SERVICES


Why Decontaminate?

                                The compelling case
                                for a regular Data Centre
                                health regime

Unplanned downtime in a Data Centre environment can                              The awareness of maintaining a
prove extremely costly, and most organisations have a                            ‘clean’ environment is growing
                                                                                 amongst the standards and the
detailed and prescriptive preventative maintenance regime                        OEM communities:
designed to mitigate the risk of such downtime. Typically,                       n   A number of hardware
                                                                                     
this regime would include monitoring and maintaining such                            manufacturers are considering the
factors as power, temperature and humidity, with particular                          cleanliness of the environment as a
                                                                                     factor when assessing the validity of
focus on the management of the airflow to ensure optimum
                                                                                     RMA and warranty claims
and requisite cooling. Contamination management is one
                                                                                 n   Several major manufacturers
                                                                                     
area that is only included on the regimes of either the more                         recommend in their hardware
enlightened Data Centre Managers or those that have                                  installation guidelines that “every 	
experienced downtime.                                                                effort should be made to ensure that
                                                                                     the target environment is as dust
                                                                                     and particulate free as possible”.
                                         No matter what its source               n   ISO 14644-1 Air Cleanliness
                                                                                     
                                         contamination can be extremely              guidelines are encouraging
                                         hazardous within a data centre:             compliance as an inherent part of the
                                         n   Dust and other particles can
                                                                                    Data Centre management process.
                                             clog air intake grills on cooling
                                                                                 The benefits of professional Data
                                             units and fans resulting in
                                                                                 Centre decontamination include:
                                             overheating, cooling equipment
                                             operating beyond capacity           n   I
                                                                                     mproved efficacy of cooling systems
                                             causing premature failure,          n   I
                                                                                     ncreased longevity and
Contamination can take various
                                             power overloads and outages             performance of hardware
forms, however over 80% of
all contaminants within a Data           n   Metal particulates such as
                                                                                n   I
                                                                                     mproved power consumption
                                             zinc whiskers can cause
Centre environment is caused                                                     n   I
                                                                                     ncreased reliability of data centre
                                             electrical shorts in equipment          uptime
by human traffic, whether this is
dust, particulate from cardboard         n   Dust and other contaminants
                                                                                n   C
                                                                                      ompliance with contamination
and packaging or contamination               can either block fire detection         best practice guidelines
created from works within the                systems preventing effective
                                             use or can actually trigger false   n   F
                                                                                      ull preventative maintenance
Data Centre. Some contamination                                                      regime
                                             alarms or actual discharge.
derives from the environment itself
                                             Airflow and the resulting cooling
                                                                                n   P
                                                                                      eace of mind through risk mitigation
including concrete particles from        n
an untreated sub floor, or fibres            can be seriously impacted by
from air filters or zinc whiskers            contaminants and debris within
                                             the subfloor and floor grills.
from oxidising metal.




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com             The Power of Prevention
SERVICES


Our Services


                                The checklist for ultimate
                                Data Centre health

8 Solutions is a Data Centre Healthcare provider operating
through two divisions; Cleaning and Decontamination and
Mechanical Services.


                                           Cleaning and                            Mechanical Services
                                           Decontamination                         n   Flooring Audits
                                                                                       
                                           Services                                    • Health and Safety
                                                                                       • Floor Integrity
                                           n   Deep Clinical Cleaning
                                               
                                               • From sub floor to high levels     n   Remedial Solutions
                                                                                       
                                                                                       • Replacement panels/sections
                                                                                         
                                           n   Maintenance Cleaning
                                               
                                                                                       • Upgrades
                                                                                         
                                               •  rom floor surface
                                                 F
                                                 to high levels                           – Stringers/pedestals
                                                                                       • Replacement of pedestals
                                           n   Surface Cleaning
                                                                                      • nstallation/securing pedestals
                                                                                         I
                                               • All surfaces                          • ESD replacement/repair
                                           n   Post Construction Services
                                                                                      • Floor strengthening
                                               • Builders Clean                        • Sub floor sealing
                                                 – Preparation for fitout
                                                                                   n   Ingress
                                                                                       
                                               • Enhanced Builders Clean
                                                                                         • nstallation of
                                                                                           I
                                                 – Preparation for use                     Koldlocks/grills
                                           n   Specialist Internal Rack Cleaning
                                                                                        • nstallation of cable
                                                                                           I
                                                                                           access points
                                               • To individual component level
                                                                                   n   Airflow
                                                                                       
                                           n   Emergency Response Service
                                               
                                                                                         • Analysis
                                               • Rapid deployment capability
                                                                                         • Remediation
                                           n   Comprehesive cleaning regime
                                               
                                               •  esigned to maintain optimum
                                                 D
                                                 levels of cleanliness and
                                                 performance




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com               The Power of Prevention
Our Services cont.

Operating                        1.     Client interest
Methodology
                                        Client confirms requirements, room sizes and location(s)


                                 2.     Comprehensive site survey conducted

                                       A site survey is required for all sites in excess of 200 square metres
                                       A self assessment survey is utilised for all sites less than 200
                                       square metres


                                 3.     8 Solutions provides a proposal and quotation

                                       8 Solutions provides a detailed proposal of services, methodologies
                                       and RAMS


                                 4.    Client submits/8 Solutions receives purchase order

                                       8 Solutions receives purchase order from the client
                                       8 Solutions proposes service schedule to client


                                 5.    Schedule of service agreed with client

                                       8 Solutions confirms schedule of services with client
                                       Confirmation of team members


                                 6.    8 Solutions delivers service

                                       8 Solutions attend site, and confirm health and safety requirements
                                       8 Solutions pre-service check including utilities and fire systems


                                 7.    8 Solutions submits a “post clean” report to client

                                       Detailed reports submitted to client on status of clean
                                       Any issues identified including flooring, health and safety contamination


                                 8.    8 Solutions post clean quality checks

                                       All clients are invited to respond to an email based quality audit
                                       8 Solutions conducts on-site post clean quality checks on a random basis




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com             The Power of Prevention
SERVICES


Deep Clinical Cleaning

                                A Data Centre clean
                                in infinite detail


Overview
An 8 Solutions Deep Clinical Clean is an intensive service                       n   A
                                                                                      nti-static wipe down of panel
designed to achieve an ISO 14644-1 level 6 standard of air                           undersides
cleanliness. It addresses every area within the Data Centre,                     n   T
                                                                                      he replacement of floor panels
from the subfloor surface up to the underside of the panels                          in accordance with 8 Solutions
                                                                                     best practice
and the floor surface, all walls, doors, ledges, and cabinet
externals. It will also address all high levels including ceiling                Whilst in the floor void the
                                                                                 8 Solutions technicians will affect
voids, overhead cabling and cable trays, all lighting including                  the following maintenance checks:
suspension systems and all building support infrastructure                       n   Visual check for zinc whiskers
                                                                                     
including roof supports and ceiling and roof surfaces.


Service detail                           Floor void
Before work begins, a thorough           The cleaning regime to address
check is performed to identify           the floor void will encompass the
all utilities including emergency        following procedures:
power off switches, all fire             n   Initial cleaning of the floor
                                             
                                                                                 n   Integrity of pedestals
                                                                                     
detection devices, including those           surface to remove heavy
located in the ceiling and floor             contamination                       n   Integrity of stringers
                                                                                     
voids and to ensure that the fire        n   Installation of requisite health
                                                                               n   ESD disc check
                                                                                     
suppression is de-activated. If the          and safety barriers and signage     n   Fire wall integrity
                                                                                     
fire system cannot be deactivated            L
                                              ifting of the floor tiles in
                                         n                                       n   Chilled water line lagging
                                                                                     
then all fire detection units will be        accordance with 8 Solutions
covered with a protective shield                                                 n   Integrity of cable trays/baskets
                                                                                     
                                             best practice
and located on a detailed plan                                                   n   State of sub floor sealing
                                                                                     
                                         n   T
                                              he removal of any sub floor
prepared by the 8 Solutions
                                             debris and disposal of same         Any identified issues will be
team leader.                                                                     reported to the client and
                                         n   The vacuuming of the subfloor
                                             
A daily health and safety and                with Hepa triple filtered vacuums   included in a post clean report.
methodology briefing will then
                                         n   T
                                              he vacuuming of all cabling,
be given to the team by the team             cable trays and baskets
leader and a risk assessment will
be performed as part of the clean.       n   The vacuuming and wipe
                                             
                                             down of all pedestals




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com             The Power of Prevention
Deep Clinical Cleaning cont.

High levels/ceiling void                  General surface                        Floor surface
The cleaning regime to address            The cleaning regime to address         The regime to address the floor
the high levels/ceiling void              the surfaces within the facility       surface will encompass the
will encompass the following              will encompass the following           following procedures:
procedures:                               procedures:
                                                                                 Vinyl surface
n   Confirmation of risk assessment
                                         n   Vacuum and anti-static wipe
                                              
    (as per site survey)                      down of all rack externals         n   Vacuuming of floor surface
                                                                                     

n   Installation of high level access
                                        n   Wipe down of wall surfaces
                                                                               n   Vacuuming and antistatic
                                                                                     
    equipment as appropriate                  including scuff removal                wipe down under racks

n   Installation of all health and
                                        n   Vacuum and wipe down
                                                                                n   Floor buffing at level as
                                                                                     
    safety signage and barriers               of all ledges                          required using specialist
                                                                                     buffers with built-in vacuums
n   Health and safety briefing
                                        n   Vacuum and wipe down
                                              
                                                                                     • Option for hand tooling
                                                                                        
    for high level working                    of all wall mounted units
                                                                                        for problem areas
n   Vacuuming and wipe down of
                                            including AHUs
    cables, cable trays and baskets       n   Vacuum and wipe down of
                                                                                Carpet tiles
n   Vacuuming and wipe down of
                                            all cable and ducting intakes      n   Intensive vacuum using triple
                                                                                     
    all lighting units, diffusers and     n   Vacuum and wipe down
                                                                                   filtered vacuum cleaners
    all support systems                       of all doors and windows
                                                                                 Grills/Koldlocks
                                          Whilst in the process of the surface
                                                                                 n   Debris removal
                                                                                     
                                          clean 8 Solutions technicians will
                                          carry out the following maintenance    n   Vacuum and wipe down
                                                                                     
                                          checks:                                    as required
                                          n   Visual inspection of all intakes
                                                                               Whilst in the process of the
                                              including                          floor surface clean 8 Solutions
                                              • Air handling Units               technicians will carry out the
                                              • Cable and ducting                following maintenance checks:

                                          n   Integrity of racks
                                                                                n   Visual inspection of floor levels
                                                                                     
n   Vacuuming and wipe down of
                                                                                   and structural integrity
    all air handling and distributions    n   Evidence of contamination
                                              
                                                                                 n   Visual inspection of panel
                                                                                     
    units                                 n   Evidence of water damage/
                                                                                    integrity
n   Vacuuming and wipe down
                                            condensation
                                                                                 n   Identification of potential
                                                                                     
    of all ducting systems                Any identified issues will                 trip hazards
n   Vacuuming and wipe down
                                        be reported to the client and
                                          included in a post clean report.       n   Grill and Koldlock integrity
                                                                                     
    of all roof structures, surfaces
                                                                                     and viability
    and supports
n   Vacuuming of any fire detection
                                                                               n   Viability of door seals
                                                                                     
    and suppression units                                                        n   Visual inspection of cable
                                                                                     
If a ceiling void is in place then in                                                and ducting ingress points
addition to the above 8 Solutions                                                Any identified issues will
will undertake to provide the                                                    be reported to the client and
following:                                                                       included in a post clean report.
n   Vacuuming of any fire detection
    
    and suppression units
n   Vacuuming and wipe down
    
    of both inner and outer
    surfaces of the ceiling tiles
n   Vacuuming and wipe down
    
    of all ceiling supports



+44 (0) 845 602 3075    enquiries@8solutions.com   www.8solutions.com            The Power of Prevention
SERVICES


Maintenance

                               Ongoing deep cleansing to
                               uphold the highest standards
                               of Data Centre health


Overview
Within 8 Solutions recommended cleaning schedule and with                        n   V
                                                                                      acuuming and wipe down
a view to maintaining their ISO standard certification, Data                         of all ducting systems
Centres should, as a minimum undertake a ‘Maintenance                            n   Vacuuming and wipe down
                                                                                     
                                                                                     of all roof structures, surfaces
Clean’ at an interval of six months after their annual ‘Deep
                                                                                     and supports
Clinical Clean’.
                                                                                 n   Vacuuming of any fire detection
                                                                                     
An 8 Solutions maintenance clean targets everything above                            and suppression units
the floor including the floor surface and all high levels and
ceiling voids where applicable.


Service detail                           High levels/ceiling void
Before beginning any work                The cleaning regime to address
within the room/facility a thorough      the high levels/ceiling void
services and utilities check is          will encompass the following
performed to identify all utilities      procedures:
including emergency power off            n   Confirmation of risk assessment
                                             
switches, all fire detection devices,        (as per site survey)
including those located in the           n   I
                                             nstallation of high level access
ceiling and floor voids and to               equipment as appropriate            If a ceiling void is in place then in
ensure that the fire suppression         n   Installation of all health and
                                                                               addition to the above 8 Solutions
is de-activated. If the fire system          safety signage and barriers         will undertake to provide the
cannot be deactivated then all fire                                              following:
                                         n   Health and safety briefing
                                             
detection units will be covered with
                                             for high level working              n   Vacuuming of any fire detection
                                                                                     
a protective shield and located on
                                             Vacuuming and wipe down of
                                                                                   and suppression units
a detailed plan prepared by the          n

8 Solutions team leader.                     cables, cable trays and baskets     n   Vacuuming and wipe down
                                                                                     
                                         n   V
                                              acuuming and wipe down of             of both inner and outer surfaces
A daily health and safety and                                                        of the ceiling tiles
                                             all lighting units, diffusers and
methodology briefing will then               all support systems                 n   Vacuuming and wipe down
                                                                                     
be given to the team by the team                                                     of all ceiling supports
leader and a risk assessment will        n   Vacuuming and wipe down
                                             
                                             of all air handling and
be performed as part of the clean.
                                             distributions units




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com             The Power of Prevention
Maintenance cont.

General surface                                                              Floor surface
The cleaning regime to address            Whilst in the process of the       The regime to address the floor
the surfaces within the facility          surface clean 8 Solutions          surface will encompass the
will encompass the following              technicians will carry out the     following procedures:
procedures:                               following maintenance checks:
                                                                             Vinyl surface
n   V
     acuum and anti-static wipe          n   Visual inspection of
                                              
    down of all rack externals                all intakes including          n   Vacuuming of floor surface
                                                                                 
n   Wipe down of wall surfaces
                                            • Air handling units           n   Vacuuming and antistatic
                                                                                 
    including scuff removal                   • Cable and ducting                wipe down under racks
n   Vacuum and wipe down
                                        n   Integrity of racks
                                                                            n   Floor buffing at level as required
                                                                                 
    of all ledges                                                                using specialist buffers with
                                          n   Evidence of contamination
                                              
                                                                                 built-in vacuums
n   Vacuum and wipe down
                                        n   Evidence of water damage/
                                              
    of all wall mounted units                                                    • Option for hand tooling
                                                                                    
                                              condensation                          for problem areas
    including AHUs
                                          Any identified issues will be      n   Final surface vacuum
                                                                                 
n   V
     acuum and wipe down of              reported to the client and
    all cable and ducting intakes         included in post clean report.     Carpet tiles
n   Vacuum and wipe down
                                                                           n   Intensive vacuum using triple
                                                                                 
    of all doors and windows                                                     filtered vacuum cleaners
                                                                             Grills/Koldlocks
                                                                             n   Debris removal
                                                                                 
                                                                             n   Vacuum and wipe down
                                                                                 
                                                                                 as required
                                                                             Whilst in the process of the
                                                                             floor surface clean 8 Solutions
                                                                             technicians will affect the following
                                                                             maintenance checks:
                                                                             n   Visual inspection of floor levels
                                                                                 
                                                                                 and structural integrity
                                                                             n   Visual inspection of panel
                                                                                 
                                                                                 integrity
                                                                             n   Identification of potential
                                                                                 
                                                                                 trip hazards
                                                                             n   Grill and Koldlock integrity
                                                                                 
                                                                                 and viability
                                                                             n   Viability of door seals
                                                                                 
                                                                             n   Visual inspection of cable
                                                                                 
                                                                                 and ducting ingress points
                                                                             Any identified issues will be
                                                                             reported to the client and
                                                                             included in a post clean report.




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com       The Power of Prevention
SERVICES


Surface Cleaning

                                Cleansing with an
                                immediate effect


Overview
An 8 Solutions Surface Clean is a basic level process
designed to provide a relatively simple surface-only clean.
This is typically used in Data Centres that have undergone
some form of change that has impacted on the cleanliness
of a facility, or for those that simply wish to more tightly
maintain the cleanliness levels. This cleaning is either
performed as an inherent part of the cleaning schedule
or on an event driven basis.
An 8 Solutions Surface Clean targets all surfaces in the room
including the floor and excludes floor and ceiling voids and
high levels.


Service detail
Before beginning any work within        cannot be deactivated then all fire
the room/facility a thorough            detection units will be covered with
services and utilities check is         a protective shield and located on
performed to identify all utilities     a detailed plan prepared by the
including emergency power off           8 Solutions team leader.
switches, all fire detection devices,
                                        A daily health and safety and
including those located in the
                                        methodology briefing will then
ceiling and floor voids and to
                                        be given to the team by the team
ensure that the fire suppression
                                        leader and a risk assessment will
is de-activated. If the fire system
                                        be performed as part of the clean.




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com           The Power of Prevention
Surface Cleaning cont.

General surface                                                                 Floor surface
The cleaning regime to address           Whilst in the process of the           The regime to address the floor
the surfaces within the facility         surface clean 8 Solutions              surface will encompass the
will encompass the following             technicians will carry out the         following procedures:
procedures:                              following maintenance checks:
    V
     acuum and anti-static wipe                                                Vinyl surface
n                                        n Visual inspection of all intakes
                                           
    down of all rack externals             including                            n   Vacuuming of floor surface
                                                                                    
n   W
     ipe down of wall surfaces              • Air handling units               n   Vacuuming and antistatic
                                                                                    
    including scuff removal                  • Cable and ducting                    wipe down under racks
n   Vacuum and wipe down
                                       n Integrity of racks
                                                                               n   Floor buffing at level as required
                                                                                    
    of all ledges                        n Evidence of contamination
                                                                                   using specialist buffers with
    Vacuum and wipe down
                                                                                  built-in vacuums
n                                        n   Evidence of water damage /
                                             
    of all wall mounted units                condensation                           • Option for hand tooling
                                                                                       
    including AHUs                                                                     for problem areas
                                         Any identified issues will
n   Vacuum and wipe down of
                                                                              n   Final surface vacuum
                                                                                    
                                         be reported to the client and
    all cable and ducting intakes        included in post clean report.         Carpet tiles
n   V
     acuum and wipe down
    of all doors and windows                                                    n   Intensive vacuum using triple
                                                                                    
                                                                                    filtered vacuum cleaners

                                                                                Grills/Koldlocks
                                                                                n   Debris removal
                                                                                    
                                                                                n   Vacuum and wipe down
                                                                                    
                                                                                    as required

                                                                                Whilst in the process of the
                                                                                floor surface clean 8 Solutions
                                                                                technicians will carry out the
                                                                                following maintenance checks:
                                                                                n   Visual inspection of floor levels
                                                                                    
                                                                                    and structural integrity
                                                                                n   Visual inspection of panel
                                                                                    
                                                                                    integrity
                                                                                n   Identification of potential
                                                                                    
                                                                                    trip hazards
                                                                                n   Grill and Koldlock integrity
                                                                                    
                                                                                    and viability
                                                                                n   Viability of door seals
                                                                                    
                                                                                n   Visual inspection of cable
                                                                                    
                                                                                    and ducting ingress points
                                                                                Any identified issues will
                                                                                be reported to the client and
                                                                                included in a post clean report.




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com          The Power of Prevention
SERVICES


Post Construction Clean

                                Maintaining Data
                                Centre health following
                                building work

Overview
8 Solutions provides two levels of Post Construction Clean:                      Builders Clean
a Builders Clean and an Enhanced Builders Clean. Both are                        The Builders Clean regime will
intended to be used after the completion of either the build of                  encompass the following:
an entire new Data Centre or an extension or enhancement to                      n   Focus on all areas from
                                                                                     
an existing facility.                                                                the subfloor to high levels
The Builders Clean is a basic level service that prepares the                    n   Removal of all ‘non-heavy’
                                                                                     
environment for the next stage of the fit out, it is not intended                    construction debris
to be in any way an ISO level clean.                                             n   Dry clean to visual acceptability
                                                                                     

The Enhanced Builders Clean will prepare the room for
                                                                                 Enhanced Builders Clean
the next stage of readiness in preparation for final stage
deployment.                                                                      The Enhanced Builders Clean
                                                                                 regime will encompass the following:
                                                                                 n   Focus on all areas from
                                                                                     
                                        Service detail                               the subfloor to high levels
                                        Before beginning any work within         n   Removal of all ‘non-heavy’
                                                                                     
                                        the room/facility a thorough check           construction debris
                                        is performed to identify all utilities   n   Wipe down of all exposed
                                                                                     
                                        including emergency power off                surfaces
                                        switches, all fire detection devices,
                                                                                 n   Dry clean to visual acceptability
                                                                                     
                                        including those located in the
                                        ceiling and floor voids and to           n   Vacuum floor surface
                                                                                     
                                        ensure that the fire suppression
                                        is de-activated. If the fire system
                                        cannot be deactivated the all fire
                                        detection units will be covered with
                                        a protective shield and located on
                                        a detailed plan prepared by the
                                        8 Solutions team leader.
                                        A daily health and safety and
                                        methodology briefing will then
                                        be given to the team by the team
                                        leader and a risk assessment will
                                        be performed as part of the clean.



+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com             The Power of Prevention
SERVICES


Rack Externals  Internals

                                Ensuring the cleanliness
                                of the Data Centre’s
                                infrastructure

Overview
All 8 Solutions technicians are fully trained in the equipment                  External Rack Cleaning
and infrastructure within a Data Centre and are qualified                       The External Rack Cleaning
to decontaminate the externals of all types of racks and                        regime will encompass the
cabinets. We also have personnel trained in cleaning                            following:
inside a rack or cabinet – including the front and rear of                      n   V
                                                                                     acuuming all external surface
any server or communication equipment. This process is,                             areas including top and bottom
                                                                                    of cabinets/racks
in most cases, carried out on a live rack, with a data centre
                                                                                n   W
                                                                                     ipe down of all surface areas
engineer in attendance or in some situations on an isolated
rack where a much more intensive clean can be performed                         n   F
                                                                                     inal wipe down with cloth
                                                                                    impregnated with specialist
including equipment removal and cleaning. This type of                              cleaning solution
clean is subject to stringent safety and procedural guidelines
and methodologies. It should be noted that breakdown and
re-assembly is not part of the 8 Solutions service and is the
responsibility of the client.


Service detail
Before any work begins within           then all fire detection units will be
the room or facility a thorough         covered with a protective shield
check is performed to identify          and located on a detailed plan
all utilities including emergency       prepared by the 8 Solutions
power off switches, all fire            team leader.
detection devices, including those
                                        A daily health and safety and
located in the ceiling and floor
                                        methodology briefing will then
voids and to ensure that the fire
                                        be given to the team by the team
suppression is deactivated. If the
                                        leader and a risk assessment will
fire system cannot be deactivated
                                        be performed as part of the clean.




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com            The Power of Prevention
Rack Externals  Internals cont.

Internal Rack Cleaning
The Internal Rack Cleaning regime
will encompass the following:
n   L
     iaison with DC engineers
    with a view to isolating the rack
n   I
    solation of rack if possible
n   A
     lternatively attendance of
    a DC engineer for each and
    every rack clean
n   Visible inspection of equipment,
    
    cable management and power
    systems
n   Confirm understanding of areas
    
    of particular sensitivity
n   V
     acuuming of all equipment
    using specialist Micro Vac
    systems linked to triple filtered
    vacuum cleaners
n   M
     Icro Vacuuming, if required,
    of equipment to circuit board
    level if required subject to the
    client isolating and “splitting“
    all units
n   V
     acuuming of all air intake/fan
    systems either generic systems
    or those specific to individual
    hardware using specialist Micro
    Vac systems linked to triple
    filtered vacuum cleaners
n   V
     acuuming of both power and
    data cabling using specialist
    Micro Vac systems linked to
    triple filtered vacuum cleaners
n   Vacuuming all accessible
    
    surface areas including the
    internal top and bottoms of
    cabinets and racks
n   W
     ipe down of all accessible
    internal surface areas
n   F
     inal wipe down of external
    surface areas with cloth
    impregnated with specialist
    cleaning solution




+44 (0) 845 602 3075   enquiries@8solutions.com   www.8solutions.com   The Power of Prevention

Weitere ähnliche Inhalte

Andere mochten auch

C:\Documents And Settings\IngenieríA\Mis Documentos\Diccionario
C:\Documents And Settings\IngenieríA\Mis Documentos\DiccionarioC:\Documents And Settings\IngenieríA\Mis Documentos\Diccionario
C:\Documents And Settings\IngenieríA\Mis Documentos\DiccionarioRosita Fernández
 
Week 2 slide presentataion edld 5352
Week 2 slide presentataion edld 5352Week 2 slide presentataion edld 5352
Week 2 slide presentataion edld 5352suplk
 
EDLD 5352 Technology Action Plan
EDLD 5352 Technology Action PlanEDLD 5352 Technology Action Plan
EDLD 5352 Technology Action Plansuplk
 
Week 2 slide presentataion edld 5352
Week 2 slide presentataion edld 5352Week 2 slide presentataion edld 5352
Week 2 slide presentataion edld 5352suplk
 
Fechas para embarazos
Fechas para embarazosFechas para embarazos
Fechas para embarazosQisoma
 
It Pays to Hire Women in Games: Successful Female Game Devs Speak
It Pays to Hire Women in Games: Successful Female Game Devs SpeakIt Pays to Hire Women in Games: Successful Female Game Devs Speak
It Pays to Hire Women in Games: Successful Female Game Devs SpeakSolveig Zarubin
 

Andere mochten auch (7)

C:\Documents And Settings\IngenieríA\Mis Documentos\Diccionario
C:\Documents And Settings\IngenieríA\Mis Documentos\DiccionarioC:\Documents And Settings\IngenieríA\Mis Documentos\Diccionario
C:\Documents And Settings\IngenieríA\Mis Documentos\Diccionario
 
Week 2 slide presentataion edld 5352
Week 2 slide presentataion edld 5352Week 2 slide presentataion edld 5352
Week 2 slide presentataion edld 5352
 
EDLD 5352 Technology Action Plan
EDLD 5352 Technology Action PlanEDLD 5352 Technology Action Plan
EDLD 5352 Technology Action Plan
 
Week 2 slide presentataion edld 5352
Week 2 slide presentataion edld 5352Week 2 slide presentataion edld 5352
Week 2 slide presentataion edld 5352
 
Diccionario
DiccionarioDiccionario
Diccionario
 
Fechas para embarazos
Fechas para embarazosFechas para embarazos
Fechas para embarazos
 
It Pays to Hire Women in Games: Successful Female Game Devs Speak
It Pays to Hire Women in Games: Successful Female Game Devs SpeakIt Pays to Hire Women in Games: Successful Female Game Devs Speak
It Pays to Hire Women in Games: Successful Female Game Devs Speak
 

Ähnlich wie 8 Solutions - Specialist Data Centre Cleaning & Decontamination

Substations vesda
Substations vesdaSubstations vesda
Substations vesdakormankung
 
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...Pieter Jan Jordaens
 
Calculation of efficiency of Aspirating Smoke Detection in Data Center
Calculation of efficiency of Aspirating Smoke Detection in Data CenterCalculation of efficiency of Aspirating Smoke Detection in Data Center
Calculation of efficiency of Aspirating Smoke Detection in Data CenterIRJET Journal
 
Fire Protection And Safety Of Power Plants
Fire Protection And Safety Of Power PlantsFire Protection And Safety Of Power Plants
Fire Protection And Safety Of Power PlantsArena International
 
Protecting Utilities from Risk - Iain Morton, Tyco Integrated Security
Protecting Utilities from Risk - Iain Morton, Tyco Integrated SecurityProtecting Utilities from Risk - Iain Morton, Tyco Integrated Security
Protecting Utilities from Risk - Iain Morton, Tyco Integrated SecurityEnergy Network marcus evans
 
High Performance Buildings
High Performance BuildingsHigh Performance Buildings
High Performance BuildingsTony Loup
 
Data centre-hosting-services
Data centre-hosting-servicesData centre-hosting-services
Data centre-hosting-servicesGareth Huxall
 
Data centre-hosting-services
Data centre-hosting-servicesData centre-hosting-services
Data centre-hosting-servicesSimon Dale
 
Data Centre Hosting Services
Data Centre Hosting ServicesData Centre Hosting Services
Data Centre Hosting Servicesscottamc26
 
Belden Industrial Ethernet White Paper
Belden Industrial Ethernet White PaperBelden Industrial Ethernet White Paper
Belden Industrial Ethernet White Paperadventive1
 
Update On The Cern. Computing And Network Infrastructure For Controls. (Cnic)...
Update On The Cern. Computing And Network Infrastructure For Controls. (Cnic)...Update On The Cern. Computing And Network Infrastructure For Controls. (Cnic)...
Update On The Cern. Computing And Network Infrastructure For Controls. (Cnic)...ESS BILBAO
 
Boosting Asset Reliability in the Energy Sector - Richard Crawford, Integrate...
Boosting Asset Reliability in the Energy Sector - Richard Crawford, Integrate...Boosting Asset Reliability in the Energy Sector - Richard Crawford, Integrate...
Boosting Asset Reliability in the Energy Sector - Richard Crawford, Integrate...Energy Network marcus evans
 
Sgs ind-ndt-hic-leaflet-en-11
Sgs ind-ndt-hic-leaflet-en-11Sgs ind-ndt-hic-leaflet-en-11
Sgs ind-ndt-hic-leaflet-en-11mntahmaz
 
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...Dhana Raj Markandu
 
A Review Paper On Nuclear S Power Plants Safety
A Review Paper On Nuclear S Power Plants SafetyA Review Paper On Nuclear S Power Plants Safety
A Review Paper On Nuclear S Power Plants SafetyDaphne Smith
 
C:\Fakepath\Amor Alarm+
C:\Fakepath\Amor Alarm+C:\Fakepath\Amor Alarm+
C:\Fakepath\Amor Alarm+stuyoungenduro
 
NDeX Data Centers: A Vault in the Cloud
NDeX Data Centers: A Vault in the CloudNDeX Data Centers: A Vault in the Cloud
NDeX Data Centers: A Vault in the Cloudassure360
 

Ähnlich wie 8 Solutions - Specialist Data Centre Cleaning & Decontamination (20)

Substations vesda
Substations vesdaSubstations vesda
Substations vesda
 
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
Paper ewea 2013 the use of a large climate chamber for extreme temperature te...
 
Calculation of efficiency of Aspirating Smoke Detection in Data Center
Calculation of efficiency of Aspirating Smoke Detection in Data CenterCalculation of efficiency of Aspirating Smoke Detection in Data Center
Calculation of efficiency of Aspirating Smoke Detection in Data Center
 
Fire Protection And Safety Of Power Plants
Fire Protection And Safety Of Power PlantsFire Protection And Safety Of Power Plants
Fire Protection And Safety Of Power Plants
 
Protecting Utilities from Risk - Iain Morton, Tyco Integrated Security
Protecting Utilities from Risk - Iain Morton, Tyco Integrated SecurityProtecting Utilities from Risk - Iain Morton, Tyco Integrated Security
Protecting Utilities from Risk - Iain Morton, Tyco Integrated Security
 
pharmaceutical lr
pharmaceutical lrpharmaceutical lr
pharmaceutical lr
 
High Performance Buildings
High Performance BuildingsHigh Performance Buildings
High Performance Buildings
 
Data centre-hosting-services
Data centre-hosting-servicesData centre-hosting-services
Data centre-hosting-services
 
Data centre-hosting-services
Data centre-hosting-servicesData centre-hosting-services
Data centre-hosting-services
 
Data Centre Hosting Services
Data Centre Hosting ServicesData Centre Hosting Services
Data Centre Hosting Services
 
Belden Industrial Ethernet White Paper
Belden Industrial Ethernet White PaperBelden Industrial Ethernet White Paper
Belden Industrial Ethernet White Paper
 
Update On The Cern. Computing And Network Infrastructure For Controls. (Cnic)...
Update On The Cern. Computing And Network Infrastructure For Controls. (Cnic)...Update On The Cern. Computing And Network Infrastructure For Controls. (Cnic)...
Update On The Cern. Computing And Network Infrastructure For Controls. (Cnic)...
 
Boosting Asset Reliability in the Energy Sector - Richard Crawford, Integrate...
Boosting Asset Reliability in the Energy Sector - Richard Crawford, Integrate...Boosting Asset Reliability in the Energy Sector - Richard Crawford, Integrate...
Boosting Asset Reliability in the Energy Sector - Richard Crawford, Integrate...
 
Sgs ind-ndt-hic-leaflet-en-11
Sgs ind-ndt-hic-leaflet-en-11Sgs ind-ndt-hic-leaflet-en-11
Sgs ind-ndt-hic-leaflet-en-11
 
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
Dhana Raj Markandu: Control System Cybersecurity - Challenges in a New Energy...
 
A Review Paper On Nuclear S Power Plants Safety
A Review Paper On Nuclear S Power Plants SafetyA Review Paper On Nuclear S Power Plants Safety
A Review Paper On Nuclear S Power Plants Safety
 
C:\Fakepath\Amor Alarm+
C:\Fakepath\Amor Alarm+C:\Fakepath\Amor Alarm+
C:\Fakepath\Amor Alarm+
 
Ispe Article
Ispe ArticleIspe Article
Ispe Article
 
NDeX Data Centers: A Vault in the Cloud
NDeX Data Centers: A Vault in the CloudNDeX Data Centers: A Vault in the Cloud
NDeX Data Centers: A Vault in the Cloud
 
Profitable aquafeed moisture control
Profitable aquafeed moisture controlProfitable aquafeed moisture control
Profitable aquafeed moisture control
 

8 Solutions - Specialist Data Centre Cleaning & Decontamination

  • 1. SERVICES Why Decontaminate? The compelling case for a regular Data Centre health regime Unplanned downtime in a Data Centre environment can The awareness of maintaining a prove extremely costly, and most organisations have a ‘clean’ environment is growing amongst the standards and the detailed and prescriptive preventative maintenance regime OEM communities: designed to mitigate the risk of such downtime. Typically, n A number of hardware this regime would include monitoring and maintaining such manufacturers are considering the factors as power, temperature and humidity, with particular cleanliness of the environment as a factor when assessing the validity of focus on the management of the airflow to ensure optimum RMA and warranty claims and requisite cooling. Contamination management is one n Several major manufacturers area that is only included on the regimes of either the more recommend in their hardware enlightened Data Centre Managers or those that have installation guidelines that “every experienced downtime. effort should be made to ensure that the target environment is as dust and particulate free as possible”. No matter what its source n ISO 14644-1 Air Cleanliness contamination can be extremely guidelines are encouraging hazardous within a data centre: compliance as an inherent part of the n Dust and other particles can Data Centre management process. clog air intake grills on cooling The benefits of professional Data units and fans resulting in Centre decontamination include: overheating, cooling equipment operating beyond capacity n I mproved efficacy of cooling systems causing premature failure, n I ncreased longevity and Contamination can take various power overloads and outages performance of hardware forms, however over 80% of all contaminants within a Data n Metal particulates such as n I mproved power consumption zinc whiskers can cause Centre environment is caused n I ncreased reliability of data centre electrical shorts in equipment uptime by human traffic, whether this is dust, particulate from cardboard n Dust and other contaminants n C ompliance with contamination and packaging or contamination can either block fire detection best practice guidelines created from works within the systems preventing effective use or can actually trigger false n F ull preventative maintenance Data Centre. Some contamination regime alarms or actual discharge. derives from the environment itself Airflow and the resulting cooling n P eace of mind through risk mitigation including concrete particles from n an untreated sub floor, or fibres can be seriously impacted by from air filters or zinc whiskers contaminants and debris within the subfloor and floor grills. from oxidising metal. +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 2. SERVICES Our Services The checklist for ultimate Data Centre health 8 Solutions is a Data Centre Healthcare provider operating through two divisions; Cleaning and Decontamination and Mechanical Services. Cleaning and Mechanical Services Decontamination n Flooring Audits Services • Health and Safety • Floor Integrity n Deep Clinical Cleaning • From sub floor to high levels n Remedial Solutions • Replacement panels/sections n Maintenance Cleaning • Upgrades • rom floor surface F to high levels – Stringers/pedestals • Replacement of pedestals n Surface Cleaning • nstallation/securing pedestals I • All surfaces • ESD replacement/repair n Post Construction Services • Floor strengthening • Builders Clean • Sub floor sealing – Preparation for fitout n Ingress • Enhanced Builders Clean • nstallation of I – Preparation for use Koldlocks/grills n Specialist Internal Rack Cleaning • nstallation of cable I access points • To individual component level n Airflow n Emergency Response Service • Analysis • Rapid deployment capability • Remediation n Comprehesive cleaning regime • esigned to maintain optimum D levels of cleanliness and performance +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 3. Our Services cont. Operating 1. Client interest Methodology Client confirms requirements, room sizes and location(s) 2. Comprehensive site survey conducted A site survey is required for all sites in excess of 200 square metres A self assessment survey is utilised for all sites less than 200 square metres 3. 8 Solutions provides a proposal and quotation 8 Solutions provides a detailed proposal of services, methodologies and RAMS 4. Client submits/8 Solutions receives purchase order 8 Solutions receives purchase order from the client 8 Solutions proposes service schedule to client 5. Schedule of service agreed with client 8 Solutions confirms schedule of services with client Confirmation of team members 6. 8 Solutions delivers service 8 Solutions attend site, and confirm health and safety requirements 8 Solutions pre-service check including utilities and fire systems 7. 8 Solutions submits a “post clean” report to client Detailed reports submitted to client on status of clean Any issues identified including flooring, health and safety contamination 8. 8 Solutions post clean quality checks All clients are invited to respond to an email based quality audit 8 Solutions conducts on-site post clean quality checks on a random basis +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 4. SERVICES Deep Clinical Cleaning A Data Centre clean in infinite detail Overview An 8 Solutions Deep Clinical Clean is an intensive service n A nti-static wipe down of panel designed to achieve an ISO 14644-1 level 6 standard of air undersides cleanliness. It addresses every area within the Data Centre, n T he replacement of floor panels from the subfloor surface up to the underside of the panels in accordance with 8 Solutions best practice and the floor surface, all walls, doors, ledges, and cabinet externals. It will also address all high levels including ceiling Whilst in the floor void the 8 Solutions technicians will affect voids, overhead cabling and cable trays, all lighting including the following maintenance checks: suspension systems and all building support infrastructure n Visual check for zinc whiskers including roof supports and ceiling and roof surfaces. Service detail Floor void Before work begins, a thorough The cleaning regime to address check is performed to identify the floor void will encompass the all utilities including emergency following procedures: power off switches, all fire n Initial cleaning of the floor n Integrity of pedestals detection devices, including those surface to remove heavy located in the ceiling and floor contamination n Integrity of stringers voids and to ensure that the fire n Installation of requisite health n ESD disc check suppression is de-activated. If the and safety barriers and signage n Fire wall integrity fire system cannot be deactivated L ifting of the floor tiles in n n Chilled water line lagging then all fire detection units will be accordance with 8 Solutions covered with a protective shield n Integrity of cable trays/baskets best practice and located on a detailed plan n State of sub floor sealing n T he removal of any sub floor prepared by the 8 Solutions debris and disposal of same Any identified issues will be team leader. reported to the client and n The vacuuming of the subfloor A daily health and safety and with Hepa triple filtered vacuums included in a post clean report. methodology briefing will then n T he vacuuming of all cabling, be given to the team by the team cable trays and baskets leader and a risk assessment will be performed as part of the clean. n The vacuuming and wipe down of all pedestals +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 5. Deep Clinical Cleaning cont. High levels/ceiling void General surface Floor surface The cleaning regime to address The cleaning regime to address The regime to address the floor the high levels/ceiling void the surfaces within the facility surface will encompass the will encompass the following will encompass the following following procedures: procedures: procedures: Vinyl surface n Confirmation of risk assessment n Vacuum and anti-static wipe (as per site survey) down of all rack externals n Vacuuming of floor surface n Installation of high level access n Wipe down of wall surfaces n Vacuuming and antistatic equipment as appropriate including scuff removal wipe down under racks n Installation of all health and n Vacuum and wipe down n Floor buffing at level as safety signage and barriers of all ledges required using specialist buffers with built-in vacuums n Health and safety briefing n Vacuum and wipe down • Option for hand tooling for high level working of all wall mounted units for problem areas n Vacuuming and wipe down of including AHUs cables, cable trays and baskets n Vacuum and wipe down of Carpet tiles n Vacuuming and wipe down of all cable and ducting intakes n Intensive vacuum using triple all lighting units, diffusers and n Vacuum and wipe down filtered vacuum cleaners all support systems of all doors and windows Grills/Koldlocks Whilst in the process of the surface n Debris removal clean 8 Solutions technicians will carry out the following maintenance n Vacuum and wipe down checks: as required n Visual inspection of all intakes Whilst in the process of the including floor surface clean 8 Solutions • Air handling Units technicians will carry out the • Cable and ducting following maintenance checks: n Integrity of racks n Visual inspection of floor levels n Vacuuming and wipe down of and structural integrity all air handling and distributions n Evidence of contamination n Visual inspection of panel units n Evidence of water damage/ integrity n Vacuuming and wipe down condensation n Identification of potential of all ducting systems Any identified issues will trip hazards n Vacuuming and wipe down be reported to the client and included in a post clean report. n Grill and Koldlock integrity of all roof structures, surfaces and viability and supports n Vacuuming of any fire detection n Viability of door seals and suppression units n Visual inspection of cable If a ceiling void is in place then in and ducting ingress points addition to the above 8 Solutions Any identified issues will will undertake to provide the be reported to the client and following: included in a post clean report. n Vacuuming of any fire detection and suppression units n Vacuuming and wipe down of both inner and outer surfaces of the ceiling tiles n Vacuuming and wipe down of all ceiling supports +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 6. SERVICES Maintenance Ongoing deep cleansing to uphold the highest standards of Data Centre health Overview Within 8 Solutions recommended cleaning schedule and with n V acuuming and wipe down a view to maintaining their ISO standard certification, Data of all ducting systems Centres should, as a minimum undertake a ‘Maintenance n Vacuuming and wipe down of all roof structures, surfaces Clean’ at an interval of six months after their annual ‘Deep and supports Clinical Clean’. n Vacuuming of any fire detection An 8 Solutions maintenance clean targets everything above and suppression units the floor including the floor surface and all high levels and ceiling voids where applicable. Service detail High levels/ceiling void Before beginning any work The cleaning regime to address within the room/facility a thorough the high levels/ceiling void services and utilities check is will encompass the following performed to identify all utilities procedures: including emergency power off n Confirmation of risk assessment switches, all fire detection devices, (as per site survey) including those located in the n I nstallation of high level access ceiling and floor voids and to equipment as appropriate If a ceiling void is in place then in ensure that the fire suppression n Installation of all health and addition to the above 8 Solutions is de-activated. If the fire system safety signage and barriers will undertake to provide the cannot be deactivated then all fire following: n Health and safety briefing detection units will be covered with for high level working n Vacuuming of any fire detection a protective shield and located on Vacuuming and wipe down of and suppression units a detailed plan prepared by the n 8 Solutions team leader. cables, cable trays and baskets n Vacuuming and wipe down n V acuuming and wipe down of of both inner and outer surfaces A daily health and safety and of the ceiling tiles all lighting units, diffusers and methodology briefing will then all support systems n Vacuuming and wipe down be given to the team by the team of all ceiling supports leader and a risk assessment will n Vacuuming and wipe down of all air handling and be performed as part of the clean. distributions units +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 7. Maintenance cont. General surface Floor surface The cleaning regime to address Whilst in the process of the The regime to address the floor the surfaces within the facility surface clean 8 Solutions surface will encompass the will encompass the following technicians will carry out the following procedures: procedures: following maintenance checks: Vinyl surface n V acuum and anti-static wipe n Visual inspection of down of all rack externals all intakes including n Vacuuming of floor surface n Wipe down of wall surfaces • Air handling units n Vacuuming and antistatic including scuff removal • Cable and ducting wipe down under racks n Vacuum and wipe down n Integrity of racks n Floor buffing at level as required of all ledges using specialist buffers with n Evidence of contamination built-in vacuums n Vacuum and wipe down n Evidence of water damage/ of all wall mounted units • Option for hand tooling condensation for problem areas including AHUs Any identified issues will be n Final surface vacuum n V acuum and wipe down of reported to the client and all cable and ducting intakes included in post clean report. Carpet tiles n Vacuum and wipe down n Intensive vacuum using triple of all doors and windows filtered vacuum cleaners Grills/Koldlocks n Debris removal n Vacuum and wipe down as required Whilst in the process of the floor surface clean 8 Solutions technicians will affect the following maintenance checks: n Visual inspection of floor levels and structural integrity n Visual inspection of panel integrity n Identification of potential trip hazards n Grill and Koldlock integrity and viability n Viability of door seals n Visual inspection of cable and ducting ingress points Any identified issues will be reported to the client and included in a post clean report. +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 8. SERVICES Surface Cleaning Cleansing with an immediate effect Overview An 8 Solutions Surface Clean is a basic level process designed to provide a relatively simple surface-only clean. This is typically used in Data Centres that have undergone some form of change that has impacted on the cleanliness of a facility, or for those that simply wish to more tightly maintain the cleanliness levels. This cleaning is either performed as an inherent part of the cleaning schedule or on an event driven basis. An 8 Solutions Surface Clean targets all surfaces in the room including the floor and excludes floor and ceiling voids and high levels. Service detail Before beginning any work within cannot be deactivated then all fire the room/facility a thorough detection units will be covered with services and utilities check is a protective shield and located on performed to identify all utilities a detailed plan prepared by the including emergency power off 8 Solutions team leader. switches, all fire detection devices, A daily health and safety and including those located in the methodology briefing will then ceiling and floor voids and to be given to the team by the team ensure that the fire suppression leader and a risk assessment will is de-activated. If the fire system be performed as part of the clean. +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 9. Surface Cleaning cont. General surface Floor surface The cleaning regime to address Whilst in the process of the The regime to address the floor the surfaces within the facility surface clean 8 Solutions surface will encompass the will encompass the following technicians will carry out the following procedures: procedures: following maintenance checks: V acuum and anti-static wipe Vinyl surface n n Visual inspection of all intakes down of all rack externals including n Vacuuming of floor surface n W ipe down of wall surfaces • Air handling units n Vacuuming and antistatic including scuff removal • Cable and ducting wipe down under racks n Vacuum and wipe down n Integrity of racks n Floor buffing at level as required of all ledges n Evidence of contamination using specialist buffers with Vacuum and wipe down built-in vacuums n n Evidence of water damage / of all wall mounted units condensation • Option for hand tooling including AHUs for problem areas Any identified issues will n Vacuum and wipe down of n Final surface vacuum be reported to the client and all cable and ducting intakes included in post clean report. Carpet tiles n V acuum and wipe down of all doors and windows n Intensive vacuum using triple filtered vacuum cleaners Grills/Koldlocks n Debris removal n Vacuum and wipe down as required Whilst in the process of the floor surface clean 8 Solutions technicians will carry out the following maintenance checks: n Visual inspection of floor levels and structural integrity n Visual inspection of panel integrity n Identification of potential trip hazards n Grill and Koldlock integrity and viability n Viability of door seals n Visual inspection of cable and ducting ingress points Any identified issues will be reported to the client and included in a post clean report. +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 10. SERVICES Post Construction Clean Maintaining Data Centre health following building work Overview 8 Solutions provides two levels of Post Construction Clean: Builders Clean a Builders Clean and an Enhanced Builders Clean. Both are The Builders Clean regime will intended to be used after the completion of either the build of encompass the following: an entire new Data Centre or an extension or enhancement to n Focus on all areas from an existing facility. the subfloor to high levels The Builders Clean is a basic level service that prepares the n Removal of all ‘non-heavy’ environment for the next stage of the fit out, it is not intended construction debris to be in any way an ISO level clean. n Dry clean to visual acceptability The Enhanced Builders Clean will prepare the room for Enhanced Builders Clean the next stage of readiness in preparation for final stage deployment. The Enhanced Builders Clean regime will encompass the following: n Focus on all areas from Service detail the subfloor to high levels Before beginning any work within n Removal of all ‘non-heavy’ the room/facility a thorough check construction debris is performed to identify all utilities n Wipe down of all exposed including emergency power off surfaces switches, all fire detection devices, n Dry clean to visual acceptability including those located in the ceiling and floor voids and to n Vacuum floor surface ensure that the fire suppression is de-activated. If the fire system cannot be deactivated the all fire detection units will be covered with a protective shield and located on a detailed plan prepared by the 8 Solutions team leader. A daily health and safety and methodology briefing will then be given to the team by the team leader and a risk assessment will be performed as part of the clean. +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 11. SERVICES Rack Externals Internals Ensuring the cleanliness of the Data Centre’s infrastructure Overview All 8 Solutions technicians are fully trained in the equipment External Rack Cleaning and infrastructure within a Data Centre and are qualified The External Rack Cleaning to decontaminate the externals of all types of racks and regime will encompass the cabinets. We also have personnel trained in cleaning following: inside a rack or cabinet – including the front and rear of n V acuuming all external surface any server or communication equipment. This process is, areas including top and bottom of cabinets/racks in most cases, carried out on a live rack, with a data centre n W ipe down of all surface areas engineer in attendance or in some situations on an isolated rack where a much more intensive clean can be performed n F inal wipe down with cloth impregnated with specialist including equipment removal and cleaning. This type of cleaning solution clean is subject to stringent safety and procedural guidelines and methodologies. It should be noted that breakdown and re-assembly is not part of the 8 Solutions service and is the responsibility of the client. Service detail Before any work begins within then all fire detection units will be the room or facility a thorough covered with a protective shield check is performed to identify and located on a detailed plan all utilities including emergency prepared by the 8 Solutions power off switches, all fire team leader. detection devices, including those A daily health and safety and located in the ceiling and floor methodology briefing will then voids and to ensure that the fire be given to the team by the team suppression is deactivated. If the leader and a risk assessment will fire system cannot be deactivated be performed as part of the clean. +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention
  • 12. Rack Externals Internals cont. Internal Rack Cleaning The Internal Rack Cleaning regime will encompass the following: n L iaison with DC engineers with a view to isolating the rack n I solation of rack if possible n A lternatively attendance of a DC engineer for each and every rack clean n Visible inspection of equipment, cable management and power systems n Confirm understanding of areas of particular sensitivity n V acuuming of all equipment using specialist Micro Vac systems linked to triple filtered vacuum cleaners n M Icro Vacuuming, if required, of equipment to circuit board level if required subject to the client isolating and “splitting“ all units n V acuuming of all air intake/fan systems either generic systems or those specific to individual hardware using specialist Micro Vac systems linked to triple filtered vacuum cleaners n V acuuming of both power and data cabling using specialist Micro Vac systems linked to triple filtered vacuum cleaners n Vacuuming all accessible surface areas including the internal top and bottoms of cabinets and racks n W ipe down of all accessible internal surface areas n F inal wipe down of external surface areas with cloth impregnated with specialist cleaning solution +44 (0) 845 602 3075 enquiries@8solutions.com www.8solutions.com The Power of Prevention