Vortex Flow Meter Model: LUGB
Vortex Flow Meter
Version Number: 940000 REV.B
Operation Manual
Vortex Flow Meter
Table of Contents Table of Contents
1. General Information
1.1 Product Description
2.Technical Data
3. Cautions for Installation
3.1 Mounting Positons
3.2 Required Lengths of Straight Runs
3.3 Anti-Cavitation
3.4 Connections
4. Electrical Wiring
4.1 LUGB-N: Pulse Output, Explosion Proof Model
3
3
4
7
7
8
9
9
12
.........................................................................
....................................................................
................................................................................
...................................................................
.....................................................................
..............................................
...........................................................................
.............................................................................
.............................................................................
..............................
4.2 LUGB-A: Two wiring 4~20mA Output, No Local Display
4.3 LUGB-V: 4~20mA Output, Pulse Output, Local Display
5. Programming and Setup
5.1 LUGB-N: No Display; Pulse Output
18
18
.................
..................
..................................................................
...............................................
4.4 LUGB-D: Local Display ...............................................................
2
6. Troubleshooting
7. Quick Installation
32
33
.............................................................................
............................................................................
1.2 Operational Principle
1.3 Product Structure
...................................................................
........................................................................
1
3
3
16
13
12
12
5.2 LUGB-A: No Display; 4~20mA Output
5.3 LUGB-V: Local Display; 4~20mA/ Pulse Output
18
19
..............................
...........................................
5.4 LUGB-D with Temperature and Pressure Compensation................. 25
1.1 Application
1.2 Operational Principle
1.3 Product Structure
Application range (1) Gas; (2) Liquid; (3) Steam
Primary measured value Flow Rate
Secondary measured value
Reference conditions
Flow conditions similar to EN 29104
Medium: Water / Gas
Electrical conductivity: ≥ 300 μS/cm
Temperature: +10...+30°C / +50...+86°F
Inlet section: ≥ 10 DN
Operating pressure: 1 bar / 14.5 psig
Flow meter accuracy
For Liquid: 1.0% of rate
For gas and steam: 1.5% of rate
1. GENERAL INFORMATION
Warning
6.
7. Do not purge the flow meter with
compressed air.
8.
3 4
This manual will assist you in installing, using and maintaining Vortex Flowmeter. It is your
responsibility to make sure that all operators have access to adequate instructions about safe
operating and maintenance procedure.
2.TECHNICAL DATA
Measuring system
Measuring accuracy
Diagram 1
with compensation)
Volume flow; (Pressure and Temperature is available for model
3. When measuring flammable liquids, observe
precautions against fire or explosion.
4. When working in hazardous environments,
always exercise appropriate safety precautions.
1. Use only fluids that are compatible with the
housing material and wetted components
of your Vortex.
2. When handling hazardous liquids, always
exercise appropriate safety precautions.
5. Handle the sensor carefully. Even small
scratches or nicks can affect accuracy.
Stress-type vortex flow meter is a speed flow meter, widely used in petroleum, chemical,
power, light industry, power, heating and other industries.
During Vortex removal, liquid may spill.
Follow the manufacturer’s safety
precautions for clean up of minor spills
For best results, calibrate the meter at
least 1 time per year.
For your safety, review the major warnings and cautions below before operating your
equipment.
LUGB series Vortex flow meters are designed for measuring the volume/mass flow of liquids,
gases and steam based on Karman vortex principle.
Adopting advanced differential algorithm along with measurement of isolation, shielding and
wave filtering, LUGB series vortex flow meters have the advantages of immunity on vibration
and noise. Meanwhile, the liabilities of LUGB series vortex flow meters are well guaranteed by
unique sensor packaging technology.
The basic structure of the vortex flow meter is shown in Diagram 1. It is mainly composed of
body, probe, vortex generator, meter rod, condenser pipe and converter.
Measured value
Vortex Flow Meter Vortex Flow Meter
Features
Modular construction
The measurement system consists of a flow sensor and a signal
converter. It is available as compact and as separate version.
N Type: 24V DC; Pulse output; No display; Ex
A Type: 24V DC; 4-20mA output; No display; Ex
V Type: 24V DC; 4-20mA/Pulse output (V type is only for Gas/
Steam application); Digital display; Ex
D Type: 24V DC; 3-wire 4-20mA/Pulse output; Temperature &
Pressure Compensation; Digital display; Ex
Notice: 1) Modbus RS485 is optional for C、V、D series
2) Dual power(24V DC+ Battery) is optional for C、V、D
series
Connection
Flange: DN15-DN300
Wafer: DN15-DN300
Measurement ratio Standard – 10:1
Temperature
Process temperature
T1 Level: -20...+70°C
T2 Level: -20...+250°C
T3 Level: -20...+350°C
Ambient temperature
(all versions)
Standard (with aluminum converter housing):
-10…+55°C
Storage temperature -20...+70°C
Pressure
EN 1092-1
DN200…DN300: PN10
DN100…DN200: PN 16
DN15…DN80: PN 25
Other pressures on request
ASME B16.5
1/2”
...8": 150 lb RF
Other pressures on request
JIS
1/2”
...8": 10 K
Other pressures on request
Sensor housing
SS304
Other materials on request
Flanges
Flange Connection: SS304
Wafer Connection Mating(Flange: Carbon Steel)
Converter Housing
Installation
Take care that flow sensor is always fully filled
Flow direction
Forward
Arrow on flow sensor indicates flow direction.
Inlet run ≥ 10 DN
Outlet run ≥ 5 DN
EN 1092-1 DN15...300 in PN 6...25
ASME 1/2”…12" in 150 lb RF
JIS 1/2”…12” in 10...20K
Design of gasket surface RF
Other sizes or pressure ratings on request
Wafer DN15…DN300
Design
Operating conditions
Installation conditions
Process connections
Materials
5 6
converter
Compact version
for Installation"
For detailed information see chapter "Cautions
Standard: polyurethane coated die-cast aluminum
Vortex Flow Meter Vortex Flow Meter
Flange
Measurable flow rate range
Nominal Diameter Liquid Gas
(mm) (In.)
3
Flow (m /h) 3
Flow (m /h)
15 1/2” 1.2 to 6.2 5 to 25
20 3/4” 1.5 to 10 8 to 50
25 1” 1.6 to 16 10 to 70
40 1-1/2” 2.5 to 25 22 to 220
50 2” 3.5 to 35 36 to 320
65 2-1/2” 6.5 to 65 50 to 480
80 3” 10 to 100 70 to 640
100 4” 15 to 150 130 to 1100
125 5” 25 to 250 200 to 1700
150 6” 36 to 380 280 to 2240
200 8” 62 to 650 580 to 4960
250 10” 140 to 1400 970 to 8000
300 12” 200 to 2000 1380 to 11000
Pipes must be fully filled with liquids. It is essential that pipes remain fully filled at all times,
otherwise flow rate indications may be affected and measurement errors may be caused.
Warning:Precaution for direct sunshine and rain when the meter is installed outside.
Flow altering device such as elbows, valves and reducers can affect accuracy. See
Install the meter with enough room for future access for maintenance purposes
Avoid all pipe locations where the flow is pulsating, such as in the outlet side of piston or
★
Avoid locations near equipment producing electrical interference such as electric motors,
★
★
Diagram 2 Typical Flow Meter System Installation
Avoid Air Bubbles. If air bubbles enter a measurement pipe, flow rate indications may be affected and
3.CAUTIONS FOR INSTALLATION
3.1 Mounting Positions
measurement errors maybe caused.
diaphragm pumps
3.2 Required Lengths of Straight Runs
diagram 2 for typical flow meter system installation
7
transformers, variable frequency, etc.
8
Ex
15×D 5×D
A. Reduced Pipe
5×D
Ex
25×D 5×D
B.Two Elbows, In plane
5×D
50×D 5×D
C. Regulating Valve
5×D
25×D 5×D 5×D
40×D 5×D 5×D
20×D 5×D
D. Expanded Pipe E.Two Elbows, Out of plane F. One Elbow
8
Note:The flow range above is for reference only. Consult the factory if you have special
requirement. Refer to the nameplate or certificate for actual flow range.
Ex
Ex
Ex
Ex
Ex
Ex
Ex
Ex
Ex
Ex
Vortex Flow Meter Vortex Flow Meter
★
★
(Correct)
h>0
h
(Incorrect)
(Correct)
h>0
h
(Incorrect)
Mounting Positions
(Correct)
(Incorrect)
(Correct) (Incorrect)
Valve
Avoiding Air Bubbles
DIN PN16 Flange Meter Dimensions
Size Code A
DIN Flange
Pressure
Rating
Flange
Diameter
(B)
Bolt Hole
Diameter
Bolt Circle
Diameter
(PCD)
Bolt Hole
Quantity
(Inch) (mm) (mm) Mpa (mm) (mm) (mm)
1/2" 15 180 1.6 95 14 65 4
3/4" 20 180 1.6 105 14 75 4
1" 25 180 1.6 115 14 85 4
1-1/4" 32 180 1.6 140 18 100 4
1-1/2" 40 180 1.6 150 18 110 4
2" 50 180 1.6 165 18 125 4
2-1/2" 65 200 1.6 185 18 145 4
3" 80 200 1.6 200 18 160 8
4" 100 200 1.6 220 18 180 8
5" 125 220 1.6 250 18 210 8
6" 150 220 1.6 285 22 240 8
8" 200 220 1.6 340 22 295 12
10" 250 250 1.6 405 26 355 12
12" 300 300 1.6 460 26 410 12
Note: For model with temperature and pressure compensation, the flowmeter length should be
increased 50mm compared to the value (A) in table above. 10
9
★
★ Downstream: allow a minimum straight pipe length at least 5 times the internal diameter of
the pipe. For example, with the 50mm pipe, there should be 250mm of straight pipe
immediately upstream. Desired upstream straight pipe length is 500mm.
The recommended guidelines are given to enhance accuracy and maximize performance.
Distance given here are minimum requirements; Double them for desired straight pipe lengths.
★
Special Notice
★ When the fluid is liquid, to ensure accurate measurement, drain all air from the system
3.3 Anti-Cavitation
pressure) of at least 1.25 times the vapor pressure, plus 2 times the pressure drop through the
Formula 1: Pb ≥ 1.25×Pv + 2× (Pin – Pout)
In formula 1: (Pb: Back pressure; Pv: Vapor Pressure; Pin: Inlet Pressure; Pout: Outlet Pressure)
Create backpressure by installing a control valve on the downstream side of the meter at the
proper distance detailed above.
When the meter contains removable coverplates. Leave the coverplate installed unless
accessory modules specify removal. Don’t remove the coverplates when the meter is
powered, or electrical shock and explosion
Cavitation can be caused by entrained air. An amount higher than about 100 mg/l of entrained
air or gas can produce error. In addition, cavitation can be caused by too little backpressure
on the flow meter. For our Vortex flow meters, you should provide a backpressure (downstream
flow meter. See formula 1.
before use
Take care that flow sensor is always fully filled
For detailed information see chapter "Cautions for Installation"
Flow direction
Forward
Arrow on flow sensor indicates flow direction.
Inlet run
Outlet run
≥10DN
≥5DN
Installation
Upstream: allow a minimum straight pipe length at least 10 times the internal diameter of
the pipe. For example, with the 50mm pipe, there should be 500mm of straight pipe
immediately upstream. Desired upstream straight pipe length is 1000mm.
3.4 CONNECTIONS
3.4.1 Flange Connection
hazard can be caused.
PCD
B
A
Vortex Flow Meter Vortex Flow Meter
Diameter
D (mm)
Pipe
Specification
H
(mm)
L
(mm)
L0
(mm)
D1
(mm)
D2
(mm)
15 Φ19×1.5 290 116 80 68 135
20 Φ26×3 290 116 80 68 135
25 Φ32×3.5 290 116 80 68 135
40 Φ49×4.5 295 116 80 80 140
50 Φ59×4.5 300 116 80 88 145
65 Φ74×4.5 308 116 80 105 165
80 Φ89×4.5 315 116 80 120 180
100 Φ109×4.5 328 118 80 148 210
125 Φ133×4.5 340 124 85 174 235
150 Φ159×4.5 351 135 90 196 270
200 Φ219×9 378 150 105 250 325
250 Φ273×11 402 166 120 300 375
300 Φ325×12 428 185 135 350 425
4. ELECTRICAL WIRING
Terminal Configuration
Terminal Wiring
Warning: Electrical Hazard Disconnect power before beginning wiring.
4.1 LUGB-N: Pulse Output, Explosion Proof Model
4.2 LUGB-A:Two-wire 4-20mA Output, No Local Display
Terminal Wiring
Terminal Symbols Description
+ Power Supply: “24V+”
- GND
Pulse Output
3.4.2 Wafer Connection
12
11
Take care that flow sensor is always fully filled
For detailed information see chapter Cautions for Installation
Flow direction
Forward
Arrow on flow sensor indicates flow direction.
Inlet run
Outlet run
≥10DN
≥5DN
Installation
Terminal Symbols Description
+A Power Supply: “24V+”
-B Current Output
Vortex Flow Meter Vortex Flow Meter
LUGB-N
Explosion Proof
Terminal Configuration
LUGB-A
GND
24V+ PLC Input
Terminal
+A -B
4.3.2 Wiring Description
(1) 2 wire 4-20mA output
(2) 3 wire 4-20mA output
(3) Pulse Output/ Scaled Pulse Output
OC
DC 24V
14
13
4.3 LUGB-V: Local Display
4.3.1 Terminal Board of V Type
X
X
X
X
DC 24V
mA
﹢
X
X
X
DC 24+
COM
4-20mA
Iout
DC 24+
COM
Fout_C
RL
-
DC 24V
X
X
DC 24+
4-20mA
mA
﹢ -
Iout
X
X
RL
DC 24V
DC 24+
COM
Fout/ Fout_C
X
X
X
X
X
X
NPN
Vortex Flow Meter Vortex Flow Meter
1
2
3
4
5
6
7
8
9
10
11
COM
+24V
lout
Fout
Fout_C
AL
AH
C_KEY
485_A
485_B
GND
COM
PE
GND
COM+PE
PE+GND
NPN
PNP OC
24V
Lithium
Battery
Battery socket
PNP output NPN output OC output
The PNP, NPN and OC output could be chosen by
shorten the followingterminals.
If the signal is interfered at working site, please try to
short the terminals as following drawing(a). After “a”
step, if the situation is not improved, please short the
terminals as drawing(b)
a b
Wire terminals NPN
PNP OC
24V NPN
PNP OC
24V NPN
PNP OC
24V
(4) RS485 Communication
15 16
RL
DC 24V
DC 24+
COM
Fout_C
X
X
X
X
X
X
PNP
DC 24V
X
X
X
X DC 24+
COM
485_B
485B
485_A
485A
R
485A
485B Note
Terminal Description
Terminal Symbols
4-20mA Current Output
Frequency or scaled pulse output
24V DC+
Platinum Resistance Input
Pressure Sensor Input
Battery+
Battery -
14
24V DC -
R 485-
S
R 485+
S
1
2
3
4
5
6
7
8
9
10
11
12
13
B-
A+
Iout
GND
Fout
V+
TRH
TRL
PIH
PVH
PVL
PIL
3V6+
3V6-
Terminal No.
Connect Pt100 or Pt1000
platinum resistance at
both ends
PIH and PIL connect IN +
and IN- of pressure sensors;
PVH and PVL connect mV
output VO + and VO- of
pressure sensors
Terminal No.
4.4 LUGB-D: Local Display
4.4.1 Three-Wiring Terminal Description
TRH TRL PIH PVH PVL PIL
1 2 3 4 5 6 7 8 9 10 11 12
Iout GND Fout V+
B- A+
485 Iout GND Fout V+
T
mA
3 2 1
PH
R-B
PL
P
13
14
3V6
3V6
ON
KBAT
OFF
Battery
Jumper Switch(1)
Jumper Switch(2)
Diagram 5-1 Three-wire 4-20mA output terminal board
Vortex Flow Meter Vortex Flow Meter
4.4.2 Three-Wiring Output Wiring Description
(1) Three-wire 4-20mA current output wiring instructions
Diagram 5-2 Three-wire 4-20mA current output wiring diagram
Terminal No.
X
DC 24V
mA
﹢
X
X
X GND
4-20mA
Iout
-
Diagram 5-3 Pulse output wiring diagram
(3) RS485 communication wiring instructions
RL
DC 24V
V+
GND
Fout
X
X
X
X
X
X
NPN
(2) Pulse output wiring instructions
DC 24V
X
X
X
X V+
GND
B-
485B
A+
485A
R
485A
485B
Diagram 5-4 RS485 communication wiring diagram
5.1 LUGB-N: No display; Pulse Output
Customer should set the correct K-factor into PLC or Flow totalizer in order to get the correct
flow rate.
5.2 LUGB-A: No display; 4-20mA Output
Only perform the Zero Point Calibration where it's necessary.
All flowmeters are tested and calibrated prior to leaving the factory, and the unique
K-factor is provided on the calibration certificate. Keep the calibration certificate well
5. PROGRAMMING AND SETUP
to avoid the loss of K-factor.
5.2.1 Zero Point Calibration
(1)
(2) Put high accuracy amperometer into the circuit loop as series connection.
(3) Adjust the potentiometer W502 to make sure the display on amperometer is 4mA.
5.2.2 Full Scale Calibration: It’s ONLY available for factory; Return the flowmeter to factory
for full scale calibration where is applicable.
Shut off the value where the flowmeter is installed, ensure there is no flow rate in pipe.
17 18
Vortex Flow Meter Vortex Flow Meter
5.3 LUGB-V: Local Display; 4~20mA/ Pulse Output
Note: all menus are present in all signal converter versions, but some parameter settings
are ONLY valid for specified models.
5.3.1 Display and Key
Section 1: Functional region which consists of battery situation, communication,
current, frequency, flow percentage (Temperature could be available on request)
3
Section 2: Units section which consists of 10 units: m /h, L/h, L/min, US Gal/min,
3
UK Gal/min, US Gal/h, UK Gal/h, kg/h, t/h, ft /h
Section 3: Flow rate (7 digital figure upper line)
Section 4: Alarm sign which consists of SET prompt and alarm prompt
Section 5: Total flow (11 digital figure lower line) with two decimal places
Five Sections on Display Screen
Buttons
Interface buttons (four keys)
Operation
Back to main
menu
Turn to previous
menu
Back to main
menu
Buttons
Interface Buttons
Turn page/Confirm
Move Cursor
Increase number/ Turn page
Exit
Menu
Main menu
Sub-menu
Password Menu
Settable Menu
Un-settable
menu
Go to sub-menu
Go to password menu
a. False or No password
will go to the next
menu
b. Correct password:
The parameter is
settable.
Set/Save
Turn to next menu
×
×
×
Move
cursor
Move
cursor
×
×
×
Back to main
menu
Set parameter
Cancel the
setting and
back to main
menu
a. Settable status:
increase number
or choose number;
b. Un-settable
status:Turn to
previous menu.
19 20
Section 1
Section 2
Section 3
Section 4
Section 5
Vortex Flow Meter Vortex Flow Meter
code Functions Parameters Note
0000
Password
Frequency
display
Password input
The second line is original
frequency
The third line is corrected
frequency/signal intensity
4 digital figure
Up key can be
used to switch
Normal display
Passwords
Display working condition, flow
rate, total flow
Note: It will display“0000”before input password. If the password is incorrect, it will go to
P1 menu automatically under un-settable status.
Type Passwords Note
User password
Engineer password
Total flow reset
Storage factory defaulted
Reload factory defaults
Total flow set
Fixed current output
1234
1010
5555
5678
1111
9999
0101
5.3.2 Parameters Set
Passwords
Main menu
Sub-menu
Passwords Code Functions Parameters Note
1234
Unit
P1
P2
P3
P4
P5
P6
P7
Damping Time
Maximum Flow
Rate
Minimum Flow
Rate
Max frequency
Output
Relative
Density
Frequency
Output Mode
0- m³/h
1- L/h
2- L/min
3- US Gal/min
4- UK Gal/min
5- US Gal/h
6- UK Gal/h
7- kg/h
8- t/h
9- ft³/h
01-99s
Maximum Flow settings, the unit
corresponds to the flow.
Minimum flow settings, the unit
corresponds to the flow.
The upper limit setting of
measuring frequency
Absolute density of medium,
Unit: kg/m3
0- Shut down and keep low level
1- Negative pulse correction
frequency
2- Positive pulse correction
frequency
3- Negative scaled pulse
4- Positive scaled pulse
Other parameters setting,
the variables associated
with units will be related
automatically,according
to the units of P1 to
calculate,such as total
flow,flow rate,scaled
pulse and so on.
To slow flow changes and
prevent jump
Exceed the maximum flow,
showing the imum flow.
When the flow rate is lower
than minimum flow rate, the
flow rate will show “0” .
When it exceeds the upper
limit, it will display max
value.
Use quality units It will be
used in the calculation
This parameter just aims
at Fout_c port operation,
Fout is not restricted by
this menu.
21 22
P8
P9
P10
Scaled-pulse
Output
Pulse Width
Communication
0.001, 0.01, 0.1, 1, 10, 100, 1000
1 ~ 2000 ms
0: RS485 1: Hart
Unit is in accord
with P1 menu.
The width setting
of scaled pulse
1: It’ s available to
current output with
HART version.
Vortex Flow Meter Vortex Flow Meter
It will display “1234”
It will display “1010”
It will display “5555”
It will display “5678”
It will display “1111”
It will display “9999”
It will display “0101”
P11
P12
P13
P14
Communication
Parameter
High Limit
Alarm
Low Limit Alarm
Backlight
R 485
S
Address
Baud Rate
Verification
Data Length
Stop Bits
Length
Address
Switch Settings
HART
Alarm Level
Alarm Value
Switch Settings
Alarm Level
Alarm Value
Working Mode
Brightness Setting
0-255
1200, 2400,
4800, 9600,
19200
N, O, E
7, 8
1, 2
0-255
Yes
no
HIGH
LOW
0-100%
Yes
no
HIGH
LOW
0-100%
0- Off mode
1- Automatic
mode
2- On mode
0-30%
1-70%
2-100%
No verify、Odd fy、
Even verify
On
Close
High Level
Low Level
Alarm Value setting,
corresponding to flow
rate
Alarm Value
On
Close
High Level
Low Level
2:2-wire power supply
shuts down; 3-wire
power supply normally
opens; battery powered
button turns off the
delay. Long press Esc
key to switch 0 mode
and 1 mode, searching
network.
Passwords Code Functions Parameters Note
9999
1010
0101
P15
P16
~
P23
P24
P25
P26
P28
P27
P29
P30
P31
P32
P33
P34
Total Flow
Linearization
of the
flowcurve
Correct
Coefficient
Diameter
Medium
Min vibration
strength
Max vibration
strength
Min vibration
frequency
Max vibration
frequency
Min working
frequency
Max working
frequency
Min signal
intensity
Fixed current
output
Modifying total flow value
The first line is corrected
frequency,the second line is
coefficient error P16-P23
F1~F8:eight coefficient
modification
Wn=Kn / KP(n:1~8)3
The first line shows the
corrected frequency;the second
line shows the meter coefficient,
and the unit of coefficient is
pulse/m³
Selecting the diameter of body
and sensor
0- Gas
1- Liquid
The collection value in second
line in the process of learning
can be manually changed.
The third line shows the strength
of the current signal.
The collection value in second
line in the process of learning
can be manually changed.
The third line shows the
frequency of the current signal.
Lowest acceptable signal
frequency
The third line shows the current
signal frequency.
Highest acceptable signal
frequency
The third line shows the current
signal frequency.
Lowest acceptable signal
frequency
The third line shows the current
signal intensity.
Input Range:0-99
Effective Value:4-20
Unit:mA
F1 must be started,and
F2-F8 are started in proper
order. If the factor is 0, this
point and following
corrected points should be
stopped.
It could be any of the
coefficient (Kn) from
F1~F8 or Max one or
Average.
Unit:mm
the type selection of
measured fluid
P27-P30 Self learning
antivibration :Continue
to press the up button 5
seconds,and the
countdown is completed
in 60 seconds.
Notice: this operation is
prohibited when there is
flow rate.
Meter working area setting
Instruction: in the pipeline
of having slight vibration,
it can significantly
enhance the capacity of
resisting disturbance
through the three screen
parameter settings and
strict limit of effective
range.
The utility model is suitable
for the current loop test,
the system adjustment and
the instrument calibration.
23 24
Passwords Code Functions Parameters Note
1234
Vortex Flow Meter Vortex Flow Meter
5.4 LUGB-D with Temperature and Pressure Compensation
5.4.1 The Basic Structure of Converter
Diagram 6-1 The basic structure of converter
5.4.2 Key Description
Key Key Description
Note: Press“+/S”(left key) and“/E”(right key) together to switch between Measuring Mode
and Secondary Measuring Mode.
+/S
/E
Short press: Page Down key, Increasing the Number Key
Long press: At modification mode,long press can cancel the modification;
while at non-modified mode, long press can exit to the secondary mode.
Short press: Page Up key, Shift Key
Long press: At modification mode,long press can save the modification;
while at non-modified mode, long press can enter to the modified mode.
5555
5678
1111
Total flow
reset
Storage
factory
defaulted
Reload
factory
defaults
Save factory defaults
Reload factory defaults
Backup current settings
Restore factory
parameters from backup
area
5.4.4 Secondary Measuring Mode Description
5.4.5 Password Mode Description
5.4.3 Measuring Mode Description
Enter the Password Password Function Note
22 Enter the user menu User Menu
33 Enter the engineering
menu
The engineer menu contents must have
been set by the operator with professional
knowledge
44
Flow meter is set and calibrated by the
factory, and after the factory, this kind of
parameter setting can be modified only
when it is equipped with appropriate
equipment conditions, otherwise it will
lead to flow meter measurement error or
failure.
1000000. 0m³
1000. 0
m³/h
T= 25.5℃
P=101.3KPa
Total Flow
Measuring Mode
Percentage
Pressure
Temperature
Flow Rate
Flow rate’s
Unit
Secondary Measuring Mode
Password: 00
Iout= 12. 000mA
Fout=500. 00Hz
Signal
Frequency
Current
Output
Frequency
Output
Fin= 500. 0Hz
Input Password
Enter the factory menu
25 26
Passwords Code Functions Parameters Note
Vortex Flow Meter Vortex Flow Meter
5.4 LUGB-D with Temperature and Pressure Compensation
5.4.6 Menu Function Description
NO. Function Setting/Description
P1
Flow rate's Unit
(Default: 0)
P2
Algorithm Selection
(Default: 0)
0: Volume Flow
1: Mass Flow
2: Normative Volume Flow
3: Gas Volume Flow
4: Gas Mass Flow
5: Saturated Steam Temperature Compensation
6: Saturated Steam Pressure Compensation
7: Superheated Steam Temp. and Pressure Compensation
P3
3
K-Factor [P/m ]
XXX.XXXXXXXX
Flowmeter's K-Factor
P4
3
Fluid Density (kg/m )
XXXX.XXXX Default:
1000.0
This menu should be set when Algorithm
3
Selection = 1 or 3 Unit: Kg/m ;
P5
Max. Flow Rate
XXXXXX.XX
This menu must be set and can't be 0.
Unit is same as Flow rate's Unit
P6
Low Flow Cutoff %
XX.X
Value: 0-20%
Default: 1%; which means the flow will be
cut when it’s less than 1%Max Flow
P7
High Flow Alarm
XXXXXX.XX
This menu must be set and can't be 0.
Unit is same as Flow rate's Unit
1: English
P8
Low Flow Alarm
XXXXXX.XX
This menu must be set and can't be 0.
Unit is same as Flow rate's Unit
P9
Damping
Time
Value: 2-32
The damping time for current output and frequency
Default: 4S
P10 R 485 Address
Value: 1-254
Default: 0
P11
When Reset Total Flow is required, input password “70” and
press “/E”
(1) User Menu
Set the instantaneous flow units, according to the flow
algorithm type to select.
Optional for:
3 3
Volume Units:m /h;m /min; Liter/h; Liter/min
Mass Units:ton/h;ton/min;kg/h;kg/min
Password: Reset
Total Flow
S
NO. Function Setting/Description
P1 Language English
P2 Pulse Output Type Select the correct pulse output
P3 Scaled Pulse Output
Only valid for pulse output; 0 is not permit
Optional for:0.00001;0.0001;0.001;0.01;0.1;1.0;
10.0;100.0
P4 Communication
Set the Modbus communication baud rate
Optional for:4800;9600
P5
Communication
Switch
Set whether to open the Modbus communication function
Optional for: Off; On
P6 Pressure Display Set whether to display fluid pressure.
P7 Default Pressure For only temperature compensation type
P8 Reference Pressure
P9 Temperature Display Set whether to display the fluid temperature
P10 Default Temperature For only pressure compensation type
P11
Temperature Sensor
Type
Pt100
Pt1000
P12
Temperature at
standard state
(Standard Temperature: 0
Standard Temperature: 20
P13
-10 : normal display
-20 : display refresh every 8 second
P14
The range of flow percentage Qi: 0 to 120%; The range of
flow coefficient Ci: 0.8 to 1.2
Flow Q0-Q4 (15,30,50,70,100%) the 5 points instrument
correction coefficient sets 5 points: C0-C4 by flow order.
C=Standard flow/displayed flow
(2)Engineering Menu
At the password input mode, enter the password 33 into the engineering menu, and the
various menu functions and the meanings of parameters are as follows:
(1) Absolute Pressure Sensor: 0
(2) Gauge Pressure Sensor: Local Atmospheric Pressure
(Unit: Kpa)
Converter Ambient
Temperature
Flow Correction
Factor
27 28
Vortex Flow Meter Vortex Flow Meter
(3) Setup Menu
In the password input state, enter 44 password into the setup menu, and the various menu
functions and parameters are as follows:
NO. Function Setting/Description
P1
P2
P3
P4
P5
P6
P7
P8
P9
Select flow signal type. According to the vortex signal in the low frequency LF,
medium frequency MF, high frequency HF area, select input capacitance match
and the low frequency LF has better anti-interference performance.
Select signal gain G = 3 good anti-interference performance, G = 12 can be
used to measure lower flow or for high temperature probe. Optional For: G = 3,6,
9,12 four types;
Manual Type: 1 | 2,3 | 4,5 | 6,7 | 8,9 | 10,13 | 14 six groups, KSG-4 = ON is a large
value.
Set the lower voltage cut by Vpp, unit: mV
Manual Type: by the KSG1-2-3 bit, set the sensitivity SB to 2-8 according to 1 +
ON = 1,2,4
Choose signal spectrum(multiple of 25). Optional For:
0=1.6-45Hz
1=2.4-65Hz
2=3.6-90Hz
3=4.8-120Hz
4=6.4-160Hz
5=8.8-220Hz
6=11-275Hz
7=14-350Hz
Select the instrument signal processing output mode: when the signal is good,
you can choose automatic mode; when the signal is poor, you can choose
digital mode.
Optional: Automatic Mode; Digital Mode
Select manual or digital menu for manual circuit
Select normal or anti-interference operation mode. Anti-noise mode has a
wider range of signal removal judgments.
Optional: Standard Mode; Anti-noise Mode
Set the signal calibration type
Optional for:
Low zone 0-1 / 4; High zone 1 / 4-1 / 2; Measured noise 5%; Measured noise
10%; Measured noise 15%;
Confirm the entry into the Flow Factor Correction submenu, as shown in the
following table.
(1) Absolute Pressure Sensor: 0
(2) Gauge Pressure Sensor: Local Atmospheric Pressure (Unit: KPa)
8=18-450Hz
10=28-700Hz
9=22-550Hz
11=34-850Hz
12=42-1050Hz
13=52-1300Hz
14=64-1600Hz
15=96-2400Hz
Signal
Selection
Gain
Select
Lower limit
Cut
Frequency
Range
Selection
Mode of
Working
Anti-noise
Selection
Signal
Calibration
Selection
50Hz Cut
K- Factor
Correction
NO. Function Setting/Description
P9.1 Correction Switch
Set the flow coefficient linear correction switch
Optional for: Off; On
P9.2
The Frequency of
Correction point 1
Set the frequency of the first correction point in Hz;
The default value is: 1/5 + band lower limit frequency of
frequency band frequency range
P9.3
The Coefficient of
Correction point 1
Set the corrected flow coefficient K1 corresponding to the
frequency of the first correction point.
The default value is the Flow Factor value in the User menu
P9.4
The Frequency of
Correction point 2
Set the frequency value of the second correction point in Hz;
The default value is 2/5 + band lower limit frequency of
frequency band frequency range
P9.5
The Coefficient of
Correction point 2
A correction flow coefficient K2 corresponding to the
frequency of the second correction point is set
The default value is the Flow Factor value in the User menu
P9.6
The Frequency of
Correction point 3
Set the frequency of the third correction point in Hz;
The default value is 3/5 + band lower limit frequency of
frequency band frequency range
P9.7
The Coefficient of
Correction point 3
Set the corrected flow coefficient K3 corresponding to the
frequency of the third correction point.
The default value is the Flow Factor value in the User menu
P9.8
The Frequency of
Correction point 4
P9.9
The Coefficient of
Correction point 4
Set the correction flow coefficient K4 corresponding to the
frequency of the fourth correction point.
The default value is the Flow Factor value in the User menu
P9.10
The Frequency of
Correction point 5
Set the frequency value of the first correction point in Hz;
The default value is frequency band upper limit frequency
P9.11
The Coefficient of
Correction point 5
Set the correction flow coefficient K5 corresponding to the
frequency of the fifth correction point
The default value is the Flow Factor value in the User menu
(4) K-Factor Correction Menu
29 30
Set the frequency value of the 4th correction point in Hz; The
default value is Frequency band frequency range *4/5+ band
lower limit frequency
Vortex Flow Meter Vortex Flow Meter
NO. Function Setting/Description
1
Initial Setting based
on different password
70: save current parameter setting as initial value and save
into EEPROM Register
90: Backup all parameters to MCUF Register
79: Reload the parameter setting from MCUF to EEPROM
2 Pt100 Calibration
Connect accurate 100 Ohm Resistor and perform the
calibration
3 Pt200 Calibration
Connect accurate 200 Ohm Resistor and perform the
calibration
4 Pt1000 Calibration
Connect accurate 1000 Ohm Resistor and perform the
calibration
5 Pt2000 Calibration
Connect accurate 2000 Ohm Resistor and perform the
calibration
6 Max. Fluid Pressure Set the Max. Fluid Pressure
7
Max. Pressure
Calibration
Calibrate it when the pressure reaches steady Max. Pressure
8 Min. Fluid Pressure Set the Min. Fluid Pressure
9
Min. Pressure
Calibration
Calibrate it when the pressure reaches steady Min. Pressure
10
4mA Output
Calibration
Use high accuracy amperemeter to get 4mA Output, and
perform this calibration
11
12mA Output
Calibration
Use high accuracy amperemeter to get 12mA Output, and
perform this calibration
12
20mA Output
Calibration
Use high accuracy amperemeter to get 20mA Output, and
perform this calibration
(5) Factory Menu
Warning: ONLY Factory can modify these menus, or it can cause trouble or damage.
Enter 55 password into the factory menu, and the menu functions and parameters meaning
are as follows:
6.TROUBLESHOTTING
Symptom Probable Cause Solution
Measureme
nt is not
accurate
1. Parameter wrong
2. Pipe is not fully filled Check if meter is fully filled
Flow rate
indication is
unstable
1. Vibration Problem
2. Air
Make sure fluid does not contain air bubbles when
fluid is liquid
3. Amplifier location –
outside electrical
interference
Make sure amplifier is not too close to sources of
electrical interference
No Display
1. No power Apply correct power
2. Incorrect power Check power value
3. Wiring connections Check power input/output connections
31 32
Add support to the line near the meter to damp the
vibrtion
Check the parameters(Transmitter, detector factor
and size)
Vortex Flow Meter Vortex Flow Meter
Vortex Flow Meter
7. QUICK INSTALLATION
Flange-Style Flow Meter Installation
Wafer-Style Flow Meter Installation
33
Vortex Flow Meter