                          January 8, 2010



          Building Envelope Investigation

                        Property Address
                         3 Cross Lane
                   Isle of Palms, SC 29451

                      Report Ordered By:
                     Mr. Mickey Durham




57 Hasell Street Charleston, SC 29491 (LOCAL) 843.296.5006 (FAX) 843.746.4735
Project Information
               OWNER INFORMATION                                        BUYER INFORMATION
Owners                                                   Buyers                  N/A
Property Address        3 Cross Lane                     Buyers Address          N/A
City, State, ZIP        Isle of Palms, SC 29451          City, State, ZIP        N/A
Phone                   N/A                              Phone                   NA/
Builder                 N/A                              Buyers Realtor          N/A
Address                 N/A                              Realty Company          N/A
Phone                   N/A                              Phone                   N/A
FAX                     N/A                              FAX                     N/A

             PROPERTY INFORMATION                                    INSPECTION INFORMATION
Type of Exterior        Stucco                           Date of Inspection(s)   1/8/10
Substrate (if known)    ICF walls/CMU foundation         Inspector               MAM/JDT
Age of Property         2007                             Present at Inspection   N/A
Square Footage          4800                             Temperature / Humidity 45
Stories                 3                                Weather Conditions      Sunny
Type of Windows         vinyl                            Last Rain               1 day




                                       Inspection Test Equipment
        Test Equipment Description                             Test Range                        Setting
                                                      Low         Medium          High
 A Tramex Interior Moisture                          10-12         13-18         19-25                2
 B Tramex Exterior Wet Wall Detector                10 - 20        21-50        51-100               4.5
 C Delmorst Moisture Probe Meter                     10-15         16-25         26-99                2
 D Structural Resistance Tester (SRT) >44 = Pass <44 = Fail                             Higher is better
Important Note:
The test equipment is used to help locate problem areas. It must be understood that the test equipment is not an
exact science but rather good tools used as indicators of possible problems. At times, because of hidden
construction within the wall cavity, the meters get false readings or no readings at all. Some meters will pick up
on metals, wiring, unique wall finishes, etc. Positive readings do not always mean there is a problem, nor do
negative readings necessarily mean there is not a problem. We do not use the equipment to obtain exact moisture
content, but rather to obtain relative readings between suspected problem areas and non problem areas. This
information is then used to help determine potential problem areas which may warrant more investigation.
General Observations
Item Description                            Yes No   Improper                          Comments
Sealants at window perimeters               X           X       Most windows not sealed or existing sealants inadequate

Mitre joints (bottom corners) of                X
Alarm sensor penetrations at windows            X
Fixed window units and mullion joints           X
Head flashing at top of windows             X           X       Head flashing not properly installed

Sealants around door perimeter              X           X       Existing sealants not adequate or perimeters not sealed

Sealants at door threshold details              X               No pans or adequate weatherproofing

Penetrations thru door threshold / tracks       X
Head flashing at top of doors               X           X       Head flashing not properly installed

Penetrations through stucco sealed              X
General appearance                                              POOR

Cracking evident                            X                   Walls, floorline band, trim, dissimilar materials

Expansion joints / Control joints               X               Joints scored off windows-not true expansion joint

Exposed mesh                                X                   Walls, trim

Impact damage                               X                   Floorline band

Rusting aggregates                          X
                                                                Inadequate positive slope allowing water
Flat horizontal surfaces                    X                   intrusion/material degradation
Delamination / Fasteners                        X
Terminations and Vinyl accessories              X
Transition joints (stucco to brick, etc.)   X           X       Improper transition detail from CMU to wall framing

Termination below grade (ground level)      X           X       System to grade; EPS trim to grade

Termination below or at slab levels         X                   System flush to slab

Deck flashing                               X           X       Deck flashings improper or inadequate

Flashing at columns                             X
Kick-out flashing                               X
Roof soffit terminations into stucco            X               No eaves
General Observations Cont.....
Eave drip edge flashing               X
Sprinkler System                      X
Gutters                               X        Gutters should be added to help divert water flow
Front Elevation




 Grid         Item       Moisture                                                            Chapter
                                    Detail Photo                 Observations
Location   Description   Readings                                                           Reference
           System                  Stucco improperly butted flush with porch-should
  6D                      N/A          N/A
            term                   have 2" reveal and flashing as required by code.
                  Rot              Improper flashing on windows/doors allowing water
  5E   Openings             2.5
                 Inside            ingress into wall cavity
                                   Red shaded areas indicate elevated readings around all
 Red
       Moisture Saturated 3.6, 3.8 openings collected on interior moisture
shaded                             scanning-severe damage observed from extensive
Right Elevation




 Grid         Item       Moisture                                                                        Chapter
                                    Detail Photo                        Observations
Location   Description   Readings                                                                       Reference
                                                   Improper flashing detail at wall/foundation
  6F       Flashing       N/A        2.1-2.2       intersection allowing water ingress and subsequent
  2B       Columns    N/A              N/A         No column cap flashing as required
 Red       Interior 2.0-5.0+                       Elevated moisture/damage observed on most openings
                                       4.4
shaded     Moisture    %                           during interior inspection
Rear Elevation #1




 Grid         Item       Moisture                                                                            Chapter
                                    Detail Photo                         Observations
Location   Description   Readings                                                                           Reference

  6C          Rot        40%+          2.6         Severe wood brick mold trim rot/damage
             Light
  4C                      N/A          N/A         No sealant on penetrations through wall system
            Fixture
                                                   Intersection of foundation/framing system requires
  7G       Floorline      N/A          2.1         weep screed to allow water egress-none installed as
 Red   Interior                                    3 red shaded areas indicate interior elevated moisture
                         2-5%          3.8
Shaded Moisture                                    readings (2-5%) with damage.
Rear Elevation #2




 Grid         Item       Moisture                                                                           Chapter
                                    Detail Photo                        Observations
Location   Description   Readings                                                                          Reference
                                                   Improper joint detail around ALL openings in
  3F       Windows Saturated           N/A         violation of applicable building codes and
 Red                                               Red shaded area indicates elevated moisture on
           Moisture Saturated          N/A
shaded                                             interior walls arounf openings with extensive damage.
Left Elevation




 Grid         Item       Moisture                                                                        Chapter
                                    Detail Photo                    Observations
Location   Description   Readings                                                                       Reference

                                              Foam bands improperly butted flush with grade with
           System
  8I                      40+%         2.2    inadequate weatherproofing-subsequent termite
            Term
                                              infestation and damage
                                              Inadequate/improper flashing at all deck/porch
  6E         Deck        Elevated      N/A
                                              intersections.
             Roof                             Improper/inadequate flashing at roof/wall
  2F                  N/A            6.5, 6.6
           Flashing                           intersections allowing water intrusion.
 Red       Interior                           Red shaded areas indicates water intrusion and interior
                    Saturated        3.1-3.4 severe interior damage to window frame rough
shaded     Moisture
Exterior Deficiencies #1




Photo 1.1- Stucco improperly butted flush to   1.2- No head flashing installed on some
wood casing with adhesive sealant failure      window headers as required by building
(roof deck door).                              code.




1.3- Separation on brick mold miters           1.4- Severe threshold/frame/wood floor
allowing water intrusion.                      damage caused by improper
                                               joint/construction details.




1.5- Severe material contamination and         1.6- Separation between dissimilar materials
failure of wall system components around       where water has breached the building
front garage door entry.                       envelope--caused by improper joint detail.
Exterior Deficiencies #2




Photo 2.1- Improper flashing detail at          2.2- Note severe termite damage to EPS
foundation/wall intersection. Code requires a   foam bands from tunneling activity to access
weep screed for H2O egress at this location.    wood components.




2.3- Exposed reinforcing fiberglass mesh        2.4- Note EIFS lamina damage and exposed
observed on aesthetic expansion joints-poor     system components.
workmanship.




2.5- Head flashing was attempted on some        2.6- Severe wood damage and rot on rear
openings, but improperly installed and in       elevation kitchen door from substandard
violation of building code.                     workmanship and inferior construction.
Interior Deficiencies/Damage #1




Photo 3.1- Extensive/severe      3.2- Complete framing failure   3.3- Damage is so severe that
water damage and termite         around openings caused by       all windows and doors will
infestation to interior window   termite infestation into wet    require removal and
wood trim.                       wood components.                replacement to properly
                                                                 remediate.




3.4- Termites use the foam       3.5- Substantial drywall        3.6- Window sill damage was
employed to insulate walls as    damage with saturated           prevalent throughout the
a tunneling mechanism to         conditions adjacent to side     interior as a result of
access moist wood.               deck door.                      improper construction.




3.7- Damage was also             3.8- Rough opening frame        3.9- Note complete framing
observed on baseboards from      and window damage.              failure around openings with
water migration and                                              visible termite
contamination.                                                   nesting/infestation.
Interior Deficiencies/Damage #2




Photo 4.1- Black mold,          4.2- Water intrusion created     4.3- Third location on third
possibly toxic stachybotrys,    climate conducive to mold        floor where mold growth was
was observed on third floor     growth observed in numerous      observed-complete removal
ceilings in drywall material.   locations.                       and replacement of
                                                                 contaminated drywall.




4.4- Note extensive water       4.5- Termite infestation to      4.6- Note water stain on floor
damage to interior window       crown mold trim on interior      caused by excessive water
trim on front elevation         window headers.                  infiltration as a result of poor
window.                                                          construction details.




4.7- Significant damage to      4.8- Concrete sub-floors         4.9- Haphazardly applied
wood flooring from moisture     observed under hardwood          caulk joint around electrical
ingress/contamination at door   material will be beneficial in   attachments.
threshold.                      remediation since no
                                deterioration is possible.
Basement Deficiencies/Damage




Photo 5.1- Black mold observed in                5.2- All contaminated basement drywall
basement drywall material from water             must be removed and replaced at the time of
infiltration.                                    remediation.




5.3- Note water stain on concrete floor at the   5.4- Mold growth and water intrusion at
grade intersection.                              slab/CMU intersection.




5.5- Note visible water stains in block from     5.6- Toxic black stachybotrys mold is
water ingress and extensive building             suspected and was observed in both ceilings
envelope failure.                                and walls (basement).
Roof Deficiencies/Damage




Photo 6.1-Note standing/ponding water on       6.2- Second location of standing water on
roof-should have positive slope.               roof decking-recent rain prior to inspection.




6.3- Waterproofing delamination caused by      6.4- Waterproofing system failure over cant
improper system installation and inadequate    strip installations at roof/wall intersections.
construction details.




6.5- Improper/inadequate flashing detail       6.6- Roof/wall flashing improperly installed
allowing to breach system at roof/vertical     and allowing water to penetrate under
wall intersection(s).                          flashing details.
CONCLUSION:
The purpose of this investigation was to determine the source of extensive water infiltration and
extent of subsequent damage as requested by the client. This home was completed in 2007 and
built by Carolina Concrete Homes, Inc. Typically, one may expect the framing system to be
wood with a sheathing on the outside to attach the siding. However, ICF (insulated concrete
form) construction was employed on the subject structure. Concrete is poured into a cavity
between two layers (outside and inside) of extruded or expanded polystyrene with reinforcements.
Since concrete will not "rot", this wall system is attractive for its integrity and thermal values.
However, ALL wall systems must be installed in accordance with applicable building codes and
design specifications in order to restrict water ingress. Our investigation revealed complete system
failure and extensive water and termite damage as a result of improper construction.

  Our pre-inspection protocol included a complete visual inspection of the entire structure, both
  interior and exterior. Visual examination of the interior revealed a number of locations where
  visible staining and damage of building materials was evident, indicating water ingress into the
  building envelope (or shell). Testing for moisture content is accomplished with several moisture
  meters, both invasive and non-invasive, which included scanning all interior walls to obtain a
  relative moisture content. Any indications of problem areas identified with moisture scanners
  are investigated further with a probe meter to ascertain a definitive moisture content. Any
  readings in wood above 20% or 1.0% in sheetrock indicate a potential problem usually
  associated with exposure of the building material to moisture from water breaching the
  envelope.

  The CABO building code R703.8, section 1 which states flashing must be installed "At the top of
  all exterior windows and doors in such a manner as to be leakproof" The 2003 (and later
  editions) International Building Code, section 1405.2 requires that all "exterior walls shall
  provide weather protection for the building". Additionally, section 1405.3.2 states that flashing
  and weepholes be installed at the system termination and structural floors, thus allowing
  incidental water infiltration to egress the wall cavity. The contractor omitted the required
  flashing detail at system terminations, floorlines, roof intersections and openings. Furthermore,
  NO construction sealant was applied on any of the exterior walls at intersections of dissimilar
  materials to prevent water intrusion. Consequently, water has already penetrated the exterior
  and contaminated underlying building materials. Additionally, severe termite damage to both
  the foam wall material and wood framing for openings was identified. The termites use the
  foam as a tunneling mechanism in order to access moist wood members. The foam should not
  come within 6" of grade level in order to prevent termite infestation. The contractor installed
  the foam flush with grade, thus allowing bug infestation. Moreover, over fifteen (15) violations
  of application standards relating to the stucco system were also detected, which all deviate from
"industry standards" and good construction practices. ALL code violations and application
deficiencies which were detected during this inspection have left the structure susceptible
to severe water ingress and subsequent building envelope failure. Consequently, the entire
exterior cladding must be removed and replaced during remediation to correct the inherently
defective design which currently exists on the subject structure. I have compiled and included a
scope of work to remediate all contaminated building materials and construction deficiencies as
requested. If you have any questions or comments concerning this report, please feel free to
contact my office.


Respectfully,



James D. Thompson
President
SC Property Pros
SCOPE OF WORK



· General Requirements--Permitting, Site Prep, Waste Disposal, Insurance etc

· Site Construction- Landscape, Scaffold

· Exterior-- Removal of exterior, windows, doors, attachments, obstructions
  -- New doors provided, solid vinyl windows to be re-used
  -- Code compliant weatherproofing/flashing
  -- Install code compliant water management/drainable stucco system
  -- Install five coat waterproofing systems on all decks and roof
  -- Install new roof
  -- Exterior paint


· Interior-- Removal and replacement of all 1st floor finishes
  -- Removal and replacement of second floor exterior walls
  -- Removal and replace of damaged flooring
  -- Repair staircase and replace contaminated treads and risers on all 4
              floors
  -- EPA compliant mold remediation
  -- Install drywall and paint
  -- Cabinets, counter tops, light and plumbing fixtures to be reinstalled

                          Cost of Construction -- $284,786


If you need a more detailed cost break-down, please feel free to contact me.

Weitere ähnliche Inhalte

Ähnlich wie Inspection Report

2011 samplereport
2011 samplereport2011 samplereport
2011 samplereportInspectPro
 
2012 sample report 50year old house
2012 sample report 50year old house2012 sample report 50year old house
2012 sample report 50year old housetk99
 
Apex Inspections Sample Report 2010
Apex Inspections Sample Report 2010Apex Inspections Sample Report 2010
Apex Inspections Sample Report 2010orderinspections
 
House Inspection Report
House Inspection ReportHouse Inspection Report
House Inspection Reportpnnazz
 
2012 sample report 50-55 year old house
2012 sample report 50-55 year old house2012 sample report 50-55 year old house
2012 sample report 50-55 year old housetk99
 
8333 Montgomery St.
8333 Montgomery St.8333 Montgomery St.
8333 Montgomery St.danfreeus
 
Elements Of A Masonry Forensic Investigation Ryan Biggs
Elements Of A Masonry Forensic Investigation Ryan BiggsElements Of A Masonry Forensic Investigation Ryan Biggs
Elements Of A Masonry Forensic Investigation Ryan BiggsMartin Demarest
 
Commercial Flat Roofing: Components and Damage Assessment
Commercial Flat Roofing: Components and Damage AssessmentCommercial Flat Roofing: Components and Damage Assessment
Commercial Flat Roofing: Components and Damage AssessmentDenis Koval
 

Ähnlich wie Inspection Report (12)

2011 samplereport
2011 samplereport2011 samplereport
2011 samplereport
 
2012 sample report 50year old house
2012 sample report 50year old house2012 sample report 50year old house
2012 sample report 50year old house
 
Apex Inspections Sample Report 2010
Apex Inspections Sample Report 2010Apex Inspections Sample Report 2010
Apex Inspections Sample Report 2010
 
Apex sample report
Apex sample reportApex sample report
Apex sample report
 
House Inspection Report
House Inspection ReportHouse Inspection Report
House Inspection Report
 
2012 sample report 50-55 year old house
2012 sample report 50-55 year old house2012 sample report 50-55 year old house
2012 sample report 50-55 year old house
 
8333 Montgomery St.
8333 Montgomery St.8333 Montgomery St.
8333 Montgomery St.
 
Elements Of A Masonry Forensic Investigation Ryan Biggs
Elements Of A Masonry Forensic Investigation Ryan BiggsElements Of A Masonry Forensic Investigation Ryan Biggs
Elements Of A Masonry Forensic Investigation Ryan Biggs
 
Commercial Flat Roofing: Components and Damage Assessment
Commercial Flat Roofing: Components and Damage AssessmentCommercial Flat Roofing: Components and Damage Assessment
Commercial Flat Roofing: Components and Damage Assessment
 
Example
ExampleExample
Example
 
Standard House
Standard HouseStandard House
Standard House
 
Atlanta Sample Home Inspection Report
Atlanta Sample Home Inspection ReportAtlanta Sample Home Inspection Report
Atlanta Sample Home Inspection Report
 

Mehr von South Carolina Property Pros (16)

West ashley-parks-map
West ashley-parks-mapWest ashley-parks-map
West ashley-parks-map
 
Sc counties
Sc countiesSc counties
Sc counties
 
Northchasmap
NorthchasmapNorthchasmap
Northchasmap
 
Kiawah map
Kiawah mapKiawah map
Kiawah map
 
Johns island-parks-map
Johns island-parks-mapJohns island-parks-map
Johns island-parks-map
 
James island-parks-map
James island-parks-mapJames island-parks-map
James island-parks-map
 
Greater charleston-area-map
Greater charleston-area-mapGreater charleston-area-map
Greater charleston-area-map
 
Edisto island map
Edisto island mapEdisto island map
Edisto island map
 
Downtown charleston-parks-map
Downtown charleston-parks-mapDowntown charleston-parks-map
Downtown charleston-parks-map
 
Daniel island northmap
Daniel island northmapDaniel island northmap
Daniel island northmap
 
Daniel island downtown
Daniel island downtownDaniel island downtown
Daniel island downtown
 
Chaspenmap
ChaspenmapChaspenmap
Chaspenmap
 
Activitiesmap
ActivitiesmapActivitiesmap
Activitiesmap
 
Flashing 101 by The SC Property Pros Charleston SC
Flashing 101 by The SC Property Pros Charleston SCFlashing 101 by The SC Property Pros Charleston SC
Flashing 101 by The SC Property Pros Charleston SC
 
Government Affairs Tax Credit Ext Chart
Government Affairs Tax Credit Ext ChartGovernment Affairs Tax Credit Ext Chart
Government Affairs Tax Credit Ext Chart
 
Stucco Installation Report
Stucco Installation ReportStucco Installation Report
Stucco Installation Report
 

Kürzlich hochgeladen

西伦敦大学毕业证学位证成绩单-怎么样做
西伦敦大学毕业证学位证成绩单-怎么样做西伦敦大学毕业证学位证成绩单-怎么样做
西伦敦大学毕业证学位证成绩单-怎么样做j5bzwet6
 
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...Authentic No 1 Amil Baba In Pakistan
 
(南达科他州立大学毕业证学位证成绩单-永久存档)
(南达科他州立大学毕业证学位证成绩单-永久存档)(南达科他州立大学毕业证学位证成绩单-永久存档)
(南达科他州立大学毕业证学位证成绩单-永久存档)oannq
 
南新罕布什尔大学毕业证学位证成绩单-学历认证
南新罕布什尔大学毕业证学位证成绩单-学历认证南新罕布什尔大学毕业证学位证成绩单-学历认证
南新罕布什尔大学毕业证学位证成绩单-学历认证kbdhl05e
 
(No.1)↠Young Call Girls in Sikanderpur (Gurgaon) ꧁❤ 9711911712 ❤꧂ Escorts
(No.1)↠Young Call Girls in Sikanderpur (Gurgaon) ꧁❤ 9711911712 ❤꧂ Escorts(No.1)↠Young Call Girls in Sikanderpur (Gurgaon) ꧁❤ 9711911712 ❤꧂ Escorts
(No.1)↠Young Call Girls in Sikanderpur (Gurgaon) ꧁❤ 9711911712 ❤꧂ EscortsDelhi Escorts Service
 
Call Girls In Karkardooma 83770 87607 Just-Dial Escorts Service 24X7 Avilable
Call Girls In Karkardooma 83770 87607 Just-Dial Escorts Service 24X7 AvilableCall Girls In Karkardooma 83770 87607 Just-Dial Escorts Service 24X7 Avilable
Call Girls In Karkardooma 83770 87607 Just-Dial Escorts Service 24X7 Avilabledollysharma2066
 
E J Waggoner against Kellogg's Pantheism 8.pptx
E J Waggoner against Kellogg's Pantheism 8.pptxE J Waggoner against Kellogg's Pantheism 8.pptx
E J Waggoner against Kellogg's Pantheism 8.pptxJackieSparrow3
 
Inspiring Through Words Power of Inspiration.pptx
Inspiring Through Words Power of Inspiration.pptxInspiring Through Words Power of Inspiration.pptx
Inspiring Through Words Power of Inspiration.pptxShubham Rawat
 

Kürzlich hochgeladen (9)

西伦敦大学毕业证学位证成绩单-怎么样做
西伦敦大学毕业证学位证成绩单-怎么样做西伦敦大学毕业证学位证成绩单-怎么样做
西伦敦大学毕业证学位证成绩单-怎么样做
 
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
Authentic No 1 Amil Baba In Pakistan Amil Baba In Faisalabad Amil Baba In Kar...
 
(南达科他州立大学毕业证学位证成绩单-永久存档)
(南达科他州立大学毕业证学位证成绩单-永久存档)(南达科他州立大学毕业证学位证成绩单-永久存档)
(南达科他州立大学毕业证学位证成绩单-永久存档)
 
Model Call Girl in Lado Sarai Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Lado Sarai Delhi reach out to us at 🔝9953056974🔝Model Call Girl in Lado Sarai Delhi reach out to us at 🔝9953056974🔝
Model Call Girl in Lado Sarai Delhi reach out to us at 🔝9953056974🔝
 
南新罕布什尔大学毕业证学位证成绩单-学历认证
南新罕布什尔大学毕业证学位证成绩单-学历认证南新罕布什尔大学毕业证学位证成绩单-学历认证
南新罕布什尔大学毕业证学位证成绩单-学历认证
 
(No.1)↠Young Call Girls in Sikanderpur (Gurgaon) ꧁❤ 9711911712 ❤꧂ Escorts
(No.1)↠Young Call Girls in Sikanderpur (Gurgaon) ꧁❤ 9711911712 ❤꧂ Escorts(No.1)↠Young Call Girls in Sikanderpur (Gurgaon) ꧁❤ 9711911712 ❤꧂ Escorts
(No.1)↠Young Call Girls in Sikanderpur (Gurgaon) ꧁❤ 9711911712 ❤꧂ Escorts
 
Call Girls In Karkardooma 83770 87607 Just-Dial Escorts Service 24X7 Avilable
Call Girls In Karkardooma 83770 87607 Just-Dial Escorts Service 24X7 AvilableCall Girls In Karkardooma 83770 87607 Just-Dial Escorts Service 24X7 Avilable
Call Girls In Karkardooma 83770 87607 Just-Dial Escorts Service 24X7 Avilable
 
E J Waggoner against Kellogg's Pantheism 8.pptx
E J Waggoner against Kellogg's Pantheism 8.pptxE J Waggoner against Kellogg's Pantheism 8.pptx
E J Waggoner against Kellogg's Pantheism 8.pptx
 
Inspiring Through Words Power of Inspiration.pptx
Inspiring Through Words Power of Inspiration.pptxInspiring Through Words Power of Inspiration.pptx
Inspiring Through Words Power of Inspiration.pptx
 

Inspection Report

  • 1. Website:www.scpropertypros.com E-Mail:jdt@scpropertypros.com January 8, 2010 Building Envelope Investigation Property Address 3 Cross Lane Isle of Palms, SC 29451 Report Ordered By: Mr. Mickey Durham 57 Hasell Street Charleston, SC 29491 (LOCAL) 843.296.5006 (FAX) 843.746.4735
  • 2. Project Information OWNER INFORMATION BUYER INFORMATION Owners Buyers N/A Property Address 3 Cross Lane Buyers Address N/A City, State, ZIP Isle of Palms, SC 29451 City, State, ZIP N/A Phone N/A Phone NA/ Builder N/A Buyers Realtor N/A Address N/A Realty Company N/A Phone N/A Phone N/A FAX N/A FAX N/A PROPERTY INFORMATION INSPECTION INFORMATION Type of Exterior Stucco Date of Inspection(s) 1/8/10 Substrate (if known) ICF walls/CMU foundation Inspector MAM/JDT Age of Property 2007 Present at Inspection N/A Square Footage 4800 Temperature / Humidity 45 Stories 3 Weather Conditions Sunny Type of Windows vinyl Last Rain 1 day Inspection Test Equipment Test Equipment Description Test Range Setting Low Medium High A Tramex Interior Moisture 10-12 13-18 19-25 2 B Tramex Exterior Wet Wall Detector 10 - 20 21-50 51-100 4.5 C Delmorst Moisture Probe Meter 10-15 16-25 26-99 2 D Structural Resistance Tester (SRT) >44 = Pass <44 = Fail Higher is better Important Note: The test equipment is used to help locate problem areas. It must be understood that the test equipment is not an exact science but rather good tools used as indicators of possible problems. At times, because of hidden construction within the wall cavity, the meters get false readings or no readings at all. Some meters will pick up on metals, wiring, unique wall finishes, etc. Positive readings do not always mean there is a problem, nor do negative readings necessarily mean there is not a problem. We do not use the equipment to obtain exact moisture content, but rather to obtain relative readings between suspected problem areas and non problem areas. This information is then used to help determine potential problem areas which may warrant more investigation.
  • 3. General Observations Item Description Yes No Improper Comments Sealants at window perimeters X X Most windows not sealed or existing sealants inadequate Mitre joints (bottom corners) of X Alarm sensor penetrations at windows X Fixed window units and mullion joints X Head flashing at top of windows X X Head flashing not properly installed Sealants around door perimeter X X Existing sealants not adequate or perimeters not sealed Sealants at door threshold details X No pans or adequate weatherproofing Penetrations thru door threshold / tracks X Head flashing at top of doors X X Head flashing not properly installed Penetrations through stucco sealed X General appearance POOR Cracking evident X Walls, floorline band, trim, dissimilar materials Expansion joints / Control joints X Joints scored off windows-not true expansion joint Exposed mesh X Walls, trim Impact damage X Floorline band Rusting aggregates X Inadequate positive slope allowing water Flat horizontal surfaces X intrusion/material degradation Delamination / Fasteners X Terminations and Vinyl accessories X Transition joints (stucco to brick, etc.) X X Improper transition detail from CMU to wall framing Termination below grade (ground level) X X System to grade; EPS trim to grade Termination below or at slab levels X System flush to slab Deck flashing X X Deck flashings improper or inadequate Flashing at columns X Kick-out flashing X Roof soffit terminations into stucco X No eaves
  • 4. General Observations Cont..... Eave drip edge flashing X Sprinkler System X Gutters X Gutters should be added to help divert water flow
  • 5. Front Elevation Grid Item Moisture Chapter Detail Photo Observations Location Description Readings Reference System Stucco improperly butted flush with porch-should 6D N/A N/A term have 2" reveal and flashing as required by code. Rot Improper flashing on windows/doors allowing water 5E Openings 2.5 Inside ingress into wall cavity Red shaded areas indicate elevated readings around all Red Moisture Saturated 3.6, 3.8 openings collected on interior moisture shaded scanning-severe damage observed from extensive
  • 6. Right Elevation Grid Item Moisture Chapter Detail Photo Observations Location Description Readings Reference Improper flashing detail at wall/foundation 6F Flashing N/A 2.1-2.2 intersection allowing water ingress and subsequent 2B Columns N/A N/A No column cap flashing as required Red Interior 2.0-5.0+ Elevated moisture/damage observed on most openings 4.4 shaded Moisture % during interior inspection
  • 7. Rear Elevation #1 Grid Item Moisture Chapter Detail Photo Observations Location Description Readings Reference 6C Rot 40%+ 2.6 Severe wood brick mold trim rot/damage Light 4C N/A N/A No sealant on penetrations through wall system Fixture Intersection of foundation/framing system requires 7G Floorline N/A 2.1 weep screed to allow water egress-none installed as Red Interior 3 red shaded areas indicate interior elevated moisture 2-5% 3.8 Shaded Moisture readings (2-5%) with damage.
  • 8. Rear Elevation #2 Grid Item Moisture Chapter Detail Photo Observations Location Description Readings Reference Improper joint detail around ALL openings in 3F Windows Saturated N/A violation of applicable building codes and Red Red shaded area indicates elevated moisture on Moisture Saturated N/A shaded interior walls arounf openings with extensive damage.
  • 9. Left Elevation Grid Item Moisture Chapter Detail Photo Observations Location Description Readings Reference Foam bands improperly butted flush with grade with System 8I 40+% 2.2 inadequate weatherproofing-subsequent termite Term infestation and damage Inadequate/improper flashing at all deck/porch 6E Deck Elevated N/A intersections. Roof Improper/inadequate flashing at roof/wall 2F N/A 6.5, 6.6 Flashing intersections allowing water intrusion. Red Interior Red shaded areas indicates water intrusion and interior Saturated 3.1-3.4 severe interior damage to window frame rough shaded Moisture
  • 10. Exterior Deficiencies #1 Photo 1.1- Stucco improperly butted flush to 1.2- No head flashing installed on some wood casing with adhesive sealant failure window headers as required by building (roof deck door). code. 1.3- Separation on brick mold miters 1.4- Severe threshold/frame/wood floor allowing water intrusion. damage caused by improper joint/construction details. 1.5- Severe material contamination and 1.6- Separation between dissimilar materials failure of wall system components around where water has breached the building front garage door entry. envelope--caused by improper joint detail.
  • 11. Exterior Deficiencies #2 Photo 2.1- Improper flashing detail at 2.2- Note severe termite damage to EPS foundation/wall intersection. Code requires a foam bands from tunneling activity to access weep screed for H2O egress at this location. wood components. 2.3- Exposed reinforcing fiberglass mesh 2.4- Note EIFS lamina damage and exposed observed on aesthetic expansion joints-poor system components. workmanship. 2.5- Head flashing was attempted on some 2.6- Severe wood damage and rot on rear openings, but improperly installed and in elevation kitchen door from substandard violation of building code. workmanship and inferior construction.
  • 12. Interior Deficiencies/Damage #1 Photo 3.1- Extensive/severe 3.2- Complete framing failure 3.3- Damage is so severe that water damage and termite around openings caused by all windows and doors will infestation to interior window termite infestation into wet require removal and wood trim. wood components. replacement to properly remediate. 3.4- Termites use the foam 3.5- Substantial drywall 3.6- Window sill damage was employed to insulate walls as damage with saturated prevalent throughout the a tunneling mechanism to conditions adjacent to side interior as a result of access moist wood. deck door. improper construction. 3.7- Damage was also 3.8- Rough opening frame 3.9- Note complete framing observed on baseboards from and window damage. failure around openings with water migration and visible termite contamination. nesting/infestation.
  • 13. Interior Deficiencies/Damage #2 Photo 4.1- Black mold, 4.2- Water intrusion created 4.3- Third location on third possibly toxic stachybotrys, climate conducive to mold floor where mold growth was was observed on third floor growth observed in numerous observed-complete removal ceilings in drywall material. locations. and replacement of contaminated drywall. 4.4- Note extensive water 4.5- Termite infestation to 4.6- Note water stain on floor damage to interior window crown mold trim on interior caused by excessive water trim on front elevation window headers. infiltration as a result of poor window. construction details. 4.7- Significant damage to 4.8- Concrete sub-floors 4.9- Haphazardly applied wood flooring from moisture observed under hardwood caulk joint around electrical ingress/contamination at door material will be beneficial in attachments. threshold. remediation since no deterioration is possible.
  • 14. Basement Deficiencies/Damage Photo 5.1- Black mold observed in 5.2- All contaminated basement drywall basement drywall material from water must be removed and replaced at the time of infiltration. remediation. 5.3- Note water stain on concrete floor at the 5.4- Mold growth and water intrusion at grade intersection. slab/CMU intersection. 5.5- Note visible water stains in block from 5.6- Toxic black stachybotrys mold is water ingress and extensive building suspected and was observed in both ceilings envelope failure. and walls (basement).
  • 15. Roof Deficiencies/Damage Photo 6.1-Note standing/ponding water on 6.2- Second location of standing water on roof-should have positive slope. roof decking-recent rain prior to inspection. 6.3- Waterproofing delamination caused by 6.4- Waterproofing system failure over cant improper system installation and inadequate strip installations at roof/wall intersections. construction details. 6.5- Improper/inadequate flashing detail 6.6- Roof/wall flashing improperly installed allowing to breach system at roof/vertical and allowing water to penetrate under wall intersection(s). flashing details.
  • 16. CONCLUSION: The purpose of this investigation was to determine the source of extensive water infiltration and extent of subsequent damage as requested by the client. This home was completed in 2007 and built by Carolina Concrete Homes, Inc. Typically, one may expect the framing system to be wood with a sheathing on the outside to attach the siding. However, ICF (insulated concrete form) construction was employed on the subject structure. Concrete is poured into a cavity between two layers (outside and inside) of extruded or expanded polystyrene with reinforcements. Since concrete will not "rot", this wall system is attractive for its integrity and thermal values. However, ALL wall systems must be installed in accordance with applicable building codes and design specifications in order to restrict water ingress. Our investigation revealed complete system failure and extensive water and termite damage as a result of improper construction. Our pre-inspection protocol included a complete visual inspection of the entire structure, both interior and exterior. Visual examination of the interior revealed a number of locations where visible staining and damage of building materials was evident, indicating water ingress into the building envelope (or shell). Testing for moisture content is accomplished with several moisture meters, both invasive and non-invasive, which included scanning all interior walls to obtain a relative moisture content. Any indications of problem areas identified with moisture scanners are investigated further with a probe meter to ascertain a definitive moisture content. Any readings in wood above 20% or 1.0% in sheetrock indicate a potential problem usually associated with exposure of the building material to moisture from water breaching the envelope. The CABO building code R703.8, section 1 which states flashing must be installed "At the top of all exterior windows and doors in such a manner as to be leakproof" The 2003 (and later editions) International Building Code, section 1405.2 requires that all "exterior walls shall provide weather protection for the building". Additionally, section 1405.3.2 states that flashing and weepholes be installed at the system termination and structural floors, thus allowing incidental water infiltration to egress the wall cavity. The contractor omitted the required flashing detail at system terminations, floorlines, roof intersections and openings. Furthermore, NO construction sealant was applied on any of the exterior walls at intersections of dissimilar materials to prevent water intrusion. Consequently, water has already penetrated the exterior and contaminated underlying building materials. Additionally, severe termite damage to both the foam wall material and wood framing for openings was identified. The termites use the foam as a tunneling mechanism in order to access moist wood members. The foam should not come within 6" of grade level in order to prevent termite infestation. The contractor installed the foam flush with grade, thus allowing bug infestation. Moreover, over fifteen (15) violations of application standards relating to the stucco system were also detected, which all deviate from
  • 17. "industry standards" and good construction practices. ALL code violations and application deficiencies which were detected during this inspection have left the structure susceptible to severe water ingress and subsequent building envelope failure. Consequently, the entire exterior cladding must be removed and replaced during remediation to correct the inherently defective design which currently exists on the subject structure. I have compiled and included a scope of work to remediate all contaminated building materials and construction deficiencies as requested. If you have any questions or comments concerning this report, please feel free to contact my office. Respectfully, James D. Thompson President SC Property Pros
  • 18. SCOPE OF WORK · General Requirements--Permitting, Site Prep, Waste Disposal, Insurance etc · Site Construction- Landscape, Scaffold · Exterior-- Removal of exterior, windows, doors, attachments, obstructions -- New doors provided, solid vinyl windows to be re-used -- Code compliant weatherproofing/flashing -- Install code compliant water management/drainable stucco system -- Install five coat waterproofing systems on all decks and roof -- Install new roof -- Exterior paint · Interior-- Removal and replacement of all 1st floor finishes -- Removal and replacement of second floor exterior walls -- Removal and replace of damaged flooring -- Repair staircase and replace contaminated treads and risers on all 4 floors -- EPA compliant mold remediation -- Install drywall and paint -- Cabinets, counter tops, light and plumbing fixtures to be reinstalled Cost of Construction -- $284,786 If you need a more detailed cost break-down, please feel free to contact me.