Design Of Reinforced Concrete Structures ii
Two-Way Slabs
1
1. Inroduction
When the ratio (L/S) is less than 2.0, slab is called two-way slab, as shown in the fig.
below. Bending will take place in the two directions in a dish-like form.
Accordingly, main reinforcement is required in the two directions.
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
2
2.Types Of Two Way Slabs
3. Design Methods
Two-way slabs
Slabs without
beams
Flat plates
Flat slabs
Slabs with beams
Two-way edge-
supported slab
Two-way ribbed
slab
Waffle slabs
Two-way Edge-
supported ribbed
slabs
Design
methods
Simplified
Design Methods
Grashoff
method.
Marcus method
Egyptian Code
method
Direct Design
Method"DDM"
Equivalent
Frame Method
" EFM "
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
3
4. Direct Design Method "D.D.M"
Before Discussion Of this Method, we have to study some concepts:
1. Limitations:
1. Three or more spans in each direction.
2. Variation in successive spans 33% ( .
3. LL 2 DL
4. Column offset 10% in each direction.
5. L/B 2.
6. For slabs on beams, for one panel
.
2. Determination of Two way slab thickness:
 Case 1 : interior and edge beams are exist.
=
=
Where:
: is the largest clear distance in the longest direction of
panels.
: is the clear distance in the short direction in the panel.
=
=
Example for finding : for fig. shown:
For panel 1 …
For panel 5 …
So h to be used should be : hmin< h < hmax
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
4
 Case 2: interior beams are not existing, thickness can be found according to table 8.8,
page 339.
3. Estimating dimensions of interior and exterior beams sections:
Dimensions can be estimated from the following figures:
Where: b = beam width,
h = slab thickness,
a =beam thickness.
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
5
► Design Procedures
Discussion will be done to one representative strip in the horizontal and vertical
directions; the same procedure can be used for the other strips.
a- Determination of total factored Static Moment :
= Strip width /8
: total factored load in t/m2
.
= clear distance in the direction of strip, and not less than 0.65 .
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
6
b- Distribution of the total factored static moment to negative and positive moments:
I. For interior Spans:
According to the code, the moments can be distributed according to factores shown in
the figure:
II. For Edge Spans :
Static Mom. Mo can be distributed, according to factors given in the table 8.9, page 341.
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
7
c- Distribution of the positive and negative factored moments to the Column and middle
strips:
Note: width of column strip is equal to 0.25l1 or 0.25l2 which is smaller.
l1: length in the direction of strip, center to center between columns.
l2: length in the direction perpendicular to l1.
I. Determination of factored moments on column and middle strips:
 Finding α and βt:
 α =
α : is ratio of flexural stiffness .
Ib : Moment of inertia of the beam in the direction of strip… can be found from
fig.8.14 and fig.8.15, pages 310 and 311.
Is : Moment of inertia of slab = , where is slab thickness.
 βt = ,
βt: Ratio of torsional stiffness
and are the modulus of elastisity of concrete for beam and slab.
Note: βt is given only for edge
beams perpendicular to the strip
Note: α is given only for the
beams in the direction of the strip
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
8
C: Cross sectional constant defines torsional properties C =
X: smallest dimension in the section of edge beam.
Y: Largest dimension in the section of edge beam.
Note: the C relation is applicable directly for rectangular section only, but when used for
L-Shape beams, we should divide it to two rectangular sections and find C.
C "A" = C1 + C2 for A and C "B" = C1 + C2 for B.
C to be used = Max (C "A" , C "B" ).
When α and βt are found, factors for moment can be found from table 8.10 page 343 for
the column strip.
Notes:
 α l2/l1 = 0.0 , when there is no interior beams in the direction of strip under
consideration.
 βt = 0.0 , when there is no extirior “edge” beams perpendicular to the strip under
consideration.
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
9
After finding the moments on the column strip, Moments on the middle strip is the
remain.
II. For the moment on the beam “ if exist ” :
If: α l2/l1 ≥ 1 … The beam moment is 85% of the moment of the column strip.
α l2/l1 = 0 … there is no beam .. mom. = 0
0 < α l2/l1 < 1 … Interpolation have to be done between 0 and 85% to find percentage
of moment on the beam from that of the column strip.
** The Mom. on the remain part of column strip = Tot. Mom. on the column strip –
Mom. on the beam.
Summary:
1- Find Mo :
2- Distribute M0 into +ve and –ve Mom.
3- Distribute Mom. Into column strip and Middle Strip.
Column strip Middle Strip
4- Distribute Mom. In column strip into Mom. On beam and remained slab.
On beam On remained Slab
After calculating Moments, we can find the ρ, then Ast required
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
10
Example 1:
For the given data, design strip 1-2-3-4 of the two way slab for flexure.
Data:
Columns are 30cm X 30cm, Equivalent partitions load=250 Kg/m2
, Live Load = 400Kg/m2
,
= 280 kg/cm2
= 4200 Kg/cm2
, slab thickness = 16cm
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
11
Solution:
Thickness is given 16cm, no need to be checked.
1- Calculate total factored load Wu "t/m2
":
Wu = 1.4 (0.16 2.5 + 0.25) + 1.7 (0.4) = 1.59 t/m2
.
2- Determine The Total Factored Static Moment (Mo) :
Mo = = = 13.83t.m
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
12
3- Distribute Mo into +ve and –ve moments :
The total factored static moment was distributed according to Table "8.9" in your
text book as shown in the following Figure.
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
13
4- Moments on the column Strip :
Evaluate the constant and
 Evaluation of :
α = . "For beam in direction of strip"
For a/h=50/16=3.125 and b/h=30/16=1.875, f=1.4 (Fig. 8.14)
α = = 4.07
 Evaluation of :
βt = . " For edge beam perpendicular to direction of strip"
CA = = 208,909.55
CB = = 128,532.48
C = Max (CA or CB) = 207393.8
βt = = 0.97
After α and βt are calculated, factors for the moment of column strip can be found
from Table 8.10, page 343
α = 4.07 =4.88 1 , βt between 0 and 2.5 , = 1.2
 – Ve exterior moment Factor :
=1 =1.2 =2
βt = 0 100 100 100
βt = 0.97 0.903 0.8797 0.7866
βt = 2.5 75 69 45
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
14
 +Ve interior moment Factor :
=1 =1.2 =2
75 69 45
 -Ve interior moment Factor :
=1 =1.2 =2
75 69 45
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
15
5- Moments on the Middle Strip: "The remain moment":
6- Moment On Beam :
As α >1 …. Beam willl resist 85% of the column strip moment.
7- Moment On Remained Slab :
Design Of Reinforced Concrete Structures ii
Two-Way Slabs
16
By:
Eng. AbdUlla Taisir Al-Madhoun
Eng. Nour Nagi Al-Hindi
.
Notes:
 For each value of moment, can be calculated, then .
 Widths to used for design and ρ calculations are :
For the remained slab of column strip: b = 1.25-0.3=0.95m
For half middle strip: b= 3.15-1.25=1.9m
Beam = 0.3m
 Beam should be designed for shear, according to
specifications of code ACI 318"13.6.8", and reported in page
344 of your text book.

More Related Content

What's hot

Design of concrete Structure 2
Design of concrete Structure 2Design of concrete Structure 2
Design of concrete Structure 2SHARIQUE AHMAD
 
Design of two way slab
Design of two way slabDesign of two way slab
Design of two way slabsarani_reza
 
Design of columns axial load as per IS 456-2000
Design of columns  axial load as per IS 456-2000Design of columns  axial load as per IS 456-2000
Design of columns axial load as per IS 456-2000PraveenKumar Shanmugam
 
Design of columns biaxial bending as per IS 456-2000
Design of columns  biaxial bending as per IS 456-2000Design of columns  biaxial bending as per IS 456-2000
Design of columns biaxial bending as per IS 456-2000PraveenKumar Shanmugam
 
Design and detailing of flat slabs
Design and detailing of flat slabs Design and detailing of flat slabs
Design and detailing of flat slabs Godfrey James
 
Singly Reinforce Concrete
Singly Reinforce ConcreteSingly Reinforce Concrete
Singly Reinforce Concreteguest00bb06
 
WIND LOAD ON BUILDING AND STR.pdf
WIND LOAD ON BUILDING AND STR.pdfWIND LOAD ON BUILDING AND STR.pdf
WIND LOAD ON BUILDING AND STR.pdfSachin Kumbhar
 
Slope deflection method
Slope deflection methodSlope deflection method
Slope deflection methodAnik Mamun
 
Design of flat plate slab and its Punching Shear Reinf.
Design of flat plate slab and its Punching Shear Reinf.Design of flat plate slab and its Punching Shear Reinf.
Design of flat plate slab and its Punching Shear Reinf.MD.MAHBUB UL ALAM
 
Column Interaction Diagram construction
Column Interaction Diagram constructionColumn Interaction Diagram construction
Column Interaction Diagram constructionPritesh Parmar
 
Design of R.C.C Beam
Design of R.C.C BeamDesign of R.C.C Beam
Design of R.C.C BeamAr. Aakansha
 
Footing design
Footing designFooting design
Footing designYasin J
 
AITC Coupling Beam Design Procedure (20151106)
AITC Coupling Beam Design Procedure (20151106)AITC Coupling Beam Design Procedure (20151106)
AITC Coupling Beam Design Procedure (20151106)Fawad Najam
 

What's hot (20)

Design of concrete Structure 2
Design of concrete Structure 2Design of concrete Structure 2
Design of concrete Structure 2
 
Design of two way slab
Design of two way slabDesign of two way slab
Design of two way slab
 
Design of columns axial load as per IS 456-2000
Design of columns  axial load as per IS 456-2000Design of columns  axial load as per IS 456-2000
Design of columns axial load as per IS 456-2000
 
Design of columns biaxial bending as per IS 456-2000
Design of columns  biaxial bending as per IS 456-2000Design of columns  biaxial bending as per IS 456-2000
Design of columns biaxial bending as per IS 456-2000
 
Wind_Load
Wind_LoadWind_Load
Wind_Load
 
Deep beam
Deep beamDeep beam
Deep beam
 
Design and detailing of flat slabs
Design and detailing of flat slabs Design and detailing of flat slabs
Design and detailing of flat slabs
 
Singly Reinforce Concrete
Singly Reinforce ConcreteSingly Reinforce Concrete
Singly Reinforce Concrete
 
WIND LOAD ON BUILDING AND STR.pdf
WIND LOAD ON BUILDING AND STR.pdfWIND LOAD ON BUILDING AND STR.pdf
WIND LOAD ON BUILDING AND STR.pdf
 
Slope deflection method
Slope deflection methodSlope deflection method
Slope deflection method
 
Design of flat plate slab and its Punching Shear Reinf.
Design of flat plate slab and its Punching Shear Reinf.Design of flat plate slab and its Punching Shear Reinf.
Design of flat plate slab and its Punching Shear Reinf.
 
Column Interaction Diagram construction
Column Interaction Diagram constructionColumn Interaction Diagram construction
Column Interaction Diagram construction
 
M3l4
M3l4M3l4
M3l4
 
Design of R.C.C Beam
Design of R.C.C BeamDesign of R.C.C Beam
Design of R.C.C Beam
 
Footing
FootingFooting
Footing
 
Shear wall and its design guidelines
Shear wall and its design guidelinesShear wall and its design guidelines
Shear wall and its design guidelines
 
Design of One-Way Slab
Design of One-Way SlabDesign of One-Way Slab
Design of One-Way Slab
 
Footing design
Footing designFooting design
Footing design
 
AITC Coupling Beam Design Procedure (20151106)
AITC Coupling Beam Design Procedure (20151106)AITC Coupling Beam Design Procedure (20151106)
AITC Coupling Beam Design Procedure (20151106)
 
Three moment theorem
Three moment theoremThree moment theorem
Three moment theorem
 

Similar to Direct-Design-Method1.pdf

Design of Flat Slab and Bridges
Design of Flat Slab and BridgesDesign of Flat Slab and Bridges
Design of Flat Slab and BridgesAnanthakumar75
 
Design Of Flat Slab
Design Of Flat Slab Design Of Flat Slab
Design Of Flat Slab Abdul Sahid
 
Reinforced concrete Course assignments, 2019
Reinforced concrete Course assignments, 2019Reinforced concrete Course assignments, 2019
Reinforced concrete Course assignments, 2019JanneHanka
 
Reinforced concrete Course Assignments, 2023
Reinforced concrete Course Assignments, 2023Reinforced concrete Course Assignments, 2023
Reinforced concrete Course Assignments, 2023JanneHanka
 
Roof bar design- a case study
Roof bar design- a case studyRoof bar design- a case study
Roof bar design- a case studyTIKESHWAR MAHTO
 
Design of concrete structure 2 project-Loay Qabaha &Basel Salame
Design of concrete structure 2 project-Loay Qabaha &Basel SalameDesign of concrete structure 2 project-Loay Qabaha &Basel Salame
Design of concrete structure 2 project-Loay Qabaha &Basel SalameLoay Qabaha
 
Design of two way slabs(d.d.m.)
Design of two way slabs(d.d.m.)Design of two way slabs(d.d.m.)
Design of two way slabs(d.d.m.)Malika khalil
 
Lecture 6 7 Rm Shear Walls
Lecture 6 7 Rm Shear WallsLecture 6 7 Rm Shear Walls
Lecture 6 7 Rm Shear WallsTeja Ande
 
base plate in bending and anchor bolts in tension
base plate in bending and anchor bolts in tensionbase plate in bending and anchor bolts in tension
base plate in bending and anchor bolts in tensionabdul latief
 
Bar bending schedule (2)
Bar bending schedule (2)Bar bending schedule (2)
Bar bending schedule (2)ManimaranS17
 
DACS_UNIT-3- RCC Flat slab ARP.pptx
DACS_UNIT-3- RCC Flat slab ARP.pptxDACS_UNIT-3- RCC Flat slab ARP.pptx
DACS_UNIT-3- RCC Flat slab ARP.pptxAbhijeet Pabale
 

Similar to Direct-Design-Method1.pdf (20)

Design of Flat Slab and Bridges
Design of Flat Slab and BridgesDesign of Flat Slab and Bridges
Design of Flat Slab and Bridges
 
DESIGN OF FLAT SLABS
DESIGN OF FLAT SLABSDESIGN OF FLAT SLABS
DESIGN OF FLAT SLABS
 
Design Of Flat Slab
Design Of Flat Slab Design Of Flat Slab
Design Of Flat Slab
 
Reinforced concrete Course assignments, 2019
Reinforced concrete Course assignments, 2019Reinforced concrete Course assignments, 2019
Reinforced concrete Course assignments, 2019
 
Crack Width
Crack WidthCrack Width
Crack Width
 
Flat slab
Flat slabFlat slab
Flat slab
 
Presentation
PresentationPresentation
Presentation
 
8th Semester (June; July-2015) Civil Engineering Question Paper
8th Semester (June; July-2015) Civil Engineering Question Paper8th Semester (June; July-2015) Civil Engineering Question Paper
8th Semester (June; July-2015) Civil Engineering Question Paper
 
Reinforced concrete Course Assignments, 2023
Reinforced concrete Course Assignments, 2023Reinforced concrete Course Assignments, 2023
Reinforced concrete Course Assignments, 2023
 
Design of a circular raft for a cylindrical core
Design of a circular raft for a cylindrical coreDesign of a circular raft for a cylindrical core
Design of a circular raft for a cylindrical core
 
Roof bar design- a case study
Roof bar design- a case studyRoof bar design- a case study
Roof bar design- a case study
 
Strata control
Strata control Strata control
Strata control
 
Rectangular tank
Rectangular tankRectangular tank
Rectangular tank
 
Design of concrete structure 2 project-Loay Qabaha &Basel Salame
Design of concrete structure 2 project-Loay Qabaha &Basel SalameDesign of concrete structure 2 project-Loay Qabaha &Basel Salame
Design of concrete structure 2 project-Loay Qabaha &Basel Salame
 
Design of two way slabs(d.d.m.)
Design of two way slabs(d.d.m.)Design of two way slabs(d.d.m.)
Design of two way slabs(d.d.m.)
 
Lecture 6 7 Rm Shear Walls
Lecture 6 7 Rm Shear WallsLecture 6 7 Rm Shear Walls
Lecture 6 7 Rm Shear Walls
 
ppt.pptx
ppt.pptxppt.pptx
ppt.pptx
 
base plate in bending and anchor bolts in tension
base plate in bending and anchor bolts in tensionbase plate in bending and anchor bolts in tension
base plate in bending and anchor bolts in tension
 
Bar bending schedule (2)
Bar bending schedule (2)Bar bending schedule (2)
Bar bending schedule (2)
 
DACS_UNIT-3- RCC Flat slab ARP.pptx
DACS_UNIT-3- RCC Flat slab ARP.pptxDACS_UNIT-3- RCC Flat slab ARP.pptx
DACS_UNIT-3- RCC Flat slab ARP.pptx
 

Recently uploaded

University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdfKamal Acharya
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlysanyuktamishra911
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756dollysharma2066
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spaintimesproduction05
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLManishPatel169454
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)simmis5
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapRishantSharmaFr
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . pptDineshKumar4165
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...tanu pandey
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 

Recently uploaded (20)

Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Vivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design SpainVivazz, Mieres Social Housing Design Spain
Vivazz, Mieres Social Housing Design Spain
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 

Direct-Design-Method1.pdf

  • 1. Design Of Reinforced Concrete Structures ii Two-Way Slabs 1 1. Inroduction When the ratio (L/S) is less than 2.0, slab is called two-way slab, as shown in the fig. below. Bending will take place in the two directions in a dish-like form. Accordingly, main reinforcement is required in the two directions.
  • 2. Design Of Reinforced Concrete Structures ii Two-Way Slabs 2 2.Types Of Two Way Slabs 3. Design Methods Two-way slabs Slabs without beams Flat plates Flat slabs Slabs with beams Two-way edge- supported slab Two-way ribbed slab Waffle slabs Two-way Edge- supported ribbed slabs Design methods Simplified Design Methods Grashoff method. Marcus method Egyptian Code method Direct Design Method"DDM" Equivalent Frame Method " EFM "
  • 3. Design Of Reinforced Concrete Structures ii Two-Way Slabs 3 4. Direct Design Method "D.D.M" Before Discussion Of this Method, we have to study some concepts: 1. Limitations: 1. Three or more spans in each direction. 2. Variation in successive spans 33% ( . 3. LL 2 DL 4. Column offset 10% in each direction. 5. L/B 2. 6. For slabs on beams, for one panel . 2. Determination of Two way slab thickness:  Case 1 : interior and edge beams are exist. = = Where: : is the largest clear distance in the longest direction of panels. : is the clear distance in the short direction in the panel. = = Example for finding : for fig. shown: For panel 1 … For panel 5 … So h to be used should be : hmin< h < hmax
  • 4. Design Of Reinforced Concrete Structures ii Two-Way Slabs 4  Case 2: interior beams are not existing, thickness can be found according to table 8.8, page 339. 3. Estimating dimensions of interior and exterior beams sections: Dimensions can be estimated from the following figures: Where: b = beam width, h = slab thickness, a =beam thickness.
  • 5. Design Of Reinforced Concrete Structures ii Two-Way Slabs 5 ► Design Procedures Discussion will be done to one representative strip in the horizontal and vertical directions; the same procedure can be used for the other strips. a- Determination of total factored Static Moment : = Strip width /8 : total factored load in t/m2 . = clear distance in the direction of strip, and not less than 0.65 .
  • 6. Design Of Reinforced Concrete Structures ii Two-Way Slabs 6 b- Distribution of the total factored static moment to negative and positive moments: I. For interior Spans: According to the code, the moments can be distributed according to factores shown in the figure: II. For Edge Spans : Static Mom. Mo can be distributed, according to factors given in the table 8.9, page 341.
  • 7. Design Of Reinforced Concrete Structures ii Two-Way Slabs 7 c- Distribution of the positive and negative factored moments to the Column and middle strips: Note: width of column strip is equal to 0.25l1 or 0.25l2 which is smaller. l1: length in the direction of strip, center to center between columns. l2: length in the direction perpendicular to l1. I. Determination of factored moments on column and middle strips:  Finding α and βt:  α = α : is ratio of flexural stiffness . Ib : Moment of inertia of the beam in the direction of strip… can be found from fig.8.14 and fig.8.15, pages 310 and 311. Is : Moment of inertia of slab = , where is slab thickness.  βt = , βt: Ratio of torsional stiffness and are the modulus of elastisity of concrete for beam and slab. Note: βt is given only for edge beams perpendicular to the strip Note: α is given only for the beams in the direction of the strip
  • 8. Design Of Reinforced Concrete Structures ii Two-Way Slabs 8 C: Cross sectional constant defines torsional properties C = X: smallest dimension in the section of edge beam. Y: Largest dimension in the section of edge beam. Note: the C relation is applicable directly for rectangular section only, but when used for L-Shape beams, we should divide it to two rectangular sections and find C. C "A" = C1 + C2 for A and C "B" = C1 + C2 for B. C to be used = Max (C "A" , C "B" ). When α and βt are found, factors for moment can be found from table 8.10 page 343 for the column strip. Notes:  α l2/l1 = 0.0 , when there is no interior beams in the direction of strip under consideration.  βt = 0.0 , when there is no extirior “edge” beams perpendicular to the strip under consideration.
  • 9. Design Of Reinforced Concrete Structures ii Two-Way Slabs 9 After finding the moments on the column strip, Moments on the middle strip is the remain. II. For the moment on the beam “ if exist ” : If: α l2/l1 ≥ 1 … The beam moment is 85% of the moment of the column strip. α l2/l1 = 0 … there is no beam .. mom. = 0 0 < α l2/l1 < 1 … Interpolation have to be done between 0 and 85% to find percentage of moment on the beam from that of the column strip. ** The Mom. on the remain part of column strip = Tot. Mom. on the column strip – Mom. on the beam. Summary: 1- Find Mo : 2- Distribute M0 into +ve and –ve Mom. 3- Distribute Mom. Into column strip and Middle Strip. Column strip Middle Strip 4- Distribute Mom. In column strip into Mom. On beam and remained slab. On beam On remained Slab After calculating Moments, we can find the ρ, then Ast required
  • 10. Design Of Reinforced Concrete Structures ii Two-Way Slabs 10 Example 1: For the given data, design strip 1-2-3-4 of the two way slab for flexure. Data: Columns are 30cm X 30cm, Equivalent partitions load=250 Kg/m2 , Live Load = 400Kg/m2 , = 280 kg/cm2 = 4200 Kg/cm2 , slab thickness = 16cm
  • 11. Design Of Reinforced Concrete Structures ii Two-Way Slabs 11 Solution: Thickness is given 16cm, no need to be checked. 1- Calculate total factored load Wu "t/m2 ": Wu = 1.4 (0.16 2.5 + 0.25) + 1.7 (0.4) = 1.59 t/m2 . 2- Determine The Total Factored Static Moment (Mo) : Mo = = = 13.83t.m
  • 12. Design Of Reinforced Concrete Structures ii Two-Way Slabs 12 3- Distribute Mo into +ve and –ve moments : The total factored static moment was distributed according to Table "8.9" in your text book as shown in the following Figure.
  • 13. Design Of Reinforced Concrete Structures ii Two-Way Slabs 13 4- Moments on the column Strip : Evaluate the constant and  Evaluation of : α = . "For beam in direction of strip" For a/h=50/16=3.125 and b/h=30/16=1.875, f=1.4 (Fig. 8.14) α = = 4.07  Evaluation of : βt = . " For edge beam perpendicular to direction of strip" CA = = 208,909.55 CB = = 128,532.48 C = Max (CA or CB) = 207393.8 βt = = 0.97 After α and βt are calculated, factors for the moment of column strip can be found from Table 8.10, page 343 α = 4.07 =4.88 1 , βt between 0 and 2.5 , = 1.2  – Ve exterior moment Factor : =1 =1.2 =2 βt = 0 100 100 100 βt = 0.97 0.903 0.8797 0.7866 βt = 2.5 75 69 45
  • 14. Design Of Reinforced Concrete Structures ii Two-Way Slabs 14  +Ve interior moment Factor : =1 =1.2 =2 75 69 45  -Ve interior moment Factor : =1 =1.2 =2 75 69 45
  • 15. Design Of Reinforced Concrete Structures ii Two-Way Slabs 15 5- Moments on the Middle Strip: "The remain moment": 6- Moment On Beam : As α >1 …. Beam willl resist 85% of the column strip moment. 7- Moment On Remained Slab :
  • 16. Design Of Reinforced Concrete Structures ii Two-Way Slabs 16 By: Eng. AbdUlla Taisir Al-Madhoun Eng. Nour Nagi Al-Hindi . Notes:  For each value of moment, can be calculated, then .  Widths to used for design and ρ calculations are : For the remained slab of column strip: b = 1.25-0.3=0.95m For half middle strip: b= 3.15-1.25=1.9m Beam = 0.3m  Beam should be designed for shear, according to specifications of code ACI 318"13.6.8", and reported in page 344 of your text book.