  Calibrate DOAS conversion model  General “lessons learned” for using energy modeling as a tool to evaluate performance:  Modeling evaluates energy consumption; don’t forget the non-energy benefits.
  • 76. Pilot Projects  Office 3  Single storey office with attached garage + shop area  Monday through Friday day time schedule
  • 78. Pilot Project  Office 3  Baseline  1 RTU, total 7 tons cooling, 76,000 Btu/h heating  Hydronic heating (electric)  Conversion  1 HRV  9 zone-level multi-split indoor units and 2 outdoor units, 4 tons cooling, 54,000 Btu/h heating
  • 80. Pilot Project  Office 3  Pre-Conversion Air Leakage Testing  Air Leakage Test Result: 0.746 cfm/ft2 at 75 Pa › Air leakage noted at roof to wall joints in garage, operable windows and overhead sectional doors in garage, ductwork.
  • 81. Pilot Projects  Office 3  Preliminary baseline modeling results  EUI 79 kBtu/ft2
  • 82. Pilot Projects  Office 3  DOAS conversion scheduled for summer 2016
  • 83. Pilot Projects  Office 3  Preliminary DOAS conversion modeling results  EUI 67 kBtu/ft2
  • 84. Pilot Projects  Office 3  Preliminary Monitoring Data Electric boiler energy consumption (secondary axis) IT room heat pump (primary axis) RTU???
  • 85. Pilot Projects  Office 3  Preliminary Monitoring Data Actual electricity consumption and modeled electricity consumption per month for the year 2013.
  • 86. Pilot Project  Office 2  What’s next?  Install DOAS conversion  Post-conversion air leakage testing and monitoring equipment install  Collect more utility data and monitoring data  Calibrate DOAS conversion model  General “lessons learned” for reconciling metered and modeled energy performance :  Expect and incorporate seasonal and other building-specific operating characteristics.
  • 88. Pilot Projects  Restaurant 1  Busy sit-in & take-out restaurant  Dining area, kitchen, basement storage  Operating hours from 9AM to midnight, daily
  • 90. Pilot Project  Restaurant 1  Baseline  Dining area: › Previously had 1 RTU, 7.5 tons cooling, 88,000 Btu/h heating › Currently no ventilation › Ductless split heat pumps for heating and cooling  Conversion  Dining area: › Install 1 HRV to reinstate ventilation at low energy penalty › Use existing ductless split heat pumps for heat and cooling
  • 91.
  • 92. Pilot Project  Restaurant 1  Pre-Conversion Air Leakage Testing  Air Leakage Test Result: 1.634 cfm/ft2 at 75 Pa › Air leakage noted at existing RTU supply and return registers, around doorway to basement, exhaust fans.
  • 93. Pilot Project  Restaurant 1  Preliminary baseline modeling results  EUI 651 kBtu/ft2
  • 94.
  • 95. Pilot Project  Restaurant 1  Post-Conversion Air Leakage Testing  Air Leakage Test Result: 1.644 cfm/ft2 at 75 Pa
  • 96. Pilot Project  Restaurant 1  Preliminary Monitoring Data Interior Air Temperature (front and back) Outdoor Air Temperature
  • 97. Pilot Project  Restaurant 1  Preliminary Monitoring Data Interior Air Temperatures ≠ Temperature at HRV Exhaust Inlet Duct Leakage in Unconditioned Attic
  • 98. Pilot Project  Restaurant 1  What’s next?  Collect more utility data and monitoring data  Create and calibrate DOAS conversion model  General “lessons learned” for reconciling metered and modeled energy performance:  Expect and mitigate system losses.
  • 100. Summary and Next Steps  Summary – progress thus far
  • 101. Summary and Next Steps  Project timeline: Year 1 Recruiting Pilot Project Participants Prototype Modeling PART 1: Establish Baseline Conditions PART 2: Calibrated Baseline Energy Model PART 3: HRV Conversion PART 4: Establish Post- Conversion Conditions
  • 102. Summary and Next Steps  Summary – some early lessons learned for connecting modeled energy performance with in-service building performance  Commissioning matters!  Expect and mitigate anomalies in monitoring data.  Expect and incorporate building- specific and seasonal operational schedules.  Expect and mitigate system losses.  Also, don’t forget the non-energy benefits.
  • 103. Summary and Next Steps  Project timeline: Year 2 PART 1: Baseline PART 2: Baseline Model PART 3: HRV Conversion PART 4: Establish Post-Conversion Conditions PART 5: Calibrated Post-Conversion Energy Model
  • 104. Summary and Next Steps  PART 1: Establish Baseline Conditions  PART 2: Calibrated Baseline Energy Model  PART 3: DOAS Conversion  PART 4: Establish Post-Conversion Conditions  PART 5: Calibrated Post-Conversion Energy Model Reliably Estimate and Validate Savings Market Transformation
  • 105.  rdh.com | buildingsciencelabs.com RDH Building Engineering Ltd. and Building Science Consulting Inc. have merged. Effective November 1, 2015, we now operate as one integrated firm. The merger brings two of the leading building science firms in North America together to provide a combination of cutting-edge research with leading design and implementation capabilities. The result is a unique offering for our clients–an ability to explore new and innovative ideas based on science and our practical knowledge of what can be built. We are excited about the possibilities as we launch the new firm. Discussion + Questions FOR FURTHER INFORMATION PLEASE VISIT