Pacific Southwest Disturbance
September 8 2011
          8,

Event Analysis Overview Presented to IEEE PSRC
May 17, 2012 – Main Committee Meeting
September 8, 2011 Event

• 11 minute cascading outage in Pacific Southwest
• 2.7 million customers out in AZ, S.CA, MX, some up to 12
  2.7 million customers out in AZ, S.CA, MX, some up to 12 
  hours
• Initiated when single 500 kV line tripped, but not sole cause
• Power redistributed, increasing flows through underlying 
  systems, causing voltage drops and equipment overloads
• Ripple effect led to tripping of lines and generators, 
  automatic load shedding, and operation of a Remedial 
  Action Scheme and an intertie separation scheme
  Action Scheme and an intertie separation scheme
• Restoration process generally effective


2                                          RELIABILITY | ACCOUNTABILITY
Customer Impacts

          Entity         Load Lost (MW)           Customers

         SDGE                  4,293               1.4 million

          CFE                  2,150
                               2 150               1.1
                                                   1 1 million

           IID                  929             146 thousand

          APS                   389              70 thousand

         WALC                    74                    Note

    Note: 64 MWs of WALC s load loss affected APS s customers 
    Note: 64 MWs of WALC’s load loss affected APS’s customers

3                                               RELIABILITY | ACCOUNTABILITY
Joint FERC/NERC Inquiry

• Announced September 9, 2012
• Teams formed comprising over 30 senior technical staff of
  Teams formed comprising over 30 senior technical staff of 
  FERC and NERC, plus several NERC contractors and industry 
  subject matter experts
• Multiple meetings and exchanges with affected entities to 
  gather facts
• T
  Team products combined into final report
            d        bi d i     fi l
• Outreach sessions to gain feedback on draft findings and 
  recommendations




4                                        RELIABILITY | ACCOUNTABILITY
Inquiry Teams

•   Data Requests/Management
•   Sequence of Events
    Sequence of Events
•   Modeling/Simulation
•   Cause Analysis/Human Performance
               y /
•   Operations Tools/ SCADA/EMS
•   Frequency Analysis
       q     y     y
•   System Planning/Design
•   Equipment Performance/System Protection
•   Restoration



5                                      RELIABILITY | ACCOUNTABILITY
Sequence of Events




6                  RELIABILITY | ACCOUNTABILITY
Simplified System Diagram




    Serrano            Devers                          Palo Verde

                             S-Corridor
    SONGS

     Path
      44             Imperial              WAPA
                Irrigation District        Lower       Hassayampa
                                                       H
                    161 kV     92 kV      Colorado
                                                         H-NG
    SDG&E
                                                        Corridor
                                S-Line

    Miguel           Imperial Valley                    North Gila



              CFE



7                                                    RELIABILITY | ACCOUNTABILITY
Phase 1 – Pre-Disturbance
             • Hot, shoulder season day; some
               generation and transmission
               outages

             • High loading on some key
               facilities: H-NG at 78% of normal
               rating; CV transformers at 83%

             • 44 minutes before loss of H-NG,
               IID’s RTCA results showed loss
               of CV 1 transformer would load
                  CV-1
               CV-2 transformer above its relay
               trip point

             • 15 27 39 APS t h i i
               15:27:39:       technician
               skipped a critical step in isolating
               the series capacitor bank at
               North Gila substation; H-NG trips
                                      ;          p


8                    RELIABILITY | ACCOUNTABILITY
Phase 2 – Trip of H-NG 500 kV
                                  • H-NG 500 kV trips at
                                    15:27:39

    15:27:39 15:28:16
    15 27 39 – 15 28 16           • APS tells WECC RC line
                                    expected to be restored
                                    quickly

                                  • H-NG flow redistributes: 77%
                                        Gf                     %
                                    to SCE-SDGE (Path 44);
                                    remainder to IID, and WALC

                                  • CV transformers immediately
                                    overloaded above relay
                                    settings

                                  • Path 44 at 5,900 amps; 8,000
                                    amp limit on SONGS
                                    separation scheme
                                      p


9                                     RELIABILITY | ACCOUNTABILITY
Initiating Event – Tripping of
           Hassayampa – North Gila 500 kV Line




     Series Capacitor
      Bypass Switch
        Arcs Over




10                             RELIABILITY | ACCOUNTABILITY
Hass. – N. Gila 500 kV Line Trip
              South of SONGS Current




                        CCM Unit 1 
                       generator trip




     Hassyampa –
     N. Gila 500 kV 
        line trip




11                                      RELIABILITY | ACCOUNTABILITY
Phase 3 – Trip of CV Transformers
                                      • 15:28:16 – CV-2 and CV-1
                                        230/92kV transformers trip on
                                        overload relays
     15:28:16 15:32:10
     15 28 16 – 15 32 10
                                      • Severe low voltage in WALC
                                        161 kV system

                                      • Loading on Path 44
                                        increases to 6,700 amps




12                                        RELIABILITY | ACCOUNTABILITY
CV Transformers Trip
               South of SONGS Current




      Coachella Valley 
        230/92 kV 
     transformers trip




13                                      RELIABILITY | ACCOUNTABILITY
Phase 4 – Ramon Xfmr Trip
                                  • 15:32:10 Ramon 230/92kV
                                    transformer trips on overload
                                    relay
     15:32:10 15:35:40
     15 32 10 – 15 35 40
                                  • 15:32:13 Blythe-Niland
                                    161kV line trips
                                  • 15:32:15 Niland – CV 161kV
                                    line trips

                                  • IID undervoltage load
                                    shedding; loss of generation
                                    and 92 kV transmission lines

                                  • Severe low voltage in WALC
                                    161 kV system
                                              t

                                  • Loading on Path 44
                                    increases to 7,800 amps;
                                                   ,      p ;
                                    settles at 7,200 amps

14                                    RELIABILITY | ACCOUNTABILITY
Ramon Transformer Trip
             South of SONGS Current


           Voltage collapse in 
             l        ll    i
            pocket, followed 
            by load tripping




         Multiple line, generator 
             and load trips

     Ramon 230/92 kV 
      transformer  trip




15                                    RELIABILITY | ACCOUNTABILITY
Voltage in Northern IID 92 kV System

                                     Over‐Voltage Trip 
                                     of 92 kV System 
                                        Capacitors




                               Trip of Over 400 
     Ramon 230/92 kV           MW in Northern 
      Transformer Trip
      Transformer Trip          IID 92 kV Load 
                                IID 92 kV Load
                                    Pocket




16                                         RELIABILITY | ACCOUNTABILITY
Blythe 161 kV Voltage


     Trip of Hassayampa 
        p          y p                          El Centro – Pilot 
                                                El Centro Pilot
     – North Gila 500 kV                        Knob 161 kV Line 
              Line                                    Trip 


           Trip of Coachella 
           Valley 230/92 kV 
            Transformers           Yucca 161/69 kV 
                                  Transformers 1 and 
                                         2 Trip
                                         2 Trip




                                       Trip of Over 400 
                                       Trip of Over 400
      Ramon 230/92 kV                  MW in Northern 
       Transformer Trip                 IID 92 kV Load 
                                            Pocket




17                                                  RELIABILITY | ACCOUNTABILITY
Phase 5 – Yuma Separates
                               • Yuma AZ Separates from IID
                                 and WALC when Gila and
                                 Yucca transformers trip
     15:35:40 15:37:55
     15 35 40 – 15 37 55
                               • Yuma load pocket isolated on
                                 single tie to SDG&E

                               • Loading on Path 44
                                 increases to 7,400 amps after
                                 Gila transformer trip; to 7,800
                                 amps after Yucca
                                         ft Y
                                 transformers and generator
                                 trip




18                                 RELIABILITY | ACCOUNTABILITY
Yuma Separation
                South of SONGS Current

                       YCA 
                    generating 
                    g          g
                     units trip




     Yucca 161/69 kV                   Pilot Knob 
     transformers  trip                161/92 kV 
                                     transformers 
                                           trip


         Gila 161/69 kV 
        transformers  trip




19                                       RELIABILITY | ACCOUNTABILITY
Phase 6 – High-Speed Cascade
                              • El Centro – Pilot Knob 161kV
                                line trips; all IID 92 kV system
                                radial from SDG&E via S-Line
     15:37:55
     15 37 55
                              • WALC 161 kV system voltage
                                returns to normal

                              • Path 44 exceeds 8,000 amp
                                setting and timer starts




20                                 RELIABILITY | ACCOUNTABILITY
El Centro – Pilot Knob 161 kV Trips



                 Early 
                Phase 4 
                activity



                               Gila 
                           transformers 
                               trip

                                             Pilot Knob 
                                           transformers 
                                                 trip


                                                           Zone 3 
                                                           pickup
               Yucca 
           transformers 
                trip




21                                         RELIABILITY | ACCOUNTABILITY
Phase 6 – High-Speed Cascade
                              • S-Line RAS trips IV
                                generation and S-Line,
                                isolating IID from SDG&E
     15:37:58 15:38:02.4
     15 37 58 – 15 38 02 4
                              • Path 44 loading increases to
                                as high as 9,500 amps and
                                reduces to 8,700 amps after
                                isolating IID




22                                RELIABILITY | ACCOUNTABILITY
Phase 6 – High-Speed Cascade
                        South of SONGS Current


                                         Imperial Valley  El 
                                         Imperial Valley – El
                                           Centro 230 kV 
        CLR                                 “S” line trip
     generating 
      units trip                                                  SONGS 
                                                                separation
                                                                       i




                   El Centro  – Pilot 
                   Knob 161 kV line 
                         trip




23                                                                   RELIABILITY | ACCOUNTABILITY
Phase 6 – High-Speed Cascade
                                • SONGS separation scheme
                                  operates; forms SDG&E,
                                  CFE, Yuma combined island
     15:38:21.2
     15 38 21 2
                                • Combined island frequency
                                  begins to collapse




24                                 RELIABILITY | ACCOUNTABILITY
SONGS 
     separation




                                SONGS Unit 3 
                                 electrically 
                                 disconnects

                                SONGS Unit 2 
                                 electrically 
                                 disconnects



                    SONGS 
                    SONGS
                  generators 
                  ring down




25                                        RELIABILITY | ACCOUNTABILITY
SONGS 
       SONGS
     separation         SONGS Unit 2 GSU 
                        trip and transfer of           SONGS aux load 
                              aux load                    on startup 
                                                        transformers




            SONGS 
          generators 
          ring down
          ring down
                                                SONGS Unit 3 GSU 
                                                trip and transfer of 
                                                      aux load




26                                          RELIABILITY | ACCOUNTABILITY
Phase 7 – S CA Separates
                             • Yuma island separates from
                               SDG&E when IV-NG 500 kV
                               trips on underfrequency
     15:38:23.12
     15 38 23 12
                             • APS UFLS operates, but
                               insufficient to stabilize load
                               pocket

                             • Yuma load pocket collapses




27                               RELIABILITY | ACCOUNTABILITY
UFLS Operations in the Island




28                   RELIABILITY | ACCOUNTABILITY
Voltage 
                                                            Voltage
                                                         peaks as tie 
                                                          lines open




       SONGS 
     separation




        SDGE UFLS begins    SDGE ties to CFE and Yuma 
          shedding load      open on underfrequency




29                                                       RELIABILITY | ACCOUNTABILITY
Phase 7 – CFE Separates
                            • Underfrequency UFLS
                              SDG&E and CFE
                              continues

     15:38:23.13
     15 38 23 13            • CFE separates from SDG&E




30                             RELIABILITY | ACCOUNTABILITY
Actual vs. Simulated Frequency

      




31                        RELIABILITY | ACCOUNTABILITY
Phase 7 – Complete Blackout
                                • IID, Yuma, SDG&E, and CFE
                                  blacked out

     By 15:38:38
     B 15 38 38




32                                 RELIABILITY | ACCOUNTABILITY
Use of PMUs in EA




33                  RELIABILITY | ACCOUNTABILITY
Sammis-Star




                                                                                                  Hard-Chamb
                                                                                                  Hard Chamb
                                                              Star-S.Cant
                                                CantC-Tidd




                                                                                 Hanna-Jun
2003 Blackout Simulations




                                                                                                                                  RELIABILITY | ACCOUNTABILITY
                                  345 kV




                                                345 kV




                                                              345 kV




                                                                                 345 kV




                                                                                                  345 kV




                                                                                                     Dale-W.Can
                                                                                                     138 kV
                                                                                                    W.Ak 138 kV
                                                                                                    Bkr Failure
                                                                                                     Cham-W.Ak
                                                                                                     138 kV
                                                                                                   E.Lima-N.Fin
                                                                                                   138 kV
                                                                                                      CantC Xfmr
                                                                                                  W.Ak-PV Q21
                                                                                                  W
                                                                                                  138
                                                                                                  1 kV




                                                                                                                        Outages
                                                                                                      Babb-W.Ak
                                                                                                      138 kV
                                                                                                   E.Lima-N.Lib
                                                                                                   E
                                                                                                   138 kV
                                                                                                      Clov-Torrey
                                                                                                      138 kV
                                                                                                      Star-S.Cant
                                                                                                      345 kV
                                                                                                       Hanna-Jun
                                                                                                       345 kV
                                                                                                   Hard-Chamb
                                                                                                   345 kV




                                                                                                                                  34
                            140


                                     120


                                                100


                                                             80


                                                                            60


                                                                                             40


                                                                                                          20


                                                                                                                    0
                                                            Amps)
                                        % of Norma Ratings (A
                                                 al
PMU Data from SONGS




35           RELIABILITY | ACCOUNTABILITY
7 Phases of Event


                                            Trip or Gila 161/69 kV 
                                            Trip or Gila 161/69 kV
                Trip of Coachella               Transformers & 
                Valley 230/92 kV                  Yuma Cogen
                 Transformers



                                               Trip of Pilot Knob 
                                              161/92 kV & Yucca 
                                                   161/69 kV                   Trip of  Pilot 
                                                 Transformers                   Knob – El 
             Trip of Hassayampa 
                                                                              Centro 161 kV 
             – North Gila 500 kV
               North Gila 500 kV 
                                                                                   Line
                      Line



                  Trip of Ramon                                        South of SONGS 
                    230/92 kV 
                        /                                                Separation
                   Transformer




     1   2                 3                             4                           5           6   7


                                     Disturbance Phases

36                                                                    RELIABILITY | ACCOUNTABILITY
EA Modeling




37                 RELIABILITY | ACCOUNTABILITY
Simulation vs. Actual Flows
                                                South of SONGS Flows
          4000




          3500




          3000




          2500
     MW




          2000




          1500




          1000




          500




             0
          15:27:30.240   15:28:56.640   15:30:23.040   15:31:49.440       15:33:15.840     15:34:42.240   15:36:08.640   15:37:35.040
                                                                      Local Time (PDT)
                                                                      L   l Ti   (PDT)

                                                             Simulated           Actual (PMU)




38                                                                                                        RELIABILITY | ACCOUNTABILITY
Inquiry Findings




39                  RELIABILITY | ACCOUNTABILITY
Key Findings

Weaknesses in two broad areas:
• Operations planning
  Operations planning
• Real‐time situational awareness
Contributing factors:
Contributing factors:
• Not studying impact of sub 100 kV facilities parallel to EHV
• Failure to recognize IROLs
   Failure to recognize IROLs
• Not studying/coordinating effects of protection systems and 
   RASs during contingency scenarios
   RASs during contingency scenarios
• Not providing effective operator tools and instructions for 
   reclosing lines with large phase angle differences

40                                        RELIABILITY | ACCOUNTABILITY
Operations Planning

Failure to consider in seasonal, next‐day, and real‐time studies:
• Status of external generation and transmission facilities
    Status of external generation and transmission facilities
• Impact of external contingencies
• Impacts on external systems
       p                  y
• Impact on BPS of reliability of sub‐100 kV facilities parallel to 
    EHV system




41                                           RELIABILITY | ACCOUNTABILITY
Operations Planning

Recommended TOP/BA Improvements in WECC:
•    Obtain information on neighboring BAs and TOPs, including 
                                g        g                ,         g
     transmission outages, generation outages and schedules, load 
     forecasts, and scheduled interchanges 
•    Identify and plan for external contingencies that could impact 
     Id tif     d l f        t     l    ti      i th t       ld i     t
     their systems and internal contingencies that could impact 
     neighbors’ systems
•    Consider facilities operated at less than 100 kV parallel to EHV 
     system that could impact BPS reliability
•    Coordinated review of planning studies to ensure operation of 
     C di        d     i    f l    i       di                     i    f
     affected Rated Paths will not result in reliability problems



42                                                 RELIABILITY | ACCOUNTABILITY
Situational Awareness

Recommended Improvements in WECC:
•    Expand entities’ external visibility in models through more 
        p                               y                 g
     complete data sharing
•    Improve use of real‐time tools to ensure constant monitoring of 
     potential internal or external contingencies
        t ti l i t    l      t     l     ti     i
•    Improve communications among entities to help maintain 
     situational awareness
     situational awareness
•    TOPs should review their real‐time monitoring tools (State 
     Estimator and RTCA) to ensure critical facilities are represented




43                                              RELIABILITY | ACCOUNTABILITY
System Protection Issues

Recommendations:
•    IID and other TOs review transformer overload protection
                                                     p
     relay settings
•    TOPs plan to take proper pre-contingency mitigation
     measures considering emergency ratings and overload
                     id i                ti        d     l d
     protection systems
•    All protection systems and separation schemes (Safety
     Nets, RAS, and SPS) studied and coordinated periodically to
     understand their impact on BPS reliability to ensure no
     unintended or undesirable effects




44                                         RELIABILITY | ACCOUNTABILITY
Questions?




45                RELIABILITY | ACCOUNTABILITY

Weitere ähnliche Inhalte

Was ist angesagt?

PA Intermodulation Distortion Measurements Using the PNA
PA Intermodulation Distortion Measurements Using the PNA PA Intermodulation Distortion Measurements Using the PNA
PA Intermodulation Distortion Measurements Using the PNA ls234
 
Design Basics on Power Amplifiers
Design Basics on Power Amplifiers Design Basics on Power Amplifiers
Design Basics on Power Amplifiers ls234
 
Mtnw Wc Presentation June 07 Rev4
Mtnw Wc Presentation   June 07 Rev4Mtnw Wc Presentation   June 07 Rev4
Mtnw Wc Presentation June 07 Rev4WashingtonChain
 
Switched capacitor
Switched capacitorSwitched capacitor
Switched capacitorGur Kan
 
Switched capacitor filter
Switched capacitor filterSwitched capacitor filter
Switched capacitor filterMinh Anh Nguyen
 
Transformer vector group_test_conditions
Transformer vector group_test_conditionsTransformer vector group_test_conditions
Transformer vector group_test_conditionsSARAVANAN A
 
MAAP4.0.6 Simulation of Beyond DBA BWR3 Mark I rev03
MAAP4.0.6 Simulation of Beyond DBA  BWR3 Mark I  rev03MAAP4.0.6 Simulation of Beyond DBA  BWR3 Mark I  rev03
MAAP4.0.6 Simulation of Beyond DBA BWR3 Mark I rev03John Bickel
 
Hybrid Analog-Digital Architecture for Massive MIMO: An Introduction
Hybrid Analog-Digital Architecture for Massive MIMO: An IntroductionHybrid Analog-Digital Architecture for Massive MIMO: An Introduction
Hybrid Analog-Digital Architecture for Massive MIMO: An IntroductionT. E. BOGALE
 
41 Atg&Ctm Fope06
41 Atg&Ctm Fope0641 Atg&Ctm Fope06
41 Atg&Ctm Fope06jubin
 
Amplifier Design
Amplifier DesignAmplifier Design
Amplifier Designimranbashir
 
Multi level inverter
Multi level inverterMulti level inverter
Multi level inverterraviarmugam
 
Gas Recovery Systems Vopak VCM Sphere Project
Gas Recovery Systems Vopak VCM Sphere ProjectGas Recovery Systems Vopak VCM Sphere Project
Gas Recovery Systems Vopak VCM Sphere ProjectFred Reyes
 
Up on the Rooftop: Updating HVAC Rooftop UnitPerformance
Up on the Rooftop: Updating HVAC Rooftop UnitPerformanceUp on the Rooftop: Updating HVAC Rooftop UnitPerformance
Up on the Rooftop: Updating HVAC Rooftop UnitPerformanceE Source Companies, LLC
 

Was ist angesagt? (19)

PA Intermodulation Distortion Measurements Using the PNA
PA Intermodulation Distortion Measurements Using the PNA PA Intermodulation Distortion Measurements Using the PNA
PA Intermodulation Distortion Measurements Using the PNA
 
Measurement Solutions for the Water and Wastewater Industries
Measurement Solutions for the Water and Wastewater IndustriesMeasurement Solutions for the Water and Wastewater Industries
Measurement Solutions for the Water and Wastewater Industries
 
Design Basics on Power Amplifiers
Design Basics on Power Amplifiers Design Basics on Power Amplifiers
Design Basics on Power Amplifiers
 
Mtnw Wc Presentation June 07 Rev4
Mtnw Wc Presentation   June 07 Rev4Mtnw Wc Presentation   June 07 Rev4
Mtnw Wc Presentation June 07 Rev4
 
Switched capacitor
Switched capacitorSwitched capacitor
Switched capacitor
 
Switched capacitor filter
Switched capacitor filterSwitched capacitor filter
Switched capacitor filter
 
Transformer vector group_test_conditions
Transformer vector group_test_conditionsTransformer vector group_test_conditions
Transformer vector group_test_conditions
 
Unit 2
Unit  2Unit  2
Unit 2
 
MAAP4.0.6 Simulation of Beyond DBA BWR3 Mark I rev03
MAAP4.0.6 Simulation of Beyond DBA  BWR3 Mark I  rev03MAAP4.0.6 Simulation of Beyond DBA  BWR3 Mark I  rev03
MAAP4.0.6 Simulation of Beyond DBA BWR3 Mark I rev03
 
Hybrid Analog-Digital Architecture for Massive MIMO: An Introduction
Hybrid Analog-Digital Architecture for Massive MIMO: An IntroductionHybrid Analog-Digital Architecture for Massive MIMO: An Introduction
Hybrid Analog-Digital Architecture for Massive MIMO: An Introduction
 
41 Atg&Ctm Fope06
41 Atg&Ctm Fope0641 Atg&Ctm Fope06
41 Atg&Ctm Fope06
 
Amplifier Design
Amplifier DesignAmplifier Design
Amplifier Design
 
1 cm72 1e
1 cm72 1e1 cm72 1e
1 cm72 1e
 
Div gpsiifsv1 mob
Div gpsiifsv1 mobDiv gpsiifsv1 mob
Div gpsiifsv1 mob
 
Presentation-MB-1
Presentation-MB-1Presentation-MB-1
Presentation-MB-1
 
Bam Nuttall Hv Test Report
Bam Nuttall   Hv Test ReportBam Nuttall   Hv Test Report
Bam Nuttall Hv Test Report
 
Multi level inverter
Multi level inverterMulti level inverter
Multi level inverter
 
Gas Recovery Systems Vopak VCM Sphere Project
Gas Recovery Systems Vopak VCM Sphere ProjectGas Recovery Systems Vopak VCM Sphere Project
Gas Recovery Systems Vopak VCM Sphere Project
 
Up on the Rooftop: Updating HVAC Rooftop UnitPerformance
Up on the Rooftop: Updating HVAC Rooftop UnitPerformanceUp on the Rooftop: Updating HVAC Rooftop UnitPerformance
Up on the Rooftop: Updating HVAC Rooftop UnitPerformance
 

Andere mochten auch

2005 Annual Report Parker Hanniffin
2005 Annual Report Parker Hanniffin2005 Annual Report Parker Hanniffin
2005 Annual Report Parker Hanniffinwmelis
 
2004 Parker Hannifin Annual Report
2004 Parker Hannifin Annual Report2004 Parker Hannifin Annual Report
2004 Parker Hannifin Annual Reportwmelis
 
129 venezuelan static var compensator
129 venezuelan static var compensator129 venezuelan static var compensator
129 venezuelan static var compensatorwmelis
 
Chaos, Order, and Innovation: Planning to Improvise
Chaos, Order, and Innovation: Planning to ImproviseChaos, Order, and Innovation: Planning to Improvise
Chaos, Order, and Innovation: Planning to ImproviseTRG Arts
 
129 venezuelan static var compensator
129 venezuelan static var compensator129 venezuelan static var compensator
129 venezuelan static var compensatorwmelis
 
2000 Parker Hannifin Annual Report
2000 Parker Hannifin Annual Report2000 Parker Hannifin Annual Report
2000 Parker Hannifin Annual Reportwmelis
 
Better Together: Loyalty, Collaboration, and Community in Philadelphia
Better Together: Loyalty, Collaboration, and Community in PhiladelphiaBetter Together: Loyalty, Collaboration, and Community in Philadelphia
Better Together: Loyalty, Collaboration, and Community in PhiladelphiaTRG Arts
 
151 south africa cap bank-protection-baker-duly-2008
151 south africa cap bank-protection-baker-duly-2008151 south africa cap bank-protection-baker-duly-2008
151 south africa cap bank-protection-baker-duly-2008wmelis
 
TRG Webinar: All in: Developing patron loyalty across departments
TRG Webinar: All in: Developing patron loyalty across departmentsTRG Webinar: All in: Developing patron loyalty across departments
TRG Webinar: All in: Developing patron loyalty across departmentsTRG Arts
 
Christmas in July: Turn up the heat on the holidays
Christmas in July: Turn up the heat on the holidaysChristmas in July: Turn up the heat on the holidays
Christmas in July: Turn up the heat on the holidaysTRG Arts
 
Stop surviving and thrive: The patron-centered business model
Stop surviving and thrive: The patron-centered business modelStop surviving and thrive: The patron-centered business model
Stop surviving and thrive: The patron-centered business modelTRG Arts
 
Would you like season tickets with that? The Art of the Upgrade
Would you like season tickets with that? The Art of the UpgradeWould you like season tickets with that? The Art of the Upgrade
Would you like season tickets with that? The Art of the UpgradeTRG Arts
 
All in: Building patron loyalty through teamwork
All in: Building patron loyalty through teamworkAll in: Building patron loyalty through teamwork
All in: Building patron loyalty through teamworkTRG Arts
 
Seat o-nomics: demand-based pricing strategies for chamber music organizations
Seat o-nomics: demand-based pricing strategies for chamber music organizationsSeat o-nomics: demand-based pricing strategies for chamber music organizations
Seat o-nomics: demand-based pricing strategies for chamber music organizationsTRG Arts
 

Andere mochten auch (17)

2005 Annual Report Parker Hanniffin
2005 Annual Report Parker Hanniffin2005 Annual Report Parker Hanniffin
2005 Annual Report Parker Hanniffin
 
Republic of indonesia
Republic of indonesiaRepublic of indonesia
Republic of indonesia
 
2004 Parker Hannifin Annual Report
2004 Parker Hannifin Annual Report2004 Parker Hannifin Annual Report
2004 Parker Hannifin Annual Report
 
Desarrollo ágil enfocado en ux
Desarrollo ágil enfocado en uxDesarrollo ágil enfocado en ux
Desarrollo ágil enfocado en ux
 
129 venezuelan static var compensator
129 venezuelan static var compensator129 venezuelan static var compensator
129 venezuelan static var compensator
 
Chaos, Order, and Innovation: Planning to Improvise
Chaos, Order, and Innovation: Planning to ImproviseChaos, Order, and Innovation: Planning to Improvise
Chaos, Order, and Innovation: Planning to Improvise
 
129 venezuelan static var compensator
129 venezuelan static var compensator129 venezuelan static var compensator
129 venezuelan static var compensator
 
2000 Parker Hannifin Annual Report
2000 Parker Hannifin Annual Report2000 Parker Hannifin Annual Report
2000 Parker Hannifin Annual Report
 
Better Together: Loyalty, Collaboration, and Community in Philadelphia
Better Together: Loyalty, Collaboration, and Community in PhiladelphiaBetter Together: Loyalty, Collaboration, and Community in Philadelphia
Better Together: Loyalty, Collaboration, and Community in Philadelphia
 
151 south africa cap bank-protection-baker-duly-2008
151 south africa cap bank-protection-baker-duly-2008151 south africa cap bank-protection-baker-duly-2008
151 south africa cap bank-protection-baker-duly-2008
 
TRG Webinar: All in: Developing patron loyalty across departments
TRG Webinar: All in: Developing patron loyalty across departmentsTRG Webinar: All in: Developing patron loyalty across departments
TRG Webinar: All in: Developing patron loyalty across departments
 
Christmas in July: Turn up the heat on the holidays
Christmas in July: Turn up the heat on the holidaysChristmas in July: Turn up the heat on the holidays
Christmas in July: Turn up the heat on the holidays
 
Presentación f.p.basica 2015/ 16
Presentación f.p.basica 2015/ 16Presentación f.p.basica 2015/ 16
Presentación f.p.basica 2015/ 16
 
Stop surviving and thrive: The patron-centered business model
Stop surviving and thrive: The patron-centered business modelStop surviving and thrive: The patron-centered business model
Stop surviving and thrive: The patron-centered business model
 
Would you like season tickets with that? The Art of the Upgrade
Would you like season tickets with that? The Art of the UpgradeWould you like season tickets with that? The Art of the Upgrade
Would you like season tickets with that? The Art of the Upgrade
 
All in: Building patron loyalty through teamwork
All in: Building patron loyalty through teamworkAll in: Building patron loyalty through teamwork
All in: Building patron loyalty through teamwork
 
Seat o-nomics: demand-based pricing strategies for chamber music organizations
Seat o-nomics: demand-based pricing strategies for chamber music organizationsSeat o-nomics: demand-based pricing strategies for chamber music organizations
Seat o-nomics: demand-based pricing strategies for chamber music organizations
 

Ähnlich wie Pacific Southwest 2011 Cascading Outage Analyzed

Rte Lebranchu Compensation And Transient Studies Onalong Ehv Overheadline
Rte Lebranchu Compensation And Transient Studies Onalong Ehv OverheadlineRte Lebranchu Compensation And Transient Studies Onalong Ehv Overheadline
Rte Lebranchu Compensation And Transient Studies Onalong Ehv Overheadlinecorinne rocherieux
 
Rourkela Steel Pant Power System
Rourkela Steel Pant Power System Rourkela Steel Pant Power System
Rourkela Steel Pant Power System Sarthak Panigrahi
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transientsmichaeljmack
 
1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter pptUtsav Yagnik
 
Emergingtrends
EmergingtrendsEmergingtrends
Emergingtrendsmkanth
 
Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings RCREEE
 
Chaper 4 Unit 1 Basics of HVDC Transmission.ppt
Chaper 4 Unit 1 Basics of HVDC Transmission.pptChaper 4 Unit 1 Basics of HVDC Transmission.ppt
Chaper 4 Unit 1 Basics of HVDC Transmission.pptonlystu007
 
Capacitor installation and re conductoring
Capacitor installation and re conductoringCapacitor installation and re conductoring
Capacitor installation and re conductoringYusuf A. KHALIL
 
Hvdc proven technology
Hvdc proven technologyHvdc proven technology
Hvdc proven technologyjefryleal
 
HVDC Transmission System Today's Upgrading Technology
HVDC Transmission System Today's Upgrading TechnologyHVDC Transmission System Today's Upgrading Technology
HVDC Transmission System Today's Upgrading TechnologyDixit Patel
 
DPE Company Profile - KV Ref 2
DPE Company Profile - KV Ref 2DPE Company Profile - KV Ref 2
DPE Company Profile - KV Ref 2Sarel Meyer
 
Online classes pe dc-dc converter
Online classes pe dc-dc converterOnline classes pe dc-dc converter
Online classes pe dc-dc converterAmit Kulkarni
 

Ähnlich wie Pacific Southwest 2011 Cascading Outage Analyzed (20)

Rte Lebranchu Compensation And Transient Studies Onalong Ehv Overheadline
Rte Lebranchu Compensation And Transient Studies Onalong Ehv OverheadlineRte Lebranchu Compensation And Transient Studies Onalong Ehv Overheadline
Rte Lebranchu Compensation And Transient Studies Onalong Ehv Overheadline
 
Rourkela Steel Pant Power System
Rourkela Steel Pant Power System Rourkela Steel Pant Power System
Rourkela Steel Pant Power System
 
Basics of hvdc
Basics of hvdc Basics of hvdc
Basics of hvdc
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
 
1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt1-ф to 1-ф Cycloconverter ppt
1-ф to 1-ф Cycloconverter ppt
 
Hvdc dad
Hvdc dadHvdc dad
Hvdc dad
 
SouravMaitiHVDC.pdf
SouravMaitiHVDC.pdfSouravMaitiHVDC.pdf
SouravMaitiHVDC.pdf
 
Emergingtrends
EmergingtrendsEmergingtrends
Emergingtrends
 
Status of hvdc links
Status of hvdc linksStatus of hvdc links
Status of hvdc links
 
132 KV GSS CHAMBAL JAIPUR
132 KV GSS CHAMBAL JAIPUR132 KV GSS CHAMBAL JAIPUR
132 KV GSS CHAMBAL JAIPUR
 
Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings Day 3: Power Supply Quality in Buildings
Day 3: Power Supply Quality in Buildings
 
Chaper 4 Unit 1 Basics of HVDC Transmission.ppt
Chaper 4 Unit 1 Basics of HVDC Transmission.pptChaper 4 Unit 1 Basics of HVDC Transmission.ppt
Chaper 4 Unit 1 Basics of HVDC Transmission.ppt
 
Transformer ppt.
Transformer ppt.Transformer ppt.
Transformer ppt.
 
SCR COMMUTATION PART 1
SCR COMMUTATION PART 1SCR COMMUTATION PART 1
SCR COMMUTATION PART 1
 
Capacitor installation and re conductoring
Capacitor installation and re conductoringCapacitor installation and re conductoring
Capacitor installation and re conductoring
 
Hvdc proven technology
Hvdc proven technologyHvdc proven technology
Hvdc proven technology
 
HVDC Transmission System Today's Upgrading Technology
HVDC Transmission System Today's Upgrading TechnologyHVDC Transmission System Today's Upgrading Technology
HVDC Transmission System Today's Upgrading Technology
 
ppt
pptppt
ppt
 
DPE Company Profile - KV Ref 2
DPE Company Profile - KV Ref 2DPE Company Profile - KV Ref 2
DPE Company Profile - KV Ref 2
 
Online classes pe dc-dc converter
Online classes pe dc-dc converterOnline classes pe dc-dc converter
Online classes pe dc-dc converter
 

Kürzlich hochgeladen

Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...shyamraj55
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxOnBoard
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitecturePixlogix Infotech
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Miguel Araújo
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Igalia
 
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...gurkirankumar98700
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfEnterprise Knowledge
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhisoniya singh
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationRidwan Fadjar
 
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersEnhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersThousandEyes
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Alan Dix
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024Scott Keck-Warren
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024The Digital Insurer
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024Results
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking MenDelhi Call girls
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerThousandEyes
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreternaman860154
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityPrincipled Technologies
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking MenDelhi Call girls
 

Kürzlich hochgeladen (20)

Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
 
Maximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptxMaximizing Board Effectiveness 2024 Webinar.pptx
Maximizing Board Effectiveness 2024 Webinar.pptx
 
Understanding the Laravel MVC Architecture
Understanding the Laravel MVC ArchitectureUnderstanding the Laravel MVC Architecture
Understanding the Laravel MVC Architecture
 
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
Mastering MySQL Database Architecture: Deep Dive into MySQL Shell and MySQL R...
 
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
Raspberry Pi 5: Challenges and Solutions in Bringing up an OpenGL/Vulkan Driv...
 
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
Kalyanpur ) Call Girls in Lucknow Finest Escorts Service 🍸 8923113531 🎰 Avail...
 
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdfThe Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
The Role of Taxonomy and Ontology in Semantic Layers - Heather Hedden.pdf
 
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | DelhiFULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
FULL ENJOY 🔝 8264348440 🔝 Call Girls in Diplomatic Enclave | Delhi
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 Presentation
 
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for PartnersEnhancing Worker Digital Experience: A Hands-on Workshop for Partners
Enhancing Worker Digital Experience: A Hands-on Workshop for Partners
 
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...Swan(sea) Song – personal research during my six years at Swansea ... and bey...
Swan(sea) Song – personal research during my six years at Swansea ... and bey...
 
SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024SQL Database Design For Developers at php[tek] 2024
SQL Database Design For Developers at php[tek] 2024
 
Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024Finology Group – Insurtech Innovation Award 2024
Finology Group – Insurtech Innovation Award 2024
 
A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024A Call to Action for Generative AI in 2024
A Call to Action for Generative AI in 2024
 
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
08448380779 Call Girls In Diplomatic Enclave Women Seeking Men
 
How to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected WorkerHow to Troubleshoot Apps for the Modern Connected Worker
How to Troubleshoot Apps for the Modern Connected Worker
 
Presentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreterPresentation on how to chat with PDF using ChatGPT code interpreter
Presentation on how to chat with PDF using ChatGPT code interpreter
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
Boost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivityBoost PC performance: How more available memory can improve productivity
Boost PC performance: How more available memory can improve productivity
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
 

Pacific Southwest 2011 Cascading Outage Analyzed

  • 1. Pacific Southwest Disturbance September 8 2011 8, Event Analysis Overview Presented to IEEE PSRC May 17, 2012 – Main Committee Meeting
  • 2. September 8, 2011 Event • 11 minute cascading outage in Pacific Southwest • 2.7 million customers out in AZ, S.CA, MX, some up to 12 2.7 million customers out in AZ, S.CA, MX, some up to 12  hours • Initiated when single 500 kV line tripped, but not sole cause • Power redistributed, increasing flows through underlying  systems, causing voltage drops and equipment overloads • Ripple effect led to tripping of lines and generators,  automatic load shedding, and operation of a Remedial  Action Scheme and an intertie separation scheme Action Scheme and an intertie separation scheme • Restoration process generally effective 2 RELIABILITY | ACCOUNTABILITY
  • 3. Customer Impacts Entity Load Lost (MW) Customers SDGE 4,293 1.4 million CFE 2,150 2 150 1.1 1 1 million IID 929 146 thousand APS 389 70 thousand WALC 74 Note Note: 64 MWs of WALC s load loss affected APS s customers  Note: 64 MWs of WALC’s load loss affected APS’s customers 3 RELIABILITY | ACCOUNTABILITY
  • 4. Joint FERC/NERC Inquiry • Announced September 9, 2012 • Teams formed comprising over 30 senior technical staff of Teams formed comprising over 30 senior technical staff of  FERC and NERC, plus several NERC contractors and industry  subject matter experts • Multiple meetings and exchanges with affected entities to  gather facts • T Team products combined into final report d bi d i fi l • Outreach sessions to gain feedback on draft findings and  recommendations 4 RELIABILITY | ACCOUNTABILITY
  • 5. Inquiry Teams • Data Requests/Management • Sequence of Events Sequence of Events • Modeling/Simulation • Cause Analysis/Human Performance y / • Operations Tools/ SCADA/EMS • Frequency Analysis q y y • System Planning/Design • Equipment Performance/System Protection • Restoration 5 RELIABILITY | ACCOUNTABILITY
  • 6. Sequence of Events 6 RELIABILITY | ACCOUNTABILITY
  • 7. Simplified System Diagram Serrano Devers Palo Verde S-Corridor SONGS Path 44 Imperial WAPA Irrigation District Lower Hassayampa H 161 kV 92 kV Colorado H-NG SDG&E Corridor S-Line Miguel Imperial Valley North Gila CFE 7 RELIABILITY | ACCOUNTABILITY
  • 8. Phase 1 – Pre-Disturbance • Hot, shoulder season day; some generation and transmission outages • High loading on some key facilities: H-NG at 78% of normal rating; CV transformers at 83% • 44 minutes before loss of H-NG, IID’s RTCA results showed loss of CV 1 transformer would load CV-1 CV-2 transformer above its relay trip point • 15 27 39 APS t h i i 15:27:39: technician skipped a critical step in isolating the series capacitor bank at North Gila substation; H-NG trips ; p 8 RELIABILITY | ACCOUNTABILITY
  • 9. Phase 2 – Trip of H-NG 500 kV • H-NG 500 kV trips at 15:27:39 15:27:39 15:28:16 15 27 39 – 15 28 16 • APS tells WECC RC line expected to be restored quickly • H-NG flow redistributes: 77% Gf % to SCE-SDGE (Path 44); remainder to IID, and WALC • CV transformers immediately overloaded above relay settings • Path 44 at 5,900 amps; 8,000 amp limit on SONGS separation scheme p 9 RELIABILITY | ACCOUNTABILITY
  • 10. Initiating Event – Tripping of Hassayampa – North Gila 500 kV Line Series Capacitor Bypass Switch Arcs Over 10 RELIABILITY | ACCOUNTABILITY
  • 11. Hass. – N. Gila 500 kV Line Trip South of SONGS Current CCM Unit 1  generator trip Hassyampa – N. Gila 500 kV  line trip 11 RELIABILITY | ACCOUNTABILITY
  • 12. Phase 3 – Trip of CV Transformers • 15:28:16 – CV-2 and CV-1 230/92kV transformers trip on overload relays 15:28:16 15:32:10 15 28 16 – 15 32 10 • Severe low voltage in WALC 161 kV system • Loading on Path 44 increases to 6,700 amps 12 RELIABILITY | ACCOUNTABILITY
  • 13. CV Transformers Trip South of SONGS Current Coachella Valley  230/92 kV  transformers trip 13 RELIABILITY | ACCOUNTABILITY
  • 14. Phase 4 – Ramon Xfmr Trip • 15:32:10 Ramon 230/92kV transformer trips on overload relay 15:32:10 15:35:40 15 32 10 – 15 35 40 • 15:32:13 Blythe-Niland 161kV line trips • 15:32:15 Niland – CV 161kV line trips • IID undervoltage load shedding; loss of generation and 92 kV transmission lines • Severe low voltage in WALC 161 kV system t • Loading on Path 44 increases to 7,800 amps; , p ; settles at 7,200 amps 14 RELIABILITY | ACCOUNTABILITY
  • 15. Ramon Transformer Trip South of SONGS Current Voltage collapse in  l ll i pocket, followed  by load tripping Multiple line, generator  and load trips Ramon 230/92 kV  transformer  trip 15 RELIABILITY | ACCOUNTABILITY
  • 16. Voltage in Northern IID 92 kV System Over‐Voltage Trip  of 92 kV System  Capacitors Trip of Over 400  Ramon 230/92 kV  MW in Northern  Transformer Trip Transformer Trip IID 92 kV Load  IID 92 kV Load Pocket 16 RELIABILITY | ACCOUNTABILITY
  • 17. Blythe 161 kV Voltage Trip of Hassayampa  p y p El Centro – Pilot  El Centro Pilot – North Gila 500 kV  Knob 161 kV Line  Line Trip  Trip of Coachella  Valley 230/92 kV  Transformers  Yucca 161/69 kV  Transformers 1 and  2 Trip 2 Trip Trip of Over 400  Trip of Over 400 Ramon 230/92 kV  MW in Northern  Transformer Trip IID 92 kV Load  Pocket 17 RELIABILITY | ACCOUNTABILITY
  • 18. Phase 5 – Yuma Separates • Yuma AZ Separates from IID and WALC when Gila and Yucca transformers trip 15:35:40 15:37:55 15 35 40 – 15 37 55 • Yuma load pocket isolated on single tie to SDG&E • Loading on Path 44 increases to 7,400 amps after Gila transformer trip; to 7,800 amps after Yucca ft Y transformers and generator trip 18 RELIABILITY | ACCOUNTABILITY
  • 19. Yuma Separation South of SONGS Current YCA  generating  g g units trip Yucca 161/69 kV  Pilot Knob  transformers  trip 161/92 kV  transformers  trip Gila 161/69 kV  transformers  trip 19 RELIABILITY | ACCOUNTABILITY
  • 20. Phase 6 – High-Speed Cascade • El Centro – Pilot Knob 161kV line trips; all IID 92 kV system radial from SDG&E via S-Line 15:37:55 15 37 55 • WALC 161 kV system voltage returns to normal • Path 44 exceeds 8,000 amp setting and timer starts 20 RELIABILITY | ACCOUNTABILITY
  • 21. El Centro – Pilot Knob 161 kV Trips Early  Phase 4  activity Gila  transformers  trip Pilot Knob  transformers  trip Zone 3  pickup Yucca  transformers  trip 21 RELIABILITY | ACCOUNTABILITY
  • 22. Phase 6 – High-Speed Cascade • S-Line RAS trips IV generation and S-Line, isolating IID from SDG&E 15:37:58 15:38:02.4 15 37 58 – 15 38 02 4 • Path 44 loading increases to as high as 9,500 amps and reduces to 8,700 amps after isolating IID 22 RELIABILITY | ACCOUNTABILITY
  • 23. Phase 6 – High-Speed Cascade South of SONGS Current Imperial Valley  El  Imperial Valley – El Centro 230 kV  CLR  “S” line trip generating  units trip SONGS  separation i El Centro  – Pilot  Knob 161 kV line  trip 23 RELIABILITY | ACCOUNTABILITY
  • 24. Phase 6 – High-Speed Cascade • SONGS separation scheme operates; forms SDG&E, CFE, Yuma combined island 15:38:21.2 15 38 21 2 • Combined island frequency begins to collapse 24 RELIABILITY | ACCOUNTABILITY
  • 25. SONGS  separation SONGS Unit 3  electrically  disconnects SONGS Unit 2  electrically  disconnects SONGS  SONGS generators  ring down 25 RELIABILITY | ACCOUNTABILITY
  • 26. SONGS  SONGS separation SONGS Unit 2 GSU  trip and transfer of  SONGS aux load  aux load on startup  transformers SONGS  generators  ring down ring down SONGS Unit 3 GSU  trip and transfer of  aux load 26 RELIABILITY | ACCOUNTABILITY
  • 27. Phase 7 – S CA Separates • Yuma island separates from SDG&E when IV-NG 500 kV trips on underfrequency 15:38:23.12 15 38 23 12 • APS UFLS operates, but insufficient to stabilize load pocket • Yuma load pocket collapses 27 RELIABILITY | ACCOUNTABILITY
  • 28. UFLS Operations in the Island 28 RELIABILITY | ACCOUNTABILITY
  • 29. Voltage  Voltage peaks as tie  lines open SONGS  separation SDGE UFLS begins  SDGE ties to CFE and Yuma  shedding load open on underfrequency 29 RELIABILITY | ACCOUNTABILITY
  • 30. Phase 7 – CFE Separates • Underfrequency UFLS SDG&E and CFE continues 15:38:23.13 15 38 23 13 • CFE separates from SDG&E 30 RELIABILITY | ACCOUNTABILITY
  • 31. Actual vs. Simulated Frequency   31 RELIABILITY | ACCOUNTABILITY
  • 32. Phase 7 – Complete Blackout • IID, Yuma, SDG&E, and CFE blacked out By 15:38:38 B 15 38 38 32 RELIABILITY | ACCOUNTABILITY
  • 33. Use of PMUs in EA 33 RELIABILITY | ACCOUNTABILITY
  • 34. Sammis-Star Hard-Chamb Hard Chamb Star-S.Cant CantC-Tidd Hanna-Jun 2003 Blackout Simulations RELIABILITY | ACCOUNTABILITY 345 kV 345 kV 345 kV 345 kV 345 kV Dale-W.Can 138 kV W.Ak 138 kV Bkr Failure Cham-W.Ak 138 kV E.Lima-N.Fin 138 kV CantC Xfmr W.Ak-PV Q21 W 138 1 kV Outages Babb-W.Ak 138 kV E.Lima-N.Lib E 138 kV Clov-Torrey 138 kV Star-S.Cant 345 kV Hanna-Jun 345 kV Hard-Chamb 345 kV 34 140 120 100 80 60 40 20 0 Amps) % of Norma Ratings (A al
  • 35. PMU Data from SONGS 35 RELIABILITY | ACCOUNTABILITY
  • 36. 7 Phases of Event Trip or Gila 161/69 kV  Trip or Gila 161/69 kV Trip of Coachella  Transformers &  Valley 230/92 kV  Yuma Cogen Transformers Trip of Pilot Knob  161/92 kV & Yucca  161/69 kV  Trip of  Pilot  Transformers Knob – El  Trip of Hassayampa  Centro 161 kV  – North Gila 500 kV North Gila 500 kV  Line Line Trip of Ramon  South of SONGS  230/92 kV  / Separation Transformer 1 2 3 4 5 6 7 Disturbance Phases 36 RELIABILITY | ACCOUNTABILITY
  • 37. EA Modeling 37 RELIABILITY | ACCOUNTABILITY
  • 38. Simulation vs. Actual Flows South of SONGS Flows 4000 3500 3000 2500 MW 2000 1500 1000 500 0 15:27:30.240 15:28:56.640 15:30:23.040 15:31:49.440 15:33:15.840 15:34:42.240 15:36:08.640 15:37:35.040 Local Time (PDT) L l Ti (PDT) Simulated Actual (PMU) 38 RELIABILITY | ACCOUNTABILITY
  • 39. Inquiry Findings 39 RELIABILITY | ACCOUNTABILITY
  • 40. Key Findings Weaknesses in two broad areas: • Operations planning Operations planning • Real‐time situational awareness Contributing factors: Contributing factors: • Not studying impact of sub 100 kV facilities parallel to EHV • Failure to recognize IROLs Failure to recognize IROLs • Not studying/coordinating effects of protection systems and  RASs during contingency scenarios RASs during contingency scenarios • Not providing effective operator tools and instructions for  reclosing lines with large phase angle differences 40 RELIABILITY | ACCOUNTABILITY
  • 41. Operations Planning Failure to consider in seasonal, next‐day, and real‐time studies: • Status of external generation and transmission facilities Status of external generation and transmission facilities • Impact of external contingencies • Impacts on external systems p y • Impact on BPS of reliability of sub‐100 kV facilities parallel to  EHV system 41 RELIABILITY | ACCOUNTABILITY
  • 42. Operations Planning Recommended TOP/BA Improvements in WECC: • Obtain information on neighboring BAs and TOPs, including  g g , g transmission outages, generation outages and schedules, load  forecasts, and scheduled interchanges  • Identify and plan for external contingencies that could impact  Id tif d l f t l ti i th t ld i t their systems and internal contingencies that could impact  neighbors’ systems • Consider facilities operated at less than 100 kV parallel to EHV  system that could impact BPS reliability • Coordinated review of planning studies to ensure operation of  C di d i f l i di i f affected Rated Paths will not result in reliability problems 42 RELIABILITY | ACCOUNTABILITY
  • 43. Situational Awareness Recommended Improvements in WECC: • Expand entities’ external visibility in models through more  p y g complete data sharing • Improve use of real‐time tools to ensure constant monitoring of  potential internal or external contingencies t ti l i t l t l ti i • Improve communications among entities to help maintain  situational awareness situational awareness • TOPs should review their real‐time monitoring tools (State  Estimator and RTCA) to ensure critical facilities are represented 43 RELIABILITY | ACCOUNTABILITY
  • 44. System Protection Issues Recommendations: • IID and other TOs review transformer overload protection p relay settings • TOPs plan to take proper pre-contingency mitigation measures considering emergency ratings and overload id i ti d l d protection systems • All protection systems and separation schemes (Safety Nets, RAS, and SPS) studied and coordinated periodically to understand their impact on BPS reliability to ensure no unintended or undesirable effects 44 RELIABILITY | ACCOUNTABILITY
  • 45. Questions? 45 RELIABILITY | ACCOUNTABILITY