HOSPITAL WIRING SYSTEM
AISWARYA T V
ROLL NO 11
What is WIRING ????
TYPES OF WIRING
DOMESTIC WIRING
COMMERCIAL WRING
INDUSTRIAL WIRING
Wires and
colour coding
CABLES VOLTAGE RATING
Types of
ELECTRICAL
CONNECTIONS
TYPES OF
JOINTS
Wiring methods
Materials for wiring interior electrical systems in buildings vary depending on:
Intended use and amount of power demand on the circuit
Type of occupancy and size of the building
National and local regulations
Environment in which the wiring must operate
Wires and cables are rated by the circuit voltage, temperature rating and
environmental conditions (moisture, sunlight, oil, chemicals) in which they can be
used. A wire or cable has a voltage (to neutral) rating and a maximum conductor
surface temperature rating. The amount of current a cable or wire can safely carry
depends on the installation conditions.
Wiring systems in a single family home or duplex, for example, are simple, with
relatively low power requirements, infrequent changes to the building structure
and layout, usually with dry, moderate temperature and non-corrosive
environmental conditions
Heavy industries have more demanding wiring requirements, such as very large
currents and higher voltages, frequent changes of equipment layout, corrosive,
or wet or explosive atmospheres. In facilities that handle flammable gases or
liquids, special rules may govern the installation and wiring of electrical
equipment in hazardous areas.
wiring materials
Modern non-metallic sheathed cables, such as (US and Canadian) Types NMB and
NMC, consist of two to four wires covered with thermoplastic insulation, plus a bare wire
for grounding (bonding), surrounded by a flexible plastic jacket. Some versions wrap the
individual conductors in paper before the plastic jacket is applied.
Generally, single conductor building wire in small sizes is solid wire, since the
wiring is not required to be very flexible. Building wire conductors larger than 10
AWG (or about 6 mm²) are stranded for flexibility during installation, but are not
sufficiently pliable to use as appliance cord.
Cables for industrial, commercial and apartment buildings may contain many
insulated conductors in an overall jacket, with helical tape steel or
aluminium armour, or steel wire armour, and perhaps as well an overall PVC
or lead jacket for protection from moisture and physical damage. Cables
intended for very flexible service or in marine applications may be
protected by woven bronze wires. Power or communications cables (e.g.,
computer networking) that are routed in or through air-handling spaces
(plenums) of office buildings are required under the model building code to
be either encased in metal conduit, or rated for low flame and smoke
production
WIRING IN HOSPITALS
In healthcare applications, people's bodies are often in
direct contact with energized equipment thus provides
extensive grounding and bonding requirements-even for
something as ordinary as a an electrical socket.
1. Maximize the physical and electromagnetic protection of
wiring by requiring metal wiring methods.
2. Minimize electrical hazards by minimizing the voltage
potential between patients and medical equipment.
3. Minimize the negative effects of power interruptions with
specific requirements for essential electrical systems.
Essential electrical
systems for hospitals
Essential electrical system (EES) has the mission of ensuring
continuity of electrical power to specific functions and areas of a
healthcare facility
One basic requirement for hospitals is the EES must consist of two
separate systems, which must be kept entirely separate from all other
wiring and equipment. They can't even share raceways, boxes, or
cabinets with other wiring. These two systems are:
Emergency system. This is limited to circuits essential to life safety
and critical patient care.
Equipment system. This supplies major electrical equipment necessary
for patient care and basic hospital operation.
● The number of transfer switches to be used shall be based upon
design and load considerations.
● Each branch of the essential electrical system shall be served by one
or more transfer switches.
● With special permission, facilities with a maximum demand on the
essential electrical system of 150 kVA will be permitted to have one
transfer switch serving the emergency branches.
● Loads served by the generating equipment shall be served by their
own transfer switches such that these loads Shall not be transferred if
the transfer will overload the generating equipment, and Shall be
automatically shed upon generating equipment overloading
The wiring of the EES must be mechanically protected, per one of the following
wiring methods:
(1) Non flexible metal raceways, Type MI cable, or Schedule 80 rigid nonmetallic
conduit.
(2) Schedule 40 rigid nonmetallic conduit or flexible nonmetallic raceways listed for
installation in concrete (where encased in not less than 50 mm (2 in.) of concrete).
(3) Flexible power cords of appliances or other utilization equipment connected to the
emergency system.
(4) Secondary circuits of Class 2 or Class 3 communication or signaling systems.
(4) Flexible metal raceways and metal sheathed cable assemblies as follows:
a. When used in listed prefabricated medical headwalls,
b. When used In listed office furnishings,
c. Where fished into existing walls or ceilings (not otherwise accessible and not
subject to physical damage), or
d. Where necessary for flexible connection to equipment.
(4) Flexible power cords of appliances or other utilization equipment connected
to the emergency system.
(5) Secondary circuits of Class 2 or Class 3 communication or signaling systems.
do not use nonmetallic raceways for branch circuits that supply patient
care areas
Patient Care Area Receptacle Rules
● EMT or Armored Cable are used
You must install all branch circuits so they have a ground path for fault current. This means
installation in a metal raceway system or a cable armor or sheath assembly-each of which must
qualify as an effective ground-fault current path.
● AC cable is listed as a suitable ground-fault path because it contains an internal bonding
strip of aluminum in direct contact with the outer metal sheath of AC cable.
● Any receptacle supplied by an emergency circuit must not use Type AC, MC, FMC, or any
other flexible cable. Emergency circuits must have a non flexible metal raceway-or MI cable
with an additional insulated copper equipment grounding (bonding) conductor.
General care areas have three requirements:
● At least two branch circuits-one from the emergency system and
one from the normal system-must supply each patient bed
location.
● All branch circuits from the normal system must originate in the
same panelboard (three exceptions apply).
● Each "patient bed location" must have a minimum of four
hospital grade electrical socket.
● If you put receptacles in a pediatric ward, use only ones listed as
tamper-resistant or ones that employ listed tamper-resistant
covers.
Hospital power sources and alternate power sources shall be permitted to serve the
essential systems of contiguous or same site facilities.Wiring Requirements.
● Separation from Other Circuits. The life safety branch and critical branch of
the emergency system shall be kept entirely independent of all other wiring and
equipment and shall not enter the same raceways, boxes, or cabinets with each
other or other wiring.
Exception: Service switchboard and transfer switch equipment.
● Mechanical Protection of the Emergency System.
The wiring of the emergency system of a hospital shall be
mechanically protected by installation in non-flexible metal raceways,
or shall be wired with Type MI cable. Where installed as branch
circuit conductors serving patient care areas, the installation shall
comply with the requirements.Exception: Flexible power cords of
appliances, or other utilization equipment, connected to the emergency
Capacity of Systems
● The essential electrical system shall have adequate capacity to
meet the demand for the operation of all functions and
equipment to be served by each system and branch.
● The generator sets shall have sufficient capacity and proper
rating to meet the demand produced by the load of the
essential electrical systems at any one time
Hospital wiring SYSTEM

More Related Content

What's hot

Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substationEmran Ali
 
Transmission and distribution system of electricity
Transmission and distribution system of electricity Transmission and distribution system of electricity
Transmission and distribution system of electricity anjali s
 
#Building wiring system#presentation#Wire is a single electrical conductor, w...
#Building wiring system#presentation#Wire is a single electrical conductor, w...#Building wiring system#presentation#Wire is a single electrical conductor, w...
#Building wiring system#presentation#Wire is a single electrical conductor, w...Bint Shameem
 
Earthing electrode, Plate Earthing, Pipe earthing | Renown Earth
Earthing electrode, Plate Earthing, Pipe earthing | Renown EarthEarthing electrode, Plate Earthing, Pipe earthing | Renown Earth
Earthing electrode, Plate Earthing, Pipe earthing | Renown EarthRenown Electrical System
 
UNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTRE
UNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTREUNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTRE
UNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTREPremanandDesai
 
Electrical distribution system
Electrical distribution system Electrical distribution system
Electrical distribution system Ankush Bharti
 
Electrical services of bs by krt
Electrical services of bs by krt Electrical services of bs by krt
Electrical services of bs by krt Krunal Thanki
 
Earthing or Grounding
Earthing or GroundingEarthing or Grounding
Earthing or GroundingAswin KP
 
types of wiring
types of wiringtypes of wiring
types of wiring2461998
 
Electrical wiring domestic and industries
Electrical wiring domestic and industriesElectrical wiring domestic and industries
Electrical wiring domestic and industriesPavan Kumar Mallepoola
 
Basics of electrical control panel
Basics of electrical control panelBasics of electrical control panel
Basics of electrical control panelCHACKOCHEN MATHEW
 
SUBSTATION OVERVIEW - A presentation on substation
SUBSTATION OVERVIEW - A presentation on substationSUBSTATION OVERVIEW - A presentation on substation
SUBSTATION OVERVIEW - A presentation on substationraiamitesh8
 

What's hot (20)

Electrical Power substation
Electrical Power substationElectrical Power substation
Electrical Power substation
 
Transmission and distribution system of electricity
Transmission and distribution system of electricity Transmission and distribution system of electricity
Transmission and distribution system of electricity
 
Substations
Substations Substations
Substations
 
Electric system
Electric systemElectric system
Electric system
 
#Building wiring system#presentation#Wire is a single electrical conductor, w...
#Building wiring system#presentation#Wire is a single electrical conductor, w...#Building wiring system#presentation#Wire is a single electrical conductor, w...
#Building wiring system#presentation#Wire is a single electrical conductor, w...
 
Earthing electrode, Plate Earthing, Pipe earthing | Renown Earth
Earthing electrode, Plate Earthing, Pipe earthing | Renown EarthEarthing electrode, Plate Earthing, Pipe earthing | Renown Earth
Earthing electrode, Plate Earthing, Pipe earthing | Renown Earth
 
Domestic wiring
Domestic wiringDomestic wiring
Domestic wiring
 
66 kv substation
66 kv substation66 kv substation
66 kv substation
 
UNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTRE
UNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTREUNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTRE
UNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTRE
 
Wiring systems
Wiring systemsWiring systems
Wiring systems
 
Electrical distribution system
Electrical distribution system Electrical distribution system
Electrical distribution system
 
Earthing
EarthingEarthing
Earthing
 
Electrical services of bs by krt
Electrical services of bs by krt Electrical services of bs by krt
Electrical services of bs by krt
 
Earthing or Grounding
Earthing or GroundingEarthing or Grounding
Earthing or Grounding
 
types of wiring
types of wiringtypes of wiring
types of wiring
 
Electrical wiring domestic and industries
Electrical wiring domestic and industriesElectrical wiring domestic and industries
Electrical wiring domestic and industries
 
Distribution transformer
Distribution transformerDistribution transformer
Distribution transformer
 
Substation
Substation Substation
Substation
 
Basics of electrical control panel
Basics of electrical control panelBasics of electrical control panel
Basics of electrical control panel
 
SUBSTATION OVERVIEW - A presentation on substation
SUBSTATION OVERVIEW - A presentation on substationSUBSTATION OVERVIEW - A presentation on substation
SUBSTATION OVERVIEW - A presentation on substation
 

Viewers also liked

Viewers also liked (20)

Electrical wiring BY Jemish
Electrical wiring BY JemishElectrical wiring BY Jemish
Electrical wiring BY Jemish
 
ELECTRICAL WIRING
ELECTRICAL WIRINGELECTRICAL WIRING
ELECTRICAL WIRING
 
Go down wiring
Go down wiringGo down wiring
Go down wiring
 
Godown management
Godown managementGodown management
Godown management
 
HOME WIRING(domestic wiring)
HOME WIRING(domestic wiring)HOME WIRING(domestic wiring)
HOME WIRING(domestic wiring)
 
Electrical Wiring Practices and Diagrams
Electrical Wiring Practices and DiagramsElectrical Wiring Practices and Diagrams
Electrical Wiring Practices and Diagrams
 
Types of wires,cables,connectors and switches
Types of wires,cables,connectors and switchesTypes of wires,cables,connectors and switches
Types of wires,cables,connectors and switches
 
Household wiring
Household wiringHousehold wiring
Household wiring
 
Types of wires and cables
Types of wires and cablesTypes of wires and cables
Types of wires and cables
 
wiring Part 3: wires & cables
wiring Part 3: wires & cableswiring Part 3: wires & cables
wiring Part 3: wires & cables
 
Assignment 1
Assignment 1Assignment 1
Assignment 1
 
seminar 4 sem
seminar 4 semseminar 4 sem
seminar 4 sem
 
ELECTRICAL WIRING AND MAINTENANCE
ELECTRICAL WIRING AND MAINTENANCEELECTRICAL WIRING AND MAINTENANCE
ELECTRICAL WIRING AND MAINTENANCE
 
Two way lighting circuit
Two way lighting circuitTwo way lighting circuit
Two way lighting circuit
 
PERULANGAN DALAM MATLAB
PERULANGAN DALAM MATLABPERULANGAN DALAM MATLAB
PERULANGAN DALAM MATLAB
 
Energy scenario sachin 27.05.14
Energy scenario sachin 27.05.14Energy scenario sachin 27.05.14
Energy scenario sachin 27.05.14
 
IE in the ccu
IE in the ccuIE in the ccu
IE in the ccu
 
Tutorial mat lab_teguhw
Tutorial mat lab_teguhwTutorial mat lab_teguhw
Tutorial mat lab_teguhw
 
Energy scenario
Energy scenarioEnergy scenario
Energy scenario
 
Signals and systems with matlab applications orchard publications
Signals and systems with matlab applications   orchard publicationsSignals and systems with matlab applications   orchard publications
Signals and systems with matlab applications orchard publications
 

Similar to Hospital wiring SYSTEM

MV Cable Catalogue
MV Cable CatalogueMV Cable Catalogue
MV Cable CatalogueRajat Mehta
 
Design considerations of electrical installations
Design considerations of electrical installationsDesign considerations of electrical installations
Design considerations of electrical installationsvishalgohel12195
 
report on electrical wiring
report on electrical wiringreport on electrical wiring
report on electrical wiringAbhidada123
 
Distribution boards and Protection devices ppt
Distribution boards and Protection devices  pptDistribution boards and Protection devices  ppt
Distribution boards and Protection devices pptZuhairQadri
 
Electrical safety in biophysical measurements
Electrical safety in biophysical measurementsElectrical safety in biophysical measurements
Electrical safety in biophysical measurementsJaya Yadav
 
Platform touch voltage protection membrane system and other railways buildin...
Platform touch voltage protection membrane system  and other railways buildin...Platform touch voltage protection membrane system  and other railways buildin...
Platform touch voltage protection membrane system and other railways buildin...Mahesh Chandra Manav
 
Jmv presentation smart power transmission projects cea
Jmv  presentation  smart power transmission projects  ceaJmv  presentation  smart power transmission projects  cea
Jmv presentation smart power transmission projects ceaMahesh Chandra Manav
 
HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)Allied Power APS
 
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...Mahesh Chandra Manav
 
Power quality presentation by jmv lps
Power quality presentation by jmv lpsPower quality presentation by jmv lps
Power quality presentation by jmv lpsMahesh Chandra Manav
 
Electrical Systems in a Building
Electrical Systems in a BuildingElectrical Systems in a Building
Electrical Systems in a BuildingGAURAV. H .TANDON
 
electricalsystemsinabuilding-150911082119-lva1-app6892 (1).pdf
electricalsystemsinabuilding-150911082119-lva1-app6892 (1).pdfelectricalsystemsinabuilding-150911082119-lva1-app6892 (1).pdf
electricalsystemsinabuilding-150911082119-lva1-app6892 (1).pdfSHRIKANTNIKAM13
 
Jmv presentation smart process plant -hurl 2017
Jmv  presentation  smart process plant -hurl 2017Jmv  presentation  smart process plant -hurl 2017
Jmv presentation smart process plant -hurl 2017Mahesh Chandra Manav
 
Electrical wiring project
Electrical wiring projectElectrical wiring project
Electrical wiring projectsam zion
 
Jmv presentation smart process plant (fertilizer)
Jmv  presentation  smart process  plant (fertilizer)Jmv  presentation  smart process  plant (fertilizer)
Jmv presentation smart process plant (fertilizer)Mahesh Chandra Manav
 
changwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBchangwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBSheikh Imran
 
Electrical services WITH WIRING FUSES DISTRIBUTION SYSTEMS
Electrical services WITH WIRING FUSES DISTRIBUTION SYSTEMSElectrical services WITH WIRING FUSES DISTRIBUTION SYSTEMS
Electrical services WITH WIRING FUSES DISTRIBUTION SYSTEMSMADHUMITHA355894
 

Similar to Hospital wiring SYSTEM (20)

Residential wiring PPT.pptx
Residential wiring PPT.pptxResidential wiring PPT.pptx
Residential wiring PPT.pptx
 
MV Cable Catalogue
MV Cable CatalogueMV Cable Catalogue
MV Cable Catalogue
 
Design considerations of electrical installations
Design considerations of electrical installationsDesign considerations of electrical installations
Design considerations of electrical installations
 
cables.pptx
cables.pptxcables.pptx
cables.pptx
 
report on electrical wiring
report on electrical wiringreport on electrical wiring
report on electrical wiring
 
Distribution boards and Protection devices ppt
Distribution boards and Protection devices  pptDistribution boards and Protection devices  ppt
Distribution boards and Protection devices ppt
 
Electrical safety in biophysical measurements
Electrical safety in biophysical measurementsElectrical safety in biophysical measurements
Electrical safety in biophysical measurements
 
Platform touch voltage protection membrane system and other railways buildin...
Platform touch voltage protection membrane system  and other railways buildin...Platform touch voltage protection membrane system  and other railways buildin...
Platform touch voltage protection membrane system and other railways buildin...
 
Jmv presentation smart power transmission projects cea
Jmv  presentation  smart power transmission projects  ceaJmv  presentation  smart power transmission projects  cea
Jmv presentation smart power transmission projects cea
 
HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)
 
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
 
Power quality presentation by jmv lps
Power quality presentation by jmv lpsPower quality presentation by jmv lps
Power quality presentation by jmv lps
 
Electrical Systems in a Building
Electrical Systems in a BuildingElectrical Systems in a Building
Electrical Systems in a Building
 
electricalsystemsinabuilding-150911082119-lva1-app6892 (1).pdf
electricalsystemsinabuilding-150911082119-lva1-app6892 (1).pdfelectricalsystemsinabuilding-150911082119-lva1-app6892 (1).pdf
electricalsystemsinabuilding-150911082119-lva1-app6892 (1).pdf
 
Jmv presentation smart process plant -hurl 2017
Jmv  presentation  smart process plant -hurl 2017Jmv  presentation  smart process plant -hurl 2017
Jmv presentation smart process plant -hurl 2017
 
Electrical wiring project
Electrical wiring projectElectrical wiring project
Electrical wiring project
 
Jmv presentation smart process plant (fertilizer)
Jmv  presentation  smart process  plant (fertilizer)Jmv  presentation  smart process  plant (fertilizer)
Jmv presentation smart process plant (fertilizer)
 
changwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DBchangwon MVP, EMDB, SMDB & DB
changwon MVP, EMDB, SMDB & DB
 
Electrical services WITH WIRING FUSES DISTRIBUTION SYSTEMS
Electrical services WITH WIRING FUSES DISTRIBUTION SYSTEMSElectrical services WITH WIRING FUSES DISTRIBUTION SYSTEMS
Electrical services WITH WIRING FUSES DISTRIBUTION SYSTEMS
 
Www.electricalwire.biz
Www.electricalwire.bizWww.electricalwire.biz
Www.electricalwire.biz
 

Recently uploaded

notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptMsecMca
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Bookingdharasingh5698
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptxJIT KUMAR GUPTA
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...SUHANI PANDEY
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringmulugeta48
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptDineshKumar4165
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaOmar Fathy
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Bookingroncy bisnoi
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxJuliansyahHarahap1
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueBhangaleSonal
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfJiananWang21
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startQuintin Balsdon
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...roncy bisnoi
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationBhangaleSonal
 

Recently uploaded (20)

notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 

Hospital wiring SYSTEM

  • 3.
  • 4. TYPES OF WIRING DOMESTIC WIRING COMMERCIAL WRING INDUSTRIAL WIRING
  • 6.
  • 8.
  • 9.
  • 10.
  • 11.
  • 12.
  • 13.
  • 14.
  • 16.
  • 17.
  • 18.
  • 20.
  • 21.
  • 22.
  • 23.
  • 24.
  • 25. Wiring methods Materials for wiring interior electrical systems in buildings vary depending on: Intended use and amount of power demand on the circuit Type of occupancy and size of the building National and local regulations Environment in which the wiring must operate Wires and cables are rated by the circuit voltage, temperature rating and environmental conditions (moisture, sunlight, oil, chemicals) in which they can be used. A wire or cable has a voltage (to neutral) rating and a maximum conductor surface temperature rating. The amount of current a cable or wire can safely carry depends on the installation conditions.
  • 26. Wiring systems in a single family home or duplex, for example, are simple, with relatively low power requirements, infrequent changes to the building structure and layout, usually with dry, moderate temperature and non-corrosive environmental conditions Heavy industries have more demanding wiring requirements, such as very large currents and higher voltages, frequent changes of equipment layout, corrosive, or wet or explosive atmospheres. In facilities that handle flammable gases or liquids, special rules may govern the installation and wiring of electrical equipment in hazardous areas.
  • 28. Modern non-metallic sheathed cables, such as (US and Canadian) Types NMB and NMC, consist of two to four wires covered with thermoplastic insulation, plus a bare wire for grounding (bonding), surrounded by a flexible plastic jacket. Some versions wrap the individual conductors in paper before the plastic jacket is applied. Generally, single conductor building wire in small sizes is solid wire, since the wiring is not required to be very flexible. Building wire conductors larger than 10 AWG (or about 6 mm²) are stranded for flexibility during installation, but are not sufficiently pliable to use as appliance cord.
  • 29. Cables for industrial, commercial and apartment buildings may contain many insulated conductors in an overall jacket, with helical tape steel or aluminium armour, or steel wire armour, and perhaps as well an overall PVC or lead jacket for protection from moisture and physical damage. Cables intended for very flexible service or in marine applications may be protected by woven bronze wires. Power or communications cables (e.g., computer networking) that are routed in or through air-handling spaces (plenums) of office buildings are required under the model building code to be either encased in metal conduit, or rated for low flame and smoke production
  • 31.
  • 32. In healthcare applications, people's bodies are often in direct contact with energized equipment thus provides extensive grounding and bonding requirements-even for something as ordinary as a an electrical socket. 1. Maximize the physical and electromagnetic protection of wiring by requiring metal wiring methods. 2. Minimize electrical hazards by minimizing the voltage potential between patients and medical equipment. 3. Minimize the negative effects of power interruptions with specific requirements for essential electrical systems.
  • 34. Essential electrical system (EES) has the mission of ensuring continuity of electrical power to specific functions and areas of a healthcare facility One basic requirement for hospitals is the EES must consist of two separate systems, which must be kept entirely separate from all other wiring and equipment. They can't even share raceways, boxes, or cabinets with other wiring. These two systems are: Emergency system. This is limited to circuits essential to life safety and critical patient care. Equipment system. This supplies major electrical equipment necessary for patient care and basic hospital operation.
  • 35. ● The number of transfer switches to be used shall be based upon design and load considerations. ● Each branch of the essential electrical system shall be served by one or more transfer switches. ● With special permission, facilities with a maximum demand on the essential electrical system of 150 kVA will be permitted to have one transfer switch serving the emergency branches. ● Loads served by the generating equipment shall be served by their own transfer switches such that these loads Shall not be transferred if the transfer will overload the generating equipment, and Shall be automatically shed upon generating equipment overloading
  • 36. The wiring of the EES must be mechanically protected, per one of the following wiring methods: (1) Non flexible metal raceways, Type MI cable, or Schedule 80 rigid nonmetallic conduit. (2) Schedule 40 rigid nonmetallic conduit or flexible nonmetallic raceways listed for installation in concrete (where encased in not less than 50 mm (2 in.) of concrete). (3) Flexible power cords of appliances or other utilization equipment connected to the emergency system. (4) Secondary circuits of Class 2 or Class 3 communication or signaling systems.
  • 37. (4) Flexible metal raceways and metal sheathed cable assemblies as follows: a. When used in listed prefabricated medical headwalls, b. When used In listed office furnishings, c. Where fished into existing walls or ceilings (not otherwise accessible and not subject to physical damage), or d. Where necessary for flexible connection to equipment. (4) Flexible power cords of appliances or other utilization equipment connected to the emergency system. (5) Secondary circuits of Class 2 or Class 3 communication or signaling systems. do not use nonmetallic raceways for branch circuits that supply patient care areas
  • 38. Patient Care Area Receptacle Rules ● EMT or Armored Cable are used You must install all branch circuits so they have a ground path for fault current. This means installation in a metal raceway system or a cable armor or sheath assembly-each of which must qualify as an effective ground-fault current path. ● AC cable is listed as a suitable ground-fault path because it contains an internal bonding strip of aluminum in direct contact with the outer metal sheath of AC cable. ● Any receptacle supplied by an emergency circuit must not use Type AC, MC, FMC, or any other flexible cable. Emergency circuits must have a non flexible metal raceway-or MI cable with an additional insulated copper equipment grounding (bonding) conductor.
  • 39. General care areas have three requirements: ● At least two branch circuits-one from the emergency system and one from the normal system-must supply each patient bed location. ● All branch circuits from the normal system must originate in the same panelboard (three exceptions apply). ● Each "patient bed location" must have a minimum of four hospital grade electrical socket. ● If you put receptacles in a pediatric ward, use only ones listed as tamper-resistant or ones that employ listed tamper-resistant covers.
  • 40. Hospital power sources and alternate power sources shall be permitted to serve the essential systems of contiguous or same site facilities.Wiring Requirements. ● Separation from Other Circuits. The life safety branch and critical branch of the emergency system shall be kept entirely independent of all other wiring and equipment and shall not enter the same raceways, boxes, or cabinets with each other or other wiring. Exception: Service switchboard and transfer switch equipment.
  • 41. ● Mechanical Protection of the Emergency System. The wiring of the emergency system of a hospital shall be mechanically protected by installation in non-flexible metal raceways, or shall be wired with Type MI cable. Where installed as branch circuit conductors serving patient care areas, the installation shall comply with the requirements.Exception: Flexible power cords of appliances, or other utilization equipment, connected to the emergency
  • 42. Capacity of Systems ● The essential electrical system shall have adequate capacity to meet the demand for the operation of all functions and equipment to be served by each system and branch. ● The generator sets shall have sufficient capacity and proper rating to meet the demand produced by the load of the essential electrical systems at any one time