Regenerative Feed Heating
• Why it is done?
• How it is done?
• Construction of Feed Heaters
• Drains (Secondary condensate) arrangement
• Cascading of drains.
• H.P. Heaters – By pass arrangement.
• Level control and its importance.
ANIL PALAMWAR – anilpalamwar@yahoo.com
1
Rankine Cycle
2
Heat Transfer and Δ T
• Q = K x A x Δ T
• Efficiency of heat transfer is maximum
when Δ T tends to Zero.
• Thus by raising the temperature of feed
water in stages we achieve a low Δ T at
every stage.
• Average temperature of at which heat is
added also increases and gives better
efficiency
3
Rankine and Carnot Cycle.
The Rankine cycle is sometimes referred to as a
practical Carnot cycle as, when an efficient turbine is
used, the TS diagram begins to resemble the Carnot
cycle.
The main difference is that heat addition (in the boiler)
and rejection (in the condenser) are isobaric in the
Rankine cycle and isothermal in the Carnot cycle.
A pump is used to pressurize the working fluid
received from the condenser as a liquid instead of as a
gas.
4
Rankine and Carnot Cycle.
All of the energy of vaporization of the working
fluid,is supplied in the boiler.(Latent Heat )
All the vaporization energy is rejected from the cycle
through the condenser.
But pumping the working fluid through the cycle as
a liquid requires a very small fraction of the energy
needed to transport it -
-as compared to compressing the working fluid as a
gas in a compressor (as in the Carnot cycle).
5
Limitations of Rankine Cycle
The efficiency of a Rankine cycle is limited by the working
fluid. Without the super critical pressure levels for the working
fluid, the temperature range of the cycle is quite small.
Turbine entry temperatures are typically 565°C (the creep limit
of stainless steel) and condenser temperatures are around 30°C.
This gives a theoretical Carnot efficiency of about 63%
compared with an actual efficiency of 42% for a modern coal-
fired power station.
This low turbine entry temperature (compared with a gas
turbine) is why the Rankine cycle is often used as a bottoming
cycle in combined cycle gas turbine power stations.
6
Rankine Advantage
Advantages the Rankine cycle over others cycles is
during the compression stage.
Relatively little work is required to drive the pump,
As the working fluid is in liquid phase at this point.
By condensing the fluid to liquid, the work required by
the pump is only 1% to 3% of the turbine power
and
contributes to a much higher efficiency for a real cycle.
7
Rankine Cycle on T-S Diagram
8
Rankine Cycle Process
•Process 1-2: The working fluid is pumped from low to high
pressure, being liquid, the pump requires little input energy.
•Process 2-3: The high pressure liquid enters boiler where it is
heated at constant pressure to become a dry saturated vapor.
•Process 3-4: The dry saturated vapor expands through a turbine,
generating power.
• This decreases the temperature and pressure of the vapor, and
some condensation may occur.
•Process 4-1: The wet vapor then enters a condenser where it is
condensed at a constant pressure to become a saturated liquid.
9
Real Rankine cycle (non-ideal)
10
Real Rankine Cycle
In a real Rankine cycle, the compression by the pump and
the expansion in the turbine are not isentropic.
These processes are non-reversible.
and entropy increases during the two processes.
(i.e.Non-Isentropic)
This increases the power required by the pump and
decreases the power generated by the turbine.
11
Rankine Cycle with Reheat
12
Rankine Cycle with Reheat
In this variation, two turbines work in series.
The first accepts steam from the boiler at high pressure.
After the steam has passed through the first turbine, it re-
enters the boiler and is reheated before passing through a
second, lower pressure turbine.
Among other advantages, this prevents the steam from
condensing during its expansion which can seriously
damage the turbine blades,
and improves the efficiency of the cycle, as more of the
heat flow into the cycle occurs at higher temperature.
13
Regenerative Rankine cycle
The regenerative Rankine cycle is so named because
after emerging from the condenser the working fluid is
heated by steam tapped from the hot portion of the
cycle.
On the diagram shown, the fluid at 2 is mixed with the
fluid at 4 (both at the same pressure) to end up with the
saturated liquid at 7.
This is called "direct contact heating".
The Regenerative Rankine cycle (with minor variants) is
commonly used in real power stations.
14
Regenerative Rankine cycle
Another variation is where 'bleed steam' from turbine
stages is sent to feed-water heaters to preheat the water on
its way from the condenser to the boiler. These heaters do
not mix the input steam and condensate, function as an
ordinary tubular heat exchanger, and are named "closed
feed-water heaters".
The regenerative features here effectively raise the nominal
cycle heat input temperature, by reducing the addition of
heat from the boiler/fuel source at the relatively low feed-
water temperatures that would exist without regenerative
feed-water heating.
This improves the efficiency of the cycle, as more of the
heat flow into the cycle occurs at higher temperature.15
Regenerative Rankine Cycle.
16
Heat Rate
HEAT RATE – Kilo Calories input to TURBNE divided by
Gross generation in KW [K.Cal/KWH]
[Gross TG Heat Rate = ((Main Steam Flow at Turbine inlet x
(Main Steam Enthalpy – Feed water Enthalpy at Eco-inlet))
+ (CRH Steam Flow x (HRH Steam Enthalpy - CRH
Enthalpy)) + (ReHeat Spray Flow x (HRH Steam Enthalpy -
Feed water Enthalpy at Eco-inlet)) / Gross Generation
Gross TG Heat Rate =
{(Main Steam Flow at Turbine inlet x
(Main Steam Enthalpy – Feed water Enthalpy at Eco-inlet)}
/ Gross Generation
17
Eco.Inlet Temp. V/s. Heat Rate for
100 MW Unit (With R/H.)
1900
2000
2100
2200
2300
2400
310 300 290 280 270 260 250 240 230 220
Eco.Inlet Temp.
H.R.inK.Cal/KWH
TG inlet Pressure = 120 Kg/cm2.
Inlet Steam Temp.=550 deg.C.
Cold R/H Pr.=32 Kg/cm2.
18
HEAT
EXCHANGERS
19
Heat Exchanger
• A heat exchanger is for efficient heat
transfer from one medium to another.
• The heat exchange may be for Cooling or
Heating.
• The media may be separated by a solid wall
(Surface heat transfer) so that they never
mix, or they may be in direct contact.
• Condenser, Feed Heaters , Oil Coolers, etc.
• De-aerator 20
21
Regenerative feed heating cycle
22
23
TOTAL HEAT IN STEAM
24
25
26
27
HEAT EXCHANGERS
Heat Exchangers may be of two types –
1] Surface Type –Tubular or Plate Type.-Fluids do not
mix.
2] Contact Type.-Hot & Cold fluids mix.
Regenerative feed heaters are all tubular surface type
except the De-aerator.
De-aerator is a contact type Heat Exchanger where HOT
and COLD fluids mix.
Plate type are used for cooling of BCW. These are
suitable for low pressure & low temperature applications.
27
Parallel Flow - Counter Flow - Cross Flow.
28
29
Parallel Flow
29
30
Tc exit is less than Th exit in Parallel Flow.
Tc-Temperature of cold fluid
Th-temperature of hot fluid
30
31
Counter Flow
31
32
In Counter flow, Tc exit can be more than Th exit
32
33
Typical Tubular Heat Exchanger(3-pass)
33
34
Tubular Heat Exchanger (1-pass)
34
35
L.M.T.D.
The Log Mean Temperature Difference
(LMTD) is used to determine the temperature
driving force –
ΔT
for heat transfer in flow systems, most notably in
heat exchangers.
LMTD is a logarithmic average of the temperature
difference between the hot and cold streams at each
end of the exchanger.
The larger the LMTD, the more heat is transferred.
35
36
L.M.T.D.-Equation
Assume that a generic heat exchanger has two ends
( "A" and "B") at which the hot and cold streams enter
or exit on either side; then, the LMTD is defined by
the logarithmic mean as follows:
 
 
where ΔTA
is the temperature difference between the
two streams at end A, and ΔTB
is the temperature
difference between the two streams at end B.
(Holds for parallel flow & also for counter flow)
36
37
Application of LMTD
Once calculated, the LMTD is usually applied to calculate the
heat transfer in an exchanger according to the simple
equation:
 
 
Where Q is the exchanged heat duty (in watts),
U is the heat transfer coefficient (in watts per kelvin per
square meter) and
A is the heat transfer surface area.
Calculation of U may be quite complicated.
37
38
Design Considerations
For efficiency, heat exchangers are designed to
maximize the surface area of the wall between
the two fluids,
while minimizing resistance to fluid flow
through the exchanger.
The exchanger's performance can also be
improved by the addition of fins or
corrugations in one or both directions,
which increase surface area and may
STREAMLINE the fluid flow
or induce turbulence
38
39
Driving Temperature
The driving temperature across the heat transfer surface
varies with position, but an appropriate mean
temperature can be defined. In most simple systems this
is the "log mean temperature difference" (LMTD).
39
40
A set of tubes is called the tube bundle and can
be made up of several types of tubes: plain,
longitudinally finned, etc.
Shell and tube heat exchangers are robust due to
their shape and are typically used for high-
pressure applications.
(with pressures greater than 30 bar and
temperatures greater than 260°C).
40
41
Design Features
•Tube diameter: Small tube diameter makes the
heat exchanger economical and compact.
However, it may foul up faster and the small size
makes mechanical cleaning difficult.
•To prevail over the fouling and cleaning
problems, larger tube diameters can be used.
•Thus to determine the tube diameter, the
available space, cost and the fouling nature of the
fluids must be considered.
41
42
•Tube thickness: The thickness of the wall of the
tubes is usually determined to ensure:
o There is enough room for corrosion
o That flow-induced vibration has resistance
o Axial strength
o Availability of spare parts
o Hoop strength (to withstand internal tube
pressure)
o Buckling strength (to withstand overpressure in
the shell)
Tube Thickness
42
43
Tube length: heat exchangers are cheaper
when the shell diameter is smaller and length
is more.
Thus, the aim is to make the heat exchanger as
long as physically possible whilst not
exceeding production capabilities.
However, the limitations are -the space
available at the site.
Also, it has to be remembered that long, thin
tubes are difficult to take out and replace.
Tube Length
43
44
Tube Pitch and Fins/corrugation
•Tube pitch: when designing the tubes, it is practical to
ensure that the tube pitch (i.e., the centre-centre distance
of adjoining tubes) is not less than 1.25 times the tubes'
outside diameter.
•A larger tube pitch leads to a larger overall shell
diameter which leads to a more expensive heat exchanger.
Tube corrugation: this type of tubes, mainly used for the
inner tubes, increases the turbulence of the fluids and the
effect is very important in the heat transfer giving a better
performance
44
45
Baffles
Baffles are used in shell and tube heat exchangers to direct fluid
across the tube bundle.
They run perpendicularly to the shell and hold the bundle,
preventing the tubes from sagging over a long length.
They also prevent the tubes from vibrating.
The most common type of baffle is the segmental baffle.
The semicircular segmental baffles are oriented at 180 degrees to
the adjacent baffles forcing the fluid to flow upward and
downwards between the tube bundle.
Baffle spacing is of large thermodynamic concern in shell and
tube heat exchangers. Baffles must be spaced with consideration
of pressure drop and heat transfer.
45
46
Baffles....contd.
For thermo economic optimization the baffles are spaced at 20%
of the shell’s inner diameter.
Too closely spaced baffles cause a greater pressure drop because
of flow redirection.
Consequently if the baffles are spaced too far apart then there
may be cooler spots in the corners between baffles.
The baffles should be spaced such that the tubes do not sag.
The other type of baffle is the disc and donut baffle which
consists of two concentric baffles.
The outer wider baffle looks like a donut, whilst the inner baffle is
shaped as a disk. This type of baffle forces the fluid to pass
around each side of the disk then through the donut baffle
generating a different type of fluid flow.
46
47
DEAERATOR-CONTACT TYPE HEAT EXCHANGER
47
HIGH PRESSURE HEATER
Design features ensure high reliability and availability
associated with long term life and low maintenance.
Independent desuperheating zone closures.
Baffle configuration and spacing based on conservative mass
and linear velocity criteria.
Fully enclosed self-venting drains sub-cooling zone.
Liberal sub-cooling zone entrance areas to permit low approach
velocities which prevent flashing of saturated drains.
Internal, centrally located venting arrangement to provide means
of continuously venting condensing zone.
Channel cover configurations for all nozzle layouts.
Stainless steel impingement plates.
48
Regenerative Feed Heating Scheme
49
H.P.Heater Details
Note feed water entry from lower side and Steam entry from
the top.
Three sections – Desuperheating – Condensing - & Cooling.
50
3-Processes in HPH
The feed-water heating process actually takes place in
three distinct steps.
First, the de-superheating zone cools the superheated
steam to the point that the steam is saturated.
Next, the condensing zone extracts the Latent Heat from
the steam/water mixture to preheat the boiler feed-water
passing through the tube side.
Finally, a drain cooler is incorporated to capture additional
energy from the liquid.
The three heating processes all occur within a single
heater.
51
Effect of High / Low Level
Lower final feed-water temperature occurs when a feed-water heater
is withdrawn due to unreliable level input to the control system or
when the level is too high or low.
If the condition is a result of high feed-water heater level, there
would be a decrease in feed-water heater temperature rise, a
decreasing DCA (Drain Cooler Approach)temperature difference,
and an increasing TTD (Terminal Temperature Difference).
The inverse is true if feed-water heater levels are too low.
In either case, risk of damage to hardware increases, heat transfer is
impaired, and feed-water to the economizer is not at the required
temperature.
There are two probable responses to a low final feed-water
temperature, neither of which is desirable:
52
Operator response –
Low feed water temperature
Over-fire the boiler to increase temperature (level too
high/low or out of service).
This action will increase fuel consumption and emissions,
as well as increase the gas temperature exiting the furnace.
The increased gas temperature will increase the reheat and
superheat sprays.
Also, the steam flow through the IP and LP stages of the
steam turbine will increase (when the heater is out of
service), causing
flashing and potential damage to the drain cooler section
and possibly cause thermal damage to the tubes.
53
Operator response –
Low feed water temperature
Open emergency drains to lower level (level too high).
This option causes an immediate loss of plant efficiency and
can cause damage to hardware if water is inducted into the
extraction line.
The worst case occurs when the water is inducted back into
the steam turbine, causing a possible catastrophic failure.
The best case is that the turbine water induction protection
(TWIP) trips the unit,
shutting the heater down and causing expensive loss of
production and other related costs.
54
Case Study
Due to lower final feed-water
temperature at a 500-MW
coal-fired plant.
The heat rate rose 47
Btu/kWh, adding $243,000
annually to the plant’s cost of
fuel.
Note that the case study does
not take into account
additional emissions cost,
effects on boiler and turbine
efficiencies, over-firing
conditions, lost production,
and other related factors,
55
Level Control
The feed-water heater, is a series of tubes carrying feed-
water through a tank shell.
Steam is injected into the shell and heat is transferred to
the feed-water inside the tubes.
The steam condenses in the shell, creating a liquid level
of condensate in the heater.
The level is controlled to create a seal and prevent blow-
through of steam.
The maximum thermal transfer between steam and the
feed-water takes place when,
the largest tube area is exposed to the steam without
allowing steam blow-through. 56
Level Control
Condensate is allowed to drain from the shell through the
normal drain.
When the tubes become submerged in condensate,
heat is transferred to the condensate rather than the tubes
with the feed-water inside,
resulting in poor heater efficiency.
A relatively small increase in condensate level,
(2-in to 4-in) over the minimum,
greatly affects the heat rate (fuel efficiency) of the
boiler.
57
58
59
60
61
62

More Related Content

What's hot

Performance calculation for feed water heater
Performance calculation  for feed water heaterPerformance calculation  for feed water heater
Performance calculation for feed water heaterSHIVAJI CHOUDHURY
 
Turbine cycle heat rate calculation
Turbine  cycle heat rate calculationTurbine  cycle heat rate calculation
Turbine cycle heat rate calculationSHIVAJI CHOUDHURY
 
Steam Turbine and Condenser
Steam Turbine and CondenserSteam Turbine and Condenser
Steam Turbine and CondenserMulugeta Wotango
 
Improvement of rankine efficinecy of steam power plants
Improvement of rankine efficinecy of steam power plantsImprovement of rankine efficinecy of steam power plants
Improvement of rankine efficinecy of steam power plantsDhilip Pugalenthi
 
Improve plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater controlImprove plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater controlHossam Zein
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsSHIVAJI CHOUDHURY
 
Steam turbine
Steam turbineSteam turbine
Steam turbineRavi97246
 
Performance evaluation and optimization of air preheater in thermal power plant
Performance evaluation and optimization of air preheater in thermal power plantPerformance evaluation and optimization of air preheater in thermal power plant
Performance evaluation and optimization of air preheater in thermal power plantIAEME Publication
 
THERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATETHERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATEManohar Tatwawadi
 
Steam Turbines
Steam Turbines Steam Turbines
Steam Turbines Amir Ayad
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boilerKongkiert Tankayura
 
Condenser in Thermal Power Plant
Condenser in Thermal Power PlantCondenser in Thermal Power Plant
Condenser in Thermal Power PlantMihir Patel
 

What's hot (20)

Steam turbine
Steam turbineSteam turbine
Steam turbine
 
Performance calculation for feed water heater
Performance calculation  for feed water heaterPerformance calculation  for feed water heater
Performance calculation for feed water heater
 
Steam Turbines Basics
Steam Turbines BasicsSteam Turbines Basics
Steam Turbines Basics
 
Turbine cycle heat rate calculation
Turbine  cycle heat rate calculationTurbine  cycle heat rate calculation
Turbine cycle heat rate calculation
 
Steam Turbine and Condenser
Steam Turbine and CondenserSteam Turbine and Condenser
Steam Turbine and Condenser
 
Improvement of rankine efficinecy of steam power plants
Improvement of rankine efficinecy of steam power plantsImprovement of rankine efficinecy of steam power plants
Improvement of rankine efficinecy of steam power plants
 
Improve plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater controlImprove plant heat rate with feedwater heater control
Improve plant heat rate with feedwater heater control
 
Steam turbine Working
Steam turbine WorkingSteam turbine Working
Steam turbine Working
 
Rankine cycle
Rankine cycleRankine cycle
Rankine cycle
 
Feedwater heaters in thermal power plants
Feedwater heaters in thermal power plantsFeedwater heaters in thermal power plants
Feedwater heaters in thermal power plants
 
Heat balance diagram
Heat balance diagramHeat balance diagram
Heat balance diagram
 
Steam turbine
Steam turbineSteam turbine
Steam turbine
 
Steam turbine
Steam turbineSteam turbine
Steam turbine
 
rankine cycle
rankine cyclerankine cycle
rankine cycle
 
Performance evaluation and optimization of air preheater in thermal power plant
Performance evaluation and optimization of air preheater in thermal power plantPerformance evaluation and optimization of air preheater in thermal power plant
Performance evaluation and optimization of air preheater in thermal power plant
 
THERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATETHERMAL POWER PLANT EFFICIENCY AND HEAT RATE
THERMAL POWER PLANT EFFICIENCY AND HEAT RATE
 
Steam Turbines
Steam Turbines Steam Turbines
Steam Turbines
 
Rankine cycle
Rankine cycleRankine cycle
Rankine cycle
 
Energy adudit methodology for boiler
Energy adudit methodology for boilerEnergy adudit methodology for boiler
Energy adudit methodology for boiler
 
Condenser in Thermal Power Plant
Condenser in Thermal Power PlantCondenser in Thermal Power Plant
Condenser in Thermal Power Plant
 

Viewers also liked

Regenerative feed water heating cycle
Regenerative feed water heating cycleRegenerative feed water heating cycle
Regenerative feed water heating cycle431996
 
Closed feed water heaters :)
Closed feed water heaters :)Closed feed water heaters :)
Closed feed water heaters :)JhePoi Santos
 
Condenser in thermal power plants
Condenser in thermal power plantsCondenser in thermal power plants
Condenser in thermal power plantsSHIVAJI CHOUDHURY
 
Heat Exchangers
Heat ExchangersHeat Exchangers
Heat ExchangersSABIC
 
Tutorial questions reheat rankine cycle
Tutorial  questions   reheat rankine cycleTutorial  questions   reheat rankine cycle
Tutorial questions reheat rankine cycleIbrahim AboKhalil
 
Heat Exchangers
Heat ExchangersHeat Exchangers
Heat Exchangersmohkab1
 
Heat exchangers and types
Heat exchangers and typesHeat exchangers and types
Heat exchangers and typesGopesh Chilveri
 
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...Living Online
 
National thermal power corporation
National thermal power corporationNational thermal power corporation
National thermal power corporationAbhishek Awasthi
 
Thermoelectric device
Thermoelectric deviceThermoelectric device
Thermoelectric devicesaikrishna
 

Viewers also liked (20)

Regenerative feed water heating cycle
Regenerative feed water heating cycleRegenerative feed water heating cycle
Regenerative feed water heating cycle
 
Closed feed water heaters :)
Closed feed water heaters :)Closed feed water heaters :)
Closed feed water heaters :)
 
Rankine cycle
Rankine cycleRankine cycle
Rankine cycle
 
Condenser in thermal power plants
Condenser in thermal power plantsCondenser in thermal power plants
Condenser in thermal power plants
 
Heat Exchangers
Heat ExchangersHeat Exchangers
Heat Exchangers
 
Heatexchangers
Heatexchangers Heatexchangers
Heatexchangers
 
Tutorial questions reheat rankine cycle
Tutorial  questions   reheat rankine cycleTutorial  questions   reheat rankine cycle
Tutorial questions reheat rankine cycle
 
Heat Exchangers
Heat ExchangersHeat Exchangers
Heat Exchangers
 
Heat exchangers
Heat exchangersHeat exchangers
Heat exchangers
 
Thermal engineering by rk rajput chapter 15
Thermal engineering by rk rajput   chapter 15Thermal engineering by rk rajput   chapter 15
Thermal engineering by rk rajput chapter 15
 
Heat Exchangers
Heat ExchangersHeat Exchangers
Heat Exchangers
 
HEAT EXCHANGERS
HEAT EXCHANGERSHEAT EXCHANGERS
HEAT EXCHANGERS
 
Heat exchangers and types
Heat exchangers and typesHeat exchangers and types
Heat exchangers and types
 
Heat exchangers
Heat exchangersHeat exchangers
Heat exchangers
 
Heat exchangers
Heat exchangersHeat exchangers
Heat exchangers
 
Steam power plant
Steam power plantSteam power plant
Steam power plant
 
Steam power plants
Steam power plantsSteam power plants
Steam power plants
 
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
Practical Medium and High Voltage Testing of Electrical Equipment for Enginee...
 
National thermal power corporation
National thermal power corporationNational thermal power corporation
National thermal power corporation
 
Thermoelectric device
Thermoelectric deviceThermoelectric device
Thermoelectric device
 

Similar to 01 regenerative feed heating

Lecture 5.pptx
Lecture 5.pptxLecture 5.pptx
Lecture 5.pptxNelyJay
 
Vapor_power cycles KM.pptx ..
Vapor_power cycles KM.pptx            ..Vapor_power cycles KM.pptx            ..
Vapor_power cycles KM.pptx ..happycocoman
 
Regenerative feed water heating system
Regenerative feed water heating systemRegenerative feed water heating system
Regenerative feed water heating systemAshrant Dass
 
Power plant engineering chapter 2
Power plant engineering chapter 2Power plant engineering chapter 2
Power plant engineering chapter 2swathi1995vangaram
 
Steam Power Cycle and Basics of Boiler
Steam Power Cycle and Basics of BoilerSteam Power Cycle and Basics of Boiler
Steam Power Cycle and Basics of BoilerMulugeta Wotango
 
Thermodynamics of thermal power plants
Thermodynamics of thermal power plantsThermodynamics of thermal power plants
Thermodynamics of thermal power plantsSugam Parnami
 
REGENERATIVE FEEDHEATING.pptx
REGENERATIVE FEEDHEATING.pptxREGENERATIVE FEEDHEATING.pptx
REGENERATIVE FEEDHEATING.pptxssuser28a1a31
 
Vapour power cycles
Vapour power cyclesVapour power cycles
Vapour power cycleskrishna khot
 
Rankine Cycle & How to increase its efficiency
Rankine Cycle & How to increase its efficiencyRankine Cycle & How to increase its efficiency
Rankine Cycle & How to increase its efficiencyRaja Dolat
 
Problems for power h.ppt
Problems for power         h.pptProblems for power         h.ppt
Problems for power h.pptMahamad Jawhar
 
Basic ccpp overview Power plant
Basic ccpp overview Power plantBasic ccpp overview Power plant
Basic ccpp overview Power plantMARLON RAMIREZ
 
Vapour power cycle thermo veer ME201 PPT
Vapour power cycle thermo veer ME201 PPTVapour power cycle thermo veer ME201 PPT
Vapour power cycle thermo veer ME201 PPTsreddyrahul
 
Supercritical steam generators
Supercritical steam generatorsSupercritical steam generators
Supercritical steam generatorsAshutosh Katti
 
Power plant based on Rankine cycle
Power plant based on Rankine cyclePower plant based on Rankine cycle
Power plant based on Rankine cycleNirav Vaghela
 

Similar to 01 regenerative feed heating (20)

Lecture 5.pptx
Lecture 5.pptxLecture 5.pptx
Lecture 5.pptx
 
Rnakine reheat regen
Rnakine reheat regenRnakine reheat regen
Rnakine reheat regen
 
Vapor_power cycles KM.pptx ..
Vapor_power cycles KM.pptx            ..Vapor_power cycles KM.pptx            ..
Vapor_power cycles KM.pptx ..
 
Power cycles
Power cyclesPower cycles
Power cycles
 
Regenerative feed water heating system
Regenerative feed water heating systemRegenerative feed water heating system
Regenerative feed water heating system
 
Power plant engineering chapter 2
Power plant engineering chapter 2Power plant engineering chapter 2
Power plant engineering chapter 2
 
Steam Power Cycle and Basics of Boiler
Steam Power Cycle and Basics of BoilerSteam Power Cycle and Basics of Boiler
Steam Power Cycle and Basics of Boiler
 
Thermodynamics of thermal power plants
Thermodynamics of thermal power plantsThermodynamics of thermal power plants
Thermodynamics of thermal power plants
 
Chapter 10 lecture
Chapter 10 lectureChapter 10 lecture
Chapter 10 lecture
 
REGENERATIVE FEEDHEATING.pptx
REGENERATIVE FEEDHEATING.pptxREGENERATIVE FEEDHEATING.pptx
REGENERATIVE FEEDHEATING.pptx
 
Vapour power cycles
Vapour power cyclesVapour power cycles
Vapour power cycles
 
Rankine Cycle & How to increase its efficiency
Rankine Cycle & How to increase its efficiencyRankine Cycle & How to increase its efficiency
Rankine Cycle & How to increase its efficiency
 
Problems for power h.ppt
Problems for power         h.pptProblems for power         h.ppt
Problems for power h.ppt
 
Power cycles 1
Power cycles 1Power cycles 1
Power cycles 1
 
Basic ccpp overview Power plant
Basic ccpp overview Power plantBasic ccpp overview Power plant
Basic ccpp overview Power plant
 
Vapour power cycle thermo veer ME201 PPT
Vapour power cycle thermo veer ME201 PPTVapour power cycle thermo veer ME201 PPT
Vapour power cycle thermo veer ME201 PPT
 
Steam power plant
Steam power plantSteam power plant
Steam power plant
 
Unit_2_58.pdf
Unit_2_58.pdfUnit_2_58.pdf
Unit_2_58.pdf
 
Supercritical steam generators
Supercritical steam generatorsSupercritical steam generators
Supercritical steam generators
 
Power plant based on Rankine cycle
Power plant based on Rankine cyclePower plant based on Rankine cycle
Power plant based on Rankine cycle
 

Recently uploaded

FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfRagavanV2
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdfKamal Acharya
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Arindam Chakraborty, Ph.D., P.E. (CA, TX)
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdfSuman Jyoti
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptNANDHAKUMARA10
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 

Recently uploaded (20)

FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank  Design by Working Stress - IS Method.pdfIntze Overhead Water Tank  Design by Working Stress - IS Method.pdf
Intze Overhead Water Tank Design by Working Stress - IS Method.pdf
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 

01 regenerative feed heating

  • 1. Regenerative Feed Heating • Why it is done? • How it is done? • Construction of Feed Heaters • Drains (Secondary condensate) arrangement • Cascading of drains. • H.P. Heaters – By pass arrangement. • Level control and its importance. ANIL PALAMWAR – anilpalamwar@yahoo.com 1
  • 3. Heat Transfer and Δ T • Q = K x A x Δ T • Efficiency of heat transfer is maximum when Δ T tends to Zero. • Thus by raising the temperature of feed water in stages we achieve a low Δ T at every stage. • Average temperature of at which heat is added also increases and gives better efficiency 3
  • 4. Rankine and Carnot Cycle. The Rankine cycle is sometimes referred to as a practical Carnot cycle as, when an efficient turbine is used, the TS diagram begins to resemble the Carnot cycle. The main difference is that heat addition (in the boiler) and rejection (in the condenser) are isobaric in the Rankine cycle and isothermal in the Carnot cycle. A pump is used to pressurize the working fluid received from the condenser as a liquid instead of as a gas. 4
  • 5. Rankine and Carnot Cycle. All of the energy of vaporization of the working fluid,is supplied in the boiler.(Latent Heat ) All the vaporization energy is rejected from the cycle through the condenser. But pumping the working fluid through the cycle as a liquid requires a very small fraction of the energy needed to transport it - -as compared to compressing the working fluid as a gas in a compressor (as in the Carnot cycle). 5
  • 6. Limitations of Rankine Cycle The efficiency of a Rankine cycle is limited by the working fluid. Without the super critical pressure levels for the working fluid, the temperature range of the cycle is quite small. Turbine entry temperatures are typically 565°C (the creep limit of stainless steel) and condenser temperatures are around 30°C. This gives a theoretical Carnot efficiency of about 63% compared with an actual efficiency of 42% for a modern coal- fired power station. This low turbine entry temperature (compared with a gas turbine) is why the Rankine cycle is often used as a bottoming cycle in combined cycle gas turbine power stations. 6
  • 7. Rankine Advantage Advantages the Rankine cycle over others cycles is during the compression stage. Relatively little work is required to drive the pump, As the working fluid is in liquid phase at this point. By condensing the fluid to liquid, the work required by the pump is only 1% to 3% of the turbine power and contributes to a much higher efficiency for a real cycle. 7
  • 8. Rankine Cycle on T-S Diagram 8
  • 9. Rankine Cycle Process •Process 1-2: The working fluid is pumped from low to high pressure, being liquid, the pump requires little input energy. •Process 2-3: The high pressure liquid enters boiler where it is heated at constant pressure to become a dry saturated vapor. •Process 3-4: The dry saturated vapor expands through a turbine, generating power. • This decreases the temperature and pressure of the vapor, and some condensation may occur. •Process 4-1: The wet vapor then enters a condenser where it is condensed at a constant pressure to become a saturated liquid. 9
  • 10. Real Rankine cycle (non-ideal) 10
  • 11. Real Rankine Cycle In a real Rankine cycle, the compression by the pump and the expansion in the turbine are not isentropic. These processes are non-reversible. and entropy increases during the two processes. (i.e.Non-Isentropic) This increases the power required by the pump and decreases the power generated by the turbine. 11
  • 12. Rankine Cycle with Reheat 12
  • 13. Rankine Cycle with Reheat In this variation, two turbines work in series. The first accepts steam from the boiler at high pressure. After the steam has passed through the first turbine, it re- enters the boiler and is reheated before passing through a second, lower pressure turbine. Among other advantages, this prevents the steam from condensing during its expansion which can seriously damage the turbine blades, and improves the efficiency of the cycle, as more of the heat flow into the cycle occurs at higher temperature. 13
  • 14. Regenerative Rankine cycle The regenerative Rankine cycle is so named because after emerging from the condenser the working fluid is heated by steam tapped from the hot portion of the cycle. On the diagram shown, the fluid at 2 is mixed with the fluid at 4 (both at the same pressure) to end up with the saturated liquid at 7. This is called "direct contact heating". The Regenerative Rankine cycle (with minor variants) is commonly used in real power stations. 14
  • 15. Regenerative Rankine cycle Another variation is where 'bleed steam' from turbine stages is sent to feed-water heaters to preheat the water on its way from the condenser to the boiler. These heaters do not mix the input steam and condensate, function as an ordinary tubular heat exchanger, and are named "closed feed-water heaters". The regenerative features here effectively raise the nominal cycle heat input temperature, by reducing the addition of heat from the boiler/fuel source at the relatively low feed- water temperatures that would exist without regenerative feed-water heating. This improves the efficiency of the cycle, as more of the heat flow into the cycle occurs at higher temperature.15
  • 17. Heat Rate HEAT RATE – Kilo Calories input to TURBNE divided by Gross generation in KW [K.Cal/KWH] [Gross TG Heat Rate = ((Main Steam Flow at Turbine inlet x (Main Steam Enthalpy – Feed water Enthalpy at Eco-inlet)) + (CRH Steam Flow x (HRH Steam Enthalpy - CRH Enthalpy)) + (ReHeat Spray Flow x (HRH Steam Enthalpy - Feed water Enthalpy at Eco-inlet)) / Gross Generation Gross TG Heat Rate = {(Main Steam Flow at Turbine inlet x (Main Steam Enthalpy – Feed water Enthalpy at Eco-inlet)} / Gross Generation 17
  • 18. Eco.Inlet Temp. V/s. Heat Rate for 100 MW Unit (With R/H.) 1900 2000 2100 2200 2300 2400 310 300 290 280 270 260 250 240 230 220 Eco.Inlet Temp. H.R.inK.Cal/KWH TG inlet Pressure = 120 Kg/cm2. Inlet Steam Temp.=550 deg.C. Cold R/H Pr.=32 Kg/cm2. 18
  • 20. Heat Exchanger • A heat exchanger is for efficient heat transfer from one medium to another. • The heat exchange may be for Cooling or Heating. • The media may be separated by a solid wall (Surface heat transfer) so that they never mix, or they may be in direct contact. • Condenser, Feed Heaters , Oil Coolers, etc. • De-aerator 20
  • 22. 22
  • 24. 24
  • 25. 25
  • 26. 26
  • 27. 27 HEAT EXCHANGERS Heat Exchangers may be of two types – 1] Surface Type –Tubular or Plate Type.-Fluids do not mix. 2] Contact Type.-Hot & Cold fluids mix. Regenerative feed heaters are all tubular surface type except the De-aerator. De-aerator is a contact type Heat Exchanger where HOT and COLD fluids mix. Plate type are used for cooling of BCW. These are suitable for low pressure & low temperature applications. 27
  • 28. Parallel Flow - Counter Flow - Cross Flow. 28
  • 30. 30 Tc exit is less than Th exit in Parallel Flow. Tc-Temperature of cold fluid Th-temperature of hot fluid 30
  • 32. 32 In Counter flow, Tc exit can be more than Th exit 32
  • 33. 33 Typical Tubular Heat Exchanger(3-pass) 33
  • 35. 35 L.M.T.D. The Log Mean Temperature Difference (LMTD) is used to determine the temperature driving force – ΔT for heat transfer in flow systems, most notably in heat exchangers. LMTD is a logarithmic average of the temperature difference between the hot and cold streams at each end of the exchanger. The larger the LMTD, the more heat is transferred. 35
  • 36. 36 L.M.T.D.-Equation Assume that a generic heat exchanger has two ends ( "A" and "B") at which the hot and cold streams enter or exit on either side; then, the LMTD is defined by the logarithmic mean as follows:     where ΔTA is the temperature difference between the two streams at end A, and ΔTB is the temperature difference between the two streams at end B. (Holds for parallel flow & also for counter flow) 36
  • 37. 37 Application of LMTD Once calculated, the LMTD is usually applied to calculate the heat transfer in an exchanger according to the simple equation:     Where Q is the exchanged heat duty (in watts), U is the heat transfer coefficient (in watts per kelvin per square meter) and A is the heat transfer surface area. Calculation of U may be quite complicated. 37
  • 38. 38 Design Considerations For efficiency, heat exchangers are designed to maximize the surface area of the wall between the two fluids, while minimizing resistance to fluid flow through the exchanger. The exchanger's performance can also be improved by the addition of fins or corrugations in one or both directions, which increase surface area and may STREAMLINE the fluid flow or induce turbulence 38
  • 39. 39 Driving Temperature The driving temperature across the heat transfer surface varies with position, but an appropriate mean temperature can be defined. In most simple systems this is the "log mean temperature difference" (LMTD). 39
  • 40. 40 A set of tubes is called the tube bundle and can be made up of several types of tubes: plain, longitudinally finned, etc. Shell and tube heat exchangers are robust due to their shape and are typically used for high- pressure applications. (with pressures greater than 30 bar and temperatures greater than 260°C). 40
  • 41. 41 Design Features •Tube diameter: Small tube diameter makes the heat exchanger economical and compact. However, it may foul up faster and the small size makes mechanical cleaning difficult. •To prevail over the fouling and cleaning problems, larger tube diameters can be used. •Thus to determine the tube diameter, the available space, cost and the fouling nature of the fluids must be considered. 41
  • 42. 42 •Tube thickness: The thickness of the wall of the tubes is usually determined to ensure: o There is enough room for corrosion o That flow-induced vibration has resistance o Axial strength o Availability of spare parts o Hoop strength (to withstand internal tube pressure) o Buckling strength (to withstand overpressure in the shell) Tube Thickness 42
  • 43. 43 Tube length: heat exchangers are cheaper when the shell diameter is smaller and length is more. Thus, the aim is to make the heat exchanger as long as physically possible whilst not exceeding production capabilities. However, the limitations are -the space available at the site. Also, it has to be remembered that long, thin tubes are difficult to take out and replace. Tube Length 43
  • 44. 44 Tube Pitch and Fins/corrugation •Tube pitch: when designing the tubes, it is practical to ensure that the tube pitch (i.e., the centre-centre distance of adjoining tubes) is not less than 1.25 times the tubes' outside diameter. •A larger tube pitch leads to a larger overall shell diameter which leads to a more expensive heat exchanger. Tube corrugation: this type of tubes, mainly used for the inner tubes, increases the turbulence of the fluids and the effect is very important in the heat transfer giving a better performance 44
  • 45. 45 Baffles Baffles are used in shell and tube heat exchangers to direct fluid across the tube bundle. They run perpendicularly to the shell and hold the bundle, preventing the tubes from sagging over a long length. They also prevent the tubes from vibrating. The most common type of baffle is the segmental baffle. The semicircular segmental baffles are oriented at 180 degrees to the adjacent baffles forcing the fluid to flow upward and downwards between the tube bundle. Baffle spacing is of large thermodynamic concern in shell and tube heat exchangers. Baffles must be spaced with consideration of pressure drop and heat transfer. 45
  • 46. 46 Baffles....contd. For thermo economic optimization the baffles are spaced at 20% of the shell’s inner diameter. Too closely spaced baffles cause a greater pressure drop because of flow redirection. Consequently if the baffles are spaced too far apart then there may be cooler spots in the corners between baffles. The baffles should be spaced such that the tubes do not sag. The other type of baffle is the disc and donut baffle which consists of two concentric baffles. The outer wider baffle looks like a donut, whilst the inner baffle is shaped as a disk. This type of baffle forces the fluid to pass around each side of the disk then through the donut baffle generating a different type of fluid flow. 46
  • 48. HIGH PRESSURE HEATER Design features ensure high reliability and availability associated with long term life and low maintenance. Independent desuperheating zone closures. Baffle configuration and spacing based on conservative mass and linear velocity criteria. Fully enclosed self-venting drains sub-cooling zone. Liberal sub-cooling zone entrance areas to permit low approach velocities which prevent flashing of saturated drains. Internal, centrally located venting arrangement to provide means of continuously venting condensing zone. Channel cover configurations for all nozzle layouts. Stainless steel impingement plates. 48
  • 50. H.P.Heater Details Note feed water entry from lower side and Steam entry from the top. Three sections – Desuperheating – Condensing - & Cooling. 50
  • 51. 3-Processes in HPH The feed-water heating process actually takes place in three distinct steps. First, the de-superheating zone cools the superheated steam to the point that the steam is saturated. Next, the condensing zone extracts the Latent Heat from the steam/water mixture to preheat the boiler feed-water passing through the tube side. Finally, a drain cooler is incorporated to capture additional energy from the liquid. The three heating processes all occur within a single heater. 51
  • 52. Effect of High / Low Level Lower final feed-water temperature occurs when a feed-water heater is withdrawn due to unreliable level input to the control system or when the level is too high or low. If the condition is a result of high feed-water heater level, there would be a decrease in feed-water heater temperature rise, a decreasing DCA (Drain Cooler Approach)temperature difference, and an increasing TTD (Terminal Temperature Difference). The inverse is true if feed-water heater levels are too low. In either case, risk of damage to hardware increases, heat transfer is impaired, and feed-water to the economizer is not at the required temperature. There are two probable responses to a low final feed-water temperature, neither of which is desirable: 52
  • 53. Operator response – Low feed water temperature Over-fire the boiler to increase temperature (level too high/low or out of service). This action will increase fuel consumption and emissions, as well as increase the gas temperature exiting the furnace. The increased gas temperature will increase the reheat and superheat sprays. Also, the steam flow through the IP and LP stages of the steam turbine will increase (when the heater is out of service), causing flashing and potential damage to the drain cooler section and possibly cause thermal damage to the tubes. 53
  • 54. Operator response – Low feed water temperature Open emergency drains to lower level (level too high). This option causes an immediate loss of plant efficiency and can cause damage to hardware if water is inducted into the extraction line. The worst case occurs when the water is inducted back into the steam turbine, causing a possible catastrophic failure. The best case is that the turbine water induction protection (TWIP) trips the unit, shutting the heater down and causing expensive loss of production and other related costs. 54
  • 55. Case Study Due to lower final feed-water temperature at a 500-MW coal-fired plant. The heat rate rose 47 Btu/kWh, adding $243,000 annually to the plant’s cost of fuel. Note that the case study does not take into account additional emissions cost, effects on boiler and turbine efficiencies, over-firing conditions, lost production, and other related factors, 55
  • 56. Level Control The feed-water heater, is a series of tubes carrying feed- water through a tank shell. Steam is injected into the shell and heat is transferred to the feed-water inside the tubes. The steam condenses in the shell, creating a liquid level of condensate in the heater. The level is controlled to create a seal and prevent blow- through of steam. The maximum thermal transfer between steam and the feed-water takes place when, the largest tube area is exposed to the steam without allowing steam blow-through. 56
  • 57. Level Control Condensate is allowed to drain from the shell through the normal drain. When the tubes become submerged in condensate, heat is transferred to the condensate rather than the tubes with the feed-water inside, resulting in poor heater efficiency. A relatively small increase in condensate level, (2-in to 4-in) over the minimum, greatly affects the heat rate (fuel efficiency) of the boiler. 57
  • 58. 58
  • 59. 59
  • 60. 60
  • 61. 61
  • 62. 62