SlideShare ist ein Scribd-Unternehmen logo
1 von 42
Pilot Protection
of
Transmission Lines

By
Suraj K
Sumanth V
Kiran R
Outline
•
•
•
•
•
•

Transmission line introduction
Typical protection schemes
Need for pilot aided schemes
Various pilot schemes
Redundancy considerations
Desirable attributes of pilot relay
Transmission Lines
• A Vital Part of the Power System:
• Provide path to transfer power between generation and load
• Operate at voltage levels from 69kV to 765kV
• Deregulated markets, economic, environmental requirements
have pushed utilities to operate transmission lines close to their
limits.
Transmission Lines
• Classification of line length depends on:
 Source-to-line Impedance Ratio (SIR), and
 Nominal voltage

• Length considerations:
 Short Lines: SIR > 4
 Medium Lines: 0.5 < SIR < 4
 Long Lines: SIR < 0.5
Typical Protection Schemes
Short Lines
•
•
•
•

Current differential
Phase comparison
Permissive Overreach Transfer Trip (POTT)
Directional Comparison Blocking (DCB)
Typical Protection Schemes
Medium Lines

• Phase comparison
• Directional Comparison Blocking (DCB)
• Permissive Underreach Transfer Trip (PUTT)
• Permissive Overreach Transfer Trip (POTT)
• Unblocking
• Step Distance
• Step or coordinated overcurrent
• Inverse time overcurrent
• Current Differential
Typical Protection Schemes
Long Lines

• Phase comparison
• Directional Comparison Blocking (DCB)
• Permissive Underreach Transfer Trip (PUTT)
• Permissive Overreach Transfer Trip (POTT)
• Unblocking
• Step Distance
• Step or coordinated overcurrent
• Current Differential
Introduction
• Nonpilot protection using overcurrent and distance relays, contain a
fundamental difficulty :
It is not possible to instantaneously clear a fault from both ends
of a transmission line if the fault is near one end of the line.
• Pilot protection is an adaptation of the principles of differential
relaying that avoids the use of control cable between terminals.
• The term ‘pilot’ refers to a communication channel between two or
more ends of a transmission line to provide instantaneous clearing
over 100% of the line.
• This form of protection is also known as ‘teleprotection’.
BUS

BUS

Need For Pilot Aided Schemes

Local Relay

Remote Relay

Communication
Channel
Pilot Communications Channels
• Distance-based pilot schemes traditionally utilize simple
on/off communications between relays, but can also utilize
peer-to-peer communications and GOOSE messaging over
digital channels
• Typical communications media include:
• Pilot-wire (50Hz, 60Hz, AT)
• Power line carrier
• Microwave
• Radio
• Optic fiber (directly connected or multiplexed
channels)
Distance-based Pilot Protection
Pilot-Aided Distance-Based Schemes
 DUTT – Direct Under-reaching Transfer Trip
 PUTT – Permissive Under-reaching Transfer Trip
 POTT – Permissive Over-reaching Transfer Trip
 Hybrid POTT – Hybrid Permissive Over-reaching
Transfer Trip
 DCB – Directional Comparison Blocking Scheme
 DCUB – Directional Comparison Unblocking
Scheme
Direct Underreaching Transfer Trip
(DUTT)
• Requires only underreaching (RU) functions which
overlap in reach (Zone 1).
•Applied with FSK channel
• GUARD frequency transmitted during normal
conditions
• TRIP frequency when one RU function operates
• Scheme does not provide tripping for faults beyond RU
reach if remote breaker is open or channel is inoperative.
• Dual pilot channels improve security
DUTT Scheme
 

Zone 1

Bus

Bus
Line

Zone 1
Permissive Underreaching
Transfer Trip (PUTT)
• Requires both under (RU) and overreaching (RO)
functions
• Identical to DUTT, with pilot tripping signal supervised by
RO (Zone 2)
PUTT Scheme
Zone 2

Zone 1

To protect end of
line
Bus

Bus
Line

Zone 1

Zone 2

Rx PKP
Zone 2
Zone 1

&

Local Trip

OR
Permissive Overreaching Transfer
Trip (POTT)
• Requires overreaching (RO) functions (Zone 2).
• Applied with FSK channel:
• GUARD frequency sent in stand-by
• TRIP frequency when one RO function operates

• No trip for external faults if pilot channel is inoperative
• Time-delayed tripping can be provided
POTT Scheme
Zone 2

Zone 1
Bus

Bus
Line

Zone 1

Zone 2

(Z1)

Tx

Zone 1

(Z1)

OR

Rx
AND

Zone 2

t

o

Trip
Line
Breakers
POTT Scheme
POTT – Permissive Over-reaching Transfer Trip

BUS

BUS

End
Zone

Communication Channel
POTT Scheme Relay
Local

Local Relay
FW IGND
D
Local Relay – Z2  

Remote Relay
FW IGND
D

Remote Relay – Z2

TRIP

Communication
Channel
POTT RX

Local Relay
ZONE 2 PKP
OR
Ground Dir OC Fwd

POTT TX

ZONE 2 PKP Remote Relay
OR
Ground Dir OC Fwd
POTT Scheme

POTT RX 2
POTT RX 3
POTT RX 4

Local Relay

Communications
Channel(s)

POTT RX 1

POTT TX 1 A to G
POTT TX 2 B to G
POTT TX 3 C to G
POTT TX 4 Multi Phase

Remote Relay
POTT Scheme
Current reversal example
TRIP

Local Relay

GND DIR OC FWD
GND DIR OC REV

Timer 
 Start  Communication 
Expire
Timer
Channel
POTT RX

POTT TX

Remote Relay

ZONE 2    OR
GND DIR OC REV
GND DIR OC FWD
POTT Scheme
Echo example
Remote FWD
IGND

Open

Remote – Z2

OPEN

Communication
Channel

POTT RX

Local Relay

POTT TX

TRIP

POTT TX

POTT RX

Communication
Channel

Remote Relay
Hybrid POTT
• Intended for three-terminal lines and weak infeed conditions
• Echo feature adds security during weak infeed conditions
• Reverse-looking distance and oc elements used to identify
external faults
Hybrid POTT
Zone 2

Zone 1
Remote

Local
Weak
system

Bus

Bus
Line

Zone 1

Zone 2

Zone 4
Directional Comparison Blocking
(DCB)
• Requires overreaching (RO) tripping and blocking (B)
functions
• ON/OFF pilot channel typically used (i.e., PLC)
• Transmitter is keyed to ON state when blocking
function(s) operate
• Receipt of signal from remote end blocks tripping
relays
• Tripping function set with Zone 2 reach or greater
• Blocking functions include Zone 3 reverse and low-set
ground overcurrent elements
DCB Scheme
Zone 2

Zone 1
Remote

Local
Bus

Bus
Line

Zone 1

Zone 2
Directional Comparison Blocking (DCB)

BUS

BUS

End Zone

Communication Channel
Directional Comparison Blocking (DCB)
Internal Faults
Local Relay – Z2

FWD IGND

TRIP Timer
Start
Expired

TRIP

Zone 2 PKP
OR

NO

Local Relay GND DIR OC Fwd

Dir Block RX

Remote Relay
Directional Comparison Blocking (DCB)
External Faults
Local Relay – Z2

FWD IGND
TRIP Timer
Start

Remote Relay – Z4
REV IGND

No TRIP
Dir Block RX

Local Relay

Zone 2 PKP
OR

DIR BLOCK TX

Communication
Channel

GND DIR OC Fwd

Zone 4 PKP
OR

GND DIR OC Rev

Remote Relay
Directional Comparison Unblocking
(DCUB)
• Applied to Permissive Overreaching (POR) schemes
to overcome the possibility of carrier signal
attenuation or loss as a result of the fault
• Unblocking provided in the receiver when signal is
lost:
• If signal is lost due to fault, at least one
permissive RO functions will be picked up
• Unblocking logic produces short-duration TRIP
signal (150-300 ms). If RO function not picked
up, channel lockout occurs until GUARD signal
returns
DCUB Scheme
Forward

Bus

Bus
Line

Forward

(Un-Block)

(Block)

Trip
Line
Breakers

Tx1

Tx2

Forward

(Block)

Rx2

AND
AND

(Un-Block)

t

AND
o

AND

Rx1

Lockout
Directional Comparison Unblocking
(DCUB)

BUS

BUS

End Zone

Communication Channel
Directional Comparison Unblocking
(DCUB)
Normal conditions

Load Current

FSK Carrier
GUARD1 RX

FSK Carrier
GUARD1 TX

Local Relay
NO Loss of Guard
NO Permission

GUARD2 TX

Communication
Channel

GUARD2 RX

Remote Relay
NO Loss of Guard
NO Permission
Directional Comparison Unblocking
(DCUB)
Normal conditions, channel failure

Load Current

Loss of Channel
FSK Carrier
NO RX
GUARD1 RX

FSK Carrier
GUARD1 TX

Local Relay
Loss of Guard
Block Timer Expired
Started

Block DCUB
until Guard OK

GUARD2 TX

Communication
Channel

GUARD2 RX
NO RX

Remote Relay

Loss of Guard

Block Timer Expired
Started

Block DCUB
until Guard OK
Directional Comparison Unblocking
(DCUB)
Internal fault, healthy channel
Local Relay – Z2

Remote Relay – Z2

TRIP

TRIP Z1

FSK Carrier

Local Relay
Zone 2 PKP
Loss of Guard
Permission

FSK Carrier

TRIP1 RX
GUARD1 RX

GUARD1 TX
TRIP1 TX

GUARD2 TX
TRIP2 TX

GUARD2 RX
TRIP2 RX

Communication
Channel

Remote Relay
ZONE 2 PKP
Directional Comparison Unblocking
(DCUB)
Internal fault, channel failure
Local Relay – Z2

Remote Relay – Z2
Loss of Channel

TRIP
FSK Carrier

Local Relay
Zone 2 PKP

TRIP Z1
FSK Carrier

NO RX
GUARD1 RX

GUARD1 TX
TRIP1 TX

GUARD2 TX
TRIP2 TX

GUARD2 RX
NO RX

Loss of Guard
Block Timer Started
Duration Timer Expired
Started

Remote Relay
ZONE 2 PKP
Loss of Guard

Communication
Channel
Redundancy Considerations
• Redundant protection systems increase dependability of the

system:
• Multiple sets of protection using same protection principle
and multiple pilot channels overcome individual element
failure, or
• Multiple sets of protection using different protection principles
and multiple channels protects against failure of one of the
protection methods.
• Security can be improved using “voting” schemes (i.e., 2-out-of3), potentially at expense of dependability.
• Redundancy of instrument transformers, battery systems, trip
coil circuits, etc. also need to be considered.
Redundant Communications

BUS

BUS

End Zone

AND Channels:
POTT Less Reliable
DCB Less Secure

OR Channels:
Communication Channel 1
Communication Channel 2

More Channel Security

POTT More Reliable
DCB More Secure
More Channel Dependability

Loss of Channel 2
Redundant Pilot Schemes
Pilot Relay Desirable Attributes
•Integrated functions:
• weak infeed
• echo
• line pick-up (SOTF)
•Basic protection elements used to key the
communication:
• distance elements
• fast and sensitive ground (zero and negative
sequence) directional IOCs with current, voltage,
and/or dual polarization
Pilot protection

Weitere ähnliche Inhalte

Was ist angesagt?

Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protectionsrini09
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Rahul Ruddra
 
Overload capacity of power transformers
Overload capacity of power transformersOverload capacity of power transformers
Overload capacity of power transformersLeonardo ENERGY
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Power system protection
Power system protectionPower system protection
Power system protectionAnu Priya
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Deviceskhemraj298
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)Rohini Haridas
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION moiz89
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protectionSalim Palayi
 
Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)Asha Anu Kurian
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]moiz89
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
 
Factors to be considered while selecting CT
Factors to be considered while selecting CTFactors to be considered while selecting CT
Factors to be considered while selecting CTParth Patel
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relaykishore kish
 
Loading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesLoading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesRaja Adapa
 
Objectives of shunt compensation
Objectives of shunt compensationObjectives of shunt compensation
Objectives of shunt compensationAyyarao T S L V
 

Was ist angesagt? (20)

Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
 
Power quality ppt
Power quality pptPower quality ppt
Power quality ppt
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
Overload capacity of power transformers
Overload capacity of power transformersOverload capacity of power transformers
Overload capacity of power transformers
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Bus Bar Protection
Bus Bar ProtectionBus Bar Protection
Bus Bar Protection
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)
 
POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION POWER SYSTEM PROTECTION
POWER SYSTEM PROTECTION
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protection
 
Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)Economic load dispatch(with and without losses)
Economic load dispatch(with and without losses)
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
 
Factors to be considered while selecting CT
Factors to be considered while selecting CTFactors to be considered while selecting CT
Factors to be considered while selecting CT
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
Loading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission LinesLoading Capability Limits of Transmission Lines
Loading Capability Limits of Transmission Lines
 
Objectives of shunt compensation
Objectives of shunt compensationObjectives of shunt compensation
Objectives of shunt compensation
 

Andere mochten auch

Lineprotection basics june2008
Lineprotection basics june2008Lineprotection basics june2008
Lineprotection basics june2008lankeshdb
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformerRitesh Verma
 
Switchgear and protection 2
Switchgear and protection 2Switchgear and protection 2
Switchgear and protection 2Md Irshad Ahmad
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1Md Irshad Ahmad
 
Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protectionBinit Das
 
Distance protection scheme for transmission line using back propagation neura...
Distance protection scheme for transmission line using back propagation neura...Distance protection scheme for transmission line using back propagation neura...
Distance protection scheme for transmission line using back propagation neura...eSAT Publishing House
 
HYPERSIM Relay Protection Webinar
HYPERSIM Relay Protection WebinarHYPERSIM Relay Protection Webinar
HYPERSIM Relay Protection WebinarEtienne Leduc
 
Electromechanical Relay
Electromechanical RelayElectromechanical Relay
Electromechanical RelayTouqeer Akbar
 
RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
RADIAL FEEDER PROTECTION PANEL DEVELOPMENTRADIAL FEEDER PROTECTION PANEL DEVELOPMENT
RADIAL FEEDER PROTECTION PANEL DEVELOPMENTHimanshu Paghdal
 
Regiones naturales colombia
Regiones naturales colombiaRegiones naturales colombia
Regiones naturales colombiasaramogollon12
 
Unmanned railway tracking and anti collision system using gsm
Unmanned railway tracking and anti collision  system  using gsmUnmanned railway tracking and anti collision  system  using gsm
Unmanned railway tracking and anti collision system using gsmvmohankumar5
 
Transmission line protection principles
Transmission line protection principlesTransmission line protection principles
Transmission line protection principlesJhon Miranda Ramos
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substationPanneerselvam Rathinam
 

Andere mochten auch (16)

Lineprotection basics june2008
Lineprotection basics june2008Lineprotection basics june2008
Lineprotection basics june2008
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
How to Create and Implement Protective Relay Test Plans
How to Create and Implement Protective Relay Test PlansHow to Create and Implement Protective Relay Test Plans
How to Create and Implement Protective Relay Test Plans
 
Switchgear and protection 2
Switchgear and protection 2Switchgear and protection 2
Switchgear and protection 2
 
Switchgear and protection 1
Switchgear and protection 1Switchgear and protection 1
Switchgear and protection 1
 
Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protection
 
ALSTOM – Micom
ALSTOM – MicomALSTOM – Micom
ALSTOM – Micom
 
distance relay
distance relaydistance relay
distance relay
 
Distance protection scheme for transmission line using back propagation neura...
Distance protection scheme for transmission line using back propagation neura...Distance protection scheme for transmission line using back propagation neura...
Distance protection scheme for transmission line using back propagation neura...
 
HYPERSIM Relay Protection Webinar
HYPERSIM Relay Protection WebinarHYPERSIM Relay Protection Webinar
HYPERSIM Relay Protection Webinar
 
Electromechanical Relay
Electromechanical RelayElectromechanical Relay
Electromechanical Relay
 
RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
RADIAL FEEDER PROTECTION PANEL DEVELOPMENTRADIAL FEEDER PROTECTION PANEL DEVELOPMENT
RADIAL FEEDER PROTECTION PANEL DEVELOPMENT
 
Regiones naturales colombia
Regiones naturales colombiaRegiones naturales colombia
Regiones naturales colombia
 
Unmanned railway tracking and anti collision system using gsm
Unmanned railway tracking and anti collision  system  using gsmUnmanned railway tracking and anti collision  system  using gsm
Unmanned railway tracking and anti collision system using gsm
 
Transmission line protection principles
Transmission line protection principlesTransmission line protection principles
Transmission line protection principles
 
protection of feeders in distribution substation
protection of feeders in distribution substationprotection of feeders in distribution substation
protection of feeders in distribution substation
 

Ähnlich wie Pilot protection

Repeater in the CDMA network
Repeater in the CDMA networkRepeater in the CDMA network
Repeater in the CDMA networkJoseph Shapira
 
optimization.ppt
optimization.pptoptimization.ppt
optimization.pptankur tomar
 
USB 3.1 Gen 2 Compliance Testing and Debug Webinar
USB 3.1 Gen 2 Compliance Testing and Debug WebinarUSB 3.1 Gen 2 Compliance Testing and Debug Webinar
USB 3.1 Gen 2 Compliance Testing and Debug Webinarteledynelecroy
 
Etl andrew bond_sspi_maio_2015
Etl andrew bond_sspi_maio_2015Etl andrew bond_sspi_maio_2015
Etl andrew bond_sspi_maio_2015SSPI Brasil
 
PLNOG19 - Krzysztof Szarkowicz - RIFT i nowe pomysły na routing
PLNOG19 - Krzysztof Szarkowicz - RIFT i nowe pomysły na routingPLNOG19 - Krzysztof Szarkowicz - RIFT i nowe pomysły na routing
PLNOG19 - Krzysztof Szarkowicz - RIFT i nowe pomysły na routingPROIDEA
 
Positioning techniques in 3 g networks (1)
Positioning techniques in 3 g networks (1)Positioning techniques in 3 g networks (1)
Positioning techniques in 3 g networks (1)kike2005
 
RFU - Unidade de radio frequência radio enlace
RFU - Unidade de radio frequência radio enlaceRFU - Unidade de radio frequência radio enlace
RFU - Unidade de radio frequência radio enlacejonatanmedeirosgomes1
 
transmission-line-protection.ppt
transmission-line-protection.ppttransmission-line-protection.ppt
transmission-line-protection.pptssuser0132001
 
Power Line Carrier Communication
Power Line Carrier CommunicationPower Line Carrier Communication
Power Line Carrier CommunicationNeha Gethe
 
Huawei_MIMO_solution.pdf
Huawei_MIMO_solution.pdfHuawei_MIMO_solution.pdf
Huawei_MIMO_solution.pdfssuser32515c
 
Codan buc presentation 6-1
Codan buc presentation 6-1Codan buc presentation 6-1
Codan buc presentation 6-1Riyadhi Anas
 
4G-Fourth Generation Mobile Communication System
4G-Fourth Generation Mobile Communication System4G-Fourth Generation Mobile Communication System
4G-Fourth Generation Mobile Communication SystemSafaet Hossain
 
crosstalk minimisation using vlsi
crosstalk minimisation using vlsicrosstalk minimisation using vlsi
crosstalk minimisation using vlsisubhradeep mitra
 

Ähnlich wie Pilot protection (20)

Repeater in the CDMA network
Repeater in the CDMA networkRepeater in the CDMA network
Repeater in the CDMA network
 
optimization.ppt
optimization.pptoptimization.ppt
optimization.ppt
 
USB 3.1 Gen 2 Compliance Testing and Debug Webinar
USB 3.1 Gen 2 Compliance Testing and Debug WebinarUSB 3.1 Gen 2 Compliance Testing and Debug Webinar
USB 3.1 Gen 2 Compliance Testing and Debug Webinar
 
Etl andrew bond_sspi_maio_2015
Etl andrew bond_sspi_maio_2015Etl andrew bond_sspi_maio_2015
Etl andrew bond_sspi_maio_2015
 
PLNOG19 - Krzysztof Szarkowicz - RIFT i nowe pomysły na routing
PLNOG19 - Krzysztof Szarkowicz - RIFT i nowe pomysły na routingPLNOG19 - Krzysztof Szarkowicz - RIFT i nowe pomysły na routing
PLNOG19 - Krzysztof Szarkowicz - RIFT i nowe pomysły na routing
 
LTE-Qualcomm EMERSON EDUARDO RODRIGUES
LTE-Qualcomm EMERSON EDUARDO RODRIGUESLTE-Qualcomm EMERSON EDUARDO RODRIGUES
LTE-Qualcomm EMERSON EDUARDO RODRIGUES
 
Positioning techniques in 3 g networks (1)
Positioning techniques in 3 g networks (1)Positioning techniques in 3 g networks (1)
Positioning techniques in 3 g networks (1)
 
Rf optimization
Rf optimizationRf optimization
Rf optimization
 
RFU - Unidade de radio frequência radio enlace
RFU - Unidade de radio frequência radio enlaceRFU - Unidade de radio frequência radio enlace
RFU - Unidade de radio frequência radio enlace
 
transmission-line-protection.ppt
transmission-line-protection.ppttransmission-line-protection.ppt
transmission-line-protection.ppt
 
Power Line Carrier Communication
Power Line Carrier CommunicationPower Line Carrier Communication
Power Line Carrier Communication
 
Umts
UmtsUmts
Umts
 
Huawei_MIMO_solution.pdf
Huawei_MIMO_solution.pdfHuawei_MIMO_solution.pdf
Huawei_MIMO_solution.pdf
 
Codan buc presentation 6-1
Codan buc presentation 6-1Codan buc presentation 6-1
Codan buc presentation 6-1
 
4G-Fourth Generation Mobile Communication System
4G-Fourth Generation Mobile Communication System4G-Fourth Generation Mobile Communication System
4G-Fourth Generation Mobile Communication System
 
PLCC.ppt
PLCC.pptPLCC.ppt
PLCC.ppt
 
crosstalk minimisation using vlsi
crosstalk minimisation using vlsicrosstalk minimisation using vlsi
crosstalk minimisation using vlsi
 
LTE Key Technologies
LTE Key TechnologiesLTE Key Technologies
LTE Key Technologies
 
Radio network overview
Radio network overviewRadio network overview
Radio network overview
 
Sit training cr
Sit training crSit training cr
Sit training cr
 

Kürzlich hochgeladen

Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Drew Madelung
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherRemote DBA Services
 
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWEREMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWERMadyBayot
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc
 
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost SavingRepurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost SavingEdi Saputra
 
ICT role in 21st century education and its challenges
ICT role in 21st century education and its challengesICT role in 21st century education and its challenges
ICT role in 21st century education and its challengesrafiqahmad00786416
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProduct Anonymous
 
Real Time Object Detection Using Open CV
Real Time Object Detection Using Open CVReal Time Object Detection Using Open CV
Real Time Object Detection Using Open CVKhem
 
AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024The Digital Insurer
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processorsdebabhi2
 
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...apidays
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024The Digital Insurer
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdflior mazor
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...DianaGray10
 
MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024MIND CTI
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FMESafe Software
 
Polkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin WoodPolkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin WoodJuan lago vázquez
 
A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?Igalia
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobeapidays
 
Ransomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdfRansomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdfOverkill Security
 

Kürzlich hochgeladen (20)

Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
Strategies for Unlocking Knowledge Management in Microsoft 365 in the Copilot...
 
Strategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a FresherStrategies for Landing an Oracle DBA Job as a Fresher
Strategies for Landing an Oracle DBA Job as a Fresher
 
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWEREMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
EMPOWERMENT TECHNOLOGY GRADE 11 QUARTER 2 REVIEWER
 
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data DiscoveryTrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
TrustArc Webinar - Unlock the Power of AI-Driven Data Discovery
 
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost SavingRepurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
Repurposing LNG terminals for Hydrogen Ammonia: Feasibility and Cost Saving
 
ICT role in 21st century education and its challenges
ICT role in 21st century education and its challengesICT role in 21st century education and its challenges
ICT role in 21st century education and its challenges
 
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemkeProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
ProductAnonymous-April2024-WinProductDiscovery-MelissaKlemke
 
Real Time Object Detection Using Open CV
Real Time Object Detection Using Open CVReal Time Object Detection Using Open CV
Real Time Object Detection Using Open CV
 
AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024AXA XL - Insurer Innovation Award Americas 2024
AXA XL - Insurer Innovation Award Americas 2024
 
Exploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone ProcessorsExploring the Future Potential of AI-Enabled Smartphone Processors
Exploring the Future Potential of AI-Enabled Smartphone Processors
 
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
Apidays New York 2024 - The Good, the Bad and the Governed by David O'Neill, ...
 
Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024Axa Assurance Maroc - Insurer Innovation Award 2024
Axa Assurance Maroc - Insurer Innovation Award 2024
 
GenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdfGenAI Risks & Security Meetup 01052024.pdf
GenAI Risks & Security Meetup 01052024.pdf
 
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
Connector Corner: Accelerate revenue generation using UiPath API-centric busi...
 
MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024MINDCTI Revenue Release Quarter One 2024
MINDCTI Revenue Release Quarter One 2024
 
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers:  A Deep Dive into Serverless Spatial Data and FMECloud Frontiers:  A Deep Dive into Serverless Spatial Data and FME
Cloud Frontiers: A Deep Dive into Serverless Spatial Data and FME
 
Polkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin WoodPolkadot JAM Slides - Token2049 - By Dr. Gavin Wood
Polkadot JAM Slides - Token2049 - By Dr. Gavin Wood
 
A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?A Year of the Servo Reboot: Where Are We Now?
A Year of the Servo Reboot: Where Are We Now?
 
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, AdobeApidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
Apidays New York 2024 - Scaling API-first by Ian Reasor and Radu Cotescu, Adobe
 
Ransomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdfRansomware_Q4_2023. The report. [EN].pdf
Ransomware_Q4_2023. The report. [EN].pdf
 

Pilot protection

  • 2. Outline • • • • • • Transmission line introduction Typical protection schemes Need for pilot aided schemes Various pilot schemes Redundancy considerations Desirable attributes of pilot relay
  • 3. Transmission Lines • A Vital Part of the Power System: • Provide path to transfer power between generation and load • Operate at voltage levels from 69kV to 765kV • Deregulated markets, economic, environmental requirements have pushed utilities to operate transmission lines close to their limits.
  • 4. Transmission Lines • Classification of line length depends on:  Source-to-line Impedance Ratio (SIR), and  Nominal voltage • Length considerations:  Short Lines: SIR > 4  Medium Lines: 0.5 < SIR < 4  Long Lines: SIR < 0.5
  • 5. Typical Protection Schemes Short Lines • • • • Current differential Phase comparison Permissive Overreach Transfer Trip (POTT) Directional Comparison Blocking (DCB)
  • 6. Typical Protection Schemes Medium Lines • Phase comparison • Directional Comparison Blocking (DCB) • Permissive Underreach Transfer Trip (PUTT) • Permissive Overreach Transfer Trip (POTT) • Unblocking • Step Distance • Step or coordinated overcurrent • Inverse time overcurrent • Current Differential
  • 7. Typical Protection Schemes Long Lines • Phase comparison • Directional Comparison Blocking (DCB) • Permissive Underreach Transfer Trip (PUTT) • Permissive Overreach Transfer Trip (POTT) • Unblocking • Step Distance • Step or coordinated overcurrent • Current Differential
  • 8. Introduction • Nonpilot protection using overcurrent and distance relays, contain a fundamental difficulty : It is not possible to instantaneously clear a fault from both ends of a transmission line if the fault is near one end of the line. • Pilot protection is an adaptation of the principles of differential relaying that avoids the use of control cable between terminals. • The term ‘pilot’ refers to a communication channel between two or more ends of a transmission line to provide instantaneous clearing over 100% of the line. • This form of protection is also known as ‘teleprotection’.
  • 9. BUS BUS Need For Pilot Aided Schemes Local Relay Remote Relay Communication Channel
  • 10. Pilot Communications Channels • Distance-based pilot schemes traditionally utilize simple on/off communications between relays, but can also utilize peer-to-peer communications and GOOSE messaging over digital channels • Typical communications media include: • Pilot-wire (50Hz, 60Hz, AT) • Power line carrier • Microwave • Radio • Optic fiber (directly connected or multiplexed channels)
  • 12. Pilot-Aided Distance-Based Schemes  DUTT – Direct Under-reaching Transfer Trip  PUTT – Permissive Under-reaching Transfer Trip  POTT – Permissive Over-reaching Transfer Trip  Hybrid POTT – Hybrid Permissive Over-reaching Transfer Trip  DCB – Directional Comparison Blocking Scheme  DCUB – Directional Comparison Unblocking Scheme
  • 13. Direct Underreaching Transfer Trip (DUTT) • Requires only underreaching (RU) functions which overlap in reach (Zone 1). •Applied with FSK channel • GUARD frequency transmitted during normal conditions • TRIP frequency when one RU function operates • Scheme does not provide tripping for faults beyond RU reach if remote breaker is open or channel is inoperative. • Dual pilot channels improve security
  • 15. Permissive Underreaching Transfer Trip (PUTT) • Requires both under (RU) and overreaching (RO) functions • Identical to DUTT, with pilot tripping signal supervised by RO (Zone 2)
  • 16. PUTT Scheme Zone 2 Zone 1 To protect end of line Bus Bus Line Zone 1 Zone 2 Rx PKP Zone 2 Zone 1 & Local Trip OR
  • 17. Permissive Overreaching Transfer Trip (POTT) • Requires overreaching (RO) functions (Zone 2). • Applied with FSK channel: • GUARD frequency sent in stand-by • TRIP frequency when one RO function operates • No trip for external faults if pilot channel is inoperative • Time-delayed tripping can be provided
  • 18. POTT Scheme Zone 2 Zone 1 Bus Bus Line Zone 1 Zone 2 (Z1) Tx Zone 1 (Z1) OR Rx AND Zone 2 t o Trip Line Breakers
  • 19. POTT Scheme POTT – Permissive Over-reaching Transfer Trip BUS BUS End Zone Communication Channel
  • 20. POTT Scheme Relay Local Local Relay FW IGND D Local Relay – Z2   Remote Relay FW IGND D Remote Relay – Z2 TRIP Communication Channel POTT RX Local Relay ZONE 2 PKP OR Ground Dir OC Fwd POTT TX ZONE 2 PKP Remote Relay OR Ground Dir OC Fwd
  • 22. POTT Scheme Current reversal example TRIP Local Relay GND DIR OC FWD GND DIR OC REV Timer   Start  Communication  Expire Timer Channel POTT RX POTT TX Remote Relay ZONE 2    OR GND DIR OC REV GND DIR OC FWD
  • 23. POTT Scheme Echo example Remote FWD IGND Open Remote – Z2 OPEN Communication Channel POTT RX Local Relay POTT TX TRIP POTT TX POTT RX Communication Channel Remote Relay
  • 24. Hybrid POTT • Intended for three-terminal lines and weak infeed conditions • Echo feature adds security during weak infeed conditions • Reverse-looking distance and oc elements used to identify external faults
  • 25. Hybrid POTT Zone 2 Zone 1 Remote Local Weak system Bus Bus Line Zone 1 Zone 2 Zone 4
  • 26. Directional Comparison Blocking (DCB) • Requires overreaching (RO) tripping and blocking (B) functions • ON/OFF pilot channel typically used (i.e., PLC) • Transmitter is keyed to ON state when blocking function(s) operate • Receipt of signal from remote end blocks tripping relays • Tripping function set with Zone 2 reach or greater • Blocking functions include Zone 3 reverse and low-set ground overcurrent elements
  • 27. DCB Scheme Zone 2 Zone 1 Remote Local Bus Bus Line Zone 1 Zone 2
  • 28. Directional Comparison Blocking (DCB) BUS BUS End Zone Communication Channel
  • 29. Directional Comparison Blocking (DCB) Internal Faults Local Relay – Z2 FWD IGND TRIP Timer Start Expired TRIP Zone 2 PKP OR NO Local Relay GND DIR OC Fwd Dir Block RX Remote Relay
  • 30. Directional Comparison Blocking (DCB) External Faults Local Relay – Z2 FWD IGND TRIP Timer Start Remote Relay – Z4 REV IGND No TRIP Dir Block RX Local Relay Zone 2 PKP OR DIR BLOCK TX Communication Channel GND DIR OC Fwd Zone 4 PKP OR GND DIR OC Rev Remote Relay
  • 31. Directional Comparison Unblocking (DCUB) • Applied to Permissive Overreaching (POR) schemes to overcome the possibility of carrier signal attenuation or loss as a result of the fault • Unblocking provided in the receiver when signal is lost: • If signal is lost due to fault, at least one permissive RO functions will be picked up • Unblocking logic produces short-duration TRIP signal (150-300 ms). If RO function not picked up, channel lockout occurs until GUARD signal returns
  • 34. Directional Comparison Unblocking (DCUB) Normal conditions Load Current FSK Carrier GUARD1 RX FSK Carrier GUARD1 TX Local Relay NO Loss of Guard NO Permission GUARD2 TX Communication Channel GUARD2 RX Remote Relay NO Loss of Guard NO Permission
  • 35. Directional Comparison Unblocking (DCUB) Normal conditions, channel failure Load Current Loss of Channel FSK Carrier NO RX GUARD1 RX FSK Carrier GUARD1 TX Local Relay Loss of Guard Block Timer Expired Started Block DCUB until Guard OK GUARD2 TX Communication Channel GUARD2 RX NO RX Remote Relay Loss of Guard Block Timer Expired Started Block DCUB until Guard OK
  • 36. Directional Comparison Unblocking (DCUB) Internal fault, healthy channel Local Relay – Z2 Remote Relay – Z2 TRIP TRIP Z1 FSK Carrier Local Relay Zone 2 PKP Loss of Guard Permission FSK Carrier TRIP1 RX GUARD1 RX GUARD1 TX TRIP1 TX GUARD2 TX TRIP2 TX GUARD2 RX TRIP2 RX Communication Channel Remote Relay ZONE 2 PKP
  • 37. Directional Comparison Unblocking (DCUB) Internal fault, channel failure Local Relay – Z2 Remote Relay – Z2 Loss of Channel TRIP FSK Carrier Local Relay Zone 2 PKP TRIP Z1 FSK Carrier NO RX GUARD1 RX GUARD1 TX TRIP1 TX GUARD2 TX TRIP2 TX GUARD2 RX NO RX Loss of Guard Block Timer Started Duration Timer Expired Started Remote Relay ZONE 2 PKP Loss of Guard Communication Channel
  • 38. Redundancy Considerations • Redundant protection systems increase dependability of the system: • Multiple sets of protection using same protection principle and multiple pilot channels overcome individual element failure, or • Multiple sets of protection using different protection principles and multiple channels protects against failure of one of the protection methods. • Security can be improved using “voting” schemes (i.e., 2-out-of3), potentially at expense of dependability. • Redundancy of instrument transformers, battery systems, trip coil circuits, etc. also need to be considered.
  • 39. Redundant Communications BUS BUS End Zone AND Channels: POTT Less Reliable DCB Less Secure OR Channels: Communication Channel 1 Communication Channel 2 More Channel Security POTT More Reliable DCB More Secure More Channel Dependability Loss of Channel 2
  • 41. Pilot Relay Desirable Attributes •Integrated functions: • weak infeed • echo • line pick-up (SOTF) •Basic protection elements used to key the communication: • distance elements • fast and sensitive ground (zero and negative sequence) directional IOCs with current, voltage, and/or dual polarization

Hinweis der Redaktion

  1. Pilot schemes speed up the clearing of faults that occur on the transmission line and inside the end zone of the local relay by communicating with the relay at the remote end of the line to determine if the fault is actually on the transmission line. Therefore, all pilot aided schemes require a communication channel be provided between the two relays. This communication between the relays can consist of a single channel or multiple channels depending on the particular application. Over this communication channel, the two relays share information regarding the fault allowing the clearing of faults on the transmission line to occur as fast as possible. Communication channels include power line carriers, Microwave radio channels, SONET channels to list a few. It is desirable to have a very secure and reliable communications channel for this purpose.
  2. The most common Pilot aided schemes are : The DUTT scheme, which stands for Direct Under-reaching Transfer Trip The PUTT scheme which stands for Permissive Under-reaching Transfer Trip The POTT scheme, which stands for Permissive Over-reaching Transfer Trip The Hybrid POTT scheme which stands for the Hybrid Permissive Over-reaching Transfer Trip The Directional Comparison Blocking Scheme And the Directional Comparison Unblocking scheme We will discuss the POTT, DCB and DCUB schemes in the following sections.
  3. Direct Under-reaching Transfer Trip Under-reaching units at each end. Local Zone 1 PKP causes local trip Under-reaching units transmit on operation Received signal trips remote breaker
  4. Permissive Under-reaching Transfer Trip Under-reaching units at each end Over-reaching units at each end Under-reaching units transmit on operation Received signal trips ONLY IF (permissive) local over-reach element is operated Trip = Local Zone 2 + Remote Zone 1
  5. Permissive Over-reaching Transfer Trip Designed for two terminal lines Over-reaching units at each end Over-reaching units transmit on operation Received signal trips ONLY IF (permissive) local and remote over-reach element have operated Strategy: Communications channel established between relays sending fault/no fault status to the other relay. Both relays set up for zone 2. If they both see the fault, the fault is on the line. If only one relay sees the fault, the fault is behind the other relay.
  6. The POTT pilot aided scheme stands for the Permissive Over-reaching transfer trip scheme; and like other Pilot aided schemes, is used to speed up the clearing of faults that occur in the end zone of a transmission line. As for all pilot aided schemes, a communication channel must be provided between the two relays located at each end of the transmission line for the POTT scheme to operate.
  7. In the POTT scheme, the Remote relay speeds up the tripping of an end zone fault by sending a permission to Trip key from the Remote relay to the local relay under 2 circumstances. ----The first reason that the remote relay will send a Permissive key is when the it detects a fault occurring within it’s over-reaching zone 2. This is where the expression “over-reaching” comes from in the term Permissive Over-reaching Transfer Trip. ---The second reason that the remote relay will send a permissive key is when it detects that ground directional overcurrent is flowing in it’s forward direction if this feature is enabled and configured. -----Therefore either Negative sequence directional overcurrent Forward element or the Neutral directional overcurrent Forward element, if configured, will send a POTT key to the Local relay, if both are configured,----- as well as when the over-reaching zone 2 pickup flag turns ON The Local relay POTT logic will only cause the breaker to trip ---if it gets the POTT key from the remote relay in the form of a receive AND, -----the local relay has detected a fault within it’s zone 2 area of protection OR, -----it detects that ground directional current is flowing in it’s Forward direction if this function is configured ----Therefore either the local relay’s Forward Negative sequence directional overcurrent element or the Forward Neutral directional overcurrent element as well as the picking up of a Zone 2 fault, will cause the POTT scheme to trip the breaker if it receives a permissive key from the remote relay.
  8. In conjunction with the Phase selector feature which determines which phase is faulted, the D60 distance elements can determine which phases of the transmission line are faulted. Therefore, the Remote D60 has the ability, -----through the communication key signals, to let the Local D60 know which phases are actually faulted. ------If the breakers used on the transmission line have the ability to trip single pole, the D60 can trip only the faulted pole of the breaker based on the received fault type. The POTT scheme in the UR D60 handles this signaling of which phase is faulted by having the ability of sending up to 4 different POTT key or transmit signals that are available in the relay. Therefore, in order to fully utilize this feature the, scheme would need to have a communication channel between the relays that can share more than one bit of information. If the communication channel you are using can only send and receive on piece of information such as a power line carrier can, which phase of the transmission line is faulted can not be sent and single pole tripping is less secure specially on evolving faults.
  9. Some additional logic has been added to the POTT scheme to add extra security to transmission lines that are connected parallel to other transmission lines. ---For example if a fault had occurred on the paralleled transmission line as shown here, the local and remote relays will operate in the following way. --The remote D60 will detect that ground current is flowing in it’s transmission line in the Forward direction, and send a permissive key to the Local relay. ---The local D60 will detect that ground current is flowing in its reverse direction. This reverse ground over-current detection does not meet the criteria defined by the POTT scheme and thus the Local relay will not Trip. After a certain time period, the breaker on the parallel line correctly tripped to attempt to clear the fault. The ground current would now begin to flow through our transmission line in the opposite direction to feed that fault if the remote breaker on the opposite end if it did not open yet. The local and the remote D60’s would now operate in the following way. ----First the Local D60 would have its Forward Negative Sequence Directional overcurrent identify current the current is flowing in the Forward direction. ----At the same time the the local D60 identified the change in direction of ground current, the remote D60 will identify this change as well. However, due to the delay in the communications channel, the POTT permissive key will not immediately be removed. Since the Negative sequence directional element of the local D60 indicates that the fault is in the forward direction and the local relay is still receiving the permission key, the POTT scheme will cause the breaker to trip,---- shutting down the transmission line when it did not need to be.
  10. The POTT scheme has added one more feature to help to speed up the tripping of a faulted transmission line, if one of the ends is open. If the breaker on the local end of the transmission line is open for any reason, the local D60 will not detect any current flow into the transmission line and therefore will not detect any faults within it’s zones of protection. If a fault did occur on the line, no key will be sent to the remote D60. ----If a fault occurred in the remote D60’s end zone as seen here,--- the remote D60 will detect the fault in it’s zone 2 and send the POTT key to speed up tripping of the local D60. Since the local D60 will not send a key because it does not see the fault, the tripping of the remote breaker will not occur until zone 2 of that relay has timed out. The additional logic in the POTT scheme which is called the Echo function works in the following way. The Local D60 must first detects that it’s own breaker is open. If it’s local breaker is open, and it receives a POTT key from the remote D60, ----it will send the POTT key sequence it received directly back to the remote relay. The local D60 is telling the remote D60 that it is ok to trip because the local end of the line is already open and clearing of the fault will be much faster, ensuring the system will not become unstable. ----The remote relay will then take this echoed POTT key and trip it’s breaker. If the Echo function is going to be used, the Line Pickup protection element must first be configured. The description of the Line pickup function will be covered later in the course.
  11. Typically applied on power line carrier. The line is sending the signal and is faulted therefor communications isn’t very reliable… we use this scheme even though it is slower then POTT because it will eventually trip line where as POTT requires a reliable comms. link. Operation: If local zone 2 operates and have not received a block from remote relay local relay will trip.
  12. The Directional Comparison Blocking scheme that is available in the D60 is one of the most popular types of tele-protection schemes used in distance applications today. The purpose of the scheme is to still speed up the tripping of faults that occur in the end zone of a transmission line, just like the POTT scheme. As for all pilot aided schemes, a communication channel must be provided between the two relays located at each end of the transmission line for the Directional Blocking scheme to operate.
  13. In the Directional Blocking scheme, the local D60 has an additional delay timer that is started by the detecting of a fault inside it’s zone 2 area of protection, or, ------the detection of ground current flowing in the forward direction. This timer is set considerably shorter than the normal zone 2 delay. When this additional timer expires the Local D60 will trip the local breaker unless the------Local D60 receives a block message or key from the remote D60.
  14. The remote D60 will only send this blocking key if it detects that the fault is located in it’s zone 4 area of protection, or, it detects that ground current is flowing in the reverse direction. Both of which, would indicate an external fault. In the event that the communications channel failed, the local relay will misoperate. This is one of the disadvantages of the DCB scheme.
  15. The Directional Comparison Unblocking scheme that is currently not available in the D60, but will be implemented in the near future. This is a scheme that was developed to operate ONLY with FSK (Frequency Shift Keying) channels, like Power Line Carriers The purpose of the scheme is to still speed up the tripping of faults that occur in the end zone of a transmission line, just like the POTT and DCB schemes. As for all pilot aided schemes, a communication channel must be provided between the two relays located at each end of the transmission line for the Directional Comparison Unblocking scheme to operate. This channel is normally a single FSK power line carrier. This scheme utilizes principles from the POTT and DCB schemes, making it the most reliable scheme when the communications channel is a power line carrier.