Technical guides for owner/manager of an air conditioning
                    system: volume 8


  How manufacturers could help
  the unfortunate energy auditor
Team

                                    France (Project coordinator)
                                     Armines - Mines de Paris

                          Austria
                                                                      Slovenia
                  Austrian Energy Agency
                                                                University of Ljubljana

                          Belgium                                         UK
                     Université de Liège                        Association of Building
                                                                     Engineers
                             Italy                                         BRE
                     Politecnico di Torino                         (Building Research
                                                                   Establishment Ltd)
                          Portugal
                      University of Porto                          Welsh School of
                                                                    Architecture

                                 Eurovent-Certification



Authors of this volume
Cleide Aparecida Silva (Université de Liège)
Cristian Cuevas (Université de Liège)
Jules Hannay (Université de Liège)
Jean Lebrun (Université de Liège)
Vladut Teodorese (Université de Liège)




  The sole responsibility for the content of this publication lies with the authors. It does not
represent the opinion of the European Communities. The European Commission is not
responsible for any use that may be made of the information contained therein.




                                                                                              2
Introduction
As already demonstrated in other chapters of the present report, the energy audit of
a whole HVAC system is not a funny game. On site measurements are unavoidable
and cost a lot of time and money. Obviously, in most installations, the highest energy
consumers are the fans. The chillers are then coming in second position.
The nominal performances of these components are usually well identified in
laboratory and in manufacturers catalogues. But their average performances are
more questionable in actual conditions of use.
From other part, providing that these components are correctly identified and
modelled, they may become valuable measuring instruments.
The object of this chapter is to show how the components manufacturers could help
the auditor by allowing him to make a better use of the information they already have.

Using a fan as air flow meter
      The principle

Airflow rates measurements are difficult in existing distribution networks: long enough
straight lines are seldom available or accessible and velocity profiles are usually not
uniform enough. A large series of measuring points is required and the final accuracy
is often disappointing. A much better solution consists in using the fan as an air flow
meter.

This can be done in two ways:

   1) By taking profit of the well known characteristics of the fan and using easy
      measurements, as supply and exhaust static pressures, rotation speed and/or
      electrical power;

   2) Even better, by measuring just one reference pressure drop at fan supply.

Both procedures are illustrated and validated hereafter.

      Fan characteristics identified on the basis of manufacturer data

A fan is currently modelled with the help of similarity variables: flow, pressure and
power factors. These factors can be correlated to each other by polynomial
expressions.
The main output of a fan model can be the airflow rate, expressed in “specific” value
(in kg/s of dry air), as usually in air conditioning. Other outputs can be the different
factors, exhaust air speed, total pressure difference, isentropic power and (isentropic)
temperature increase across the fan (these two last outputs can be used as checking
information).
The fan is supposed to be characterised by the diameter of its impeller (scale
variable), its (fictitious) exhaust area and the coefficients of the polynomial
correlations.
Supply air conditions (temperature, pressure and moisture content), rotation speed
and static pressure difference are taken as input variables.




                                                                                      3
This gives the information flow diagram of Figure 1.




                         Figure 1: Example of fan polynomial model


The first equations of this model are built on the basis of the definitions of two (flow
and pressure) similarity factors:




Two dynamic pressures are considered: one at the exhaust and the other one at the
periphery of the impeller:




                                                                                           4
The other non-dimensional variables considered are the isentropic effectiveness and
the power factor:




The three factors are inter-correlated through polynomial laws such as:




This model is from long time well validated and easy to tune…Polynomials are fitted
to manufacturer’s performance data.
Total and static pressures have to be carefully distinguished at fan exhaust:
manufacturers present fan performance in terms of total pressure rise, whereas the
measurements are usually made in terms of static pressures.
Fan characteristics are generally provided by the manufacturers as “data sheets”,
showing the operating curves of the fan (relationships among the different variables
of the system).
A typical example of data sheet is presented in Figure 2.
This information might be better used if the manufacturers were giving:
The experimental points actually available;
The correlation equations actually used to generate the curves.
Still today, the fan simulation model built by the manufacturer is only “offered” to
“important” customers as manufacturers of air handling units. The equations are then
embedded inside black box selection and simulation software.




                                                                                  5
Figure 2 Fan characteristics as presented by the manufacturer
Some points can be selected in the diagram of Figure 2, in order to identify the
polynomial laws already presented. An example of selection is made on Figure 3; it
corresponds to three different rotation speeds.




                    Figure 3 Reference points selected for parameter identification
The phi-psi and lambda-psi regression curves identified on these points are
presented in Figure 4 and Figure 5.


                                                                                      6
Figure 4 Identification of the phi-psi characteristic




                    Figure 5 Identification of the lambda-psi characteristic
A phi – psi characteristic appears to be accurate enough for airflow rate
measurements, when the fan has backward-curved blades (as in the present case).
The airflow rate can be currently determined with an accuracy of about 5 %. In the
case of fans with forward-curved blades, the pressure rise is relatively insensitive to
airflow rate and a more accurate result can be obtained by using the efficiency
characteristic. The electrical consumption is then a better indicator of the flow rate.
However, this second approach requires a correct identification of all electrical losses
(electrical motor and frequency driver, if any).

       Experimental validation

               The fan
The validation is performed on the fan whose characteristics were already identified.
The fan considered in this study was originally installed in a box, downstream of a
“radiator”(Figure 6).




                                                                                        7
Figure 6 the tested fan


               Tightness of the fan box
A first experimental arrangement (Figure 7) was made in order to verify the tightness
of the fan box.
The tightness test consisted in injecting air inside the box, thanks to an auxiliary fan,
after having closed both (supply and exhaust) openings.
Injected airflow rate and box-ambient over-pressure were simultaneously measured.
This allows identifying a fictitious leakage area.
An example of measuring result is shown in Figure 8. In the case considered, the
leakage flow rate is estimated to 16.8 g/s, which corresponds to a leakage (fictitious
isentropic nozzle throat) diameter of 27.3 mm.


                      Fan box


                                                         Small fan




               Figure 7 Experimental identification of the fan box leakage area




                                                                                        8
φ 30/60 mm.
           Fan box                                                     tamb = 20,5°C
                                                                       HRamb = 54 %
                                       ∆P = 604 Pa                     Patm = 981 mbar

        ∆P = 350 Pa

                             Figure 8 Leakage measurement


              Experimental characterization of the fan
The fan system is characterised at different rotation speeds; it’s equipped with a
frequency inverter working between 8.5 and 50.5 Hz.
The experimental arrangement is shown in Figures 9 to 11.
Three tests series have been performed: they correspond to three pressure drop
characteristics of the air circuit:
    1) With coil and with a diaphragm used to measure the flow rate (highest
       pressure drop)
    2) With coil and with a nozzle used to measure the flow rate (medium pressure
       drop)
    3) Without coil and with a nozzle used to measure the flow rate (lowest pressure
       drop).
              ∆Prad        ∆Paf
                                                                ∆Pop


      tamb
      HRamb
      Patm


                                                         &
                                                        Win
                                   Ninv
                                   finv
                                    &
                                   Wm
                                   I
                Figure 9 Experimental characterization of the fan (principle schema)




                                                                                         9
Figure 10 Experimental arrangement (back view)




                     Figure 11 Experimental arrangement (front view)


The inverter is provided with direct measurements of the frequency and of the
electrical power supplied to the fan motor. The electrical power supplied to the
inverter and the fan rotation speeds are also measured in these tests. This makes
possible to identify the inverter loss and the frequency “sliding” of the electric motor.
The tests results are presented in Figure 12 and Figure 13.




                           Figure 12 Inverter loss and efficiency




                                                                                      10
Figure 13 Motor sliding
As it can be seen here, both the inverter loss and the motor sliding can be identified
through linear correlations.
By combining these measuring results with the characteristics already identified (from
manufacturer data), it’s also possible to identify:
    1) The global electromechanical loss and corresponding efficiency of the inverter-
       motor subsystem (Figure 14);
    2) The same terms for the whole inverter-motor-fan system (Figure 15).

Such characteristics would be easy to combine with on site measurements.




              Figure 14 Fan shaft power as function of motor electrical power




                                                                                   11
Figure 15 Global loss and global efficiency


The test results were also used to validate the laws identified from manufacturer
data.
An example of such checking is presented in Figure 16: simulated and measured
total pressure differences are compared for same flow rates and rotation speeds. The
agreement is considered as satisfactory (the actual total pressure at fan exhaust is
not directly measured here, but re-calculated by reference to a hypothetical exhaust
area).




        Figure 16 Comparison among simulated and measured pressure differences



       Validation of a much more expedient method

A much more expedient method is proposed by some manufacturers (as the present
one).
The fan selected for this study was equipped with openings and connecting pipes for
differential pressure measurements as shown in Figure 17 and Figure 18.


                                                                                 12
Figure 17 Differential pressure measuring device (principle)




                        Figure 18 Measuring device (outside the fan)




                        Figure 19 Measuring device (inside the fan)



The measuring principle is described in the manufacturer catalogue as follows:




                                                                                 13
This means that the fan inlet is used as a measuring nozzle. The “K” constant
“contains” the flow contraction effect.
The method can be validated with the test results available. A fictitious nozzle
exhaust diameter is identified at each regime.
Examples of results are presented in Figure 20.




               Figure 20 Exhaust diameter of the (fictitious) fan supply nozzle
A (fairly constant) fictitious diameter of 193 mm is here identified. The actual diameter
is 257 mm. This corresponds to a contraction factor of (193/257)2 = 0.564 and is in
good agreement with the “K” value indicated by the manufacturer.

Using refrigeration compressor as enthalpy flow meter

   The principle
Determining on site the cooling power actually provided by a chiller is also a delicate
matter. That power should correspond to the enthalpy flow of the secondary fluid
(usually water or brine) supplying the evaporator. But neither the flow rate, nor the
supply-exhaust temperature difference are easy to measure.

The measurements are not easier on refrigerant side.



                                                                                      14
An interesting alternative consists in using the chiller compressor as enthalpy flow
meter. But, as seen hereafter, this would require a better dialog with manufacturers…

Data provided by the manufacturers

Analysis

Each manufacturer seems having his own way to present data in his catalogue.
Unfortunately, this “personal” presentation can be a source of confusion.
Data available are nor fully clear, neither complete and the reader is, most of the
time, recommended to“…contact the local manufacturer office…” as solution.
Unfortunately, these offices are not always able to help: it may occur that the
information is just no more available, because of too old machines, no more
produced or replaced by new models.
Some examples of machine designations and physical data presentations used by
some manufacturers are presented hereafter, outlining the differences found among
them.

Examples

Figure 21 gives the designation data found in the catalogue data of manufacturer A.




           Manufacturer A




  Evaporator cooling capacity
                        Figure 21 Chiller designation of manufacturer A.


Figure 22 gives the designation data found in the catalogue of manufacturer B.




                                                                                  15
Reference evaporator cooling capacity – Nominal Tons




                     Figure 22: Chiller designation of manufacturer B
The presentation of physical data is not standardized, as seen in Figure 21 and
Figure 22. Here also, each manufacturer has his personalised presentation and
attention must be paid to each item presented (nominal loads, refrigerant type, fan
capacity, flow rates, etc.), when manipulating catalogues coming from different
manufacturers.
The units must be carefully identified: Some manufacturers use a “semi- SI” system
with kW, bar, kg/s, m³/h, etc. Other ones are still using Imperial units.
But other elementary questions must be answered, as, for example, if the data refers
to one, or to several devices (e.g. one or two condenser fans), to partial or global air
flow rate, etc.




                                                                                     16
!
          n
     ntio
Atte




Figure 23 Chiller physical data given by manufacturer A




                                                          17
Figure 24 Chiller, physical data given by manufacturer B


ARI and Eurovent standards

Hopefully, standardized ARI and/or Eurovent reference data are usually also
available in main manufacturer catalogues and can be freely downloaded from
Internet. This is a great advantage for the users. There exist other standards, but
they are not free!




                                                                                18
Chiller modelling and parameter identification

Modelling
Various simulation models are currently available. An example of information flow
diagram used for chiller modelling is presented in Figure 22. It corresponds to the
model of a chiller with scroll compressor(s) and with air-cooled condenser. In this
model, the condenser and the evaporator are modelled as fictitious semi-isothermal
heat exchangers. A hypothetical proportional control law is applied to the condenser
fan.




                       Figure 25 Example information flow diagram
The same model can be used in two steps:
   1) Parameter identification on one or several reference points;
   2) Simulation in all other conditions of use.

Attention must be paid to the domain of validity of such model, after tuning: according
to the manufacturer: no extrapolation should be done outside the domain covered by
the catalogue.

Parameter identification

This is most delicate operation. If well done, simulation is no more a problem. Figure
26 shows the data usually found in the manufacturer catalogue. A “block diagram” of
the identification procedure is presented in Figure 27. The parameters identified are
indicated in
Figure 28.
The identification process can be done “manually” and iteratively, by considering the
result trends after each step. Default values are used as first guesses for each
component separately at the nominal point. These values are tuned in order to obtain
results that fit to all orders of magnitude. Finally the parameters are tuned again, in
order to obtain a better agreement with all experimental results and/or all
manufacturer data available.


                                                                                    19
The parameter identification is considered as satisfactory if all thermal and electrical
powers are predicted with accuracy of the order of ± 2 %.




                                                                                     20
cd – condenser
 ev – evaporator
                                                  taex_cd
 cp – compressor
 e v – expansion valve

                                                    Air
                    tex_cd                          Condenser      tsu_cd


                                                                               taex_cp
                                                                Compressor
              tsu_e v
                                                 tasu_cd

Expansion
valve
                                                                                   &
                                                                                   Wcp
                             Manufacturer data

                                                                &
                                                                Q ev           tsu_cp
              tex_e v

              tsu_ev                                               tex_ev    R22
                                       Evaporator



              twex_ev                                   twsu_ev
                                                                       &
                                                                       Mw




    Figure 26 Data usually found in a manufacturer catalogue




    Figure 27 “Block diagram” of the identification procedure




                                                                                         21
Figure 28 Parameters identified for chiller model



Simulation

At this stage, any user can introduce his proper data, in other to calculate the chiller
performances, as shown in Figure 29.




                        Figure 29 Chiller performances calculation




                                                                                       22
Examples of results

                The examples of results presented hereafter are obtained with data provided by both
                manufacturers (A and B) already selected. The agreement between simulation and
                catalogue data is very satisfactory.

                60000                                                                                   20000
                          Qev     Qev,ARI       Qev,part-load,50%                                                       Wcp     Wcp,ARI     Wcp,part-load,50%
                56000
                52000
                                                                                                        16000
                48000
                44000
                40000                                                                                   12000




                                                                                              Wcp [W]
      Qev [W]




                36000
                32000
                                                                                                        8000
                28000
                24000
                20000                                                                                   4000
                16000
                12000
                                                                                                              0
                    12000       20000     28000       36000         44000   52000     60000                    0              4000         8000          12000       16000        20000

                                                Qev,man [W]                                                                                 Wcp,man [W]


                                              Figure 30 Calculated versus catalogue data (manufacturer A)


      50000                                                                                                   20000
                        Qev        Qev ,ARI                                                                                    W          WARI

      45000                                                                                                   18000



      40000                                                                                                   16000
Qev [W]




                                                                                                        [W]




      35000                                                                                                   14000



      30000
                                                                                                        W




                                                                                                              12000



      25000                                                                                                   10000



      20000                                                                                                    8000
         20000           25000          30000        35000          40000     45000      50000                   8000         10000       12000       14000      16000   18000       20000
                                                 Qev,man [W]                                                                                      Wman [W]


                                              Figure 31 Calculated versus catalogue data (manufacturer A)


                Illustration of the measuring method by simulation

                The compressor model (contained in the chiller model already presented) can be
                used for an easy and accurate determination the chiller cooling power on site.
                The two examples of simulation results presented in Figure 32 and Figure 33
                demonstrate that very simple (linear) relationships could be used to determine the
                chiller cooling power as function of the refrigerant pressure measured at compressor
                supply. In full load and at constant rotation speed, this supply pressure is the almost
                unique variable to be considered. A slight shift can be applied to this law as function


                                                                                                                                                                             23
of a second variable: the temperature of the secondary fluid at condenser supply
(Figure 32) or, more directly, the condensing pressure (Figure 33).




    Figure 32 Chiller cooling power as function of the compressor supply pressure (with
            condenser supply air temperature as second independent variable)




    Figure 33 Chiller cooling power as function of the compressor supply pressure (with
              compressor exhaust pressure as second independent variable)


Such procedure is easy to apply on site, because, most of the time, both (evaporation
and condensation) pressures are actually given on the chiller control board…




                                                                                          24

Weitere ähnliche Inhalte

Andere mochten auch

<3 Year Together
<3 Year Together<3 Year Together
<3 Year Togetherbrrowle1
 
Fondos para enviar
Fondos para enviarFondos para enviar
Fondos para enviarrolonare
 
Auditac carbon and cooling in uk office environments dunn knight
Auditac carbon and cooling in uk office environments dunn knightAuditac carbon and cooling in uk office environments dunn knight
Auditac carbon and cooling in uk office environments dunn knightRoyal Mail
 
Marcus evans workshop presentation
Marcus evans workshop presentationMarcus evans workshop presentation
Marcus evans workshop presentationRoyal Mail
 
Aiesec vietnam national award ignite 2012
Aiesec vietnam national award ignite 2012Aiesec vietnam national award ignite 2012
Aiesec vietnam national award ignite 2012Vu Thu Trang
 
Guillermina rolon arellan
Guillermina rolon arellanGuillermina rolon arellan
Guillermina rolon arellanrolonare
 
Using Community Initiatives to Drive Brand Results
Using Community Initiatives to Drive Brand ResultsUsing Community Initiatives to Drive Brand Results
Using Community Initiatives to Drive Brand ResultsDylan Thomas
 
Auditac tg 9 how to integrate eneff and aci with full benefit in the structur...
Auditac tg 9 how to integrate eneff and aci with full benefit in the structur...Auditac tg 9 how to integrate eneff and aci with full benefit in the structur...
Auditac tg 9 how to integrate eneff and aci with full benefit in the structur...Royal Mail
 

Andere mochten auch (8)

<3 Year Together
<3 Year Together<3 Year Together
<3 Year Together
 
Fondos para enviar
Fondos para enviarFondos para enviar
Fondos para enviar
 
Auditac carbon and cooling in uk office environments dunn knight
Auditac carbon and cooling in uk office environments dunn knightAuditac carbon and cooling in uk office environments dunn knight
Auditac carbon and cooling in uk office environments dunn knight
 
Marcus evans workshop presentation
Marcus evans workshop presentationMarcus evans workshop presentation
Marcus evans workshop presentation
 
Aiesec vietnam national award ignite 2012
Aiesec vietnam national award ignite 2012Aiesec vietnam national award ignite 2012
Aiesec vietnam national award ignite 2012
 
Guillermina rolon arellan
Guillermina rolon arellanGuillermina rolon arellan
Guillermina rolon arellan
 
Using Community Initiatives to Drive Brand Results
Using Community Initiatives to Drive Brand ResultsUsing Community Initiatives to Drive Brand Results
Using Community Initiatives to Drive Brand Results
 
Auditac tg 9 how to integrate eneff and aci with full benefit in the structur...
Auditac tg 9 how to integrate eneff and aci with full benefit in the structur...Auditac tg 9 how to integrate eneff and aci with full benefit in the structur...
Auditac tg 9 how to integrate eneff and aci with full benefit in the structur...
 

Ähnlich wie Auditac tg8 how manufacturers could help auditors

391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdfBlentBulut5
 
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...IRJET Journal
 
IRJET- Development of X-Wire Probe for Hot Wire Anemometry
IRJET- Development of X-Wire Probe for Hot Wire AnemometryIRJET- Development of X-Wire Probe for Hot Wire Anemometry
IRJET- Development of X-Wire Probe for Hot Wire AnemometryIRJET Journal
 
Pulsation and Vibration Study Of Reciprocating Compressor According To API 6...
Pulsation and Vibration Study Of Reciprocating Compressor  According To API 6...Pulsation and Vibration Study Of Reciprocating Compressor  According To API 6...
Pulsation and Vibration Study Of Reciprocating Compressor According To API 6...IJMER
 
IRJET- Enhancement of Heat Transfer Effectiveness of Plate-Pin Fin Heat S...
IRJET-  	  Enhancement of Heat Transfer Effectiveness of Plate-Pin Fin Heat S...IRJET-  	  Enhancement of Heat Transfer Effectiveness of Plate-Pin Fin Heat S...
IRJET- Enhancement of Heat Transfer Effectiveness of Plate-Pin Fin Heat S...IRJET Journal
 
IRJET- Thermal Analysis on Solar Air Heater Duct
IRJET- Thermal Analysis on Solar Air Heater DuctIRJET- Thermal Analysis on Solar Air Heater Duct
IRJET- Thermal Analysis on Solar Air Heater DuctIRJET Journal
 
Pulsation and vibration study of reciprocating compressor according to api 618
Pulsation and vibration study of reciprocating compressor according to api 618Pulsation and vibration study of reciprocating compressor according to api 618
Pulsation and vibration study of reciprocating compressor according to api 618John Kingsley
 
Parametric study of_centrifugal_fan_performance_ex
Parametric study of_centrifugal_fan_performance_exParametric study of_centrifugal_fan_performance_ex
Parametric study of_centrifugal_fan_performance_exVnTunNguyn13
 
Development of Software for Sizing of Axial Flow Fans -- Zeus Numerix
Development of Software for Sizing of Axial Flow Fans -- Zeus NumerixDevelopment of Software for Sizing of Axial Flow Fans -- Zeus Numerix
Development of Software for Sizing of Axial Flow Fans -- Zeus NumerixAbhishek Jain
 
Experimental investigation of damping force of twin tube shock absorber
Experimental investigation of damping force of twin tube shock absorberExperimental investigation of damping force of twin tube shock absorber
Experimental investigation of damping force of twin tube shock absorberIJERA Editor
 
cfd analysis on ejector cooling system with variable throat geometry
 cfd analysis on ejector cooling system with variable throat geometry cfd analysis on ejector cooling system with variable throat geometry
cfd analysis on ejector cooling system with variable throat geometryIjripublishers Ijri
 
CFD ANALYSIS IN AN EJECTOR OF GAS TURBINE ENGINE TEST BED
CFD ANALYSIS IN AN EJECTOR OF GAS TURBINE ENGINE TEST BEDCFD ANALYSIS IN AN EJECTOR OF GAS TURBINE ENGINE TEST BED
CFD ANALYSIS IN AN EJECTOR OF GAS TURBINE ENGINE TEST BEDIAEME Publication
 
Ijri te-03-010 cfd analysis on ejector cooling system with variable throat ge...
Ijri te-03-010 cfd analysis on ejector cooling system with variable throat ge...Ijri te-03-010 cfd analysis on ejector cooling system with variable throat ge...
Ijri te-03-010 cfd analysis on ejector cooling system with variable throat ge...Ijripublishers Ijri
 
Review Paper on Experimental Analysis of Vortex Tube
Review Paper on Experimental Analysis of Vortex TubeReview Paper on Experimental Analysis of Vortex Tube
Review Paper on Experimental Analysis of Vortex TubeIRJET Journal
 
Flow Field Measurements in a Large Controlled Ventilated Room
Flow Field Measurements in a Large Controlled Ventilated RoomFlow Field Measurements in a Large Controlled Ventilated Room
Flow Field Measurements in a Large Controlled Ventilated RoomIRJET Journal
 
An overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testingAn overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testingBill Spohn
 

Ähnlich wie Auditac tg8 how manufacturers could help auditors (20)

391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf391861703-Mod-5-Fan-Measurement-and-Testing.pdf
391861703-Mod-5-Fan-Measurement-and-Testing.pdf
 
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
IRJET- Design and Simulation of an Ejector as an Expansion Device for Constan...
 
IRJET- Development of X-Wire Probe for Hot Wire Anemometry
IRJET- Development of X-Wire Probe for Hot Wire AnemometryIRJET- Development of X-Wire Probe for Hot Wire Anemometry
IRJET- Development of X-Wire Probe for Hot Wire Anemometry
 
Pulsation and Vibration Study Of Reciprocating Compressor According To API 6...
Pulsation and Vibration Study Of Reciprocating Compressor  According To API 6...Pulsation and Vibration Study Of Reciprocating Compressor  According To API 6...
Pulsation and Vibration Study Of Reciprocating Compressor According To API 6...
 
IRJET- Enhancement of Heat Transfer Effectiveness of Plate-Pin Fin Heat S...
IRJET-  	  Enhancement of Heat Transfer Effectiveness of Plate-Pin Fin Heat S...IRJET-  	  Enhancement of Heat Transfer Effectiveness of Plate-Pin Fin Heat S...
IRJET- Enhancement of Heat Transfer Effectiveness of Plate-Pin Fin Heat S...
 
IRJET- Thermal Analysis on Solar Air Heater Duct
IRJET- Thermal Analysis on Solar Air Heater DuctIRJET- Thermal Analysis on Solar Air Heater Duct
IRJET- Thermal Analysis on Solar Air Heater Duct
 
Pulsation and vibration study of reciprocating compressor according to api 618
Pulsation and vibration study of reciprocating compressor according to api 618Pulsation and vibration study of reciprocating compressor according to api 618
Pulsation and vibration study of reciprocating compressor according to api 618
 
Parametric study of_centrifugal_fan_performance_ex
Parametric study of_centrifugal_fan_performance_exParametric study of_centrifugal_fan_performance_ex
Parametric study of_centrifugal_fan_performance_ex
 
Development of Software for Sizing of Axial Flow Fans -- Zeus Numerix
Development of Software for Sizing of Axial Flow Fans -- Zeus NumerixDevelopment of Software for Sizing of Axial Flow Fans -- Zeus Numerix
Development of Software for Sizing of Axial Flow Fans -- Zeus Numerix
 
Experimental investigation of damping force of twin tube shock absorber
Experimental investigation of damping force of twin tube shock absorberExperimental investigation of damping force of twin tube shock absorber
Experimental investigation of damping force of twin tube shock absorber
 
M01312106112
M01312106112M01312106112
M01312106112
 
Airflow detector
Airflow detectorAirflow detector
Airflow detector
 
Lp3420942103
Lp3420942103Lp3420942103
Lp3420942103
 
cfd analysis on ejector cooling system with variable throat geometry
 cfd analysis on ejector cooling system with variable throat geometry cfd analysis on ejector cooling system with variable throat geometry
cfd analysis on ejector cooling system with variable throat geometry
 
CFD ANALYSIS IN AN EJECTOR OF GAS TURBINE ENGINE TEST BED
CFD ANALYSIS IN AN EJECTOR OF GAS TURBINE ENGINE TEST BEDCFD ANALYSIS IN AN EJECTOR OF GAS TURBINE ENGINE TEST BED
CFD ANALYSIS IN AN EJECTOR OF GAS TURBINE ENGINE TEST BED
 
Ijri te-03-010 cfd analysis on ejector cooling system with variable throat ge...
Ijri te-03-010 cfd analysis on ejector cooling system with variable throat ge...Ijri te-03-010 cfd analysis on ejector cooling system with variable throat ge...
Ijri te-03-010 cfd analysis on ejector cooling system with variable throat ge...
 
Review Paper on Experimental Analysis of Vortex Tube
Review Paper on Experimental Analysis of Vortex TubeReview Paper on Experimental Analysis of Vortex Tube
Review Paper on Experimental Analysis of Vortex Tube
 
Flow Field Measurements in a Large Controlled Ventilated Room
Flow Field Measurements in a Large Controlled Ventilated RoomFlow Field Measurements in a Large Controlled Ventilated Room
Flow Field Measurements in a Large Controlled Ventilated Room
 
An overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testingAn overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testing
 
Pneumatic Handbook.pdf
Pneumatic Handbook.pdfPneumatic Handbook.pdf
Pneumatic Handbook.pdf
 

Mehr von Royal Mail

Sample energy survey overview
Sample energy survey overviewSample energy survey overview
Sample energy survey overviewRoyal Mail
 
Managing energy consumption to improve forecasting checklist
Managing energy consumption to improve forecasting checklistManaging energy consumption to improve forecasting checklist
Managing energy consumption to improve forecasting checklistRoyal Mail
 
Comfortable energy reduction checklist
Comfortable energy reduction checklistComfortable energy reduction checklist
Comfortable energy reduction checklistRoyal Mail
 
Best practice checklist
Best practice checklistBest practice checklist
Best practice checklistRoyal Mail
 
Carbon footprinting checklist
Carbon footprinting checklistCarbon footprinting checklist
Carbon footprinting checklistRoyal Mail
 
Phil Evans CV April 2012
Phil Evans CV April 2012Phil Evans CV April 2012
Phil Evans CV April 2012Royal Mail
 
Luxury flats energy survey report
Luxury flats energy survey reportLuxury flats energy survey report
Luxury flats energy survey reportRoyal Mail
 
Retailer x distribution centre walkround energy survey april 2010
Retailer x distribution centre walkround energy survey april 2010Retailer x distribution centre walkround energy survey april 2010
Retailer x distribution centre walkround energy survey april 2010Royal Mail
 
Green bridge phil evans energy saving booklet 2012
Green bridge phil evans energy saving booklet 2012Green bridge phil evans energy saving booklet 2012
Green bridge phil evans energy saving booklet 2012Royal Mail
 
Purpose pyramid sept 2011
Purpose pyramid sept 2011Purpose pyramid sept 2011
Purpose pyramid sept 2011Royal Mail
 
Sample building energy performance proposal jan 2012
Sample building energy performance proposal jan 2012Sample building energy performance proposal jan 2012
Sample building energy performance proposal jan 2012Royal Mail
 
Phil Evans CV January 2012
Phil Evans CV January 2012Phil Evans CV January 2012
Phil Evans CV January 2012Royal Mail
 
Audit ac tech guide for owner manager of acs vol 1 are you sure you are not p...
Audit ac tech guide for owner manager of acs vol 1 are you sure you are not p...Audit ac tech guide for owner manager of acs vol 1 are you sure you are not p...
Audit ac tech guide for owner manager of acs vol 1 are you sure you are not p...Royal Mail
 
Tg 2 auditing of acs and epbd
Tg 2 auditing of acs and epbdTg 2 auditing of acs and epbd
Tg 2 auditing of acs and epbdRoyal Mail
 
Auditac tg3 system recognition for field visit
Auditac tg3 system recognition for field visitAuditac tg3 system recognition for field visit
Auditac tg3 system recognition for field visitRoyal Mail
 
Auditac tg4 prelim audit methodology for ac
Auditac tg4 prelim audit methodology for acAuditac tg4 prelim audit methodology for ac
Auditac tg4 prelim audit methodology for acRoyal Mail
 
Auditac tg 5 energy conservation opportunities
Auditac  tg 5 energy conservation opportunitiesAuditac  tg 5 energy conservation opportunities
Auditac tg 5 energy conservation opportunitiesRoyal Mail
 
Auditac tg4 prelim audit methodology for ac
Auditac tg4 prelim audit methodology for acAuditac tg4 prelim audit methodology for ac
Auditac tg4 prelim audit methodology for acRoyal Mail
 
Auditac tg 5 energy conservation opportunities
Auditac  tg 5 energy conservation opportunitiesAuditac  tg 5 energy conservation opportunities
Auditac tg 5 energy conservation opportunitiesRoyal Mail
 
Auditac tg 6 how to benefit from eurovent cert database and retrieve past eq...
Auditac  tg 6 how to benefit from eurovent cert database and retrieve past eq...Auditac  tg 6 how to benefit from eurovent cert database and retrieve past eq...
Auditac tg 6 how to benefit from eurovent cert database and retrieve past eq...Royal Mail
 

Mehr von Royal Mail (20)

Sample energy survey overview
Sample energy survey overviewSample energy survey overview
Sample energy survey overview
 
Managing energy consumption to improve forecasting checklist
Managing energy consumption to improve forecasting checklistManaging energy consumption to improve forecasting checklist
Managing energy consumption to improve forecasting checklist
 
Comfortable energy reduction checklist
Comfortable energy reduction checklistComfortable energy reduction checklist
Comfortable energy reduction checklist
 
Best practice checklist
Best practice checklistBest practice checklist
Best practice checklist
 
Carbon footprinting checklist
Carbon footprinting checklistCarbon footprinting checklist
Carbon footprinting checklist
 
Phil Evans CV April 2012
Phil Evans CV April 2012Phil Evans CV April 2012
Phil Evans CV April 2012
 
Luxury flats energy survey report
Luxury flats energy survey reportLuxury flats energy survey report
Luxury flats energy survey report
 
Retailer x distribution centre walkround energy survey april 2010
Retailer x distribution centre walkround energy survey april 2010Retailer x distribution centre walkround energy survey april 2010
Retailer x distribution centre walkround energy survey april 2010
 
Green bridge phil evans energy saving booklet 2012
Green bridge phil evans energy saving booklet 2012Green bridge phil evans energy saving booklet 2012
Green bridge phil evans energy saving booklet 2012
 
Purpose pyramid sept 2011
Purpose pyramid sept 2011Purpose pyramid sept 2011
Purpose pyramid sept 2011
 
Sample building energy performance proposal jan 2012
Sample building energy performance proposal jan 2012Sample building energy performance proposal jan 2012
Sample building energy performance proposal jan 2012
 
Phil Evans CV January 2012
Phil Evans CV January 2012Phil Evans CV January 2012
Phil Evans CV January 2012
 
Audit ac tech guide for owner manager of acs vol 1 are you sure you are not p...
Audit ac tech guide for owner manager of acs vol 1 are you sure you are not p...Audit ac tech guide for owner manager of acs vol 1 are you sure you are not p...
Audit ac tech guide for owner manager of acs vol 1 are you sure you are not p...
 
Tg 2 auditing of acs and epbd
Tg 2 auditing of acs and epbdTg 2 auditing of acs and epbd
Tg 2 auditing of acs and epbd
 
Auditac tg3 system recognition for field visit
Auditac tg3 system recognition for field visitAuditac tg3 system recognition for field visit
Auditac tg3 system recognition for field visit
 
Auditac tg4 prelim audit methodology for ac
Auditac tg4 prelim audit methodology for acAuditac tg4 prelim audit methodology for ac
Auditac tg4 prelim audit methodology for ac
 
Auditac tg 5 energy conservation opportunities
Auditac  tg 5 energy conservation opportunitiesAuditac  tg 5 energy conservation opportunities
Auditac tg 5 energy conservation opportunities
 
Auditac tg4 prelim audit methodology for ac
Auditac tg4 prelim audit methodology for acAuditac tg4 prelim audit methodology for ac
Auditac tg4 prelim audit methodology for ac
 
Auditac tg 5 energy conservation opportunities
Auditac  tg 5 energy conservation opportunitiesAuditac  tg 5 energy conservation opportunities
Auditac tg 5 energy conservation opportunities
 
Auditac tg 6 how to benefit from eurovent cert database and retrieve past eq...
Auditac  tg 6 how to benefit from eurovent cert database and retrieve past eq...Auditac  tg 6 how to benefit from eurovent cert database and retrieve past eq...
Auditac tg 6 how to benefit from eurovent cert database and retrieve past eq...
 

Kürzlich hochgeladen

Market Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMarket Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMintel Group
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Seta Wicaksana
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Pereraictsugar
 
Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...Americas Got Grants
 
Guide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDFGuide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDFChandresh Chudasama
 
1911 Gold Corporate Presentation Apr 2024.pdf
1911 Gold Corporate Presentation Apr 2024.pdf1911 Gold Corporate Presentation Apr 2024.pdf
1911 Gold Corporate Presentation Apr 2024.pdfShaun Heinrichs
 
8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCR8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCRashishs7044
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?Olivia Kresic
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCRashishs7044
 
Financial-Statement-Analysis-of-Coca-cola-Company.pptx
Financial-Statement-Analysis-of-Coca-cola-Company.pptxFinancial-Statement-Analysis-of-Coca-cola-Company.pptx
Financial-Statement-Analysis-of-Coca-cola-Company.pptxsaniyaimamuddin
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessSeta Wicaksana
 
TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024Adnet Communications
 
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!Doge Mining Website
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckHajeJanKamps
 
Appkodes Tinder Clone Script with Customisable Solutions.pptx
Appkodes Tinder Clone Script with Customisable Solutions.pptxAppkodes Tinder Clone Script with Customisable Solutions.pptx
Appkodes Tinder Clone Script with Customisable Solutions.pptxappkodes
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy Verified Accounts
 
Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737Riya Pathan
 
International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...ssuserf63bd7
 

Kürzlich hochgeladen (20)

Market Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 EditionMarket Sizes Sample Report - 2024 Edition
Market Sizes Sample Report - 2024 Edition
 
Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...Ten Organizational Design Models to align structure and operations to busines...
Ten Organizational Design Models to align structure and operations to busines...
 
Kenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith PereraKenya Coconut Production Presentation by Dr. Lalith Perera
Kenya Coconut Production Presentation by Dr. Lalith Perera
 
Corporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information TechnologyCorporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information Technology
 
Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...Church Building Grants To Assist With New Construction, Additions, And Restor...
Church Building Grants To Assist With New Construction, Additions, And Restor...
 
Guide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDFGuide Complete Set of Residential Architectural Drawings PDF
Guide Complete Set of Residential Architectural Drawings PDF
 
1911 Gold Corporate Presentation Apr 2024.pdf
1911 Gold Corporate Presentation Apr 2024.pdf1911 Gold Corporate Presentation Apr 2024.pdf
1911 Gold Corporate Presentation Apr 2024.pdf
 
8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCR8447779800, Low rate Call girls in Saket Delhi NCR
8447779800, Low rate Call girls in Saket Delhi NCR
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?
 
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
 
Financial-Statement-Analysis-of-Coca-cola-Company.pptx
Financial-Statement-Analysis-of-Coca-cola-Company.pptxFinancial-Statement-Analysis-of-Coca-cola-Company.pptx
Financial-Statement-Analysis-of-Coca-cola-Company.pptx
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful Business
 
TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024TriStar Gold Corporate Presentation - April 2024
TriStar Gold Corporate Presentation - April 2024
 
Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)Japan IT Week 2024 Brochure by 47Billion (English)
Japan IT Week 2024 Brochure by 47Billion (English)
 
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
Unlocking the Future: Explore Web 3.0 Workshop to Start Earning Today!
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
 
Appkodes Tinder Clone Script with Customisable Solutions.pptx
Appkodes Tinder Clone Script with Customisable Solutions.pptxAppkodes Tinder Clone Script with Customisable Solutions.pptx
Appkodes Tinder Clone Script with Customisable Solutions.pptx
 
Buy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail AccountsBuy gmail accounts.pdf Buy Old Gmail Accounts
Buy gmail accounts.pdf Buy Old Gmail Accounts
 
Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737Independent Call Girls Andheri Nightlaila 9967584737
Independent Call Girls Andheri Nightlaila 9967584737
 
International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...International Business Environments and Operations 16th Global Edition test b...
International Business Environments and Operations 16th Global Edition test b...
 

Auditac tg8 how manufacturers could help auditors

  • 1. Technical guides for owner/manager of an air conditioning system: volume 8 How manufacturers could help the unfortunate energy auditor
  • 2. Team France (Project coordinator) Armines - Mines de Paris Austria Slovenia Austrian Energy Agency University of Ljubljana Belgium UK Université de Liège Association of Building Engineers Italy BRE Politecnico di Torino (Building Research Establishment Ltd) Portugal University of Porto Welsh School of Architecture Eurovent-Certification Authors of this volume Cleide Aparecida Silva (Université de Liège) Cristian Cuevas (Université de Liège) Jules Hannay (Université de Liège) Jean Lebrun (Université de Liège) Vladut Teodorese (Université de Liège) The sole responsibility for the content of this publication lies with the authors. It does not represent the opinion of the European Communities. The European Commission is not responsible for any use that may be made of the information contained therein. 2
  • 3. Introduction As already demonstrated in other chapters of the present report, the energy audit of a whole HVAC system is not a funny game. On site measurements are unavoidable and cost a lot of time and money. Obviously, in most installations, the highest energy consumers are the fans. The chillers are then coming in second position. The nominal performances of these components are usually well identified in laboratory and in manufacturers catalogues. But their average performances are more questionable in actual conditions of use. From other part, providing that these components are correctly identified and modelled, they may become valuable measuring instruments. The object of this chapter is to show how the components manufacturers could help the auditor by allowing him to make a better use of the information they already have. Using a fan as air flow meter The principle Airflow rates measurements are difficult in existing distribution networks: long enough straight lines are seldom available or accessible and velocity profiles are usually not uniform enough. A large series of measuring points is required and the final accuracy is often disappointing. A much better solution consists in using the fan as an air flow meter. This can be done in two ways: 1) By taking profit of the well known characteristics of the fan and using easy measurements, as supply and exhaust static pressures, rotation speed and/or electrical power; 2) Even better, by measuring just one reference pressure drop at fan supply. Both procedures are illustrated and validated hereafter. Fan characteristics identified on the basis of manufacturer data A fan is currently modelled with the help of similarity variables: flow, pressure and power factors. These factors can be correlated to each other by polynomial expressions. The main output of a fan model can be the airflow rate, expressed in “specific” value (in kg/s of dry air), as usually in air conditioning. Other outputs can be the different factors, exhaust air speed, total pressure difference, isentropic power and (isentropic) temperature increase across the fan (these two last outputs can be used as checking information). The fan is supposed to be characterised by the diameter of its impeller (scale variable), its (fictitious) exhaust area and the coefficients of the polynomial correlations. Supply air conditions (temperature, pressure and moisture content), rotation speed and static pressure difference are taken as input variables. 3
  • 4. This gives the information flow diagram of Figure 1. Figure 1: Example of fan polynomial model The first equations of this model are built on the basis of the definitions of two (flow and pressure) similarity factors: Two dynamic pressures are considered: one at the exhaust and the other one at the periphery of the impeller: 4
  • 5. The other non-dimensional variables considered are the isentropic effectiveness and the power factor: The three factors are inter-correlated through polynomial laws such as: This model is from long time well validated and easy to tune…Polynomials are fitted to manufacturer’s performance data. Total and static pressures have to be carefully distinguished at fan exhaust: manufacturers present fan performance in terms of total pressure rise, whereas the measurements are usually made in terms of static pressures. Fan characteristics are generally provided by the manufacturers as “data sheets”, showing the operating curves of the fan (relationships among the different variables of the system). A typical example of data sheet is presented in Figure 2. This information might be better used if the manufacturers were giving: The experimental points actually available; The correlation equations actually used to generate the curves. Still today, the fan simulation model built by the manufacturer is only “offered” to “important” customers as manufacturers of air handling units. The equations are then embedded inside black box selection and simulation software. 5
  • 6. Figure 2 Fan characteristics as presented by the manufacturer Some points can be selected in the diagram of Figure 2, in order to identify the polynomial laws already presented. An example of selection is made on Figure 3; it corresponds to three different rotation speeds. Figure 3 Reference points selected for parameter identification The phi-psi and lambda-psi regression curves identified on these points are presented in Figure 4 and Figure 5. 6
  • 7. Figure 4 Identification of the phi-psi characteristic Figure 5 Identification of the lambda-psi characteristic A phi – psi characteristic appears to be accurate enough for airflow rate measurements, when the fan has backward-curved blades (as in the present case). The airflow rate can be currently determined with an accuracy of about 5 %. In the case of fans with forward-curved blades, the pressure rise is relatively insensitive to airflow rate and a more accurate result can be obtained by using the efficiency characteristic. The electrical consumption is then a better indicator of the flow rate. However, this second approach requires a correct identification of all electrical losses (electrical motor and frequency driver, if any). Experimental validation The fan The validation is performed on the fan whose characteristics were already identified. The fan considered in this study was originally installed in a box, downstream of a “radiator”(Figure 6). 7
  • 8. Figure 6 the tested fan Tightness of the fan box A first experimental arrangement (Figure 7) was made in order to verify the tightness of the fan box. The tightness test consisted in injecting air inside the box, thanks to an auxiliary fan, after having closed both (supply and exhaust) openings. Injected airflow rate and box-ambient over-pressure were simultaneously measured. This allows identifying a fictitious leakage area. An example of measuring result is shown in Figure 8. In the case considered, the leakage flow rate is estimated to 16.8 g/s, which corresponds to a leakage (fictitious isentropic nozzle throat) diameter of 27.3 mm. Fan box Small fan Figure 7 Experimental identification of the fan box leakage area 8
  • 9. φ 30/60 mm. Fan box tamb = 20,5°C HRamb = 54 % ∆P = 604 Pa Patm = 981 mbar ∆P = 350 Pa Figure 8 Leakage measurement Experimental characterization of the fan The fan system is characterised at different rotation speeds; it’s equipped with a frequency inverter working between 8.5 and 50.5 Hz. The experimental arrangement is shown in Figures 9 to 11. Three tests series have been performed: they correspond to three pressure drop characteristics of the air circuit: 1) With coil and with a diaphragm used to measure the flow rate (highest pressure drop) 2) With coil and with a nozzle used to measure the flow rate (medium pressure drop) 3) Without coil and with a nozzle used to measure the flow rate (lowest pressure drop). ∆Prad ∆Paf ∆Pop tamb HRamb Patm & Win Ninv finv & Wm I Figure 9 Experimental characterization of the fan (principle schema) 9
  • 10. Figure 10 Experimental arrangement (back view) Figure 11 Experimental arrangement (front view) The inverter is provided with direct measurements of the frequency and of the electrical power supplied to the fan motor. The electrical power supplied to the inverter and the fan rotation speeds are also measured in these tests. This makes possible to identify the inverter loss and the frequency “sliding” of the electric motor. The tests results are presented in Figure 12 and Figure 13. Figure 12 Inverter loss and efficiency 10
  • 11. Figure 13 Motor sliding As it can be seen here, both the inverter loss and the motor sliding can be identified through linear correlations. By combining these measuring results with the characteristics already identified (from manufacturer data), it’s also possible to identify: 1) The global electromechanical loss and corresponding efficiency of the inverter- motor subsystem (Figure 14); 2) The same terms for the whole inverter-motor-fan system (Figure 15). Such characteristics would be easy to combine with on site measurements. Figure 14 Fan shaft power as function of motor electrical power 11
  • 12. Figure 15 Global loss and global efficiency The test results were also used to validate the laws identified from manufacturer data. An example of such checking is presented in Figure 16: simulated and measured total pressure differences are compared for same flow rates and rotation speeds. The agreement is considered as satisfactory (the actual total pressure at fan exhaust is not directly measured here, but re-calculated by reference to a hypothetical exhaust area). Figure 16 Comparison among simulated and measured pressure differences Validation of a much more expedient method A much more expedient method is proposed by some manufacturers (as the present one). The fan selected for this study was equipped with openings and connecting pipes for differential pressure measurements as shown in Figure 17 and Figure 18. 12
  • 13. Figure 17 Differential pressure measuring device (principle) Figure 18 Measuring device (outside the fan) Figure 19 Measuring device (inside the fan) The measuring principle is described in the manufacturer catalogue as follows: 13
  • 14. This means that the fan inlet is used as a measuring nozzle. The “K” constant “contains” the flow contraction effect. The method can be validated with the test results available. A fictitious nozzle exhaust diameter is identified at each regime. Examples of results are presented in Figure 20. Figure 20 Exhaust diameter of the (fictitious) fan supply nozzle A (fairly constant) fictitious diameter of 193 mm is here identified. The actual diameter is 257 mm. This corresponds to a contraction factor of (193/257)2 = 0.564 and is in good agreement with the “K” value indicated by the manufacturer. Using refrigeration compressor as enthalpy flow meter The principle Determining on site the cooling power actually provided by a chiller is also a delicate matter. That power should correspond to the enthalpy flow of the secondary fluid (usually water or brine) supplying the evaporator. But neither the flow rate, nor the supply-exhaust temperature difference are easy to measure. The measurements are not easier on refrigerant side. 14
  • 15. An interesting alternative consists in using the chiller compressor as enthalpy flow meter. But, as seen hereafter, this would require a better dialog with manufacturers… Data provided by the manufacturers Analysis Each manufacturer seems having his own way to present data in his catalogue. Unfortunately, this “personal” presentation can be a source of confusion. Data available are nor fully clear, neither complete and the reader is, most of the time, recommended to“…contact the local manufacturer office…” as solution. Unfortunately, these offices are not always able to help: it may occur that the information is just no more available, because of too old machines, no more produced or replaced by new models. Some examples of machine designations and physical data presentations used by some manufacturers are presented hereafter, outlining the differences found among them. Examples Figure 21 gives the designation data found in the catalogue data of manufacturer A. Manufacturer A Evaporator cooling capacity Figure 21 Chiller designation of manufacturer A. Figure 22 gives the designation data found in the catalogue of manufacturer B. 15
  • 16. Reference evaporator cooling capacity – Nominal Tons Figure 22: Chiller designation of manufacturer B The presentation of physical data is not standardized, as seen in Figure 21 and Figure 22. Here also, each manufacturer has his personalised presentation and attention must be paid to each item presented (nominal loads, refrigerant type, fan capacity, flow rates, etc.), when manipulating catalogues coming from different manufacturers. The units must be carefully identified: Some manufacturers use a “semi- SI” system with kW, bar, kg/s, m³/h, etc. Other ones are still using Imperial units. But other elementary questions must be answered, as, for example, if the data refers to one, or to several devices (e.g. one or two condenser fans), to partial or global air flow rate, etc. 16
  • 17. ! n ntio Atte Figure 23 Chiller physical data given by manufacturer A 17
  • 18. Figure 24 Chiller, physical data given by manufacturer B ARI and Eurovent standards Hopefully, standardized ARI and/or Eurovent reference data are usually also available in main manufacturer catalogues and can be freely downloaded from Internet. This is a great advantage for the users. There exist other standards, but they are not free! 18
  • 19. Chiller modelling and parameter identification Modelling Various simulation models are currently available. An example of information flow diagram used for chiller modelling is presented in Figure 22. It corresponds to the model of a chiller with scroll compressor(s) and with air-cooled condenser. In this model, the condenser and the evaporator are modelled as fictitious semi-isothermal heat exchangers. A hypothetical proportional control law is applied to the condenser fan. Figure 25 Example information flow diagram The same model can be used in two steps: 1) Parameter identification on one or several reference points; 2) Simulation in all other conditions of use. Attention must be paid to the domain of validity of such model, after tuning: according to the manufacturer: no extrapolation should be done outside the domain covered by the catalogue. Parameter identification This is most delicate operation. If well done, simulation is no more a problem. Figure 26 shows the data usually found in the manufacturer catalogue. A “block diagram” of the identification procedure is presented in Figure 27. The parameters identified are indicated in Figure 28. The identification process can be done “manually” and iteratively, by considering the result trends after each step. Default values are used as first guesses for each component separately at the nominal point. These values are tuned in order to obtain results that fit to all orders of magnitude. Finally the parameters are tuned again, in order to obtain a better agreement with all experimental results and/or all manufacturer data available. 19
  • 20. The parameter identification is considered as satisfactory if all thermal and electrical powers are predicted with accuracy of the order of ± 2 %. 20
  • 21. cd – condenser ev – evaporator taex_cd cp – compressor e v – expansion valve Air tex_cd Condenser tsu_cd taex_cp Compressor tsu_e v tasu_cd Expansion valve & Wcp Manufacturer data & Q ev tsu_cp tex_e v tsu_ev tex_ev R22 Evaporator twex_ev twsu_ev & Mw Figure 26 Data usually found in a manufacturer catalogue Figure 27 “Block diagram” of the identification procedure 21
  • 22. Figure 28 Parameters identified for chiller model Simulation At this stage, any user can introduce his proper data, in other to calculate the chiller performances, as shown in Figure 29. Figure 29 Chiller performances calculation 22
  • 23. Examples of results The examples of results presented hereafter are obtained with data provided by both manufacturers (A and B) already selected. The agreement between simulation and catalogue data is very satisfactory. 60000 20000 Qev Qev,ARI Qev,part-load,50% Wcp Wcp,ARI Wcp,part-load,50% 56000 52000 16000 48000 44000 40000 12000 Wcp [W] Qev [W] 36000 32000 8000 28000 24000 20000 4000 16000 12000 0 12000 20000 28000 36000 44000 52000 60000 0 4000 8000 12000 16000 20000 Qev,man [W] Wcp,man [W] Figure 30 Calculated versus catalogue data (manufacturer A) 50000 20000 Qev Qev ,ARI W WARI 45000 18000 40000 16000 Qev [W] [W] 35000 14000 30000 W 12000 25000 10000 20000 8000 20000 25000 30000 35000 40000 45000 50000 8000 10000 12000 14000 16000 18000 20000 Qev,man [W] Wman [W] Figure 31 Calculated versus catalogue data (manufacturer A) Illustration of the measuring method by simulation The compressor model (contained in the chiller model already presented) can be used for an easy and accurate determination the chiller cooling power on site. The two examples of simulation results presented in Figure 32 and Figure 33 demonstrate that very simple (linear) relationships could be used to determine the chiller cooling power as function of the refrigerant pressure measured at compressor supply. In full load and at constant rotation speed, this supply pressure is the almost unique variable to be considered. A slight shift can be applied to this law as function 23
  • 24. of a second variable: the temperature of the secondary fluid at condenser supply (Figure 32) or, more directly, the condensing pressure (Figure 33). Figure 32 Chiller cooling power as function of the compressor supply pressure (with condenser supply air temperature as second independent variable) Figure 33 Chiller cooling power as function of the compressor supply pressure (with compressor exhaust pressure as second independent variable) Such procedure is easy to apply on site, because, most of the time, both (evaporation and condensation) pressures are actually given on the chiller control board… 24