Port State Control guidance for examination of fixed CO2 firefighting systems and
conducting fire drills onboard Cruise Ships during scheduled examinations.
(CG-CVC-2 / July 2013)
1. General
These guidelines are intended to assist Port State Control Officers (PSCOs) when
examining fixed CO2 firefighting systems and conducting fire drills during scheduled
passenger vessel examinations. Although this guidance focuses on Cruise Ships, the
methodology may be applied to all ships, and is intended to assist in determining that
the CO2 system is kept in good working order (SOLAS 74 (09 Cons) regulation II-
2/14.2.1.2; crew members are trained and familiar with ship arrangements (SOLAS
74 (09 Cons) regulation II-2/15); and that the crew competencies comply with the
intent of SOLAS III, Regulation 19.3.1 and 19.3.4.
Note: These Guidelines are intended to supplement existing guidance1
and should not
be considered all inclusive, nor is it expected that the PSCO verify/complete every
item herein in order to determine vessel compliance.
2. Background
It has been more than two years since the Assistant Commandant for Marine Safety
issued two Marine Safety Alerts that addressed critical concerns related to the fixed
CO2 system noted during the investigation of the engine room fire on the
CARNIVAL SPLENDOR; Alert 10(a)-10 and 10(b)-10 dated December 21, 2010.
Since the CARNIVAL SPLENDOR engine room fire, two more major fires have
occurred on cruise ships operating out of U.S. Ports: CARNIVAL TRIUMPH and
GRANDEUR OF THE SEAS. These casualties highlight the importance of
shipboard firefighting equipment maintenance and proper crew training to ensure
their readiness to combat a shipboard fire.
3. Safety
a. General: Whenever an examination of a fixed carbon dioxide fire-extinguishing
system is taking place, strict safety precautions should be followed to avoid
accidental discharges and to reduce the risk to individuals performing or
witnessing the activities from the hazards associated with CO2. Prior to the
examination of any fixed CO2 firefighting system, the PSCO should ensure that
Coast Guard personnel are familiar with NVIC 09-00, and utilize the appropriate
CG issued Personal Protective Equipment (PPE) in accordance with existing
policy and verify that:
i. ship board personnel demonstrate compliance and/or knowledge of the
fixed CO2 firefighting system;
1
MSC.1/Circ.1318 - Guidelines for the Maintenance and Inspections of Fixed Carbon Dioxide Fire-Extinguishing Systems;
MSC.1/Circ.1432 - Revised Guidelines for the Maintenance and Inspection of Fire Protection Systems and Appliances; and NVIC 06-
91
ii. that the crew acknowledges all CO2 discharging functions shall be
simulated and no activation or disassembling of any system components
shall be performed (i.e. opening/closing of valves, activation of remotes,
disconnecting linkage, etc.);
iii. the CO2 room ventilation shall be turned on and operating properly for at
least 15 minutes before inspection of the CO2 room;
iv. the CO2 room vent outlet(s) are examined to ensure they are opened and
in serviceable condition;
v. all means of egress are clear and that adequate lighting is available. The
CO2 room door must be secured in the open position. PSCOs should not
enter the CO2 room without a crewmember responsible for CO2 system
maintenance (Chief Engineer, Chief Officer or other responsible person –
this person may or may not be assigned the duties of activating the system
during the fire drill).
b. Inspection or Maintenance: Maintenance and inspections should be carried out in
accordance with the ship’s maintenance plan having due regard to ensuring the
reliability of the system. The onboard maintenance plan should be included in the
ship’s safety management system and should be based on the system
manufacturer’s recommendations. Certain maintenance procedures and
inspections may be performed by competent crew members while others are
required to be performed by persons specially trained in the maintenance of such
systems (servicing technicians). The onboard maintenance plan should indicate
which inspections and what system maintenance procedures can be completed by
the crew (or servicing technician) and which items must be completed by a
servicing technician. At times PSCOs may witness an inspection or maintenance
of a fixed CO2 firefighting system in order to clear a deficiency. In these cases,
the PSCO should be aware of additional safeguards necessary to avoid accidental
discharges such as locking or removing the operating arms from directional
valves, or shutting and locking the system block valve, evacuating the space
protected, etc. PSCOs should interview the servicing personnel to verify they are
an authorized servicing agency for the installed equipment and are familiar with
the operation of the system. PSCOs should review the safety procedures with the
servicing personnel before witnessing repairs/maintenance. Personnel which are
not engaged in the repairs, maintenance or testing but may be performing work
activities in the immediate or surrounding areas (i.e. engine room crewmembers,
cadets, etc.) should be notified of the impending activities before work is begun.
4. Fixed CO2 firefighting system examination guidance (SOLAS II-2, Reg. 14.2.2)
during scheduled PSC exams
a. PSCOs should review Marine Safety Alerts 10(a) – 10 and 10(b) – 10 to
familiarize themselves with examples of discrepancies pertaining to fixed CO2
firefighting systems.
b. Examine the ship's maintenance plan required by SOLAS II-2/14 and the
Firefighting Instruction Manual (FIM) for maintenance, testing and inspections
required. Compare the maintenance plan and FIM with posted instruction for
operating the installed CO2 system, test procedures and images referenced for
verification to ensure these items agree with the CO2 system arrangements as
installed. PSCOs should question crewmembers (i.e. Chief Engineer or Chief
Officer) assigned responsibility for the CO2 system maintenance to gauge their
familiarity with the FIM and installed system.
c. Visually examine the individual lines connecting the CO2 bottles to the CO2
distribution piping system paying particular attention to their tightness. Visually
check for the use of hemp or other types of sealant (extruding from the connection
per the photo in MSA 10(b)-10 (pg 2) as most high pressure systems utilize a
mechanical connection which does not require the use of sealant. At no time
should components be disassembled for the PSCO’s examination.
d. Using care to not actuate the system, visually examine the CO2 actuator arms,
valves, associated hardware and other piping connections for proper assembly and
tightness (loose bolts, unions, control heads, missing gaskets, loose disconnected
hoses).
e. Pay particular attention to proper installation of control valves (i.e. directional
flow check valves, handles provided, etc.) Verify that control valves and release
stations are correctly labeled as to the spaces served by that section of the system.
f. Check the maintenance plan (SOLAS II-2/14.2.2.2 & SMS) indicating the results
of previous maintenance record and inspections performed either by ship’s crew
or specially trained personnel (certified technician). Confirm that inspections
check for proper operation of pressure switches for control of ventilation fans and
fuel shut-offs for the protected space.
g. Any concerns noted during the visual exam should be brought to the attention of
the Master or Chief Engineer.
Note: Other fire protection systems, fire fighting systems and appliances are just as
important as the fixed CO2 system and may even be integral to the fixed CO2
system’s ability to extinguish a fire. PSCOs should be cognizant of other
equipment and design factors, such as ventilation shutdowns, remote fuel
quick closing valves, hatches, scuttles, doors and fire boundaries/insulation
(i.e. A-60 bulkheads) when performing the PSC exam.
5. Fire Drills (SOLAS Ch. II-2, Reg. 15 & Ch. III, Reg. 19 & NVIC 06 – 91)
a. When witnessing fire drills during each annual and semi-annual COC
examination it is important to ensure that the fire location selected will properly
evaluate the crew’s response to a high consequence fire. As such, during the next
Cruise Ship scheduled exam the PSCO shall select an engine room for the fire
drill location. Once a vessel has completed this initial fire drill of an engine
room, other locations may be selected during subsequent PSC exams, however a
fire drill will be conducted in the engine room at least once during the vessel’s
COC annual cycle. The location in which the fire drill was held shall be recorded
in the remarks section of the COC.
b. Examine the ship's instructions related to onboard training and drills required by
SOLAS II-2/15. In addition to the normal observations associated with a fire drill
(i.e. proper muster, appropriate gear/donning of gear, passenger instructions, etc.)
the PSCO should pay particular attention to the competency of crewmembers
assigned to operating fire fighting systems. The following questions may assist in
evaluating their knowledge and experience with their assigned duties related to
the CO2 system:
i. How does the crewmember receive training and familiarization with the
operational requirements of the system or equipment for which they are
assigned responsibility?
ii. Where does activation of the system take place (remote/bridge) and who is
responsible for authorizing activation (master/fire team leader);
iii. Can the crewmember explain how to operate the system or appliance; confirm
their explanation corresponds to the written/posted instructions;
iv. What other actions are required prior to activating the system (i.e. ventilation
& power secured, engine room evacuation, etc.). Note: This may be part of
the Master’s responsibility prior to giving permission to activate the system.
v. How is permission passed to activate the CO2 system?
vi. How does the crewmember verify the system has activated and what are some
indicators available to the crewmember that the system did or did not function
properly?
vii. If presented with the scenario that the fixed CO2 system did not activate
properly, what actions are taken? Is there a secondary means to activate?
Does the crewmember need permission to activate by the secondary means &
does this align with the shipboard firefighting instructions/procedures/
training?
viii. Does their explanation correspond to posted instructions? Are there any other
system functions required to direct the discharge of CO2 to the space
intended? (i.e. bypass valves, manually opening of control valves, etc.);
ix. What actions must be taken before the space can be re-entered after the CO2
system is discharged? How are temperatures monitored to verify the fire is
extinguished? How much time must elapse before the space can be
ventilated? (at least 1 hour is recommended)
6. Discrepancies identified
a. The Master shall immediately be notified of any discrepancy (i.e. issues with
components of the fixed CO2 firefighting system affecting the proper operation;
written or posted operational procedure; or crew knowledge of assigned duties).
b. Not all discrepancies or concerns discovered will prevent the CO2 system from
discharging as designed (i.e. hemp packing discovered in mechanical seal
fittings), however based on the critical concerns identified in the MSA’s, PSCOs
should provide copies of the MSAs to the Master if similar discrepancies are
noted. The PSCO should also review the Coast Guard’s recommendations as
outlined in the MSAs with the Master.
Note: Maintenance, inspections and service performed on a fixed CO2
firefighting system shall be in accordance with the vessels maintenance plan
and/or the Manufacturer’s FIM.
c. Deficiencies that are corrected-on-the-spot, or, in other words, deficiencies
corrected before the PSCO completes his or her visit to the vessel shall be
documented as follows:
i. Detainable deficiencies corrected-on-the-spot must always be documented on
the form B and entered into MISLE as corrected;
ii. Serious deficiencies corrected-on-the-spot should be documented on the form
B and entered into MISLE as corrected (example - anything that would
qualify as a code 17 deficiency should be documented in this way);
iii. Lesser deficiencies corrected on the spot need not be documented on the form
B and entered into MISLE unless the deficiencies are attributed to a systemic
failure of the maintenance program contained in the vessel's safety
management system. If this is the case, an expanded ISM exam should also be
conducted.
iv. With the exception of initial COC exams on passenger ships, for multiple-day
PSC exams, the PSCO should provide the master with a form A/B at the end
of each day. Lesser deficiencies documented on an earlier days form B and
corrected by the end of the PSC exam need not be entered into MISLE as a
deficiency unless it meets the criterion discussed above (iii.).
v. As a point of reference, current policy for U.S. inspected vessels does not
require inspectors to document deficiencies corrected on the spot with an 835
or MISLE deficiency (but the situation may merit a narrative entry to discuss
how an issue was handled). Keep this in mind when writing form B’s and
making MISLE entries for PSC exam lesser deficiencies.
d. The following examples are provided to assist the PSCO in determining the
appropriate course of action for discrepancies identified:
i. Crew knowledge of assigned duties or conflicts with posted vs.
Manufacturer’s instructions should be documented on the Form B. This may
be remedied by the Master as follows: providing additional training, re-
assigning of duties or by amending the posted instructions and ensuring all
crewmembers assigned with duties affected by the changes are aware of the
amendments. For deficiencies other than failure of two consecutive fire drills
(detainable), the PSCO should issue a code 17.
ii. Loose fittings discovered on flex (or hard pipe) connections, connecting the
CO2 bottles to the servicing branch line should be documented on the Form B
as a code 17.
Note: The OCMI maintains discretion for allowing a vessel to sail with
outstanding deficiencies provided in his/her opinion safe alternative
arrangements have been made.

More Related Content

What's hot

Department of Shipping, Bangladesh approved MEO Class-3 CoC Exam Preparatory ...
Department of Shipping, Bangladesh approved MEO Class-3 CoC Exam Preparatory ...Department of Shipping, Bangladesh approved MEO Class-3 CoC Exam Preparatory ...
Department of Shipping, Bangladesh approved MEO Class-3 CoC Exam Preparatory ...Mohammud Hanif Dewan M.Phil.
 
02 Years Pre-sea Course Syllabus of Department of Shipping, Bangladesh
02 Years Pre-sea Course Syllabus of Department of Shipping, Bangladesh02 Years Pre-sea Course Syllabus of Department of Shipping, Bangladesh
02 Years Pre-sea Course Syllabus of Department of Shipping, BangladeshMohammud Hanif Dewan M.Phil.
 
Abs 1975 single point moorings
Abs 1975 single point mooringsAbs 1975 single point moorings
Abs 1975 single point mooringsIgnacio Santana
 
2003 structures
2003 structures2003 structures
2003 structuresHifon Wong
 
Check interval escalation
Check interval escalationCheck interval escalation
Check interval escalationMohammed Hadi
 
Ves04 errv-management-guidelines-issue-4
Ves04 errv-management-guidelines-issue-4Ves04 errv-management-guidelines-issue-4
Ves04 errv-management-guidelines-issue-4hainguyenbk
 
SPCC Plan Training
SPCC Plan TrainingSPCC Plan Training
SPCC Plan Traininglhanrahan
 
PEOLMWFY2008
PEOLMWFY2008PEOLMWFY2008
PEOLMWFY2008Will P
 
Tugas iii etops approval
Tugas iii etops approvalTugas iii etops approval
Tugas iii etops approvalLalu Giat Putra
 
CMC FAA Certification
CMC FAA CertificationCMC FAA Certification
CMC FAA CertificationSteve Gonczy
 
Check interval escalation
Check interval escalation Check interval escalation
Check interval escalation Mohammed Awad
 
ETOPS - Extended Twinned Engine Operations
ETOPS - Extended Twinned Engine OperationsETOPS - Extended Twinned Engine Operations
ETOPS - Extended Twinned Engine OperationsKelvin Lam
 

What's hot (16)

Department of Shipping, Bangladesh approved MEO Class-3 CoC Exam Preparatory ...
Department of Shipping, Bangladesh approved MEO Class-3 CoC Exam Preparatory ...Department of Shipping, Bangladesh approved MEO Class-3 CoC Exam Preparatory ...
Department of Shipping, Bangladesh approved MEO Class-3 CoC Exam Preparatory ...
 
02 Years Pre-sea Course Syllabus of Department of Shipping, Bangladesh
02 Years Pre-sea Course Syllabus of Department of Shipping, Bangladesh02 Years Pre-sea Course Syllabus of Department of Shipping, Bangladesh
02 Years Pre-sea Course Syllabus of Department of Shipping, Bangladesh
 
Abs 1975 single point moorings
Abs 1975 single point mooringsAbs 1975 single point moorings
Abs 1975 single point moorings
 
2003 structures
2003 structures2003 structures
2003 structures
 
Check interval escalation
Check interval escalationCheck interval escalation
Check interval escalation
 
Maintenance
MaintenanceMaintenance
Maintenance
 
Ves04 errv-management-guidelines-issue-4
Ves04 errv-management-guidelines-issue-4Ves04 errv-management-guidelines-issue-4
Ves04 errv-management-guidelines-issue-4
 
Psc checklist
Psc checklistPsc checklist
Psc checklist
 
SPCC Plan Training
SPCC Plan TrainingSPCC Plan Training
SPCC Plan Training
 
PEOLMWFY2008
PEOLMWFY2008PEOLMWFY2008
PEOLMWFY2008
 
MEO Class 4&5 Prep. Course Syllabus
MEO Class 4&5 Prep. Course SyllabusMEO Class 4&5 Prep. Course Syllabus
MEO Class 4&5 Prep. Course Syllabus
 
Tugas iii etops approval
Tugas iii etops approvalTugas iii etops approval
Tugas iii etops approval
 
CMC FAA Certification
CMC FAA CertificationCMC FAA Certification
CMC FAA Certification
 
Surveys of Merchant Ships
Surveys of Merchant Ships Surveys of Merchant Ships
Surveys of Merchant Ships
 
Check interval escalation
Check interval escalation Check interval escalation
Check interval escalation
 
ETOPS - Extended Twinned Engine Operations
ETOPS - Extended Twinned Engine OperationsETOPS - Extended Twinned Engine Operations
ETOPS - Extended Twinned Engine Operations
 

Viewers also liked

Viewers also liked (14)

Quản trị xuất nhập khẩu
Quản trị xuất nhập khẩu Quản trị xuất nhập khẩu
Quản trị xuất nhập khẩu
 
Shipdocumentation
ShipdocumentationShipdocumentation
Shipdocumentation
 
Tokyo mou deficiency codes (june 2014)
Tokyo mou deficiency codes (june 2014)Tokyo mou deficiency codes (june 2014)
Tokyo mou deficiency codes (june 2014)
 
Ch4 ke hoach van hanh va to chuc VTCC
Ch4 ke hoach van hanh va to chuc VTCCCh4 ke hoach van hanh va to chuc VTCC
Ch4 ke hoach van hanh va to chuc VTCC
 
Ch5 quan ly VTCC
Ch5 quan ly VTCCCh5 quan ly VTCC
Ch5 quan ly VTCC
 
Quan ly kho va hang ton kho ch1
Quan ly kho va hang ton kho ch1Quan ly kho va hang ton kho ch1
Quan ly kho va hang ton kho ch1
 
Full+toefl grammar
Full+toefl grammarFull+toefl grammar
Full+toefl grammar
 
Quan ly kho va hang ton kho ch3
Quan ly kho va hang ton kho ch3Quan ly kho va hang ton kho ch3
Quan ly kho va hang ton kho ch3
 
Quan ly kho va hang ton kho ch2
Quan ly kho va hang ton kho ch2Quan ly kho va hang ton kho ch2
Quan ly kho va hang ton kho ch2
 
VẬN CHUYỂN HÀNG HÓA BẰNG CONTAINER ĐƯỜNG BIỂN
VẬN CHUYỂN HÀNG HÓA BẰNG CONTAINER ĐƯỜNG BIỂN VẬN CHUYỂN HÀNG HÓA BẰNG CONTAINER ĐƯỜNG BIỂN
VẬN CHUYỂN HÀNG HÓA BẰNG CONTAINER ĐƯỜNG BIỂN
 
30 thuật ngữ tiếng anh thường dùng trong xuất nhập khẩu
30 thuật ngữ tiếng anh thường dùng trong xuất nhập khẩu30 thuật ngữ tiếng anh thường dùng trong xuất nhập khẩu
30 thuật ngữ tiếng anh thường dùng trong xuất nhập khẩu
 
Export Procedures and Documents
Export Procedures and DocumentsExport Procedures and Documents
Export Procedures and Documents
 
Shipping Container Architecture Research
Shipping Container Architecture ResearchShipping Container Architecture Research
Shipping Container Architecture Research
 
EXPORT IMPORT
EXPORT IMPORTEXPORT IMPORT
EXPORT IMPORT
 

Similar to Port state control guidance for examination of fixed co2 firefighting systems

P_3__MODU_code_rev_0.pptx
P_3__MODU_code_rev_0.pptxP_3__MODU_code_rev_0.pptx
P_3__MODU_code_rev_0.pptxantonygrande
 
Aged aircraft maintenance.
Aged aircraft maintenance.Aged aircraft maintenance.
Aged aircraft maintenance.S P Singh
 
Laid up vessel reactivation guide- West of England
Laid up vessel reactivation guide- West of EnglandLaid up vessel reactivation guide- West of England
Laid up vessel reactivation guide- West of EnglandDeva RG
 
Watch keeping duties , responsibilities and cargo documentation
Watch keeping duties ,  responsibilities and cargo documentationWatch keeping duties ,  responsibilities and cargo documentation
Watch keeping duties , responsibilities and cargo documentationOladokun Sulaiman Olanrewaju
 
CE oral Q&A .pdf which give oral preparation QA for MCA chief engineer oral e...
CE oral Q&A .pdf which give oral preparation QA for MCA chief engineer oral e...CE oral Q&A .pdf which give oral preparation QA for MCA chief engineer oral e...
CE oral Q&A .pdf which give oral preparation QA for MCA chief engineer oral e...sailorizzhere
 
Imo entry into enclosed space permit
Imo entry into enclosed space permitImo entry into enclosed space permit
Imo entry into enclosed space permitPrince Mathew
 
Carnival splendor
Carnival splendorCarnival splendor
Carnival splendorJomonJohny5
 
Old Dominion University
Old Dominion UniversityOld Dominion University
Old Dominion Universitybutest
 
Old Dominion University
Old Dominion UniversityOld Dominion University
Old Dominion Universitybutest
 
draft IMC 7.03 officer in charge a navigational watch
draft IMC 7.03 officer in charge a navigational watchdraft IMC 7.03 officer in charge a navigational watch
draft IMC 7.03 officer in charge a navigational watchAkmad Yani Ridzani
 
Student Declaration on Submission I confirm that all the work in.docx
Student Declaration on Submission I confirm that all the work in.docxStudent Declaration on Submission I confirm that all the work in.docx
Student Declaration on Submission I confirm that all the work in.docxflorriezhamphrey3065
 
Widespread Fatigue Damage
Widespread Fatigue DamageWidespread Fatigue Damage
Widespread Fatigue Damagesyedrooh
 
06 5759-tec ops-sect 3 (3.01-3.10)- repairs, maint & insp
06 5759-tec ops-sect 3 (3.01-3.10)- repairs, maint & insp06 5759-tec ops-sect 3 (3.01-3.10)- repairs, maint & insp
06 5759-tec ops-sect 3 (3.01-3.10)- repairs, maint & inspharish chandra CHOPRA
 
Internal cleaning of fuel tanks
Internal cleaning of fuel tanksInternal cleaning of fuel tanks
Internal cleaning of fuel tanksMohamed Basyoni
 
Guidelines for periodic servicing and maintenance of lifeboats
Guidelines for periodic servicing and maintenance of lifeboatsGuidelines for periodic servicing and maintenance of lifeboats
Guidelines for periodic servicing and maintenance of lifeboatsAna Vicente
 

Similar to Port state control guidance for examination of fixed co2 firefighting systems (20)

P_3__MODU_code_rev_0.pptx
P_3__MODU_code_rev_0.pptxP_3__MODU_code_rev_0.pptx
P_3__MODU_code_rev_0.pptx
 
Aged aircraft maintenance.
Aged aircraft maintenance.Aged aircraft maintenance.
Aged aircraft maintenance.
 
Laid up vessel reactivation guide- West of England
Laid up vessel reactivation guide- West of EnglandLaid up vessel reactivation guide- West of England
Laid up vessel reactivation guide- West of England
 
Watch keeping duties , responsibilities and cargo documentation
Watch keeping duties ,  responsibilities and cargo documentationWatch keeping duties ,  responsibilities and cargo documentation
Watch keeping duties , responsibilities and cargo documentation
 
CE oral Q&A .pdf which give oral preparation QA for MCA chief engineer oral e...
CE oral Q&A .pdf which give oral preparation QA for MCA chief engineer oral e...CE oral Q&A .pdf which give oral preparation QA for MCA chief engineer oral e...
CE oral Q&A .pdf which give oral preparation QA for MCA chief engineer oral e...
 
Imo entry into enclosed space permit
Imo entry into enclosed space permitImo entry into enclosed space permit
Imo entry into enclosed space permit
 
Stcw
StcwStcw
Stcw
 
Carnival splendor
Carnival splendorCarnival splendor
Carnival splendor
 
Old Dominion University
Old Dominion UniversityOld Dominion University
Old Dominion University
 
Old Dominion University
Old Dominion UniversityOld Dominion University
Old Dominion University
 
draft IMC 7.03 officer in charge a navigational watch
draft IMC 7.03 officer in charge a navigational watchdraft IMC 7.03 officer in charge a navigational watch
draft IMC 7.03 officer in charge a navigational watch
 
Fire Fighting system on ship
Fire Fighting system on shipFire Fighting system on ship
Fire Fighting system on ship
 
hhh
hhhhhh
hhh
 
Student Declaration on Submission I confirm that all the work in.docx
Student Declaration on Submission I confirm that all the work in.docxStudent Declaration on Submission I confirm that all the work in.docx
Student Declaration on Submission I confirm that all the work in.docx
 
Widespread Fatigue Damage
Widespread Fatigue DamageWidespread Fatigue Damage
Widespread Fatigue Damage
 
06 5759-tec ops-sect 3 (3.01-3.10)- repairs, maint & insp
06 5759-tec ops-sect 3 (3.01-3.10)- repairs, maint & insp06 5759-tec ops-sect 3 (3.01-3.10)- repairs, maint & insp
06 5759-tec ops-sect 3 (3.01-3.10)- repairs, maint & insp
 
Cmr
CmrCmr
Cmr
 
Transcript
TranscriptTranscript
Transcript
 
Internal cleaning of fuel tanks
Internal cleaning of fuel tanksInternal cleaning of fuel tanks
Internal cleaning of fuel tanks
 
Guidelines for periodic servicing and maintenance of lifeboats
Guidelines for periodic servicing and maintenance of lifeboatsGuidelines for periodic servicing and maintenance of lifeboats
Guidelines for periodic servicing and maintenance of lifeboats
 

Recently uploaded

Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile ServiceCunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile ServiceHigh Profile Call Girls
 
EDUROOT SME_ Performance upto March-2024.pptx
EDUROOT SME_ Performance upto March-2024.pptxEDUROOT SME_ Performance upto March-2024.pptx
EDUROOT SME_ Performance upto March-2024.pptxaaryamanorathofficia
 
Regional Snapshot Atlanta Aging Trends 2024
Regional Snapshot Atlanta Aging Trends 2024Regional Snapshot Atlanta Aging Trends 2024
Regional Snapshot Atlanta Aging Trends 2024ARCResearch
 
↑VVIP celebrity ( Pune ) Serampore Call Girls 8250192130 unlimited shot and a...
↑VVIP celebrity ( Pune ) Serampore Call Girls 8250192130 unlimited shot and a...↑VVIP celebrity ( Pune ) Serampore Call Girls 8250192130 unlimited shot and a...
↑VVIP celebrity ( Pune ) Serampore Call Girls 8250192130 unlimited shot and a...ranjana rawat
 
Fair Trash Reduction - West Hartford, CT
Fair Trash Reduction - West Hartford, CTFair Trash Reduction - West Hartford, CT
Fair Trash Reduction - West Hartford, CTaccounts329278
 
VIP Russian Call Girls in Indore Ishita 💚😋 9256729539 🚀 Indore Escorts
VIP Russian Call Girls in Indore Ishita 💚😋  9256729539 🚀 Indore EscortsVIP Russian Call Girls in Indore Ishita 💚😋  9256729539 🚀 Indore Escorts
VIP Russian Call Girls in Indore Ishita 💚😋 9256729539 🚀 Indore Escortsaditipandeya
 
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
VIP Kolkata Call Girl Jatin Das Park 👉 8250192130 Available With Room
VIP Kolkata Call Girl Jatin Das Park 👉 8250192130  Available With RoomVIP Kolkata Call Girl Jatin Das Park 👉 8250192130  Available With Room
VIP Kolkata Call Girl Jatin Das Park 👉 8250192130 Available With Roomishabajaj13
 
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…nishakur201
 
##9711199012 Call Girls Delhi Rs-5000 UpTo 10 K Hauz Khas Whats Up Number
##9711199012 Call Girls Delhi Rs-5000 UpTo 10 K Hauz Khas  Whats Up Number##9711199012 Call Girls Delhi Rs-5000 UpTo 10 K Hauz Khas  Whats Up Number
##9711199012 Call Girls Delhi Rs-5000 UpTo 10 K Hauz Khas Whats Up NumberMs Riya
 
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...ranjana rawat
 
2024: The FAR, Federal Acquisition Regulations - Part 28
2024: The FAR, Federal Acquisition Regulations - Part 282024: The FAR, Federal Acquisition Regulations - Part 28
2024: The FAR, Federal Acquisition Regulations - Part 28JSchaus & Associates
 
2024 Zoom Reinstein Legacy Asbestos Webinar
2024 Zoom Reinstein Legacy Asbestos Webinar2024 Zoom Reinstein Legacy Asbestos Webinar
2024 Zoom Reinstein Legacy Asbestos WebinarLinda Reinstein
 
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Climate change and safety and health at work
Climate change and safety and health at workClimate change and safety and health at work
Climate change and safety and health at workChristina Parmionova
 
Expressive clarity oral presentation.pptx
Expressive clarity oral presentation.pptxExpressive clarity oral presentation.pptx
Expressive clarity oral presentation.pptxtsionhagos36
 
Global debate on climate change and occupational safety and health.
Global debate on climate change and occupational safety and health.Global debate on climate change and occupational safety and health.
Global debate on climate change and occupational safety and health.Christina Parmionova
 

Recently uploaded (20)

Delhi Russian Call Girls In Connaught Place ➡️9999965857 India's Finest Model...
Delhi Russian Call Girls In Connaught Place ➡️9999965857 India's Finest Model...Delhi Russian Call Girls In Connaught Place ➡️9999965857 India's Finest Model...
Delhi Russian Call Girls In Connaught Place ➡️9999965857 India's Finest Model...
 
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile ServiceCunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
Cunningham Road Call Girls Bangalore WhatsApp 8250192130 High Profile Service
 
EDUROOT SME_ Performance upto March-2024.pptx
EDUROOT SME_ Performance upto March-2024.pptxEDUROOT SME_ Performance upto March-2024.pptx
EDUROOT SME_ Performance upto March-2024.pptx
 
Regional Snapshot Atlanta Aging Trends 2024
Regional Snapshot Atlanta Aging Trends 2024Regional Snapshot Atlanta Aging Trends 2024
Regional Snapshot Atlanta Aging Trends 2024
 
↑VVIP celebrity ( Pune ) Serampore Call Girls 8250192130 unlimited shot and a...
↑VVIP celebrity ( Pune ) Serampore Call Girls 8250192130 unlimited shot and a...↑VVIP celebrity ( Pune ) Serampore Call Girls 8250192130 unlimited shot and a...
↑VVIP celebrity ( Pune ) Serampore Call Girls 8250192130 unlimited shot and a...
 
Fair Trash Reduction - West Hartford, CT
Fair Trash Reduction - West Hartford, CTFair Trash Reduction - West Hartford, CT
Fair Trash Reduction - West Hartford, CT
 
VIP Russian Call Girls in Indore Ishita 💚😋 9256729539 🚀 Indore Escorts
VIP Russian Call Girls in Indore Ishita 💚😋  9256729539 🚀 Indore EscortsVIP Russian Call Girls in Indore Ishita 💚😋  9256729539 🚀 Indore Escorts
VIP Russian Call Girls in Indore Ishita 💚😋 9256729539 🚀 Indore Escorts
 
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
(PRIYA) Call Girls Rajgurunagar ( 7001035870 ) HI-Fi Pune Escorts Service
 
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(NEHA) Bhosari Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
VIP Kolkata Call Girl Jatin Das Park 👉 8250192130 Available With Room
VIP Kolkata Call Girl Jatin Das Park 👉 8250192130  Available With RoomVIP Kolkata Call Girl Jatin Das Park 👉 8250192130  Available With Room
VIP Kolkata Call Girl Jatin Das Park 👉 8250192130 Available With Room
 
Call Girls Service Connaught Place @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
Call Girls Service Connaught Place @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...Call Girls Service Connaught Place @9999965857 Delhi 🫦 No Advance  VVIP 🍎 SER...
Call Girls Service Connaught Place @9999965857 Delhi 🫦 No Advance VVIP 🍎 SER...
 
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
Goa Escorts WhatsApp Number South Goa Call Girl … 8588052666…
 
##9711199012 Call Girls Delhi Rs-5000 UpTo 10 K Hauz Khas Whats Up Number
##9711199012 Call Girls Delhi Rs-5000 UpTo 10 K Hauz Khas  Whats Up Number##9711199012 Call Girls Delhi Rs-5000 UpTo 10 K Hauz Khas  Whats Up Number
##9711199012 Call Girls Delhi Rs-5000 UpTo 10 K Hauz Khas Whats Up Number
 
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
The Most Attractive Pune Call Girls Handewadi Road 8250192130 Will You Miss T...
 
2024: The FAR, Federal Acquisition Regulations - Part 28
2024: The FAR, Federal Acquisition Regulations - Part 282024: The FAR, Federal Acquisition Regulations - Part 28
2024: The FAR, Federal Acquisition Regulations - Part 28
 
2024 Zoom Reinstein Legacy Asbestos Webinar
2024 Zoom Reinstein Legacy Asbestos Webinar2024 Zoom Reinstein Legacy Asbestos Webinar
2024 Zoom Reinstein Legacy Asbestos Webinar
 
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
(DIVYA) Call Girls Wakad ( 7001035870 ) HI-Fi Pune Escorts Service
 
Climate change and safety and health at work
Climate change and safety and health at workClimate change and safety and health at work
Climate change and safety and health at work
 
Expressive clarity oral presentation.pptx
Expressive clarity oral presentation.pptxExpressive clarity oral presentation.pptx
Expressive clarity oral presentation.pptx
 
Global debate on climate change and occupational safety and health.
Global debate on climate change and occupational safety and health.Global debate on climate change and occupational safety and health.
Global debate on climate change and occupational safety and health.
 

Port state control guidance for examination of fixed co2 firefighting systems

  • 1. Port State Control guidance for examination of fixed CO2 firefighting systems and conducting fire drills onboard Cruise Ships during scheduled examinations. (CG-CVC-2 / July 2013) 1. General These guidelines are intended to assist Port State Control Officers (PSCOs) when examining fixed CO2 firefighting systems and conducting fire drills during scheduled passenger vessel examinations. Although this guidance focuses on Cruise Ships, the methodology may be applied to all ships, and is intended to assist in determining that the CO2 system is kept in good working order (SOLAS 74 (09 Cons) regulation II- 2/14.2.1.2; crew members are trained and familiar with ship arrangements (SOLAS 74 (09 Cons) regulation II-2/15); and that the crew competencies comply with the intent of SOLAS III, Regulation 19.3.1 and 19.3.4. Note: These Guidelines are intended to supplement existing guidance1 and should not be considered all inclusive, nor is it expected that the PSCO verify/complete every item herein in order to determine vessel compliance. 2. Background It has been more than two years since the Assistant Commandant for Marine Safety issued two Marine Safety Alerts that addressed critical concerns related to the fixed CO2 system noted during the investigation of the engine room fire on the CARNIVAL SPLENDOR; Alert 10(a)-10 and 10(b)-10 dated December 21, 2010. Since the CARNIVAL SPLENDOR engine room fire, two more major fires have occurred on cruise ships operating out of U.S. Ports: CARNIVAL TRIUMPH and GRANDEUR OF THE SEAS. These casualties highlight the importance of shipboard firefighting equipment maintenance and proper crew training to ensure their readiness to combat a shipboard fire. 3. Safety a. General: Whenever an examination of a fixed carbon dioxide fire-extinguishing system is taking place, strict safety precautions should be followed to avoid accidental discharges and to reduce the risk to individuals performing or witnessing the activities from the hazards associated with CO2. Prior to the examination of any fixed CO2 firefighting system, the PSCO should ensure that Coast Guard personnel are familiar with NVIC 09-00, and utilize the appropriate CG issued Personal Protective Equipment (PPE) in accordance with existing policy and verify that: i. ship board personnel demonstrate compliance and/or knowledge of the fixed CO2 firefighting system; 1 MSC.1/Circ.1318 - Guidelines for the Maintenance and Inspections of Fixed Carbon Dioxide Fire-Extinguishing Systems; MSC.1/Circ.1432 - Revised Guidelines for the Maintenance and Inspection of Fire Protection Systems and Appliances; and NVIC 06- 91
  • 2. ii. that the crew acknowledges all CO2 discharging functions shall be simulated and no activation or disassembling of any system components shall be performed (i.e. opening/closing of valves, activation of remotes, disconnecting linkage, etc.); iii. the CO2 room ventilation shall be turned on and operating properly for at least 15 minutes before inspection of the CO2 room; iv. the CO2 room vent outlet(s) are examined to ensure they are opened and in serviceable condition; v. all means of egress are clear and that adequate lighting is available. The CO2 room door must be secured in the open position. PSCOs should not enter the CO2 room without a crewmember responsible for CO2 system maintenance (Chief Engineer, Chief Officer or other responsible person – this person may or may not be assigned the duties of activating the system during the fire drill). b. Inspection or Maintenance: Maintenance and inspections should be carried out in accordance with the ship’s maintenance plan having due regard to ensuring the reliability of the system. The onboard maintenance plan should be included in the ship’s safety management system and should be based on the system manufacturer’s recommendations. Certain maintenance procedures and inspections may be performed by competent crew members while others are required to be performed by persons specially trained in the maintenance of such systems (servicing technicians). The onboard maintenance plan should indicate which inspections and what system maintenance procedures can be completed by the crew (or servicing technician) and which items must be completed by a servicing technician. At times PSCOs may witness an inspection or maintenance of a fixed CO2 firefighting system in order to clear a deficiency. In these cases, the PSCO should be aware of additional safeguards necessary to avoid accidental discharges such as locking or removing the operating arms from directional valves, or shutting and locking the system block valve, evacuating the space protected, etc. PSCOs should interview the servicing personnel to verify they are an authorized servicing agency for the installed equipment and are familiar with the operation of the system. PSCOs should review the safety procedures with the servicing personnel before witnessing repairs/maintenance. Personnel which are not engaged in the repairs, maintenance or testing but may be performing work activities in the immediate or surrounding areas (i.e. engine room crewmembers, cadets, etc.) should be notified of the impending activities before work is begun. 4. Fixed CO2 firefighting system examination guidance (SOLAS II-2, Reg. 14.2.2) during scheduled PSC exams a. PSCOs should review Marine Safety Alerts 10(a) – 10 and 10(b) – 10 to familiarize themselves with examples of discrepancies pertaining to fixed CO2 firefighting systems.
  • 3. b. Examine the ship's maintenance plan required by SOLAS II-2/14 and the Firefighting Instruction Manual (FIM) for maintenance, testing and inspections required. Compare the maintenance plan and FIM with posted instruction for operating the installed CO2 system, test procedures and images referenced for verification to ensure these items agree with the CO2 system arrangements as installed. PSCOs should question crewmembers (i.e. Chief Engineer or Chief Officer) assigned responsibility for the CO2 system maintenance to gauge their familiarity with the FIM and installed system. c. Visually examine the individual lines connecting the CO2 bottles to the CO2 distribution piping system paying particular attention to their tightness. Visually check for the use of hemp or other types of sealant (extruding from the connection per the photo in MSA 10(b)-10 (pg 2) as most high pressure systems utilize a mechanical connection which does not require the use of sealant. At no time should components be disassembled for the PSCO’s examination. d. Using care to not actuate the system, visually examine the CO2 actuator arms, valves, associated hardware and other piping connections for proper assembly and tightness (loose bolts, unions, control heads, missing gaskets, loose disconnected hoses). e. Pay particular attention to proper installation of control valves (i.e. directional flow check valves, handles provided, etc.) Verify that control valves and release stations are correctly labeled as to the spaces served by that section of the system. f. Check the maintenance plan (SOLAS II-2/14.2.2.2 & SMS) indicating the results of previous maintenance record and inspections performed either by ship’s crew or specially trained personnel (certified technician). Confirm that inspections check for proper operation of pressure switches for control of ventilation fans and fuel shut-offs for the protected space. g. Any concerns noted during the visual exam should be brought to the attention of the Master or Chief Engineer. Note: Other fire protection systems, fire fighting systems and appliances are just as important as the fixed CO2 system and may even be integral to the fixed CO2 system’s ability to extinguish a fire. PSCOs should be cognizant of other equipment and design factors, such as ventilation shutdowns, remote fuel quick closing valves, hatches, scuttles, doors and fire boundaries/insulation (i.e. A-60 bulkheads) when performing the PSC exam. 5. Fire Drills (SOLAS Ch. II-2, Reg. 15 & Ch. III, Reg. 19 & NVIC 06 – 91) a. When witnessing fire drills during each annual and semi-annual COC examination it is important to ensure that the fire location selected will properly evaluate the crew’s response to a high consequence fire. As such, during the next
  • 4. Cruise Ship scheduled exam the PSCO shall select an engine room for the fire drill location. Once a vessel has completed this initial fire drill of an engine room, other locations may be selected during subsequent PSC exams, however a fire drill will be conducted in the engine room at least once during the vessel’s COC annual cycle. The location in which the fire drill was held shall be recorded in the remarks section of the COC. b. Examine the ship's instructions related to onboard training and drills required by SOLAS II-2/15. In addition to the normal observations associated with a fire drill (i.e. proper muster, appropriate gear/donning of gear, passenger instructions, etc.) the PSCO should pay particular attention to the competency of crewmembers assigned to operating fire fighting systems. The following questions may assist in evaluating their knowledge and experience with their assigned duties related to the CO2 system: i. How does the crewmember receive training and familiarization with the operational requirements of the system or equipment for which they are assigned responsibility? ii. Where does activation of the system take place (remote/bridge) and who is responsible for authorizing activation (master/fire team leader); iii. Can the crewmember explain how to operate the system or appliance; confirm their explanation corresponds to the written/posted instructions; iv. What other actions are required prior to activating the system (i.e. ventilation & power secured, engine room evacuation, etc.). Note: This may be part of the Master’s responsibility prior to giving permission to activate the system. v. How is permission passed to activate the CO2 system? vi. How does the crewmember verify the system has activated and what are some indicators available to the crewmember that the system did or did not function properly? vii. If presented with the scenario that the fixed CO2 system did not activate properly, what actions are taken? Is there a secondary means to activate? Does the crewmember need permission to activate by the secondary means & does this align with the shipboard firefighting instructions/procedures/ training? viii. Does their explanation correspond to posted instructions? Are there any other system functions required to direct the discharge of CO2 to the space intended? (i.e. bypass valves, manually opening of control valves, etc.); ix. What actions must be taken before the space can be re-entered after the CO2 system is discharged? How are temperatures monitored to verify the fire is extinguished? How much time must elapse before the space can be ventilated? (at least 1 hour is recommended) 6. Discrepancies identified
  • 5. a. The Master shall immediately be notified of any discrepancy (i.e. issues with components of the fixed CO2 firefighting system affecting the proper operation; written or posted operational procedure; or crew knowledge of assigned duties). b. Not all discrepancies or concerns discovered will prevent the CO2 system from discharging as designed (i.e. hemp packing discovered in mechanical seal fittings), however based on the critical concerns identified in the MSA’s, PSCOs should provide copies of the MSAs to the Master if similar discrepancies are noted. The PSCO should also review the Coast Guard’s recommendations as outlined in the MSAs with the Master. Note: Maintenance, inspections and service performed on a fixed CO2 firefighting system shall be in accordance with the vessels maintenance plan and/or the Manufacturer’s FIM. c. Deficiencies that are corrected-on-the-spot, or, in other words, deficiencies corrected before the PSCO completes his or her visit to the vessel shall be documented as follows: i. Detainable deficiencies corrected-on-the-spot must always be documented on the form B and entered into MISLE as corrected; ii. Serious deficiencies corrected-on-the-spot should be documented on the form B and entered into MISLE as corrected (example - anything that would qualify as a code 17 deficiency should be documented in this way); iii. Lesser deficiencies corrected on the spot need not be documented on the form B and entered into MISLE unless the deficiencies are attributed to a systemic failure of the maintenance program contained in the vessel's safety management system. If this is the case, an expanded ISM exam should also be conducted. iv. With the exception of initial COC exams on passenger ships, for multiple-day PSC exams, the PSCO should provide the master with a form A/B at the end of each day. Lesser deficiencies documented on an earlier days form B and corrected by the end of the PSC exam need not be entered into MISLE as a deficiency unless it meets the criterion discussed above (iii.). v. As a point of reference, current policy for U.S. inspected vessels does not require inspectors to document deficiencies corrected on the spot with an 835 or MISLE deficiency (but the situation may merit a narrative entry to discuss how an issue was handled). Keep this in mind when writing form B’s and making MISLE entries for PSC exam lesser deficiencies. d. The following examples are provided to assist the PSCO in determining the appropriate course of action for discrepancies identified: i. Crew knowledge of assigned duties or conflicts with posted vs. Manufacturer’s instructions should be documented on the Form B. This may
  • 6. be remedied by the Master as follows: providing additional training, re- assigning of duties or by amending the posted instructions and ensuring all crewmembers assigned with duties affected by the changes are aware of the amendments. For deficiencies other than failure of two consecutive fire drills (detainable), the PSCO should issue a code 17. ii. Loose fittings discovered on flex (or hard pipe) connections, connecting the CO2 bottles to the servicing branch line should be documented on the Form B as a code 17. Note: The OCMI maintains discretion for allowing a vessel to sail with outstanding deficiencies provided in his/her opinion safe alternative arrangements have been made.