25. Process output (%) Settling Times: Fastest Process 62 58 60% 54 50 0 4 8 12 16 20 Time (seconds) Setpoint Case 1 - CIF Case 3 - Control in DCS (async)
26. Process output (%) Settling Times: Very Fast Process 62 58 55% 54 50 0 4 8 12 16 20 Time (seconds) Setpoint Case 1 - CIF Case 3 - Control in DCS (async)
27. Settling Times: Fast Process Process output (%) 62 58 66% 54 50 0 4 8 12 16 20 Time (seconds) Setpoint Case 1 - CIF Case 3 - Control in DCS (async)
28. Settling Times: Medium Process Process output (%) 62 58 39% 54 50 0 4 8 12 16 20 Time (seconds) Setpoint Case 1 - CIF Case 3 - Control in DCS (async)
29. Presence Of Disturbance: Fastest Process Process output (%) 66 64 62 60 58 56 40 50 60 70 80 90 100 Time (seconds) Setpoint Case 1 - CIF Case 3 - Control in DCS (async)
30. Presence Of Disturbance: Different Processes Setpoint CIF 1.811 control in DCS (async) 1.811 Fastest 65% better 0.642 2.132 Very Fast 50% better 1.058 0.517 Fast 55% better 0.231 0.82 Medium 35% better 0.53
31. Impact of Tighter Control Loop Control limit Digital Analogue Pneumatic Manual
32. Recommended For Fast Loop Response Control in the field usingFOUNDATION™fieldbustechnology is recommended by SGSI for simple and cascading loops, not for complex loops. Major benefits identified by SGSI are reduced process controller loading, reduced network traffic enabling more loopsper segment, aswell as very fast loop response.
33. Proven Technology Reduced Wiring and Installation Greater Reliability Why ? Proactive Maintenance Tighter Control
34. The Need For Reliability The global process industry loses $20billion, or five percent of annual production, due to unscheduled downtime and poor quality. ARC estimates that almost 80 percent of these losses are preventable, with 40 percent largely due to operator error. ARC Insight 10th June 2010
38. Customer Experience FOUNDATION™ FieldbusCIF with inherent backup capability prevented 2 incorrect plant shutdowns,which would have resulted from communication interruptions.