1. BILLET YARD LIGHTING STUDY
(4) MH1000 FLOODS @ 35’ BY HOMOGENIZER 1 TO 6
(2)MH1000FLOODS@35’
ABOVEHOMOGENIZERS7AND8
(2)MH1000FLOODS@35’
BYDROSSBLDG
(2)MH400FLOODS@15’
ONDROSSBLDG
60,000 SQUARE FOOT BILLET
AND LOG STORAGE YARD:
THIS AREA IS ACCESSED BY
HEAVY FORK LIFTS 24/7 AND,
FOR SAFETY REASONS, NEEDS
HIGHER LIGHTING LEVELS
THAN A STANDARD STORAGE
YARD WHERE SECURITY
WOULD BE THE PRIMARY
CONCERN. IT IS CURRENTLY
LIT BY (8) MH1000 FLOODS
MOUNTED AT 35’ AND (2)
MH400 FLOODS MOUNTED
AT 15’. MEASURED LIGHT
LEVELS RANGE FROM 5FC
ALONG FRONT OF TANDEM
BLDG TO 1.5 TO 2FC IN
MIDDLE OF YARD.
HEAVY FORKLIFT TRAFFIC IN STORAGE YARD, NIGHT AND DAY HOMOGENIZER 1 TO 6 OVERHANG
2. BILLET YARD LIGHTING STUDY
(8) LITHONIA 295W HLF 1 P3 WITH MFL
OPTICS
(2) LITHONIA 166W HLF 1 P1 WITH MFL
OPTICS
SIMULATION RUNS WITH LOWER
WATTAGE FIXTURES RESULT LIGHT LEVELS
LOWER THAN EXISTING LEVELS. FIXTURES
WITH HIGHER WATTAGES STILL DON’T FILL
IN THE SOUTHEAST CORNER, BUT DO
OVER-LIGHT THE AREAS CLOSEST TO THE
FIXTURES.
SIMULATION ONLY SHOWS OUTPUT FROM
FIXTURES DIRECTED AT THE STORAGE
YARD. FIXTURES LIGHTING THE AREAS
AROUND THE HOMOGENIZER OVENS
WERE NOT SIMULATED.
DROSS STORAGE BLDG HOMGENIZER 7 AND 8 STRUCTURE