International Journal of Applied Power Engineering (IJAPE)
Vol. 3, No. 2, August 2014, pp. 130~139
ISSN: 2252-8792  130
Journal homepage: http://iaesjournal.com/online/index.php/IJAPE
Comparison of FACTS Devices for Two Area Power System
Stability Enhancement using MATLAB Modelling
J.N.Rai*, Naimul Hasan**, B.B.Arora*
*Department of Electrical Engineering, Delhi Technological University, Delhi, India
**Department of Electrical Engineering, Jamia Millia Islamia, Delhi, India
Article Info ABSTRACT
Article history:
Received Mar 2, 2014
Revised Jul 10, 2014
Accepted Jul 3, 2014
Modern Power Transmission networks are becoming increasingly stressed
due to growing demand and restrictions on building new lines. Losing
stability is one of the major threat of such a stressed system following a
disturbance. Flexible ac transmission system (FACTS) devices are found to
be very effective in a transmission network for better utilization of its
existing facilities without sacrificing the desired stability margin. The static
synchronous compensator (STATCOM) and Static Var Compensator (SVC)
are the shunt devices of the flexible AC transmission systems (FACTS)
family. When system voltage is low, STATCOM generates reactive power
and when system voltage is high it absorbs reactive power whereas the Static
Var compensator provides the fast acting dynamic compensation in case of
severe faults. In this Paper, the performance of SVC is compared with the
performance of STATCOM. Proposed controllers are implemented using
MATLAB/SIMULINK. Simulation results indicate that the STATCOM
controller installed with two machine systems provides better damping
characteristics in rotor angle as compared to two machine system installed
with SVC. Thus, transient stability enhancement of the two machine system
installed with STATCOM is better than that installed with SVC.
Keyword:
FACTS
STATCOM
SVC
Transient Stability
Two Area Power System
Copyright © 2014 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
J.N.Rai,
Department of Electrical Engineering,
Delhi Technological University,
Delhi, India.
Email: jnrai.phd@gmail.com
1. INTRODUCTION
Modern power system is a complex network comprising of transmission lines, variety of loads and
numerous amount of generators. Today modern power system is facing various challenges due to day by day
increasing complexity in their structure and operation. In the recent past years, power system instability got a
wide attention due to increased load demand. With the increased loading of long transmission lines, the
problem of transient stability after a major fault was becoming a serious issue. With the lack of new
generation and over exploitation of existing facilities make these types of problems more severe in modern
power systems. Demand for power was rising day by day due to rapid development in industrial sector [2].
Since the last decade, the traditional concepts and practices adopted by power system have changed due to
deregulation of electricity market. The changes arises due to lack of adequate funds in setting up the new
plants for generation and overall to improve the efficiency of the power system. The deregulated structure is
introducing the competition at various levels in trading sectors.
To meet this demand, it becomes essential to enhance the existing generation and transmission
facilities. With the increased loading of long transmission lines, the problem of transient stability can become
a transmission limiting factor. The design of modern power system should be flexible so that it can adapt
itself to variable momentary conditions. While the power flow in some of the transmission lines in their
normal limits, other lines get overloaded, which overall deteriorates the system security, stability and voltage
IJAPE ISSN: 2252-8792 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai)
131
profiles. Now it becomes more important to control power flow along transmission lines to meet the need of
power transfer [5]. In AC power systems, the electrical generation and load must balance at all times up to
some extent i.e. power system must be self-regulating. Stability depends upon both initial operating
conditions of the system and severity of disturbance. If the generation is less than load, there is drop in
voltage and frequency which leads to generation minus transmission losses and there is chance of system
collapse. In case of minor faults, generator excitation controller with only excitation control is sufficient but
it is not sufficient to maintain the stability of system under major faults occurring near generator terminals.
Thus there is great need to improve electric power utilization, simultaneously maintain the system security
and stability.
2. LITERATURE REVIEW
In this chapter some selected research papers related to two area power system stability
enhancement using FACTS controllers are reviewed as:-
D. Murali, et al. presents the new challenges to power system stability and in particular transient
stability and small signal stability for two area power system [2]. They investigate the improvement of
transient stability for two area power system with effective use of different types of FACTS controllers. The
performance of UPFC was compared with different types of FACTS devices like Static Var Compensator,
Static Synchronous Series Compensator, Thyristor controlled series compensator etc.
Anuradha S. Deshpande, et al. proposed a method of evaluating the first swing stability of a large
power system in presence of FACTS devices [3]. They considered FACT device and associated transmission
line were represented by its equivalent pi circuit model. The model is then interfaced to the power network to
obtain the system reduced admittance matrix which was used to generate the machine swing curves.The
proposed method of generating dynamic response and evaluating first swing stability of a power system in
the presence of FACTS device is tested on the three machine eleven bus sample test system. The results
shows that the first swing of the generator gets reduced which further improves first swing stability.
SthitaprajnaRath, et al. presents a comprehensive review on the research and developments in
power system stability enhancement using FACTS damping controllers [4]. They discussed about the several
technical issues that may create hindrance in FACTS devices installations.
They conclude that with the use of FACTS controllers, maximum power can be transferred while maintaining
dynamic stability and security.
Dr. M. Rajaram, et al. described the real and reactive power flow control through a transmission
line by placing a FACT (UPFC) device at sending end of an electrical power transmission system [5].
Matlab/Simulink shows the performance of UPFC. Power flow control performance of UPFC was compared
with other FACTS devices like SVC, STATCOM and SSSC.
Arun Kumar, et al. presented a detailed study on power system stability enhancement like
frequency stability, rotor angle stability and voltage stability by using different FACTS controllers like SVC,
TCSC, SSSC, STATCOM, UPFC and IPFC in an integrated power system networks [6]. They conclude
about the essential features of FACTS controllers and their potential to enhance the system stability.
SamehKamel, et al. presents a report on modeling of the standard IEEE 14 bus system by using
power system toolbox (PST) package [7]. They described the basic fact about the system which was tested
under small and large disturbances to improve the dynamic stability and stability margins. Results show a
precise solution of increased stability margins when different FACTS controllers were added. FACTS
controllers were modeled and tested to show the effect of these controllers on stability margins under both
small and large disturbances.
Salim Haddad, et al. presents a case study on modeling and interface of different FACTS devices in
distributed power system by the use of Matlab [8]. Simulation results investigate about the amount of active
and reactive power flowing through transmission system. Results also depict the efficiency of FACTS
devices in improving the stability of the power system.
M.A. Abido presented a review on the research and developments in the power system stability
enhancement using FACTS controllers [9]. They thoroughly discussed about how FACTS devices were
installed in the system to overcome the related issues which may arise during installation. Also a brief review
of FACTS applications to optimal power flow was presented.
Rahul Somalwar, et al. presented a review of enhancement of transient stability by FACTS devices
[10]. They also described about the coordination problem that likely to be occur among different control
schemes. They investigate the system under fault conditions by using equal area criterion method.
K. Venkateswarlu, ET al.described the analysis and enhancement of transient stability using shunt
controlled FACTS controllers [11]. They briefly described that FACTS devices open up new opportunities
for controlling power and enhancing the usable capacity in existing system. Results show the basic
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 130 – 139
132
simulation of STATCOM for enhancing the transient stability of a two machine system using Matlab. The
system was simulated under three phase fault condition and transient stability was predicted before and after
the use of FACT device i.e. STATCOM.
Thomas J. Overbye, et al. presented the use of FACTS devices for power system stability
enhancement [12]. They thoroughly describe the research on the development of new techniques for analysis
and control of power systems using flexible AC transmission systems (FACTS) devices for both voltage and
transient stability time frames. Results indicate that the FACTS devices are widely used to increase system
stability margins by permitting control intervention during a system disturbance.
Alok Kumar Mohanty, et al. described the power system stability improvement using FACTS
devices [13]. They briefly described about the challenges faced by modern power system under fault
conditions and explained the need of FACTS devices to overcome these problems. In addition, they listed out
the power system constraints and proposed the solutions to meet the power demand in future. They
summarized about the semiconductor technology used in FACTS devices.
S.Abazari, et al. proposed the transient stability improvement by using advanced static Var
Compensator (SVC) [14]. They propose a new method for calculating the current references for an ASVC.
The current references calculated are based on Transient energy function (TEF). Simulation was carried out
with the help of C++ and Matlab Simulink. Results show a comparison between optimal control and bang-
bang control in an ASVC for improving transient stability in a multi-machine system.
Dr.Tarlochan Kaur, et al. proposed transient stability improvement of long transmission line
system by using SVC [15]. They briefly described that shunt FACTS devices-SVC is used in a two area
power system for improving the transient stability. Matlab Simulation describes the two area power system
with various loads connected at different buses in different cases is being studied. Results indicate that after
fault clearing, high transients had appeared in rotor angle difference of two machines when SVC was not
connected to system.
Mohammad Mohammadi presents the voltage stability analysis with static Var Compensator
(SVC) for various faults in power system with and without power system stabilizer (PSS) [16]. He
thoroughly described that when Shunt FACTS devices were placed at midpoint of transmission line, they
play a very important role in controlling the reactive power flow, voltage fluctuations and transient stability
of the two machine system. His study mainly deals with the location of FACTS devices to improve the
transient stability of power system.
D.K Sharma, et al. described a method of voltage stability in power system using STATCOM [17].
They proposed that placing of FACTS devices at key location is an important aspect. They studied the
various FACTS devices that can be installed and FACTS devices model is incorporated into Newton-
Raphson algorithm to perform load flow analysis. The proposed algorithm is tested on standard IEEE 30 bus
power system for optimal allocation of STATCOM.
S.H Hosseini, et al. proposed the transient stability enhancement of AC transmission system using
STATCOM [18]. They briefly described that STATCOM can increase transmission capacity, damping low
frequency oscillations and improves transient stability. They proposed a control block diagram of
STATCOM for transient stability improvement. Matlab was used for simulating the results of two machine
system. Results indicate that the STATCOM not only improves the transient stability but also compensated
the reactive power in steady state.
Aarti Rai, et al. described the enhancement of voltage stability and reactive power control of
distribution system using FACTS devices [19]. They thoroughly described the optimal location of FACTS
devices, voltage stability analysis and control of reactive power in system. Matlab software was used for
simulation and the performance of the whole system such as voltage stability, transient stability and power
swings were analyzed and compared with and without FACTS devices.
Y.L Tan, et al. presents the effects of FACTS controller line compensation on power system
stability [20]. They described the effects of line compensation of SMIB power system using FC-TCR type
TCSC or SVC for transient stability enhancement. They presented a novel method for analysis of line
compensation by SVC. The maximum power transfer for a line depends on degree of compensation. The
results indicate the effectiveness of SVC for stability enhancement is increased if the degree of compensation
is increased.
Sidharta Panda, et al. described the improvement in power system transient stability with an off-
center location of shunt FACTS devices [21]. Their study deals with the placement of Shunt FACTS devices
to improve the transient stability of a long transmission line with predefined direction of real power flow.
They proved the validity of mid-point location of shunt FACTS devices.
Bindeshwar Singh, presents the application of FACTS controllers in power system for enhances the
power system stability [22]. They predicted different kind of stabilities with various FACTS devices. He
presents the current status of research and developments in the field of the power system stability such as
IJAPE ISSN: 2252-8792 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai)
133
rotor angle stability, frequency stability, and voltage stability enhancement by using different FACTS
controllers in an integrated power system networks.
S.K Srivastava presents an overview on advanced power electronic based FACTS controllers [23].
He studied the better utilization of power system capabilities by installing the FACTS devices. He explained
the basic concept of FACTS devices and their utilization to enhance the stability and security of modern
power system.
V. Kakkar, et al. explained the recent trends on FACTS and D-FACTS [24]. They briefly explained
about the challenges faced by modern power system which includes limited available energy resources, time,
capital required and land use restrictions. Results indicate that D-FACTS have more reliability and cost
saving approach over FACTS devices.
Karim Sebaa, et al. presents the power system dynamic stability enhancement via coordinated
design of PSS and SVC based controllers using hierarchical real coded NSGA-II [25]. Results indicate the
solution of tuning and location of minimum number of PSS and FACTS based controllers were proposed.
S.V Ravi Kumar, et al. presents the transient stability using UPFC and SVC [26]. They thoroughly
described the damping of power system oscillations after a three phase fault and also analyze the effect of
UPFC and SVC on transient stability performance of power system. They developed a general program for
transient stability studies using modified portioned approach. The modelling of SVC and UPFC were studied
and tested on a 10-generator, 39-bus, New England test generator. Results indicate that the SVC helps in
improving the system performance by improving critical clearing time.
Nasimul Islam Maruf, et al. presents a study on thyristor controlled series capacitor as a useful
FACT device [27]. They discussed the basic principle and benefits of TCSC during the fault conditions. They
conclude that TCSC is a useful FACT device for enhancing the transient stability, steady state stability,
dynamic stability and voltage stability of power system under severe conditions.
Vibhor Gupta described the study and effects of UPFC and its control system for power flow
control and voltage injection in power system [28]. He studied the operating modes of UPFC. Simulation is
carried out in MATLAB and results indicate the use of power flow controller and voltage injection. He
concludes about the benefits of using UPFC in the system.
S.JavedSajjadi, described the effects of series and shunt FACTS devices in transient stability
enhancement of multi-machine system [29]. They described the injection model of unified power flow
controller and series quadrature voltage injection. Results indicate that the shunt compensation was used for
power oscillation damping and effects of series and shunt compensation on transient stability was discussed.
N.K Sharma, et al. described the performance of UPFC in several modes operation using different
control mechanism based on proportional plus integral control (PI) and Proportional plus integral plus
derivative control (PID) [30]. They also developed ANFIS based controller by using ANFIS editor of Matlab.
The MATLAB simulation results indicate the capability of UPFC on power flow control and the
effectiveness of controllers on the performance of UPFC in the different operating modes.
T.K. Gangopadhyay, et al. discussed the problem of designing the damping controller for low
frequency oscillations in power system under dynamic uncertainty [31]. They applied H mixed sensitivity
technique to design robust damping controllers for unified power flow controller in uncertain conditions.
3. FACTS CONTROLLERS
FACTS are defined as“a power electronic based system and other static equipment that provide
control of one or more AC transmission system parameters to enhance controllability and increase power
transfer capability.Basically, FACTS controllers can be divided into four categories [1]:
 Series Controller
 Shunt Controller
 Combined series-series Controller
 Combined series-shunt Controller
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 130 – 139
134
Table 1. Comparison among FACTS Controllers
3.1. Static VAR Compensator (SVC)
SVC is an electrical device for providing the fast reactive power on high voltage transmission
networks. An SVC is based on thyristor controlled reactors (TCR), thyristor switched capacitors (TSC),
and/or Fixed Capacitors (FC) tuned to Filters as shown in fig1. A TCR consists of a fixed reactor in series
with a bi-directional thyristor valve. TCR reactors are as a rule of air core type, glass fibre insulated, epoxy
resin impregnated [15].
Figure 1. SVC Model
SVCs had a great advantage over simple mechanically-switched compensation schemes is their fast
instantaneous response to changes in the system voltage. For this reason they are often operated at close to
their zero-point in order to maximize the reactive power correction they can rapidly provide in system
whenever required. They are in general cheaper, higher-capacity, faster, efficient and more reliable over
dynamic compensation schemes such as synchronous condensers [15].
3.2. Static Synchronous Compensator (STATCOM)
A Static synchronous compensator is a shunt-connected static Var compensator whose capacitive or
inductive output current can be controlled independently of the ac system voltage. STATCOM is made up of
a coupling transformer, a VSC and a dc energy storage device as shown in fig2. STATCOM is capable of
exchanging reactive power with the transmission line because of its small energy storage device i.e. small dc
capacitor, if this dc capacitor is replaced with dc storage battery or other dc voltage source, the controller can
exchange real and reactive power with the transmission system, extending its region of operation from two to
four quadrants.
IJAPE ISSN: 2252-8792 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai)
135
Figure 2. STATCOM Model
4. SIMULATION MODEL AND RESULTS
Consider a two area power system (Area-1 & Area-2) with shunt FACTS devices, connected by a
long transmission line as shown in fig-3. Two 1000MW hydraulic generation plants M1 and M2 are
connected to a load centre through 500KV, 720KM transmission line. The system was interconnected
through 5 buses and RL load. Two machines are equipped with a hydraulic turbine and governor (HTG),
excitation system, power system stabilizer and FACT device (SVC or STATCOM).
Figure 3. SLD of two area power system
4.1. Two Area System with Three Phase Fault
Two area system as shown in fig.-4 is considered in this study.
Figure 4. Two Area Systems during Three Phase Fault
It is considered that a 3-phase symmetrical short circuit fault of 0.1seconds occur at bus B1. The
system is simulated in MATLAB/Simulink environment and graphs are shown in fig.-5 and fig.-6. From the
fig.-5, it is inferred that without the FACT device and Power system stabilizer, the oscillation in generator
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 130 – 139
136
rotor angle of Area1 and Area2 increases and settling time for the oscillations is found to be high. The
difference of the two rotor angle is taken into account and plotted against time.
Figure 5. Difference of two rotor angles with time during three phase fault
Figure 6. Variation of terminal voltages with time
4.2 Two Area System with FACT device (SVC) and Power System Stabilizer
Two area system as shown in figure 7 is considered in this study.
Figure 7. Two Area System installed with SVC and PSS
The system has a SVC installed at B2. It is considered that a 3-phase symmetrical short circuit fault
of 0.1seconds occur at bus B1. Put the Generic type PSS in service by setting the command in PSS block
equal to 1. Open the SVC block menu and change the SVC mode of operation to voltage regulation. The
system is simulated in Matlab/Simulink environment and graphs of SVC are shown in fig-8 and fig-9. From
the fig-8, it is inferred that the oscillations in generator rotor angle is decreased and setting time for the
oscillations is found to be 4.0 seconds.
Figure 8. Difference of two rotor angles with time installed with SVC and PSS
IJAPE ISSN: 2252-8792 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai)
137
Figure 9. Variation of terminal voltages with time installed with SVC and PSS
4.3 Two Area System with FACT device (STATCOM) and Power System Stabilizer
Two area system as shown in figure 10 is considered in this study.
Figure 10. Two Area System installed with STATCOM and PSS
The system has a STATCOM installed at B2. It is considered that a 3-phase symmetrical short
circuit fault of 0.1seconds occur at bus B1. Put the Generic type PSS in service by setting the command in
PSS block equal to 1. Open the STATCOM block menu and change the STATCOM mode of operation to
voltage regulation. The system is simulated in Matlab/Simulink environment and graphs of STATCOM are
shown in fig-11 and fig-12. From the fig-11, it is inferred that the oscillations in generator rotor angle is
decreased and setting time for the oscillations is found to be 2.8 seconds. Also, terminal voltages profile has
been improved after clearance of fault installed with STATCOM. Hence, the transient stability of two
machine system installed with STATCOM has been improved considerably and post settling time of the
system after facing disturbance is also improved.
Figure 11. Difference of two rotor angles with time installed with STATCOM and PSS
Figure 12. Variation of terminal voltages with time installed with STATCOM and PSS
 ISSN: 2252-8792
IJAPE Vol. 3, No. 2, August 2014 : 130 – 139
138
4.4 Comparison between FACTS Devices
From the simulation results shown in Fig4-Fig12, a comparison is made between the above FACTS
devices for stability enhancement of two area power system as shown in Table-2. From the Table-2, it is
inferred that STATCOM is the effective FACT device for stability enhancement over SVC as the post
settling time obtained from the use of STATCOM is less as compared to that obtained from SVC.
Table 2. Comparison between FACTS Devices for Power System
Two-areaPower
System
with
PowerSystem
Stability
Enhancement
Post settling
time(inseconds)
SVC YES 4.0
STATCOM YES 2.8
5. CONCLUSION
In this paper, various constraints of the modern power system were discussed and on the basis of
these constraints, need of FACTS devices were presented. The dynamics of the power system is compared
with and without the presence of FACTS devices and Power system stabilizers in the event of major
disturbances. The performance of one of the FACT device i.e. STATCOM for transient stability
enhancement is compared with the performance of other FACT device i.e. SVC. Controller’s inputs are
chosen carefully to provide necessary damping in rotor angle and results are taken through simulation.
Proposed FACTS controllers were implemented in MATLAB/SIMULINK. Simulation results indicate that
the STATCOM controller installed with two machine systems provides better damping characteristics in
rotor angle as compared to two machine system installed with SVC. Also, the post settling time of the two
machine system installed with STATCOM is found to be less i.e. near to 2.8sec than the system with SVC.
Thus, transient stability enhancement of the two machine system installed with STATCOM is better than that
installed with SVC.
REFERENCES
[1] Hingorani, N. G., &Gyugyi, L. (2000). Understanding FACTS: concepts and technology of flexible AC
transmission systems (Vol. 1). M. El-Hawary (Ed.). New York: IEEE press.
[2] Murali, D., Rajaram, D. M., &Reka, N. (2010). Comparison of FACTS devices for power system stability
enhancement. International Journal of Computer Applications (0975–8887) Volume, 30-35.
[3] Deshpande, A. S., Kadam, P. A. and Rana, V. M. (2011, May). First Swing Stability of Power System Using FACTS
Device. 2011 National Conference on Recent trends in Engineering and Technology.
[4] Rath, S., Sahu B., & Dash, P. (2012). Power System Operation and Control Using FACTS Devices. International
Journal of Engineering Research and Technology. 1(5).
[5] Murali, D., &Rajaram, M. (2010). Active and Reactive Power Flow Control using FACTS Devices. International
Journal of Computer Applications. 9(8). 45-50.
[6] Kumar, A., &Priya, G. (2012, December). Power system stability enhancement using FACTS controllers.
In Emerging Trends in Electrical Engineering and Energy Management (ICETEEEM), 2012 International
Conference on (pp. 84-87). IEEE.
[7] Kodsi, S. M., &Canizares, C. A. (2003). Modeling and simulation of IEEE 14 bus system with FACTS
controllers. University of Waterloo, Canada, Tech. Rep.
[8] Haddad, S., Haddouche, A. &Bouyeda, H. (2009, April). The use of FACTS Devices in Distributed power systems-
Modelling, Interface and case study.International Journal of Computer and Electrical Engineering. 1(1).
[9] Abido, M. A. (2009). POWER SYSTEM STABILITY ENHANCEMENT USING FACTS CONTROLLERS: A
REVIEW. Arabian Journal for Science & Engineering (Springer Science & Business Media BV), 34.
[10] Somalwar, R. &Khemaria, M. (2012, March). A Review of enhancement of Transient stability using FACTS
Devices. International journal of Emerging Technologies in Sciences and Engineering, 5(3).
[11] Venkateswarlu, K. and Babu, C. S,. (2011, May). Analysis and Enhancement of Transient Stability using SHUNT
Controlled FACTS Controllers. International Journal of Engineering Sciences Research. 1(2).
[12] Overbye, T. J., & Brown, D. (1993, August). Use of FACTS devices for power system stability enhancement.
In Circuits and Systems, 1993. Proceedings of the 36th Midwest Symposium on (pp. 1019-1022). IEEE.
[13] Mohanty, A. K., &Barik, A. K. (2011). Power System Stability Improvement Using FACTS Devices. International
Journal of Modern Engineering Research, 1(2), 666-672.
[14] ABAZARI & EMADI. (2003). Transient stability improvement by using advanced static VAR
compensators. Electric Power Components and Systems, 31(4), 321-334.
IJAPE ISSN: 2252-8792 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai)
139
[15] Kaur, T. and Kakran, S. (2012). Transient stability Improvement of Long Transmission Line System by Using
SVC. International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. 1(4).
[16] Mohammadi, M. (2011). Voltage Stability Analysis with Static Var Compensator (SVC) for Various Faults in
Power System with and Without Power System Stabilizers (PSS). Research Journal of Applied Sciences,
Engineering and Technology, 3(7): 668-676.
[17] Sharma, D., K., Ahmed, A., Saluja, R. &Parmar, R. Voltage Stability in Power System Using STATCOM.
International Journal of Electronics and Computer Science Engineering. 1(2): 198-208.
[18] Hosseini, S. H., &Ajami, A. (2002, October). Transient stability enhancement of AC transmission system using
STATCOM. In TENCON'02. Proceedings. 2002 IEEE Region 10 Conference on Computers, Communications,
Control and Power Engineering (Vol. 3, pp. 1809-1812). IEEE.
[19] Rai, A. (2012). Enhancement of Voltage Stability and Reactive power control of Distribution System using FACTS
devices. International Journal of Scientific research Engineering and Technology. 1(9): 001-005.
[20] Tan, Y. L., & Wang, Y. (1998). Effects of FACTS controller line compensation on power system stability. Power
Engineering Review, IEEE, 18(6), 45-47.
[21] Panda, S., & Patel, R. N. (2006). Improving power system transient stability with an off-centre location of shunt
FACTS devices. JOURNAL OF ELECTRICAL ENGINEERING-BRATISLAVA-, 57(6), 365.
[22] Singh, B. (2011). Applications of FACTS Controllers in Power Systems for Enhance the Power System Stability:
A State-of-the-art. International Journal of Reviews in Computing, 6.
[23] Srivastava, S. K. (2010). Advanced Power Electronics Based FACTS Controllers: An Overview. Asian Power
Electronics Journal, 4(3), 90-95.
[24] Kakkar, V., & Agarwal, N. K. (2010, September). Recent trends on FACTS and D-FACTS. In Modern Electric
Power Systems (MEPS), 2010 Proceedings of the International Symposium (pp. 1-8). IEEE.
[25] Sebaa, K., &Boudour, M. (2008, July). Power system dynamic stability enhancement via coordinated design of
PSSs and SVC-based controllers using hierarchical real coded NSGA-II. In Power and Energy Society General
Meeting-Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE (pp. 1-8). IEEE.
[26] Kumar, S. R., &Nagaraju, S. S. (2007). Transient stability improvement using UPFC and SVC. ARPN Journal of
Engineering and Applied Sciences, 2(3), 38-45.
[27] Maruf, N. I., Mohsin, A., Shoeb, A., Islam, K., & Hossain, M. (2010). Study of thyristor controlled series capacitor
(TCSC) as a useful FACTS device.International Journal of Engineering Science and Technology, 2(9), 4357-4360.
[28] Gupta, V. (2010). Study and Effects of UPFC and its Control System for Power Flow Control and Voltage
Injection in a Power System. International journal of engineering science and technology, 2(7), 2558-2566.
[29] Sajjadi, S. J., Mohseninejad, M. H., &Afsharnia, S. EFFECTS OF SERIES AND SHUNT FACTS DEVICES IN
TRANSIENT STABILITY ENHANCEMENT OF MULTI-MACHINE POWER SYSTEMS..
[30] Sharma, N. K., &Jagtap, P. P. (2010, November). Modelling and application of unified power flow controller
(UPFC). In Emerging Trends in Engineering and Technology (ICETET), 2010 3rd International Conference
on (pp. 350-355). IEEE.
[31] Gangopadhyay, T. K., Sil, A., & Paul, S. (2009, November). Design of robust UPFC controller for damping power
system oscillations using H∞ mixed sensitivity technique. In Advances in Power System Control, Operation and
Management (APSCOM 2009), 8th International Conference on (pp. 1-6). IET.
[32] Edris, A. A., Adapa, R., Baker, M. H., Bohmann, L., Clark, K., Habashi, K. & Wood, R. R. (1997). Proposed terms
and definitions for flexible AC transmission system (FACTS). IEEE Power Engineering Review, 17, 46-46.

More Related Content

What's hot

Swing, voltage stability and power transfer capability in transmission system...
Swing, voltage stability and power transfer capability in transmission system...Swing, voltage stability and power transfer capability in transmission system...
Swing, voltage stability and power transfer capability in transmission system...
eSAT Journals
 
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
ijtsrd
 
Transient stability-enhancement-of-power-system-using-upfc-unified-power-flow...
Transient stability-enhancement-of-power-system-using-upfc-unified-power-flow...Transient stability-enhancement-of-power-system-using-upfc-unified-power-flow...
Transient stability-enhancement-of-power-system-using-upfc-unified-power-flow...
rameshss
 
Reactive power aspects in reliability assessment of power systems
Reactive power aspects in reliability assessment of power systemsReactive power aspects in reliability assessment of power systems
Reactive power aspects in reliability assessment of power systems
IAEME Publication
 

What's hot (20)

Low-voltage ride-through for a three-phase four-leg photovoltaic system using...
Low-voltage ride-through for a three-phase four-leg photovoltaic system using...Low-voltage ride-through for a three-phase four-leg photovoltaic system using...
Low-voltage ride-through for a three-phase four-leg photovoltaic system using...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Facts applications
Facts applicationsFacts applications
Facts applications
 
Swing, voltage stability and power transfer capability
Swing, voltage stability and power transfer capabilitySwing, voltage stability and power transfer capability
Swing, voltage stability and power transfer capability
 
Swing, voltage stability and power transfer capability in transmission system...
Swing, voltage stability and power transfer capability in transmission system...Swing, voltage stability and power transfer capability in transmission system...
Swing, voltage stability and power transfer capability in transmission system...
 
Interconnection power system
Interconnection power systemInterconnection power system
Interconnection power system
 
Indian wind energy status
Indian wind energy statusIndian wind energy status
Indian wind energy status
 
IRJET- Analysis of Power System Stability using Various FACTS Controllers
IRJET- Analysis of Power System Stability using Various FACTS ControllersIRJET- Analysis of Power System Stability using Various FACTS Controllers
IRJET- Analysis of Power System Stability using Various FACTS Controllers
 
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
A Review on Optimization Techniques for Power Quality Improvement using DSTAT...
 
A Literature Review on Experimental Study of Power Losses in Transmission Lin...
A Literature Review on Experimental Study of Power Losses in Transmission Lin...A Literature Review on Experimental Study of Power Losses in Transmission Lin...
A Literature Review on Experimental Study of Power Losses in Transmission Lin...
 
Under voltage load shedding for contingency analysis to optimize power loss ...
Under voltage load shedding for contingency analysis to  optimize power loss ...Under voltage load shedding for contingency analysis to  optimize power loss ...
Under voltage load shedding for contingency analysis to optimize power loss ...
 
Transient stability-enhancement-of-power-system-using-upfc-unified-power-flow...
Transient stability-enhancement-of-power-system-using-upfc-unified-power-flow...Transient stability-enhancement-of-power-system-using-upfc-unified-power-flow...
Transient stability-enhancement-of-power-system-using-upfc-unified-power-flow...
 
A New approach for controlling the power flow in a transmission system using ...
A New approach for controlling the power flow in a transmission system using ...A New approach for controlling the power flow in a transmission system using ...
A New approach for controlling the power flow in a transmission system using ...
 
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
Power Flow Study and Performance of STATCOM and TCSC in Improvement Voltage S...
 
An Overview of FACTS Controllers for Power Quality Improvement
An Overview of FACTS Controllers for Power Quality ImprovementAn Overview of FACTS Controllers for Power Quality Improvement
An Overview of FACTS Controllers for Power Quality Improvement
 
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
 
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
IRJET- Voltage Stability Improvement and Reactive Power Compensation using ST...
 
Selection the optimum place of FACTS devices using fuzzy control system
Selection the optimum place of FACTS devices using fuzzy control systemSelection the optimum place of FACTS devices using fuzzy control system
Selection the optimum place of FACTS devices using fuzzy control system
 
Reactive power aspects in reliability assessment of power systems
Reactive power aspects in reliability assessment of power systemsReactive power aspects in reliability assessment of power systems
Reactive power aspects in reliability assessment of power systems
 
Et33879883
Et33879883Et33879883
Et33879883
 

Similar to Comparison of FACTS Devices for Two Area Power System Stability Enhancement using MATLAB Modelling

Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system
IJECEIAES
 
Development of Power System Stabilizer Using Modern Optimization Approach
Development of Power System Stabilizer Using Modern Optimization ApproachDevelopment of Power System Stabilizer Using Modern Optimization Approach
Development of Power System Stabilizer Using Modern Optimization Approach
ijtsrd
 
ARGGGGGGGGGGGGGGGGGGGGGGGGTICLE REVIEW.docx
ARGGGGGGGGGGGGGGGGGGGGGGGGTICLE REVIEW.docxARGGGGGGGGGGGGGGGGGGGGGGGGTICLE REVIEW.docx
ARGGGGGGGGGGGGGGGGGGGGGGGGTICLE REVIEW.docx
BiniamHailemariam
 
transient stability improvement in power system in multi machine system with ...
transient stability improvement in power system in multi machine system with ...transient stability improvement in power system in multi machine system with ...
transient stability improvement in power system in multi machine system with ...
Kumar Goud
 

Similar to Comparison of FACTS Devices for Two Area Power System Stability Enhancement using MATLAB Modelling (20)

07 22 sep15 8711 18507-2-sm -edit_FACT Device for Reactive Power Compensation...
07 22 sep15 8711 18507-2-sm -edit_FACT Device for Reactive Power Compensation...07 22 sep15 8711 18507-2-sm -edit_FACT Device for Reactive Power Compensation...
07 22 sep15 8711 18507-2-sm -edit_FACT Device for Reactive Power Compensation...
 
Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system Impact of hybrid FACTS devices on the stability of the Kenyan power system
Impact of hybrid FACTS devices on the stability of the Kenyan power system
 
F010324347
F010324347F010324347
F010324347
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
D1072535
D1072535D1072535
D1072535
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
FLC based on static var compensator for power system transient stability enha...
FLC based on static var compensator for power system transient stability enha...FLC based on static var compensator for power system transient stability enha...
FLC based on static var compensator for power system transient stability enha...
 
Comparison of Multi-Machine Transient Stability Limit Using UPFC
Comparison of Multi-Machine Transient Stability Limit Using UPFCComparison of Multi-Machine Transient Stability Limit Using UPFC
Comparison of Multi-Machine Transient Stability Limit Using UPFC
 
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...
 
Hs3414301435
Hs3414301435Hs3414301435
Hs3414301435
 
Al4201250256
Al4201250256Al4201250256
Al4201250256
 
Development of Power System Stabilizer Using Modern Optimization Approach
Development of Power System Stabilizer Using Modern Optimization ApproachDevelopment of Power System Stabilizer Using Modern Optimization Approach
Development of Power System Stabilizer Using Modern Optimization Approach
 
Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...
Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...
Application of Multilevel Voltage-Source-Converter in FACTS Devices for Power...
 
Multi-machine transient stability by using static synchronous series compensator
Multi-machine transient stability by using static synchronous series compensatorMulti-machine transient stability by using static synchronous series compensator
Multi-machine transient stability by using static synchronous series compensator
 
A350103
A350103A350103
A350103
 
A350103
A350103A350103
A350103
 
ARGGGGGGGGGGGGGGGGGGGGGGGGTICLE REVIEW.docx
ARGGGGGGGGGGGGGGGGGGGGGGGGTICLE REVIEW.docxARGGGGGGGGGGGGGGGGGGGGGGGGTICLE REVIEW.docx
ARGGGGGGGGGGGGGGGGGGGGGGGGTICLE REVIEW.docx
 
TSA-assesment of GTPS kotri
TSA-assesment of GTPS kotriTSA-assesment of GTPS kotri
TSA-assesment of GTPS kotri
 
Bd044339344
Bd044339344Bd044339344
Bd044339344
 
transient stability improvement in power system in multi machine system with ...
transient stability improvement in power system in multi machine system with ...transient stability improvement in power system in multi machine system with ...
transient stability improvement in power system in multi machine system with ...
 

More from IJAPEJOURNAL

Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineOptimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
IJAPEJOURNAL
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
IJAPEJOURNAL
 
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
IJAPEJOURNAL
 
Implementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanImplementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in Pakistan
IJAPEJOURNAL
 
Ash Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeAsh Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation Scheme
IJAPEJOURNAL
 

More from IJAPEJOURNAL (20)

Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
 
Underwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterUnderwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman Filter
 
Investigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointInvestigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation Point
 
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineOptimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
 
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceImpact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
 
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingEnhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
 
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
 
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
 
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
 
An Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsAn Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC Motors
 
Implementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanImplementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in Pakistan
 
Modeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationModeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based Application
 
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
 
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
 
Hybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsHybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic Applications
 
Ash Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeAsh Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation Scheme
 
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
 
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
 

Recently uploaded

"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
HenryBriggs2
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 

Recently uploaded (20)

HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Moment Distribution Method For Btech Civil
Moment Distribution Method For Btech CivilMoment Distribution Method For Btech Civil
Moment Distribution Method For Btech Civil
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 
Learn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic MarksLearn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic Marks
 
Introduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdfIntroduction to Data Visualization,Matplotlib.pdf
Introduction to Data Visualization,Matplotlib.pdf
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptxA CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
A CASE STUDY ON CERAMIC INDUSTRY OF BANGLADESH.pptx
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
 

Comparison of FACTS Devices for Two Area Power System Stability Enhancement using MATLAB Modelling

  • 1. International Journal of Applied Power Engineering (IJAPE) Vol. 3, No. 2, August 2014, pp. 130~139 ISSN: 2252-8792  130 Journal homepage: http://iaesjournal.com/online/index.php/IJAPE Comparison of FACTS Devices for Two Area Power System Stability Enhancement using MATLAB Modelling J.N.Rai*, Naimul Hasan**, B.B.Arora* *Department of Electrical Engineering, Delhi Technological University, Delhi, India **Department of Electrical Engineering, Jamia Millia Islamia, Delhi, India Article Info ABSTRACT Article history: Received Mar 2, 2014 Revised Jul 10, 2014 Accepted Jul 3, 2014 Modern Power Transmission networks are becoming increasingly stressed due to growing demand and restrictions on building new lines. Losing stability is one of the major threat of such a stressed system following a disturbance. Flexible ac transmission system (FACTS) devices are found to be very effective in a transmission network for better utilization of its existing facilities without sacrificing the desired stability margin. The static synchronous compensator (STATCOM) and Static Var Compensator (SVC) are the shunt devices of the flexible AC transmission systems (FACTS) family. When system voltage is low, STATCOM generates reactive power and when system voltage is high it absorbs reactive power whereas the Static Var compensator provides the fast acting dynamic compensation in case of severe faults. In this Paper, the performance of SVC is compared with the performance of STATCOM. Proposed controllers are implemented using MATLAB/SIMULINK. Simulation results indicate that the STATCOM controller installed with two machine systems provides better damping characteristics in rotor angle as compared to two machine system installed with SVC. Thus, transient stability enhancement of the two machine system installed with STATCOM is better than that installed with SVC. Keyword: FACTS STATCOM SVC Transient Stability Two Area Power System Copyright © 2014 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: J.N.Rai, Department of Electrical Engineering, Delhi Technological University, Delhi, India. Email: jnrai.phd@gmail.com 1. INTRODUCTION Modern power system is a complex network comprising of transmission lines, variety of loads and numerous amount of generators. Today modern power system is facing various challenges due to day by day increasing complexity in their structure and operation. In the recent past years, power system instability got a wide attention due to increased load demand. With the increased loading of long transmission lines, the problem of transient stability after a major fault was becoming a serious issue. With the lack of new generation and over exploitation of existing facilities make these types of problems more severe in modern power systems. Demand for power was rising day by day due to rapid development in industrial sector [2]. Since the last decade, the traditional concepts and practices adopted by power system have changed due to deregulation of electricity market. The changes arises due to lack of adequate funds in setting up the new plants for generation and overall to improve the efficiency of the power system. The deregulated structure is introducing the competition at various levels in trading sectors. To meet this demand, it becomes essential to enhance the existing generation and transmission facilities. With the increased loading of long transmission lines, the problem of transient stability can become a transmission limiting factor. The design of modern power system should be flexible so that it can adapt itself to variable momentary conditions. While the power flow in some of the transmission lines in their normal limits, other lines get overloaded, which overall deteriorates the system security, stability and voltage
  • 2. IJAPE ISSN: 2252-8792  Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai) 131 profiles. Now it becomes more important to control power flow along transmission lines to meet the need of power transfer [5]. In AC power systems, the electrical generation and load must balance at all times up to some extent i.e. power system must be self-regulating. Stability depends upon both initial operating conditions of the system and severity of disturbance. If the generation is less than load, there is drop in voltage and frequency which leads to generation minus transmission losses and there is chance of system collapse. In case of minor faults, generator excitation controller with only excitation control is sufficient but it is not sufficient to maintain the stability of system under major faults occurring near generator terminals. Thus there is great need to improve electric power utilization, simultaneously maintain the system security and stability. 2. LITERATURE REVIEW In this chapter some selected research papers related to two area power system stability enhancement using FACTS controllers are reviewed as:- D. Murali, et al. presents the new challenges to power system stability and in particular transient stability and small signal stability for two area power system [2]. They investigate the improvement of transient stability for two area power system with effective use of different types of FACTS controllers. The performance of UPFC was compared with different types of FACTS devices like Static Var Compensator, Static Synchronous Series Compensator, Thyristor controlled series compensator etc. Anuradha S. Deshpande, et al. proposed a method of evaluating the first swing stability of a large power system in presence of FACTS devices [3]. They considered FACT device and associated transmission line were represented by its equivalent pi circuit model. The model is then interfaced to the power network to obtain the system reduced admittance matrix which was used to generate the machine swing curves.The proposed method of generating dynamic response and evaluating first swing stability of a power system in the presence of FACTS device is tested on the three machine eleven bus sample test system. The results shows that the first swing of the generator gets reduced which further improves first swing stability. SthitaprajnaRath, et al. presents a comprehensive review on the research and developments in power system stability enhancement using FACTS damping controllers [4]. They discussed about the several technical issues that may create hindrance in FACTS devices installations. They conclude that with the use of FACTS controllers, maximum power can be transferred while maintaining dynamic stability and security. Dr. M. Rajaram, et al. described the real and reactive power flow control through a transmission line by placing a FACT (UPFC) device at sending end of an electrical power transmission system [5]. Matlab/Simulink shows the performance of UPFC. Power flow control performance of UPFC was compared with other FACTS devices like SVC, STATCOM and SSSC. Arun Kumar, et al. presented a detailed study on power system stability enhancement like frequency stability, rotor angle stability and voltage stability by using different FACTS controllers like SVC, TCSC, SSSC, STATCOM, UPFC and IPFC in an integrated power system networks [6]. They conclude about the essential features of FACTS controllers and their potential to enhance the system stability. SamehKamel, et al. presents a report on modeling of the standard IEEE 14 bus system by using power system toolbox (PST) package [7]. They described the basic fact about the system which was tested under small and large disturbances to improve the dynamic stability and stability margins. Results show a precise solution of increased stability margins when different FACTS controllers were added. FACTS controllers were modeled and tested to show the effect of these controllers on stability margins under both small and large disturbances. Salim Haddad, et al. presents a case study on modeling and interface of different FACTS devices in distributed power system by the use of Matlab [8]. Simulation results investigate about the amount of active and reactive power flowing through transmission system. Results also depict the efficiency of FACTS devices in improving the stability of the power system. M.A. Abido presented a review on the research and developments in the power system stability enhancement using FACTS controllers [9]. They thoroughly discussed about how FACTS devices were installed in the system to overcome the related issues which may arise during installation. Also a brief review of FACTS applications to optimal power flow was presented. Rahul Somalwar, et al. presented a review of enhancement of transient stability by FACTS devices [10]. They also described about the coordination problem that likely to be occur among different control schemes. They investigate the system under fault conditions by using equal area criterion method. K. Venkateswarlu, ET al.described the analysis and enhancement of transient stability using shunt controlled FACTS controllers [11]. They briefly described that FACTS devices open up new opportunities for controlling power and enhancing the usable capacity in existing system. Results show the basic
  • 3.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 130 – 139 132 simulation of STATCOM for enhancing the transient stability of a two machine system using Matlab. The system was simulated under three phase fault condition and transient stability was predicted before and after the use of FACT device i.e. STATCOM. Thomas J. Overbye, et al. presented the use of FACTS devices for power system stability enhancement [12]. They thoroughly describe the research on the development of new techniques for analysis and control of power systems using flexible AC transmission systems (FACTS) devices for both voltage and transient stability time frames. Results indicate that the FACTS devices are widely used to increase system stability margins by permitting control intervention during a system disturbance. Alok Kumar Mohanty, et al. described the power system stability improvement using FACTS devices [13]. They briefly described about the challenges faced by modern power system under fault conditions and explained the need of FACTS devices to overcome these problems. In addition, they listed out the power system constraints and proposed the solutions to meet the power demand in future. They summarized about the semiconductor technology used in FACTS devices. S.Abazari, et al. proposed the transient stability improvement by using advanced static Var Compensator (SVC) [14]. They propose a new method for calculating the current references for an ASVC. The current references calculated are based on Transient energy function (TEF). Simulation was carried out with the help of C++ and Matlab Simulink. Results show a comparison between optimal control and bang- bang control in an ASVC for improving transient stability in a multi-machine system. Dr.Tarlochan Kaur, et al. proposed transient stability improvement of long transmission line system by using SVC [15]. They briefly described that shunt FACTS devices-SVC is used in a two area power system for improving the transient stability. Matlab Simulation describes the two area power system with various loads connected at different buses in different cases is being studied. Results indicate that after fault clearing, high transients had appeared in rotor angle difference of two machines when SVC was not connected to system. Mohammad Mohammadi presents the voltage stability analysis with static Var Compensator (SVC) for various faults in power system with and without power system stabilizer (PSS) [16]. He thoroughly described that when Shunt FACTS devices were placed at midpoint of transmission line, they play a very important role in controlling the reactive power flow, voltage fluctuations and transient stability of the two machine system. His study mainly deals with the location of FACTS devices to improve the transient stability of power system. D.K Sharma, et al. described a method of voltage stability in power system using STATCOM [17]. They proposed that placing of FACTS devices at key location is an important aspect. They studied the various FACTS devices that can be installed and FACTS devices model is incorporated into Newton- Raphson algorithm to perform load flow analysis. The proposed algorithm is tested on standard IEEE 30 bus power system for optimal allocation of STATCOM. S.H Hosseini, et al. proposed the transient stability enhancement of AC transmission system using STATCOM [18]. They briefly described that STATCOM can increase transmission capacity, damping low frequency oscillations and improves transient stability. They proposed a control block diagram of STATCOM for transient stability improvement. Matlab was used for simulating the results of two machine system. Results indicate that the STATCOM not only improves the transient stability but also compensated the reactive power in steady state. Aarti Rai, et al. described the enhancement of voltage stability and reactive power control of distribution system using FACTS devices [19]. They thoroughly described the optimal location of FACTS devices, voltage stability analysis and control of reactive power in system. Matlab software was used for simulation and the performance of the whole system such as voltage stability, transient stability and power swings were analyzed and compared with and without FACTS devices. Y.L Tan, et al. presents the effects of FACTS controller line compensation on power system stability [20]. They described the effects of line compensation of SMIB power system using FC-TCR type TCSC or SVC for transient stability enhancement. They presented a novel method for analysis of line compensation by SVC. The maximum power transfer for a line depends on degree of compensation. The results indicate the effectiveness of SVC for stability enhancement is increased if the degree of compensation is increased. Sidharta Panda, et al. described the improvement in power system transient stability with an off- center location of shunt FACTS devices [21]. Their study deals with the placement of Shunt FACTS devices to improve the transient stability of a long transmission line with predefined direction of real power flow. They proved the validity of mid-point location of shunt FACTS devices. Bindeshwar Singh, presents the application of FACTS controllers in power system for enhances the power system stability [22]. They predicted different kind of stabilities with various FACTS devices. He presents the current status of research and developments in the field of the power system stability such as
  • 4. IJAPE ISSN: 2252-8792  Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai) 133 rotor angle stability, frequency stability, and voltage stability enhancement by using different FACTS controllers in an integrated power system networks. S.K Srivastava presents an overview on advanced power electronic based FACTS controllers [23]. He studied the better utilization of power system capabilities by installing the FACTS devices. He explained the basic concept of FACTS devices and their utilization to enhance the stability and security of modern power system. V. Kakkar, et al. explained the recent trends on FACTS and D-FACTS [24]. They briefly explained about the challenges faced by modern power system which includes limited available energy resources, time, capital required and land use restrictions. Results indicate that D-FACTS have more reliability and cost saving approach over FACTS devices. Karim Sebaa, et al. presents the power system dynamic stability enhancement via coordinated design of PSS and SVC based controllers using hierarchical real coded NSGA-II [25]. Results indicate the solution of tuning and location of minimum number of PSS and FACTS based controllers were proposed. S.V Ravi Kumar, et al. presents the transient stability using UPFC and SVC [26]. They thoroughly described the damping of power system oscillations after a three phase fault and also analyze the effect of UPFC and SVC on transient stability performance of power system. They developed a general program for transient stability studies using modified portioned approach. The modelling of SVC and UPFC were studied and tested on a 10-generator, 39-bus, New England test generator. Results indicate that the SVC helps in improving the system performance by improving critical clearing time. Nasimul Islam Maruf, et al. presents a study on thyristor controlled series capacitor as a useful FACT device [27]. They discussed the basic principle and benefits of TCSC during the fault conditions. They conclude that TCSC is a useful FACT device for enhancing the transient stability, steady state stability, dynamic stability and voltage stability of power system under severe conditions. Vibhor Gupta described the study and effects of UPFC and its control system for power flow control and voltage injection in power system [28]. He studied the operating modes of UPFC. Simulation is carried out in MATLAB and results indicate the use of power flow controller and voltage injection. He concludes about the benefits of using UPFC in the system. S.JavedSajjadi, described the effects of series and shunt FACTS devices in transient stability enhancement of multi-machine system [29]. They described the injection model of unified power flow controller and series quadrature voltage injection. Results indicate that the shunt compensation was used for power oscillation damping and effects of series and shunt compensation on transient stability was discussed. N.K Sharma, et al. described the performance of UPFC in several modes operation using different control mechanism based on proportional plus integral control (PI) and Proportional plus integral plus derivative control (PID) [30]. They also developed ANFIS based controller by using ANFIS editor of Matlab. The MATLAB simulation results indicate the capability of UPFC on power flow control and the effectiveness of controllers on the performance of UPFC in the different operating modes. T.K. Gangopadhyay, et al. discussed the problem of designing the damping controller for low frequency oscillations in power system under dynamic uncertainty [31]. They applied H mixed sensitivity technique to design robust damping controllers for unified power flow controller in uncertain conditions. 3. FACTS CONTROLLERS FACTS are defined as“a power electronic based system and other static equipment that provide control of one or more AC transmission system parameters to enhance controllability and increase power transfer capability.Basically, FACTS controllers can be divided into four categories [1]:  Series Controller  Shunt Controller  Combined series-series Controller  Combined series-shunt Controller
  • 5.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 130 – 139 134 Table 1. Comparison among FACTS Controllers 3.1. Static VAR Compensator (SVC) SVC is an electrical device for providing the fast reactive power on high voltage transmission networks. An SVC is based on thyristor controlled reactors (TCR), thyristor switched capacitors (TSC), and/or Fixed Capacitors (FC) tuned to Filters as shown in fig1. A TCR consists of a fixed reactor in series with a bi-directional thyristor valve. TCR reactors are as a rule of air core type, glass fibre insulated, epoxy resin impregnated [15]. Figure 1. SVC Model SVCs had a great advantage over simple mechanically-switched compensation schemes is their fast instantaneous response to changes in the system voltage. For this reason they are often operated at close to their zero-point in order to maximize the reactive power correction they can rapidly provide in system whenever required. They are in general cheaper, higher-capacity, faster, efficient and more reliable over dynamic compensation schemes such as synchronous condensers [15]. 3.2. Static Synchronous Compensator (STATCOM) A Static synchronous compensator is a shunt-connected static Var compensator whose capacitive or inductive output current can be controlled independently of the ac system voltage. STATCOM is made up of a coupling transformer, a VSC and a dc energy storage device as shown in fig2. STATCOM is capable of exchanging reactive power with the transmission line because of its small energy storage device i.e. small dc capacitor, if this dc capacitor is replaced with dc storage battery or other dc voltage source, the controller can exchange real and reactive power with the transmission system, extending its region of operation from two to four quadrants.
  • 6. IJAPE ISSN: 2252-8792  Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai) 135 Figure 2. STATCOM Model 4. SIMULATION MODEL AND RESULTS Consider a two area power system (Area-1 & Area-2) with shunt FACTS devices, connected by a long transmission line as shown in fig-3. Two 1000MW hydraulic generation plants M1 and M2 are connected to a load centre through 500KV, 720KM transmission line. The system was interconnected through 5 buses and RL load. Two machines are equipped with a hydraulic turbine and governor (HTG), excitation system, power system stabilizer and FACT device (SVC or STATCOM). Figure 3. SLD of two area power system 4.1. Two Area System with Three Phase Fault Two area system as shown in fig.-4 is considered in this study. Figure 4. Two Area Systems during Three Phase Fault It is considered that a 3-phase symmetrical short circuit fault of 0.1seconds occur at bus B1. The system is simulated in MATLAB/Simulink environment and graphs are shown in fig.-5 and fig.-6. From the fig.-5, it is inferred that without the FACT device and Power system stabilizer, the oscillation in generator
  • 7.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 130 – 139 136 rotor angle of Area1 and Area2 increases and settling time for the oscillations is found to be high. The difference of the two rotor angle is taken into account and plotted against time. Figure 5. Difference of two rotor angles with time during three phase fault Figure 6. Variation of terminal voltages with time 4.2 Two Area System with FACT device (SVC) and Power System Stabilizer Two area system as shown in figure 7 is considered in this study. Figure 7. Two Area System installed with SVC and PSS The system has a SVC installed at B2. It is considered that a 3-phase symmetrical short circuit fault of 0.1seconds occur at bus B1. Put the Generic type PSS in service by setting the command in PSS block equal to 1. Open the SVC block menu and change the SVC mode of operation to voltage regulation. The system is simulated in Matlab/Simulink environment and graphs of SVC are shown in fig-8 and fig-9. From the fig-8, it is inferred that the oscillations in generator rotor angle is decreased and setting time for the oscillations is found to be 4.0 seconds. Figure 8. Difference of two rotor angles with time installed with SVC and PSS
  • 8. IJAPE ISSN: 2252-8792  Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai) 137 Figure 9. Variation of terminal voltages with time installed with SVC and PSS 4.3 Two Area System with FACT device (STATCOM) and Power System Stabilizer Two area system as shown in figure 10 is considered in this study. Figure 10. Two Area System installed with STATCOM and PSS The system has a STATCOM installed at B2. It is considered that a 3-phase symmetrical short circuit fault of 0.1seconds occur at bus B1. Put the Generic type PSS in service by setting the command in PSS block equal to 1. Open the STATCOM block menu and change the STATCOM mode of operation to voltage regulation. The system is simulated in Matlab/Simulink environment and graphs of STATCOM are shown in fig-11 and fig-12. From the fig-11, it is inferred that the oscillations in generator rotor angle is decreased and setting time for the oscillations is found to be 2.8 seconds. Also, terminal voltages profile has been improved after clearance of fault installed with STATCOM. Hence, the transient stability of two machine system installed with STATCOM has been improved considerably and post settling time of the system after facing disturbance is also improved. Figure 11. Difference of two rotor angles with time installed with STATCOM and PSS Figure 12. Variation of terminal voltages with time installed with STATCOM and PSS
  • 9.  ISSN: 2252-8792 IJAPE Vol. 3, No. 2, August 2014 : 130 – 139 138 4.4 Comparison between FACTS Devices From the simulation results shown in Fig4-Fig12, a comparison is made between the above FACTS devices for stability enhancement of two area power system as shown in Table-2. From the Table-2, it is inferred that STATCOM is the effective FACT device for stability enhancement over SVC as the post settling time obtained from the use of STATCOM is less as compared to that obtained from SVC. Table 2. Comparison between FACTS Devices for Power System Two-areaPower System with PowerSystem Stability Enhancement Post settling time(inseconds) SVC YES 4.0 STATCOM YES 2.8 5. CONCLUSION In this paper, various constraints of the modern power system were discussed and on the basis of these constraints, need of FACTS devices were presented. The dynamics of the power system is compared with and without the presence of FACTS devices and Power system stabilizers in the event of major disturbances. The performance of one of the FACT device i.e. STATCOM for transient stability enhancement is compared with the performance of other FACT device i.e. SVC. Controller’s inputs are chosen carefully to provide necessary damping in rotor angle and results are taken through simulation. Proposed FACTS controllers were implemented in MATLAB/SIMULINK. Simulation results indicate that the STATCOM controller installed with two machine systems provides better damping characteristics in rotor angle as compared to two machine system installed with SVC. Also, the post settling time of the two machine system installed with STATCOM is found to be less i.e. near to 2.8sec than the system with SVC. Thus, transient stability enhancement of the two machine system installed with STATCOM is better than that installed with SVC. REFERENCES [1] Hingorani, N. G., &Gyugyi, L. (2000). Understanding FACTS: concepts and technology of flexible AC transmission systems (Vol. 1). M. El-Hawary (Ed.). New York: IEEE press. [2] Murali, D., Rajaram, D. M., &Reka, N. (2010). Comparison of FACTS devices for power system stability enhancement. International Journal of Computer Applications (0975–8887) Volume, 30-35. [3] Deshpande, A. S., Kadam, P. A. and Rana, V. M. (2011, May). First Swing Stability of Power System Using FACTS Device. 2011 National Conference on Recent trends in Engineering and Technology. [4] Rath, S., Sahu B., & Dash, P. (2012). Power System Operation and Control Using FACTS Devices. International Journal of Engineering Research and Technology. 1(5). [5] Murali, D., &Rajaram, M. (2010). Active and Reactive Power Flow Control using FACTS Devices. International Journal of Computer Applications. 9(8). 45-50. [6] Kumar, A., &Priya, G. (2012, December). Power system stability enhancement using FACTS controllers. In Emerging Trends in Electrical Engineering and Energy Management (ICETEEEM), 2012 International Conference on (pp. 84-87). IEEE. [7] Kodsi, S. M., &Canizares, C. A. (2003). Modeling and simulation of IEEE 14 bus system with FACTS controllers. University of Waterloo, Canada, Tech. Rep. [8] Haddad, S., Haddouche, A. &Bouyeda, H. (2009, April). The use of FACTS Devices in Distributed power systems- Modelling, Interface and case study.International Journal of Computer and Electrical Engineering. 1(1). [9] Abido, M. A. (2009). POWER SYSTEM STABILITY ENHANCEMENT USING FACTS CONTROLLERS: A REVIEW. Arabian Journal for Science & Engineering (Springer Science & Business Media BV), 34. [10] Somalwar, R. &Khemaria, M. (2012, March). A Review of enhancement of Transient stability using FACTS Devices. International journal of Emerging Technologies in Sciences and Engineering, 5(3). [11] Venkateswarlu, K. and Babu, C. S,. (2011, May). Analysis and Enhancement of Transient Stability using SHUNT Controlled FACTS Controllers. International Journal of Engineering Sciences Research. 1(2). [12] Overbye, T. J., & Brown, D. (1993, August). Use of FACTS devices for power system stability enhancement. In Circuits and Systems, 1993. Proceedings of the 36th Midwest Symposium on (pp. 1019-1022). IEEE. [13] Mohanty, A. K., &Barik, A. K. (2011). Power System Stability Improvement Using FACTS Devices. International Journal of Modern Engineering Research, 1(2), 666-672. [14] ABAZARI & EMADI. (2003). Transient stability improvement by using advanced static VAR compensators. Electric Power Components and Systems, 31(4), 321-334.
  • 10. IJAPE ISSN: 2252-8792  Comparison of FACTS Devices for Two Area Power System Stability Enhancement … (J.N.Rai) 139 [15] Kaur, T. and Kakran, S. (2012). Transient stability Improvement of Long Transmission Line System by Using SVC. International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. 1(4). [16] Mohammadi, M. (2011). Voltage Stability Analysis with Static Var Compensator (SVC) for Various Faults in Power System with and Without Power System Stabilizers (PSS). Research Journal of Applied Sciences, Engineering and Technology, 3(7): 668-676. [17] Sharma, D., K., Ahmed, A., Saluja, R. &Parmar, R. Voltage Stability in Power System Using STATCOM. International Journal of Electronics and Computer Science Engineering. 1(2): 198-208. [18] Hosseini, S. H., &Ajami, A. (2002, October). Transient stability enhancement of AC transmission system using STATCOM. In TENCON'02. Proceedings. 2002 IEEE Region 10 Conference on Computers, Communications, Control and Power Engineering (Vol. 3, pp. 1809-1812). IEEE. [19] Rai, A. (2012). Enhancement of Voltage Stability and Reactive power control of Distribution System using FACTS devices. International Journal of Scientific research Engineering and Technology. 1(9): 001-005. [20] Tan, Y. L., & Wang, Y. (1998). Effects of FACTS controller line compensation on power system stability. Power Engineering Review, IEEE, 18(6), 45-47. [21] Panda, S., & Patel, R. N. (2006). Improving power system transient stability with an off-centre location of shunt FACTS devices. JOURNAL OF ELECTRICAL ENGINEERING-BRATISLAVA-, 57(6), 365. [22] Singh, B. (2011). Applications of FACTS Controllers in Power Systems for Enhance the Power System Stability: A State-of-the-art. International Journal of Reviews in Computing, 6. [23] Srivastava, S. K. (2010). Advanced Power Electronics Based FACTS Controllers: An Overview. Asian Power Electronics Journal, 4(3), 90-95. [24] Kakkar, V., & Agarwal, N. K. (2010, September). Recent trends on FACTS and D-FACTS. In Modern Electric Power Systems (MEPS), 2010 Proceedings of the International Symposium (pp. 1-8). IEEE. [25] Sebaa, K., &Boudour, M. (2008, July). Power system dynamic stability enhancement via coordinated design of PSSs and SVC-based controllers using hierarchical real coded NSGA-II. In Power and Energy Society General Meeting-Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE (pp. 1-8). IEEE. [26] Kumar, S. R., &Nagaraju, S. S. (2007). Transient stability improvement using UPFC and SVC. ARPN Journal of Engineering and Applied Sciences, 2(3), 38-45. [27] Maruf, N. I., Mohsin, A., Shoeb, A., Islam, K., & Hossain, M. (2010). Study of thyristor controlled series capacitor (TCSC) as a useful FACTS device.International Journal of Engineering Science and Technology, 2(9), 4357-4360. [28] Gupta, V. (2010). Study and Effects of UPFC and its Control System for Power Flow Control and Voltage Injection in a Power System. International journal of engineering science and technology, 2(7), 2558-2566. [29] Sajjadi, S. J., Mohseninejad, M. H., &Afsharnia, S. EFFECTS OF SERIES AND SHUNT FACTS DEVICES IN TRANSIENT STABILITY ENHANCEMENT OF MULTI-MACHINE POWER SYSTEMS.. [30] Sharma, N. K., &Jagtap, P. P. (2010, November). Modelling and application of unified power flow controller (UPFC). In Emerging Trends in Engineering and Technology (ICETET), 2010 3rd International Conference on (pp. 350-355). IEEE. [31] Gangopadhyay, T. K., Sil, A., & Paul, S. (2009, November). Design of robust UPFC controller for damping power system oscillations using H∞ mixed sensitivity technique. In Advances in Power System Control, Operation and Management (APSCOM 2009), 8th International Conference on (pp. 1-6). IET. [32] Edris, A. A., Adapa, R., Baker, M. H., Bohmann, L., Clark, K., Habashi, K. & Wood, R. R. (1997). Proposed terms and definitions for flexible AC transmission system (FACTS). IEEE Power Engineering Review, 17, 46-46.