NERC
Consulting
Services
North American Electric Reliability Corporation
The electric reliability organization (ERO) for North America
Its mission is to assure the reliability of the bulk power system
in North America
Oversight by the Federal Energy Regulatory Commission (FERC)
Prior to August 2003 blackout, was only a standards body
Granted enforcement authority by the federal government as a
result of the 2003 blackout
2
What is NERC?
 Keep transmission and generation on line when is supposed to
 Make sure it trips off line when is supposed to
3
What is NERC?
4
NERC Standards that we can assist with:
NERC Standard Description Done by CE?
PRC-001-1.1(ii) System Protection Coordination Yes
PRC-002 Disturbance Monitoring
PRC-002-NPCC-01 Disturbance Monitoring Yes
PRC-005-1.1b Transmission and Generation Protection System Maintenance and Testing Yes
PRC-005-2(i) Protection System Maintenance Yes
PRC-005-6 Protection System, Automatic Reclosing, and Sudden Pressure Relaying Yes
PRC-006-2 Automatic Under frequency Load Shedding Yes
PRC-006-NPCC-1 Automatic Under frequency Load Shedding Yes
PRC-008-0
Implementation and Documentation of Underfrequency Load Shedding Equipment
Maintenance Program
Yes
PRC-018-1 Disturbance Monitoring Equipment Installation and Data Reporting Yes
PRC-019-2
Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and
Protection
Yes
PRC-023-3 Transmission Relay Loadability Yes
PRC-024-2 Generator Frequency and Voltage Protective Relay Settings Yes
PRC-025-1 Generator Relay Loadability Yes
PRC-026-1 Relay Performance During Stable Power Swings
PRC-027-1 Coordination of Protection Systems for Performance During Faults
5
NERC Standards that we can assist with:
NERC Standard Description Done by CE?
VAR-001-4.1 Voltage and Reactive Control
VAR-002-4 Generator Operation for Maintaining Network Voltage Schedules
MOD-025-2
Verification and Data Reporting of Generator Real and Reactive Power Capability and
Synchronous Condenser Reactive Power Capability
MOD-026-1
Verification of Models and Data for Generator Excitation Control System or Plant
Volt/Var Control Functions
MOD-027-1
Verification of Models and Data for Turbine/Governor and Load Control or Active
Power/Frequency Control Functions
MOD-032-1 Data for Power System Modeling and Analysis
Description: Communicate Failures, changes in Protection and Control Schemes, or
changes in Operating Conditions to Affected Entities
Applies to: All entities in the BES
Required Info: Description of Failed Equipment
Description of Modified Equipment
Description of New Operating Conditions
Revised Protective Device Settings
Revised Fault Analysis (if applicable)
Enforcement Date: 5/29/2015
6
PRC-001-1: System Protection Coordination
Description: Installation of Sequence of Events, Digital Fault Recorders, and Dynamic
Disturbance Recorders to provide adequate data on system events to
facilitate the analysis of BES Disturbances
Applies to: GO’s with units >50MVA and Plants >300 MVA (Sequence of Events) and
Plants>200MVA connected to BES via a GSU (Digital Fault Recorder)
Required Info: System One-Line Diagram
List of All Protective Relays in path from Generator to BES Interconnection
List of All Circuit Breakers in path from Generator to BES Interconnection
Plant Layout Drawing showing locations of Relays and Breakers
Enforcement Date: 10/20/2013
7
PRC-002-NPCC-01: Disturbance Monitoring and Reporting Requirements
PRC-018-1: DisturbanceMonitoringEquipmentInstallationandDataReporting
Description: Installation of Sequence of Events, Digital Fault Recorders, and Dynamic Disturbance
Recorders to provide adequate data on system events to facilitate the analysis of
BES Disturbances
Applies to: Generator Operators connected to BES where the TO has notified them that they
need to provide Sequence of Events, Digital Fault Recorder, or a Dynamic Disturbance
Required Info: System One-Line Diagram
List of All Protective Relays (type, mfr) in path from Generator to BES Interconnection
List of All Circuit Breakers in path from Generator to BES Interconnection
Plant Layout Drawing showing locations of Relays and Breakers
Enforcement Date: 7/1/2013
8
PRC-002-2: Disturbance Monitoring and Reporting Requirements
PRC-018-1: DisturbanceMonitoringEquipmentInstallationandDataReporting
Description: To ensure all transmission and generation Protection Systems affecting
the reliability of the Bulk Electric System (BES) are maintained and tested
by having a documented Protection System maintenance and testing
program (PSMTP) and documented and dated test results
Applies to: All entities in the BES
Required Info: System Relay and Metering One-Line Diagrams
List of All Protective Relays (type, mfr) in path to BES
AC 3 line and DC schematic diagrams
Protective Relay Settings/Settings Files
Enforcement Date: 11/25/2013
9
PRC-005-1.1b: Transmission and Generation Protection
System Maintenance and Testing
Description: To ensure all transmission and generation Protection Systems affecting the reliability of the Bulk
Electric System (BES) are maintained and tested by having a documented Protection
System maintenance program (PSMP) and documented and dated test results
Applies to: All entities in the BES
Required Info: System Relay and Metering One-Line Diagrams
List of All Protective Relays (type, mfr) in path to BES
Relay Monitoring Systems
Battery and Charger Systems
AC 3 line and DC schematic diagrams
Original Protective Relay Settings and Current Settings
Enforcement Date: 5/29/15
10
PRC-005-2(i): Protection System Maintenance
11
PRC-005-6: Protection System, Automatic Reclosing, and
Sudden Pressure Relaying Maintenance
Description: To ensure all transmission and generation Protection Systems affecting the reliability of the Bulk
Electric System (BES) are maintained and tested by having a documented Protection
System maintenance program (PSMP) and documented and dated test results
Applies to: All entities in the BES
Required Info: System Relay and Metering One-Line Diagrams
List of All Protective Relays (type, mfr) in path to BES including Transformer Sudden Pressure Relays
Relay Monitoring Systems
Battery and Charger Systems
AC 3 line and DC schematic diagrams
Original Protective Relay Settings and Current Settings
Enforcement Date: 1/1/16
12
PRC-005-2 Key Requirements
PSMP to define maintenance intervals as time based or performance based
Intervals for Time based Maintenance defined by type of relay (EM or Digital) and relay monitoring
Ranges from 6 to 12 years
Verify the that relays communications are functioning every 4 months if not monitored
Unmonitored Station Batteries
Verify dc voltage and electrolytes every 4 months
Verify charger, continuity, connection resistance every 18 months
Perform capacity test every 3-6 years depending on type of battery
CT/PT Verification Tests – verify that current & voltage inputs to the relays are providing expected quantities every 6
years for unmonitored relays and every 12 years if self diagnostics and alarming is monitored
Trip Tests – verify operation all breaker trips coils and lockout relays every 6 years, aux relays every 12 yrs
Alarm Monitoring – verify alarms are sent to a monitoring location where corrective action can be initiated within 24
hours
13
PRC-006-2: Automatic Underfrequency Load Shedding
Description: To establish design and documentation requirements for automatic underfrequency
load shedding (UFLS) programs to arrest declining frequency, assist recovery of frequency
following underfrequency events and provide last resort system preservation measures.
Applies to: All entities in the BES (Generators > 20 MVA)
Required Info: Regional Planning Coordinator Requirements for UFLS scheme
List of All Protective Relays which will respond to system frequency excursions and initiate
UFLS scheme
Underfrequency limit curves for generating units and V/Hz curves for power transformers
AC 3 line and DC schematic diagrams
Original Protective Relay Settings and Current Settings
Enforcement Date: 10/1/2015
Description: Provide a regional reliability standard for automatic underfrequency load shedding
(UFLS) programs to preserve the security and integrity of the bulk power system
during declining system frequency events
Applies to: All entities in the BES
Required Info: Regional Planning Coordinator Requirements for UFLS scheme
List of All Protective Relays which will respond to system frequency excursions and
initiate UFLS scheme
Underfrequency limit curves for generating units
AC 3 line and DC schematic diagrams
Original Protective Relay Settings and Current Settings
Enforcement Date: 1/1/16
14
PRC-006-NPCC-1: Automatic Underfrequency Load Shedding
Description: This study reviews the facility’s generator excitation system(s) limiters and
protection settings for both coordination and proper protection.
Applies to: Generating units > 20MVA, synchronous condenser > 20MVA, plant with total
generation > 75MVA
Required Info: Generator specification sheet(s)
Step-up transformer nameplate/specification sheet(s)
System Impedance Data
Exciter system limiters and protection settings
Loss of field and Over excitation protections (if applicable)
Enforcement Date: 5/29/2015
15
PRC-019-02: Coordination of Generating Unit or Plant
Capabilities, Voltage Regulating Controls, and Protection
Description: This study reviews the facility’s line relays looking out to transmission to ensure
that loadability is not limited while still adequately protecting the line.
Applies to: TO’s, GO’s, and distribution providers with load-responsive phase protection
Required Info: System One-Line Diagram
Line relay setting(s)
Generator step-up transformer overcurrent protection relay setting(s)
Owned transmission line data
Reported MW capability to local ISO
Enforcement Date: 10/20/2013
16
PRC-023-2: Transmission Relay Loadability
Description: This study reviews the facility’s over/under frequency and voltage set points to
avoid nuisance tripping during system (grid) events.
Applies to: GO’s having been notified of required compliance
Required Info: Plant under/over voltage relay settings
Plant under/over frequency relay settings
Enforcement Date: 3/20/2014
17
PRC-024-1: Generator Frequency and Voltage Protection
Relay Settings
Description: This study reviews the facility’s generator protection settings to prevent
nuisance tripping during system (grid) events.
Applies to: GO’s having been notified of required compliance
Required Info: System One-Line Diagram
Plant generation and step-up transformer protection relay settings
Step-up transformer nameplate
Reported MW capability to local ISO
Enforcement Date: 7/17/2014
18
PRC-025-1: Generator Relay Loadability
Description: Evaluating load-shed systems to ensure they do not cause nuisance
trips during stable power swings
Applies to: GO’s having been notified of required compliance
Required Info: System One-Line Diagram
Load Shedding Scheme Drawing Package
Generator and Step-Up Transformer Specification Sheet(s)
Enforcement Date: TBD
19
PRC-026-1: Relay Performance During Stable Power Swings
Description: Ensure protective devices are properly coordinated to ensure that
faults are isolated with minimal system load interruption
Applies to: GO’s, TO’s, and Distribution Providers with protection systems
installed for detecting and isolating faults on the bulk energy system
Required Info: System One-Line Diagram
All protective relay settings
Enforcement Date: 8/2015
20
PRC-027-1: Coordination of Protection System Performance
During Faults
Description: To ensure that voltage levels, reactive flows, and reactive resources
are monitored, controlled, and maintained within limits in Real-time to
protect equipment and the reliable operation of the Interconnection
Applies to: GO’s and TO’s having been notified of required compliance
Required Info: Voltage/reactive power monitoring and control system diagrams
Enforcement Date: 8/1/2014
21
VAR-001-4: Voltage and Reactive Control
Description: To ensure generators provide reactive support and voltage control,
within generating Facility capabilities, in order to protect
equipment and maintain reliable operation of the Interconnection
Applies to: GO’s having been notified of required compliance
Required Info: System One-Line Diagram
Generator voltage control system set point(s) and specification(s)
Enforcement Date: v.03 - 8/1/2014; v.04 - TBD
22
VAR-002-4: Generator Operation for Maintaining Network
Voltage Schedules
Description: Verifies generator capability data, specifically real and reactive power capability.
This is a machine test and does not require protective device coordination in order
to successfully complete the test. Protective devices can be adjusted to allow for as
successful test.
Applies to: Generator Operators connected to BES with individual generating units greater
than 20 MVA or an aggregate generating capacity greater than 75 MVA
Required Info: Generator “D” Curve
Protective Device Coordination Data
Data Gathering Points
Plant One Line Diagram
Enforcement Date: 2/1/2016
23
MOD-025-2: Verification and Data Reporting of Generator
Real and Reactive Power Capability
Description: To verify that the generator excitation control system or plant volt/var control
function model (including the power system stabilizer model and the impedance
compensator model) and the model parameters used in dynamic simulations
accurately represent the generator excitation control system or plant volt/var control
function behavior
Applies to: Generator Operators connected to BES with individual generating units greater than
100 MVA (EIR)
Required Info: Detailed Excitation Controller Documentation
Detailed Volt/VAR Control System Documentation
DCS Monitoring Points List or Plant of Relay Protection Diagram
Plant Three-Line Diagram
Enforcement Date: 7/1/2014
24
MOD-026-1: Verification of Models and Data for Generator
Excitation Control System or Plant Volt/VAR Control Functions
Description: To verify that the turbine/governor and load control or active power/frequency
control model and the model parameters, used in dynamic simulations that assess
Bulk Electric System (BES) reliability, accurately represent generator unit real power
response to system frequency variations.
Applies to: Generator Operators connected to BES with individual generating units greater
than 100 MVA (EIR)
Required Info: Detailed Automatic Voltage Regulator or Governor Documentation
Load Control Programming and Documentation
System/Machine Limiter Setpoints and Documentation
Plant Relay Protection One-Line Diagram
Enforcement Date: 7/1/2014
25
MOD-027-1: Verification of Models and Data for Turbine/Governor and Load
Control or Active Power/Frequency Control Functions
Description: To establish consistent modeling data requirements and reporting
procedures for development of planning horizon cases necessary to
support analysis of the reliability of the interconnected transmission system.
Applies to: All entities in the BES
Required Info: All Machine Data
All Plant Impedance Data
All Line Impedance Data
All Transformer Data
System Component Data
Enforcement Date: 7/1/2015
26
MOD-032-1: Data for Power System Modeling and Analysis

More Related Content

What's hot

Analysis optimization and monitoring system
Analysis optimization and monitoring system Analysis optimization and monitoring system
Analysis optimization and monitoring system
slmnsvn
 

What's hot (19)

IRJET - Automated Monitoring Test Rig for Circuit Breaker Operation
IRJET -  	  Automated Monitoring Test Rig for Circuit Breaker OperationIRJET -  	  Automated Monitoring Test Rig for Circuit Breaker Operation
IRJET - Automated Monitoring Test Rig for Circuit Breaker Operation
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Ni project presentation version 3
Ni project presentation version 3Ni project presentation version 3
Ni project presentation version 3
 
Moment of power system reliability
Moment of power system reliabilityMoment of power system reliability
Moment of power system reliability
 
Speed Sensor less DTC of VSI fed Induction Motor with Simple Flux Regulation ...
Speed Sensor less DTC of VSI fed Induction Motor with Simple Flux Regulation ...Speed Sensor less DTC of VSI fed Induction Motor with Simple Flux Regulation ...
Speed Sensor less DTC of VSI fed Induction Motor with Simple Flux Regulation ...
 
An investigation on the application and challenges for wide area monitoring a...
An investigation on the application and challenges for wide area monitoring a...An investigation on the application and challenges for wide area monitoring a...
An investigation on the application and challenges for wide area monitoring a...
 
A Fuzzy-PD Controller to Improve the Performance of HVDC System
A Fuzzy-PD Controller to Improve the Performance of HVDC SystemA Fuzzy-PD Controller to Improve the Performance of HVDC System
A Fuzzy-PD Controller to Improve the Performance of HVDC System
 
WAMS Applications , Wide Area Monitoring Systems WAMS
WAMS Applications , Wide Area Monitoring Systems WAMSWAMS Applications , Wide Area Monitoring Systems WAMS
WAMS Applications , Wide Area Monitoring Systems WAMS
 
IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...
IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...
IRJET- A New Load Frequency Control Method of Multi-Area Power System Via the...
 
Automation
AutomationAutomation
Automation
 
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
 
Terra firmware plant-controller_data_sheet-v1
Terra firmware plant-controller_data_sheet-v1Terra firmware plant-controller_data_sheet-v1
Terra firmware plant-controller_data_sheet-v1
 
Starting of induction motor fed with stand-alone DFIG
Starting of induction motor fed with stand-alone DFIGStarting of induction motor fed with stand-alone DFIG
Starting of induction motor fed with stand-alone DFIG
 
MICOM P 632
MICOM P 632MICOM P 632
MICOM P 632
 
Analysis optimization and monitoring system
Analysis optimization and monitoring system Analysis optimization and monitoring system
Analysis optimization and monitoring system
 
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
Power Factor Control at ABA Control 33/11kV Injection Substation Using Auto T...
 
IRJET - Vector Control of Permenant Magnet Synchronous Motor
IRJET -  	  Vector Control of Permenant Magnet Synchronous MotorIRJET -  	  Vector Control of Permenant Magnet Synchronous Motor
IRJET - Vector Control of Permenant Magnet Synchronous Motor
 
Control Strategy for PWM Voltage Source Converter Using Fuzzy Logic for Adjus...
Control Strategy for PWM Voltage Source Converter Using Fuzzy Logic for Adjus...Control Strategy for PWM Voltage Source Converter Using Fuzzy Logic for Adjus...
Control Strategy for PWM Voltage Source Converter Using Fuzzy Logic for Adjus...
 
T34123128
T34123128T34123128
T34123128
 

Viewers also liked

2015_Muldoon_Brook Stickleback Androgens
2015_Muldoon_Brook Stickleback Androgens2015_Muldoon_Brook Stickleback Androgens
2015_Muldoon_Brook Stickleback Androgens
Breda Rahmanian
 
Pairings Guide Creative
Pairings Guide CreativePairings Guide Creative
Pairings Guide Creative
Samer Abusada
 
CE Power - Capabilities General - Brian Wilson
CE Power - Capabilities General  - Brian WilsonCE Power - Capabilities General  - Brian Wilson
CE Power - Capabilities General - Brian Wilson
Brian V. Wilson
 

Viewers also liked (12)

آموزش سونی
آموزش سونی آموزش سونی
آموزش سونی
 
2015_Muldoon_Brook Stickleback Androgens
2015_Muldoon_Brook Stickleback Androgens2015_Muldoon_Brook Stickleback Androgens
2015_Muldoon_Brook Stickleback Androgens
 
Pairings Guide Creative
Pairings Guide CreativePairings Guide Creative
Pairings Guide Creative
 
CE Power - Capabilities General - Brian Wilson
CE Power - Capabilities General  - Brian WilsonCE Power - Capabilities General  - Brian Wilson
CE Power - Capabilities General - Brian Wilson
 
Citations UCEM (Clarification 5.3.1)
Citations UCEM (Clarification 5.3.1)Citations UCEM (Clarification 5.3.1)
Citations UCEM (Clarification 5.3.1)
 
16052016 інвест.пропозиції дніпр.області ua
16052016 інвест.пропозиції дніпр.області ua16052016 інвест.пропозиції дніпр.області ua
16052016 інвест.пропозиції дніпр.області ua
 
cepower
cepowercepower
cepower
 
Creativity in Society
Creativity in SocietyCreativity in Society
Creativity in Society
 
Reference letter - Ms Schoeman
Reference letter - Ms SchoemanReference letter - Ms Schoeman
Reference letter - Ms Schoeman
 
Toronto is faling me
Toronto is faling meToronto is faling me
Toronto is faling me
 
Legalisir transkrip
Legalisir transkripLegalisir transkrip
Legalisir transkrip
 
Evaluación alineada
Evaluación alineadaEvaluación alineada
Evaluación alineada
 

Similar to CE Power NERC Compliance

protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.ppt
Thien Phan Bản
 
Real-Time Monitoring and Assessment of Circuit Breaker Operations for Diagnos...
Real-Time Monitoring and Assessment of Circuit Breaker Operations for Diagnos...Real-Time Monitoring and Assessment of Circuit Breaker Operations for Diagnos...
Real-Time Monitoring and Assessment of Circuit Breaker Operations for Diagnos...
Associate Professor in VSB Coimbatore
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power System
vkmalik
 

Similar to CE Power NERC Compliance (20)

Power system Protection Services in India
Power system Protection Services in IndiaPower system Protection Services in India
Power system Protection Services in India
 
protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.ppt
 
protectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.pptprotectionsettings-120425102109-phpapp01.ppt
protectionsettings-120425102109-phpapp01.ppt
 
Power System Protection
Power System ProtectionPower System Protection
Power System Protection
 
Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)Tes p-122.01-r0 (2)
Tes p-122.01-r0 (2)
 
8.1.1_PAR 2030.7_Bower_EPRI/SNL Microgrid Symposium
8.1.1_PAR 2030.7_Bower_EPRI/SNL Microgrid Symposium8.1.1_PAR 2030.7_Bower_EPRI/SNL Microgrid Symposium
8.1.1_PAR 2030.7_Bower_EPRI/SNL Microgrid Symposium
 
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
A Load Shedding Scheme Based On Frequency Response Model With Fast Voltage St...
 
Grid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power SystemGrid Event Analysis In Indian Power System
Grid Event Analysis In Indian Power System
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
 
Functions and performance requirements of excitation systems
Functions and performance requirements of excitation systemsFunctions and performance requirements of excitation systems
Functions and performance requirements of excitation systems
 
Voltage Sag and Swell Identification Using FFT Analysis and Mitigation with DVR
Voltage Sag and Swell Identification Using FFT Analysis and Mitigation with DVRVoltage Sag and Swell Identification Using FFT Analysis and Mitigation with DVR
Voltage Sag and Swell Identification Using FFT Analysis and Mitigation with DVR
 
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdfH15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
H15 POWER SYSTEM PROTECTION EMERSON EDUARDO RODRIGUES.pdf
 
Psoc
PsocPsoc
Psoc
 
Real-Time Monitoring and Assessment of Circuit Breaker Operations for Diagnos...
Real-Time Monitoring and Assessment of Circuit Breaker Operations for Diagnos...Real-Time Monitoring and Assessment of Circuit Breaker Operations for Diagnos...
Real-Time Monitoring and Assessment of Circuit Breaker Operations for Diagnos...
 
Sm bat datasheet_rev1.0_20050511
Sm bat datasheet_rev1.0_20050511Sm bat datasheet_rev1.0_20050511
Sm bat datasheet_rev1.0_20050511
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
An Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power SystemAn Overview Of Agbami Fpso Electrical Power System
An Overview Of Agbami Fpso Electrical Power System
 
VOLTAGE STABILITY IN NIGERIA 330KV INTEGRATED 52 BUS POWER NETWORK USING PATT...
VOLTAGE STABILITY IN NIGERIA 330KV INTEGRATED 52 BUS POWER NETWORK USING PATT...VOLTAGE STABILITY IN NIGERIA 330KV INTEGRATED 52 BUS POWER NETWORK USING PATT...
VOLTAGE STABILITY IN NIGERIA 330KV INTEGRATED 52 BUS POWER NETWORK USING PATT...
 
Alan Bull CTOTF NERC Presentation
Alan Bull CTOTF NERC PresentationAlan Bull CTOTF NERC Presentation
Alan Bull CTOTF NERC Presentation
 
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS IN MULTI- MACHINE POWER SYSTEM U...
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS  IN MULTI- MACHINE POWER SYSTEM U...DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS  IN MULTI- MACHINE POWER SYSTEM U...
DESIGN OF MPSS AND TCSC DAMPING CONTROLLERS IN MULTI- MACHINE POWER SYSTEM U...
 

More from Brian V. Wilson

CEP-SwitchgearRetrofill Upgrade SellSheet
CEP-SwitchgearRetrofill Upgrade SellSheetCEP-SwitchgearRetrofill Upgrade SellSheet
CEP-SwitchgearRetrofill Upgrade SellSheet
Brian V. Wilson
 
CEP Arc-Resistant Switchgear_Solution Profile
CEP Arc-Resistant Switchgear_Solution ProfileCEP Arc-Resistant Switchgear_Solution Profile
CEP Arc-Resistant Switchgear_Solution Profile
Brian V. Wilson
 
CEP-Capabilities Listing SellSheet
CEP-Capabilities Listing SellSheetCEP-Capabilities Listing SellSheet
CEP-Capabilities Listing SellSheet
Brian V. Wilson
 
TechSolve_Expert_AD_060515
TechSolve_Expert_AD_060515TechSolve_Expert_AD_060515
TechSolve_Expert_AD_060515
Brian V. Wilson
 
OHMEP_FullBook_FinalDraftSpread
OHMEP_FullBook_FinalDraftSpreadOHMEP_FullBook_FinalDraftSpread
OHMEP_FullBook_FinalDraftSpread
Brian V. Wilson
 
TechSolve_Expert_AD_041715
TechSolve_Expert_AD_041715TechSolve_Expert_AD_041715
TechSolve_Expert_AD_041715
Brian V. Wilson
 
TechSolve_Expert_AD_022015
TechSolve_Expert_AD_022015TechSolve_Expert_AD_022015
TechSolve_Expert_AD_022015
Brian V. Wilson
 
Manny_Ad_Update_20150212
Manny_Ad_Update_20150212Manny_Ad_Update_20150212
Manny_Ad_Update_20150212
Brian V. Wilson
 
Manny_Ad_Update_20150212
Manny_Ad_Update_20150212Manny_Ad_Update_20150212
Manny_Ad_Update_20150212
Brian V. Wilson
 

More from Brian V. Wilson (13)

NERC
NERCNERC
NERC
 
CEP-SwitchgearRetrofill Upgrade SellSheet
CEP-SwitchgearRetrofill Upgrade SellSheetCEP-SwitchgearRetrofill Upgrade SellSheet
CEP-SwitchgearRetrofill Upgrade SellSheet
 
CEP-ServicesBrochure
CEP-ServicesBrochureCEP-ServicesBrochure
CEP-ServicesBrochure
 
CEP-SCADA Brochure-rev
CEP-SCADA Brochure-revCEP-SCADA Brochure-rev
CEP-SCADA Brochure-rev
 
CEP Arc-Resistant Switchgear_Solution Profile
CEP Arc-Resistant Switchgear_Solution ProfileCEP Arc-Resistant Switchgear_Solution Profile
CEP Arc-Resistant Switchgear_Solution Profile
 
CEP-Capabilities Listing SellSheet
CEP-Capabilities Listing SellSheetCEP-Capabilities Listing SellSheet
CEP-Capabilities Listing SellSheet
 
TS Overview
TS OverviewTS Overview
TS Overview
 
TechSolve_Expert_AD_060515
TechSolve_Expert_AD_060515TechSolve_Expert_AD_060515
TechSolve_Expert_AD_060515
 
OHMEP_FullBook_FinalDraftSpread
OHMEP_FullBook_FinalDraftSpreadOHMEP_FullBook_FinalDraftSpread
OHMEP_FullBook_FinalDraftSpread
 
TechSolve_Expert_AD_041715
TechSolve_Expert_AD_041715TechSolve_Expert_AD_041715
TechSolve_Expert_AD_041715
 
TechSolve_Expert_AD_022015
TechSolve_Expert_AD_022015TechSolve_Expert_AD_022015
TechSolve_Expert_AD_022015
 
Manny_Ad_Update_20150212
Manny_Ad_Update_20150212Manny_Ad_Update_20150212
Manny_Ad_Update_20150212
 
Manny_Ad_Update_20150212
Manny_Ad_Update_20150212Manny_Ad_Update_20150212
Manny_Ad_Update_20150212
 

CE Power NERC Compliance

  • 2. North American Electric Reliability Corporation The electric reliability organization (ERO) for North America Its mission is to assure the reliability of the bulk power system in North America Oversight by the Federal Energy Regulatory Commission (FERC) Prior to August 2003 blackout, was only a standards body Granted enforcement authority by the federal government as a result of the 2003 blackout 2 What is NERC?
  • 3.  Keep transmission and generation on line when is supposed to  Make sure it trips off line when is supposed to 3 What is NERC?
  • 4. 4 NERC Standards that we can assist with: NERC Standard Description Done by CE? PRC-001-1.1(ii) System Protection Coordination Yes PRC-002 Disturbance Monitoring PRC-002-NPCC-01 Disturbance Monitoring Yes PRC-005-1.1b Transmission and Generation Protection System Maintenance and Testing Yes PRC-005-2(i) Protection System Maintenance Yes PRC-005-6 Protection System, Automatic Reclosing, and Sudden Pressure Relaying Yes PRC-006-2 Automatic Under frequency Load Shedding Yes PRC-006-NPCC-1 Automatic Under frequency Load Shedding Yes PRC-008-0 Implementation and Documentation of Underfrequency Load Shedding Equipment Maintenance Program Yes PRC-018-1 Disturbance Monitoring Equipment Installation and Data Reporting Yes PRC-019-2 Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection Yes PRC-023-3 Transmission Relay Loadability Yes PRC-024-2 Generator Frequency and Voltage Protective Relay Settings Yes PRC-025-1 Generator Relay Loadability Yes PRC-026-1 Relay Performance During Stable Power Swings PRC-027-1 Coordination of Protection Systems for Performance During Faults
  • 5. 5 NERC Standards that we can assist with: NERC Standard Description Done by CE? VAR-001-4.1 Voltage and Reactive Control VAR-002-4 Generator Operation for Maintaining Network Voltage Schedules MOD-025-2 Verification and Data Reporting of Generator Real and Reactive Power Capability and Synchronous Condenser Reactive Power Capability MOD-026-1 Verification of Models and Data for Generator Excitation Control System or Plant Volt/Var Control Functions MOD-027-1 Verification of Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions MOD-032-1 Data for Power System Modeling and Analysis
  • 6. Description: Communicate Failures, changes in Protection and Control Schemes, or changes in Operating Conditions to Affected Entities Applies to: All entities in the BES Required Info: Description of Failed Equipment Description of Modified Equipment Description of New Operating Conditions Revised Protective Device Settings Revised Fault Analysis (if applicable) Enforcement Date: 5/29/2015 6 PRC-001-1: System Protection Coordination
  • 7. Description: Installation of Sequence of Events, Digital Fault Recorders, and Dynamic Disturbance Recorders to provide adequate data on system events to facilitate the analysis of BES Disturbances Applies to: GO’s with units >50MVA and Plants >300 MVA (Sequence of Events) and Plants>200MVA connected to BES via a GSU (Digital Fault Recorder) Required Info: System One-Line Diagram List of All Protective Relays in path from Generator to BES Interconnection List of All Circuit Breakers in path from Generator to BES Interconnection Plant Layout Drawing showing locations of Relays and Breakers Enforcement Date: 10/20/2013 7 PRC-002-NPCC-01: Disturbance Monitoring and Reporting Requirements PRC-018-1: DisturbanceMonitoringEquipmentInstallationandDataReporting
  • 8. Description: Installation of Sequence of Events, Digital Fault Recorders, and Dynamic Disturbance Recorders to provide adequate data on system events to facilitate the analysis of BES Disturbances Applies to: Generator Operators connected to BES where the TO has notified them that they need to provide Sequence of Events, Digital Fault Recorder, or a Dynamic Disturbance Required Info: System One-Line Diagram List of All Protective Relays (type, mfr) in path from Generator to BES Interconnection List of All Circuit Breakers in path from Generator to BES Interconnection Plant Layout Drawing showing locations of Relays and Breakers Enforcement Date: 7/1/2013 8 PRC-002-2: Disturbance Monitoring and Reporting Requirements PRC-018-1: DisturbanceMonitoringEquipmentInstallationandDataReporting
  • 9. Description: To ensure all transmission and generation Protection Systems affecting the reliability of the Bulk Electric System (BES) are maintained and tested by having a documented Protection System maintenance and testing program (PSMTP) and documented and dated test results Applies to: All entities in the BES Required Info: System Relay and Metering One-Line Diagrams List of All Protective Relays (type, mfr) in path to BES AC 3 line and DC schematic diagrams Protective Relay Settings/Settings Files Enforcement Date: 11/25/2013 9 PRC-005-1.1b: Transmission and Generation Protection System Maintenance and Testing
  • 10. Description: To ensure all transmission and generation Protection Systems affecting the reliability of the Bulk Electric System (BES) are maintained and tested by having a documented Protection System maintenance program (PSMP) and documented and dated test results Applies to: All entities in the BES Required Info: System Relay and Metering One-Line Diagrams List of All Protective Relays (type, mfr) in path to BES Relay Monitoring Systems Battery and Charger Systems AC 3 line and DC schematic diagrams Original Protective Relay Settings and Current Settings Enforcement Date: 5/29/15 10 PRC-005-2(i): Protection System Maintenance
  • 11. 11 PRC-005-6: Protection System, Automatic Reclosing, and Sudden Pressure Relaying Maintenance Description: To ensure all transmission and generation Protection Systems affecting the reliability of the Bulk Electric System (BES) are maintained and tested by having a documented Protection System maintenance program (PSMP) and documented and dated test results Applies to: All entities in the BES Required Info: System Relay and Metering One-Line Diagrams List of All Protective Relays (type, mfr) in path to BES including Transformer Sudden Pressure Relays Relay Monitoring Systems Battery and Charger Systems AC 3 line and DC schematic diagrams Original Protective Relay Settings and Current Settings Enforcement Date: 1/1/16
  • 12. 12 PRC-005-2 Key Requirements PSMP to define maintenance intervals as time based or performance based Intervals for Time based Maintenance defined by type of relay (EM or Digital) and relay monitoring Ranges from 6 to 12 years Verify the that relays communications are functioning every 4 months if not monitored Unmonitored Station Batteries Verify dc voltage and electrolytes every 4 months Verify charger, continuity, connection resistance every 18 months Perform capacity test every 3-6 years depending on type of battery CT/PT Verification Tests – verify that current & voltage inputs to the relays are providing expected quantities every 6 years for unmonitored relays and every 12 years if self diagnostics and alarming is monitored Trip Tests – verify operation all breaker trips coils and lockout relays every 6 years, aux relays every 12 yrs Alarm Monitoring – verify alarms are sent to a monitoring location where corrective action can be initiated within 24 hours
  • 13. 13 PRC-006-2: Automatic Underfrequency Load Shedding Description: To establish design and documentation requirements for automatic underfrequency load shedding (UFLS) programs to arrest declining frequency, assist recovery of frequency following underfrequency events and provide last resort system preservation measures. Applies to: All entities in the BES (Generators > 20 MVA) Required Info: Regional Planning Coordinator Requirements for UFLS scheme List of All Protective Relays which will respond to system frequency excursions and initiate UFLS scheme Underfrequency limit curves for generating units and V/Hz curves for power transformers AC 3 line and DC schematic diagrams Original Protective Relay Settings and Current Settings Enforcement Date: 10/1/2015
  • 14. Description: Provide a regional reliability standard for automatic underfrequency load shedding (UFLS) programs to preserve the security and integrity of the bulk power system during declining system frequency events Applies to: All entities in the BES Required Info: Regional Planning Coordinator Requirements for UFLS scheme List of All Protective Relays which will respond to system frequency excursions and initiate UFLS scheme Underfrequency limit curves for generating units AC 3 line and DC schematic diagrams Original Protective Relay Settings and Current Settings Enforcement Date: 1/1/16 14 PRC-006-NPCC-1: Automatic Underfrequency Load Shedding
  • 15. Description: This study reviews the facility’s generator excitation system(s) limiters and protection settings for both coordination and proper protection. Applies to: Generating units > 20MVA, synchronous condenser > 20MVA, plant with total generation > 75MVA Required Info: Generator specification sheet(s) Step-up transformer nameplate/specification sheet(s) System Impedance Data Exciter system limiters and protection settings Loss of field and Over excitation protections (if applicable) Enforcement Date: 5/29/2015 15 PRC-019-02: Coordination of Generating Unit or Plant Capabilities, Voltage Regulating Controls, and Protection
  • 16. Description: This study reviews the facility’s line relays looking out to transmission to ensure that loadability is not limited while still adequately protecting the line. Applies to: TO’s, GO’s, and distribution providers with load-responsive phase protection Required Info: System One-Line Diagram Line relay setting(s) Generator step-up transformer overcurrent protection relay setting(s) Owned transmission line data Reported MW capability to local ISO Enforcement Date: 10/20/2013 16 PRC-023-2: Transmission Relay Loadability
  • 17. Description: This study reviews the facility’s over/under frequency and voltage set points to avoid nuisance tripping during system (grid) events. Applies to: GO’s having been notified of required compliance Required Info: Plant under/over voltage relay settings Plant under/over frequency relay settings Enforcement Date: 3/20/2014 17 PRC-024-1: Generator Frequency and Voltage Protection Relay Settings
  • 18. Description: This study reviews the facility’s generator protection settings to prevent nuisance tripping during system (grid) events. Applies to: GO’s having been notified of required compliance Required Info: System One-Line Diagram Plant generation and step-up transformer protection relay settings Step-up transformer nameplate Reported MW capability to local ISO Enforcement Date: 7/17/2014 18 PRC-025-1: Generator Relay Loadability
  • 19. Description: Evaluating load-shed systems to ensure they do not cause nuisance trips during stable power swings Applies to: GO’s having been notified of required compliance Required Info: System One-Line Diagram Load Shedding Scheme Drawing Package Generator and Step-Up Transformer Specification Sheet(s) Enforcement Date: TBD 19 PRC-026-1: Relay Performance During Stable Power Swings
  • 20. Description: Ensure protective devices are properly coordinated to ensure that faults are isolated with minimal system load interruption Applies to: GO’s, TO’s, and Distribution Providers with protection systems installed for detecting and isolating faults on the bulk energy system Required Info: System One-Line Diagram All protective relay settings Enforcement Date: 8/2015 20 PRC-027-1: Coordination of Protection System Performance During Faults
  • 21. Description: To ensure that voltage levels, reactive flows, and reactive resources are monitored, controlled, and maintained within limits in Real-time to protect equipment and the reliable operation of the Interconnection Applies to: GO’s and TO’s having been notified of required compliance Required Info: Voltage/reactive power monitoring and control system diagrams Enforcement Date: 8/1/2014 21 VAR-001-4: Voltage and Reactive Control
  • 22. Description: To ensure generators provide reactive support and voltage control, within generating Facility capabilities, in order to protect equipment and maintain reliable operation of the Interconnection Applies to: GO’s having been notified of required compliance Required Info: System One-Line Diagram Generator voltage control system set point(s) and specification(s) Enforcement Date: v.03 - 8/1/2014; v.04 - TBD 22 VAR-002-4: Generator Operation for Maintaining Network Voltage Schedules
  • 23. Description: Verifies generator capability data, specifically real and reactive power capability. This is a machine test and does not require protective device coordination in order to successfully complete the test. Protective devices can be adjusted to allow for as successful test. Applies to: Generator Operators connected to BES with individual generating units greater than 20 MVA or an aggregate generating capacity greater than 75 MVA Required Info: Generator “D” Curve Protective Device Coordination Data Data Gathering Points Plant One Line Diagram Enforcement Date: 2/1/2016 23 MOD-025-2: Verification and Data Reporting of Generator Real and Reactive Power Capability
  • 24. Description: To verify that the generator excitation control system or plant volt/var control function model (including the power system stabilizer model and the impedance compensator model) and the model parameters used in dynamic simulations accurately represent the generator excitation control system or plant volt/var control function behavior Applies to: Generator Operators connected to BES with individual generating units greater than 100 MVA (EIR) Required Info: Detailed Excitation Controller Documentation Detailed Volt/VAR Control System Documentation DCS Monitoring Points List or Plant of Relay Protection Diagram Plant Three-Line Diagram Enforcement Date: 7/1/2014 24 MOD-026-1: Verification of Models and Data for Generator Excitation Control System or Plant Volt/VAR Control Functions
  • 25. Description: To verify that the turbine/governor and load control or active power/frequency control model and the model parameters, used in dynamic simulations that assess Bulk Electric System (BES) reliability, accurately represent generator unit real power response to system frequency variations. Applies to: Generator Operators connected to BES with individual generating units greater than 100 MVA (EIR) Required Info: Detailed Automatic Voltage Regulator or Governor Documentation Load Control Programming and Documentation System/Machine Limiter Setpoints and Documentation Plant Relay Protection One-Line Diagram Enforcement Date: 7/1/2014 25 MOD-027-1: Verification of Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions
  • 26. Description: To establish consistent modeling data requirements and reporting procedures for development of planning horizon cases necessary to support analysis of the reliability of the interconnected transmission system. Applies to: All entities in the BES Required Info: All Machine Data All Plant Impedance Data All Line Impedance Data All Transformer Data System Component Data Enforcement Date: 7/1/2015 26 MOD-032-1: Data for Power System Modeling and Analysis