APPLICATION OF SVC FOR VOLTAGE CONTROL IN WIND FARM
POWER SYSTEM
Dr. M. P. Sharma Devandra Saini
AEN, RVPNL, Jaipur Asst. Prof., EE Deptt., SIT, Jaipur
Swati Harsh Sarfaraz Nawaz
Asst. Prof., EE Deptt.,AICE, Jaipur Associate Prof. Deptt., SKIT, Jaipur
ABSTRACT
Most of wind power plants are installed far away from load centers, hence require
long EHV transmission lines for evacuation system for pooling the power and transmitting to
far off load centers. Wind Power Generation is infirm and variable subject to vagaries of
nature. Due to large variations in wind power generation, power flows on transmission lines
are also vary and accordingly there is a wide variation in power transmission system voltage
from minimum 0.8 pu to maximum 1.20 pu. Due to low & high power system voltages,
transmission lines are tripped resulting constrained in wind power evacuation. In this paper
Static Var Compensator is proposed at wind power plants penetrated power system. In this
paper simulation studies have been carried out to validate the effectiveness of the SVC for
voltage control with the variation in wind power generation. Case studies are carried out on
18-bus Rajasthan power system to demonstrate the performance of the SVC during high and
low wind power generation conditions. Wind power plants penetrated part of Rajasthan
power system has been modeled using Mi-Power power system analysis software designed
by the M/s PRDC Bangalore. Results of tests conducted on the model system in various
possible field conditions are presented and discussed.
I. INTRODUCTION
In Rajasthan, most of wind power plants are concentrated in western part i.e.
Jaisalmer which is far away from load centers. As on 31-3-2013, total 2140 MW capacity
wind power plants are installed in Jaisalmer area. For evacuation of wind power generation
from Jaisalmer to load centers, 2 nos. 400 kV lines, 3 nos. 220 kV lines & 2 nos. 132 kV lines
INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING
& TECHNOLOGY (IJEET)
ISSN 0976 – 6545(Print)
ISSN 0976 – 6553(Online)
Volume 4, Issue 3, May - June (2013), pp. 95-114
© IAEME: www.iaeme.com/ijeet.asp
Journal Impact Factor (2013): 5.5028 (Calculated by GISI)
www.jifactor.com
IJEET
© I A E M E
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
96
have been constructed. There is a huge variations in wind generation i.e. variation is from
zero to maximum generation. Variation in wind power generation on typical days is shown in
following figures:-
Fig-1: HOURLY AVERAGE WIND GENERATION for 15 March, 2013
Fig-2: HOURLY AVERAGE WIND GENERATION for 23 March, 2013
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
97
Fig-3: HOURLY AVERAGE WIND GENERATION for 10 April,2013
Fig-4: HOURLY AVERAGE WIND GENERATION for 15 April, 2013
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
98
Due to variation in wind power generation, power transmission voltage is fluctuated. Voltage
fluctuations are mainly due to
Long EHV transmission lines
Lack of load in western Rajasthan
Erratic variation in generation pattern
Wind Generators do not provide the required VAR support
Over-voltage causes over-fluxing in transformers resulting in tripping of transformers. Due to
over voltages, transmission lines also tripped. With the help of FACTS devices, it is possible
to regulate power system voltage with the variation of wind power generation.
II. SVC AND POWER SYSTEM V-I CHARACTERISTICS
SVC V-I Characteristic
SVC composed of a controllable reactor and a fixed capacitor. The composite
characteristic of SVC is derived by adding the individual characteristics of the components.
SVC are defined by the slope reactance when the controlled voltage is within the control
range.
Fig 5: SVC V-I characteristics
The V-I characteristics are described by the following three equations:
Within control range (-Icmax ≤ Isvc ≤ ILmax )
V = Vref + XsL Isvc
When V<Vmin , the SVC will reach its capacitive limit
B= -Bcmax
When Isvc>ILmax , the SVC will reach its inductive limit
B= BLmax
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
99
Power System V-I Characteristic
The system V-I characteristic is determined by considering the Thevenin equivalent
circuit as viewed from the bus whose voltage is to be regulated by the SVC. The Thevenin
impedance in Fig-6 is predominantly an inductive reactance. The corresponding bus voltage
versus reactive current characteristic is shown in fig-7. Bus voltage increases linearly with
capacitive current injection at bus and decreases linearly with inductive current injection at
bus. Fig-8 shows the effect of source voltage on the V-I characteristic of the power system
bus. and Fig-9 shows the system equivalent reactance on the V-I characteristic of the power
system bus
Fig-6 : Thevenin equivalent circuit of HVAC network
Fig-7: Power system bus Voltage-Reactive current characteristic
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
100
Fig-8: Effect of varying source voltage on V-I characteristic of power system bus
Fig-9: Effect of varying system reactance on V-I characteristic of power system bus
Composite SVC-Power System V-I Characteristic
The system characteristic may be expressed as
V = Eth – Xth Is
Where
V = Power system bus voltage
Is = Bus load current
Eth = Source voltage
Xth = System Thevenin reactance
For inductive load current Is is positive and for capacitive load current Is is negative.
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
101
The SVC characteristic may be expressed as
V = V0 + XSL Is
Where
V = Power system bus voltage
Is = SVC current
Vo = SVC reference voltage where net SVC current is zero
XSL = SVC slope reactance
For inductive SVC current Is is positive and for capacitive SVC current Is is
negative. For voltage outside the control range, the ratio V/Is is determined by the ratings of
the inductor and capacitor. The solution of SVC and power system characteristic equations
graphically illustrated in figure 10. Three system characteristics are considered in the figure,
corresponding to three values of the source voltage. The middle characteristic represents the
nominal system conditions and is assummed to intersect the SVC characteristic at Point A
where V = V0 and I = Is . If the system voltage increases by Eth , due to decrease of
system load level, bus voltage V will increase to V1 without an SVC. With the SVC, the
operating point moves to B, by absorbing inductive current I3. Therefore, SVC hold the
voltage V3 instead of V1 without the SVC.
Similarly if the system voltage decreases by Eth , due to increase of system load
level, bus voltage V will decrease to V2 without an SVC. With the SVC, the operating point
moves to C, by injecting capacitive current I4. Therefore, SVC hold the voltage V4 instead of
V2 without the SVC.
Fig10: Graphical solution of SVC operating point for given system conditions
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
102
III. RESPONSE OF SVC DURING LOW VOLTAGE AND HIGH WIND POWER
GENERATION CONDITION
SVC of (+)150/(-)150 MVAR capacity is connected at 400 kV GSS Jaisalmer through
400/33 kV transformer (Bus-19). Due to high wind power generation SVC reference voltage
is set to 1.10 PU. The slope of SVC is 0.09. The purpose of connecting SVC at Bus number
19 is to regulate the voltage at bus number 2 i.e. Jaisalmer 400 kV bus with the increase in
wind power generation. To demonstrate the effect of SVC on voltage and system losses, load
flow studies have been carried out without and with (+)150/(-)150 MVAR SVC at Bus-19 for
various wind power generation schedule. Following four cases have been considered in the
load flow studies:-
S.
No.
Particulars Connected
capacity of
wind power
plants (MW)
Net Wind Power Despatch (MW)
Case-1
(45 % of
IC)
Case-2
(55 % of
IC)
Case-3
(65 % of
IC)
Case-4
(75 % of IC)
1 400 kV GSS
Jaisalmer
1340 603 737 871 1005
2 220 kV GSS
Amarsagar
760 342 408 494 570
3 132 kV GSS
Jaisalmer
40 18 22 26 30
Total 2140 963 1177 1391 1605
OUTPUT OF LOAD FLOW STUDIES
Case-1 : 45 % wind power generation of installed wind farms capacity
Power plots of load flow study without SVC at Bus-19 is placed at fig-11A and Power plots
of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged
is placed at fig-11B.
Case-2: 55 % wind power generation of installed wind farms capacity
Power plots of load flow study without SVC at Bus-19 is placed at fig-12A and Power plots
of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged
is placed at fig-12B.
Case-3: 65 % wind power generation of installed wind farms capacity
Power plots of load flow study without SVC at Bus-19 is placed at fig-13A and Power plots
of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged
is placed at fig-13B.
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
103
Case-4: 75 % wind power generation of installed wind farms capacity
Power plots of load flow study without SVC at 400 kV GSS Jaisalmer is placed at fig-14A
and Power plots of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions
remains unchanged is placed at fig-14B.
EFFECT OF SVC ON POWER SYSTEM VOLTAGE
Power system voltage without and with SVC are tabulated in Table-1. With the
increase of wind power generation, transmission voltages are decreased due to increase of
power flow on transmission lines. With SVC fall in transmission voltages are much lesser
than without SVC.
Table-1: Bus voltages (kV) without and with SVC in high wind power generation
condition
S.
No.
Particulars Case-1
(45 % of IC)
Case-2
(55 % of IC)
Case-3
(65 % of IC)
Case-4
(75 % of IC)
Wind Power Generation (MW) 963 1177 1391 1605
A 400 kV bus voltage
1 400 kV GSS
Jaisalmer
Without SVC 401.48 396.19 388.46 377.40
With SVC 406.91 402.76 396.93 388..86
2 400 kV GSS Barmer Without SVC 402 398 392 384
With SVC 405 402 397 390
3 400 kV GSS Rajwest
LTPS
Without SVC 402 398 392 384
With SVC 405 401 397 390
B 220 kV bus voltage
1 400 kV GSS
Jaisalmer
Without SVC 221 217 213 206
With SVC 223 221 217 212
2 400 kV GSS Barmer Without SVC 219 216 212 205
With SVC 222 219 215 210
3 220 kV GSS
Amarsagar
Without SVC 219 216 211 204
With SVC 221 219 215 210
4 220 kV GSS Phalodi Without SVC 202 198 194 187
With SVC 203 200 196 191
5 220 kV GSS Tinwari Without SVC 205 203 202 199
With SVC 205 204 203 201
C 132 kV bus voltage
1 220 kV GSS
Amarsagar
Without SVC 131 129 126 122
With SVC 133 131 129 126
2 220 kV GSS Phalodi Without SVC 115 113 109 105
With SVC 116 114 111 107
3 220 kV GSS Tinwari Without SVC 119 118 117 116
With SVC 119 118 117 116
4 132 kV GSS
Jaisalmer
Without SVC 130 128 125 121
With SVC 131 130 128 126
D SVC Bus voltage Without SVC 33.97 33.52 32.87 31.93
With SVC 34.73 34.43 34.01 33.43
E MVAR loading on
SVC (Capacitive)
Without SVC - - - -
With SVC 57 66 79 98
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
104
EFFECT OF SVC ON POWER TRANSMISSION LOSSES
Power system voltage without and with SVC for various wind power generation schedules
are tabulated in Table-2.
Table-2: Power System Losses without and with SVC in high wind power generation
condition
S.
No.
Particulars Case-1
(45 % of
IC)
Case-2
(55 % of
IC)
Case-3
(65 % of
IC)
Case-4
(75 % of IC)
1 Wind Power
Generation
(MW)
963 1177 1391 1605
2 Without SVC
Losses (MW)
31.10 43.71 60.14 82.62
3 With SVC Losses
(MW)
30.63 42.88 58.30 78.06
Above tabulated data indicates that with SVC transmission losses are reduced due to increase
of system voltage and decrease of reactive power flow on transmission lines.
Fig.11A: Without SVC at Bus-19 (45 % i.e. 963 MW wind power generation)
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
105
Fig.11B: With (+) 150/(-)150 MVAR SVC at Bus-19 (45 % i.e. 963 MW wind power
generation)
Fig.12A: Without SVC at Bus-19 (55 % i.e. 1177 MW wind power generation)
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
106
Fig.12B: With (+) 150/(-)150 MVAR SVC at 400 kV GSS Jaisalmer (55 % i.e. 1177
MW wind power generation)
Fig.13A: Without SVC at Bus-19 (65 % i.e. 1391 MW wind power generation)
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
107
Fig.13B: With (+) 150/(-)150 MVAR SVC at Bus-19 (65 % i.e. 1391 MW wind power
generation)
Fig.14A: With SVC at Bus-19 (75 % i.e. 1605 MW wind power generation)
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
108
Fig.14B: With (+) 150/(-)150 MVAR SVC at Bus-19 (75 % i.e. 1605 MW wind power
generation)
Fig.15: Bus-2 Voltage without and with SVC with variation in wind power generation
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
109
Fig.16: Loading (MVAR) on SVC with variation in wind power generation
IV. EFFECT OF SVC DURING HIGH VOLTAGE AND LOW WIND POWER
GENERATION CONDITION
SVC of (+)150/(-)150 MVAR capacity is connected at 400 kV GSS Jaisalmer through
400/33 kV transformer (Bus-19). Due to low wind power generation SVC reference voltage
is set to 0.90 PU. The slope of SVC is 0.09. The purpose of connecting SVC at Bus number
19 is to regulate the voltage at bus number 2 i.e. Jaisalmer 400 kV bus with the decrease in
wind power generation. To demonstrate the effect of SVC on voltage load flow studies have
been carried out without and with (+)150/(-)150 MVAR SVC at 400 kV GSS Jaisalmer for
various wind power generation schedule. Following two cases have been considered in the
load flow studies:-
S.
No.
Particulars Connected capacity of wind
power plants (MW)
Net Wind Power Despatch
(MW)
Case-1
(35 % of
IC)
Case-2
(25 % of IC)
1 400 kV GSS
Jaisalmer
1340 469 335
2 220 kV GSS
Amarsagar
760 266 190
3 132 kV GSS
Jaisalmer
40 14 10
Total 2140 749 535
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
110
OUTPUT OF LOAD FLOW STUDIES
Case-1 : 35 % wind power generation of installed wind farms capacity
Power plots of load flow study without SVC at Bus-19 is placed at fig-17A and Power plots of
LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged is
placed at fig-17B.
Case-2: 25 % wind power generation of installed wind farms capacity
Power plots of load flow study without SVC at Bus-19 is placed at fig-18A and Power plots of
LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged is
placed at fig-18B.
EFFECT OF SVC ON POWER SYSTEM VOLTAGE
Power system voltage without and with SVC are tabulated in Table-3. With the decrease
of wind power generation, transmission voltages are increased due to decrease of power flow on
transmission lines. With SVC rise in transmission voltages are less than without SVC.
Table-3 : Bus voltages (kV) without and with SVC in low wind power generation condition
S.
No.
Particulars Case-1
(35 % of IC)
Case-2
(25 % of IC)
Wind Power Generation (MW) 749 535
A 400 kV bus voltage
1 400 kV GSS Jaisalmer Without SVC 427.04 428.39
With SVC 412.80 414.14
2 400 kV GSS Barmer Without SVC 427 428
With SVC 419 420
3 400 kV GSS Rajwest LTPS Without SVC 426 428
With SVC 419 421
B 220 kV bus voltage
1 400 kV GSS Jaisalmer Without SVC 235 236
With SVC 228 228
2 400 kV GSS Barmer Without SVC 234 235
With SVC 228 229
3 220 kV GSS Amarsagar Without SVC 233 233
With SVC 226 227
4 220 kV GSS Phalodi Without SVC 218 219
With SVC 214 215
5 220 kV GSS Tinwari Without SVC 218 219
With SVC 217 218
C 132 kV bus voltage
1 220 kV GSS Amarsagar Without SVC 140 140
With SVC 136 136
2 220 kV GSS Phalodi Without SVC 125 126
With SVC 123 124
3 220 kV GSS Tinwari Without SVC 127 127
With SVC 126 127
4 132 kV GSS Jaisalmer Without SVC 139 139
With SVC 135 136
D SVC Bus voltage Without SVC 36.13 36.25
With SVC 34.11 34.21
E MVAR loading on SVC
(Inductive)
Without SVC - -
With SVC 158 161
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
111
Fig.17A: Without SVC at Bus-19 (35 % i.e. 749 MW wind power generation)
Fig.17B: With (+) 150/(-)150 MVAR SVC at Bus-19 (35 % i.e. 749 MW wind power
generation)
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
112
Fig.18A: Without SVC at Bus-19 (25 % i.e. 535 MW wind power generation)
Fig.18B: With (+) 150/(-)150 MVAR SVC at Bus-19 (25 % i.e. 535 MW wind power
generation)
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
113
V. CONCLUSION
Most of wind power plants are installed far away from load centers. Long EHV
transmission lines are being constructed for evacuation of wind power generation up to load
centers without planning reactive power management and voltage control. Reactive power
management using shunt reactors and shunt capacitors is not successful in wind power plants
penetrated power system due to large & sudden variation in wind power generation. SVC is
able to regulate the power transmission voltage with the variation in wind power generation.
With the help of Static Var Compensator high as well as low transmission voltages can be
controlled. During high power system voltage, SVC absorb reactive power and function as
shunt reactor and there is less rise in system voltage with SVC as compared to without SVC.
During low power system voltage, SVC generates reactive power & function as shunt
capacitor. Therefore, there is less drop in system voltage with SVC as compared without
SVC.
VI. REFERENCE
[1]. N.G. Hingorani and L. Gyugy, Understanding FACTS, Concepts and Technology of
Flexible AC Transmission System. New York: Inst. Elect. Electron. Eng., Inc., 2000.
[2]. J. J. Paserba, D. J. Leonard, N.W. Miller, S. T. Naumann, M. G. Lauby, and F. P. Sener,
“Coordination of a distribution level continuously controlled compensation device with
existing substation equipment for long term var management,” IEEE Trans. Power Del., vol.
9, no. 2, pp.1034–1040, Apr. 1994.
[3]. K. M. Son, K. S. Moon, S. K. Lee, and J. K. Park, “Coordination of an SVC with a
ULTC reserving compensation margin for emergency control,” IEEE Trans. Power Del., vol.
15, no. 4, pp. 1193–1198, Oct. 2000.
[4]. Task Force no. 2 on Static Var Compensators, Static Var Compensators (1986).
[5]. IEEE Special Stability Controls Working Group, “Static var compensator models for
power flow and dynamic performance simulation,” IEEE Trans. Power Syst., vol. 9, no. 1,
pp. 229–240, Feb. 1994.
[6]. R.A. Schlueter, ,A voltage stability security assessment method,” IEEE Trans. on Power
Systems, vol. 13, no. 4, November 1998, pp. 1423- 1438.
[7]. D. Jovcic, Pahalawaththa, N., Zavahir, M. & Hassan, H.A. (2003) “SVC Dynamic
analytical Model”_ IEEE Trans. On Power Delivery, Vol. 18, No. 4, (October), pp. 1455 -
1461.
[8]. FACTS Controllers in Power Transmission and Distribution By- K.R. Padiyar.
[9] Ameer H. Abd and D.S.Chavan, “Impact of Wind Farm of Double-Fed Induction
Generator (Dfig) on Voltage Quality”, International Journal of Electrical Engineering &
Technology (IJEET), Volume 3, Issue 1, 2012, pp. 235 - 246, ISSN Print : 0976-6545,
ISSN Online: 0976-6553.
[10] Dr. M. P. Sharma and Sarfaraz Nawaz, “Understanding Operation of Shunt Capacitors
and Oltc for Transmission Loss Reduction”, International Journal of Electrical Engineering &
Technology (IJEET), Volume 4, Issue 2, 2013, pp. 344 - 357, ISSN Print : 0976-6545,
ISSN Online: 0976-6553.
[11] T. Nageswara Prasad, V. Chandra Jagan Mohan and Dr. V.C. Veera Reddy, “Shunt
Compensator for Integration of Wind Farm to Polluted Distribution System”, International
Journal of Electrical Engineering & Technology (IJEET), Volume 3, Issue 3, 2012,
pp. 89 - 101, ISSN Print : 0976-6545, ISSN Online: 0976-6553.
International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 –
6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME
114
BIOGRAPHIES
Dr. M. P. Sharma received the B.E. degree in Electrical Engineering in 1996 Govt.
Engineering College, Kota, Rajasthan and M. E. degree in Power Systems in 2001 and Ph.D.
degree in 2009 from Malaviya Regional Engineering College, Jaipur (Now name as MNIT).
He is presently working as Assistant Engineer, Rajasthan Rajya Vidhyut Prasaran Nigam
Ltd., Jaipur. He is involved in the system studies of Rajasthan power system for development
of power transmission system in Rajasthan and planning of the power evacuation system for
new power plants. His research interest includes Reactive Power Optimization, Power
System Stability, reduction of T&D losses and protection of power system.(email:
mahavir_sh@rediffmail.com)
Devendra Saini received the B.Tech. degree in electrical engineering from Rajasthan
Technical University, Kota, in 2011. He is currently pursuing the M.Tech.degree in Power
System from the Jodhpur National University ,Jodhpur. He is currently an Assistant Professor
at the Electrical Engi. Dept. Shankara Institute Of Technology , Jaipur ,Rajasthan. His
research interests are in the areas of FACTS power system problems, controls and transient
stability (email :devendrasaini786@gmail.com)
Swati Harsh has received her B.E. degree from University of Rajasthan. She is currently
working as Assistant professor in department of Electrical Engineering at Anand
International College of Engineering. She is currently pursuing M.Tech. (Power System)
from Swami Keshvanand Institute of Technology, Management and Gramothan (SKIT)
(email: swatiharsh1st@gmail.com)
Sarfaraz Nawaz has received his B.E. degree from University of Rajasthan and M.Tech.
degree from MNIT, Jaipur. His research interests include power systems and power
electronics. He is currently an Associate Professor of the Electrical Engg. Dept., Swami
Keshvanand Institute of Technology, Management and Gramothan (SKIT) , Jaipur,
Rajasthan. (email: eesarfaraz1983@rediffmail.com)

More Related Content

What's hot

Study On Speed Control of DC MOTOR Using Thyristor
Study On Speed Control of DC MOTOR Using ThyristorStudy On Speed Control of DC MOTOR Using Thyristor
Study On Speed Control of DC MOTOR Using ThyristorIRJET Journal
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
A Matlab/Simulink Model for the control scheme utilized to improve power qual...
A Matlab/Simulink Model for the control scheme utilized to improve power qual...A Matlab/Simulink Model for the control scheme utilized to improve power qual...
A Matlab/Simulink Model for the control scheme utilized to improve power qual...AM Publications
 
Study on Excitation system in Power sector
Study on Excitation system in Power sectorStudy on Excitation system in Power sector
Study on Excitation system in Power sectorBoben Anto Chemmannoor
 
Analysis and Simulation of Asynchronous Machine Connected with Load Accomplis...
Analysis and Simulation of Asynchronous Machine Connected with Load Accomplis...Analysis and Simulation of Asynchronous Machine Connected with Load Accomplis...
Analysis and Simulation of Asynchronous Machine Connected with Load Accomplis...YogeshIJTSRD
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Performance comparison of SVC and SSSC with POD controller for Power System S...
Performance comparison of SVC and SSSC with POD controller for Power System S...Performance comparison of SVC and SSSC with POD controller for Power System S...
Performance comparison of SVC and SSSC with POD controller for Power System S...IOSR Journals
 
DYNAMIC MODELLING OF EXCITATION AND GOVERNOR EFFECT ON STABILITY OF ELECTRICA...
DYNAMIC MODELLING OF EXCITATION AND GOVERNOR EFFECT ON STABILITY OF ELECTRICA...DYNAMIC MODELLING OF EXCITATION AND GOVERNOR EFFECT ON STABILITY OF ELECTRICA...
DYNAMIC MODELLING OF EXCITATION AND GOVERNOR EFFECT ON STABILITY OF ELECTRICA...UKOIMA KELVIN MNSE, MNIEEE
 
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...IJMER
 
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...IJAPEJOURNAL
 
Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...IAEME Publication
 
Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...Indra S Wahyudi
 
methods to control speed of dc motors
methods to control speed of dc motorsmethods to control speed of dc motors
methods to control speed of dc motorsharshid panchal
 
Unbalanced Voltages Impacts on the Energy Performance of Induction Motors
Unbalanced Voltages Impacts on the Energy Performance of Induction Motors  Unbalanced Voltages Impacts on the Energy Performance of Induction Motors
Unbalanced Voltages Impacts on the Energy Performance of Induction Motors IJECEIAES
 

What's hot (20)

Study On Speed Control of DC MOTOR Using Thyristor
Study On Speed Control of DC MOTOR Using ThyristorStudy On Speed Control of DC MOTOR Using Thyristor
Study On Speed Control of DC MOTOR Using Thyristor
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
40220140505011
4022014050501140220140505011
40220140505011
 
A Matlab/Simulink Model for the control scheme utilized to improve power qual...
A Matlab/Simulink Model for the control scheme utilized to improve power qual...A Matlab/Simulink Model for the control scheme utilized to improve power qual...
A Matlab/Simulink Model for the control scheme utilized to improve power qual...
 
Study on Excitation system in Power sector
Study on Excitation system in Power sectorStudy on Excitation system in Power sector
Study on Excitation system in Power sector
 
Analysis and Simulation of Asynchronous Machine Connected with Load Accomplis...
Analysis and Simulation of Asynchronous Machine Connected with Load Accomplis...Analysis and Simulation of Asynchronous Machine Connected with Load Accomplis...
Analysis and Simulation of Asynchronous Machine Connected with Load Accomplis...
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Eo34861869
Eo34861869Eo34861869
Eo34861869
 
B010211015
B010211015B010211015
B010211015
 
Performance comparison of SVC and SSSC with POD controller for Power System S...
Performance comparison of SVC and SSSC with POD controller for Power System S...Performance comparison of SVC and SSSC with POD controller for Power System S...
Performance comparison of SVC and SSSC with POD controller for Power System S...
 
Harmonic Elimination Using STATCOM for SEIG Fed Induction Motor Load
Harmonic Elimination Using STATCOM for SEIG Fed Induction Motor LoadHarmonic Elimination Using STATCOM for SEIG Fed Induction Motor Load
Harmonic Elimination Using STATCOM for SEIG Fed Induction Motor Load
 
DYNAMIC MODELLING OF EXCITATION AND GOVERNOR EFFECT ON STABILITY OF ELECTRICA...
DYNAMIC MODELLING OF EXCITATION AND GOVERNOR EFFECT ON STABILITY OF ELECTRICA...DYNAMIC MODELLING OF EXCITATION AND GOVERNOR EFFECT ON STABILITY OF ELECTRICA...
DYNAMIC MODELLING OF EXCITATION AND GOVERNOR EFFECT ON STABILITY OF ELECTRICA...
 
40220140505010
4022014050501040220140505010
40220140505010
 
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...Grid fault Control Scheme for Peak Current Reduction in  Photovoltaic Inverte...
Grid fault Control Scheme for Peak Current Reduction in Photovoltaic Inverte...
 
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
 
Ijmet 10 01_109
Ijmet 10 01_109Ijmet 10 01_109
Ijmet 10 01_109
 
Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...Study of the impact on the protection plan of a pv production integrated to t...
Study of the impact on the protection plan of a pv production integrated to t...
 
Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...Effect of converter dc fault on the transient stability of a multi machine po...
Effect of converter dc fault on the transient stability of a multi machine po...
 
methods to control speed of dc motors
methods to control speed of dc motorsmethods to control speed of dc motors
methods to control speed of dc motors
 
Unbalanced Voltages Impacts on the Energy Performance of Induction Motors
Unbalanced Voltages Impacts on the Energy Performance of Induction Motors  Unbalanced Voltages Impacts on the Energy Performance of Induction Motors
Unbalanced Voltages Impacts on the Energy Performance of Induction Motors
 

Similar to Application of svc for voltage control in wind farm power system 2

A new control methods for offshore grid connected wind energy conversion syst...
A new control methods for offshore grid connected wind energy conversion syst...A new control methods for offshore grid connected wind energy conversion syst...
A new control methods for offshore grid connected wind energy conversion syst...IAEME Publication
 
Multi-machine system with Series FACTS device: Static synchronous series comp...
Multi-machine system with Series FACTS device: Static synchronous series comp...Multi-machine system with Series FACTS device: Static synchronous series comp...
Multi-machine system with Series FACTS device: Static synchronous series comp...IRJET Journal
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMIJERA Editor
 
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdfDesign_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdfEngnr Kami Zeb
 
Advanced five level five phase cascaded multilevel inverter with svpwm algorit
Advanced five level   five phase cascaded multilevel inverter with svpwm algoritAdvanced five level   five phase cascaded multilevel inverter with svpwm algorit
Advanced five level five phase cascaded multilevel inverter with svpwm algoritIAEME Publication
 
Minimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOMMinimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOMIRJET Journal
 
Wind energy conversion systems using fuzzy controlled statcom for power qua
Wind energy conversion systems using fuzzy controlled statcom for power quaWind energy conversion systems using fuzzy controlled statcom for power qua
Wind energy conversion systems using fuzzy controlled statcom for power quaIAEME Publication
 
Optimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow ControlOptimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow ControlIJMER
 
Enhancing the Control of Iraqi Power System Using FACTS Devices and Renewabl...
Enhancing the Control of Iraqi Power System Using FACTS  Devices and Renewabl...Enhancing the Control of Iraqi Power System Using FACTS  Devices and Renewabl...
Enhancing the Control of Iraqi Power System Using FACTS Devices and Renewabl...IJMER
 
Voltage Flicker Mitigation of Wind Farm Using a STATCOM
Voltage Flicker Mitigation of Wind Farm Using a STATCOMVoltage Flicker Mitigation of Wind Farm Using a STATCOM
Voltage Flicker Mitigation of Wind Farm Using a STATCOMDr. Sudhir Kumar Srivastava
 
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion SystemIRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion SystemIRJET Journal
 
Analysis of SVPWM for Inverter fed DTC of Induction motor Drive
Analysis of SVPWM for Inverter fed DTC of Induction motor DriveAnalysis of SVPWM for Inverter fed DTC of Induction motor Drive
Analysis of SVPWM for Inverter fed DTC of Induction motor DriveIJSRED
 

Similar to Application of svc for voltage control in wind farm power system 2 (20)

A new control methods for offshore grid connected wind energy conversion syst...
A new control methods for offshore grid connected wind energy conversion syst...A new control methods for offshore grid connected wind energy conversion syst...
A new control methods for offshore grid connected wind energy conversion syst...
 
40220130405019
4022013040501940220130405019
40220130405019
 
Multi-machine system with Series FACTS device: Static synchronous series comp...
Multi-machine system with Series FACTS device: Static synchronous series comp...Multi-machine system with Series FACTS device: Static synchronous series comp...
Multi-machine system with Series FACTS device: Static synchronous series comp...
 
Mitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOMMitigation of Voltage Fluctuations in Power System Using STATCOM
Mitigation of Voltage Fluctuations in Power System Using STATCOM
 
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdfDesign_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
Design_and_Investigation_of_FRT_Schemes_for_Three-Phase_Grid-Tied_PV_System.pdf
 
Advanced five level five phase cascaded multilevel inverter with svpwm algorit
Advanced five level   five phase cascaded multilevel inverter with svpwm algoritAdvanced five level   five phase cascaded multilevel inverter with svpwm algorit
Advanced five level five phase cascaded multilevel inverter with svpwm algorit
 
Minimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOMMinimization of Power Loss in Distribution System using SVC and STATCOM
Minimization of Power Loss in Distribution System using SVC and STATCOM
 
Wind energy conversion systems using fuzzy controlled statcom for power qua
Wind energy conversion systems using fuzzy controlled statcom for power quaWind energy conversion systems using fuzzy controlled statcom for power qua
Wind energy conversion systems using fuzzy controlled statcom for power qua
 
Optimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow ControlOptimal Location of Statcom for Power Flow Control
Optimal Location of Statcom for Power Flow Control
 
Ib3313831387
Ib3313831387Ib3313831387
Ib3313831387
 
Ib3313831387
Ib3313831387Ib3313831387
Ib3313831387
 
Enhancing the Control of Iraqi Power System Using FACTS Devices and Renewabl...
Enhancing the Control of Iraqi Power System Using FACTS  Devices and Renewabl...Enhancing the Control of Iraqi Power System Using FACTS  Devices and Renewabl...
Enhancing the Control of Iraqi Power System Using FACTS Devices and Renewabl...
 
40220140504004
4022014050400440220140504004
40220140504004
 
Voltage Flicker Mitigation of Wind Farm Using a STATCOM
Voltage Flicker Mitigation of Wind Farm Using a STATCOMVoltage Flicker Mitigation of Wind Farm Using a STATCOM
Voltage Flicker Mitigation of Wind Farm Using a STATCOM
 
40220140506002
4022014050600240220140506002
40220140506002
 
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion SystemIRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
IRJET- Low Volatge Ride through Solution for Wind Energy Conversion System
 
40220130405018 2
40220130405018 240220130405018 2
40220130405018 2
 
Analysis of SVPWM for Inverter fed DTC of Induction motor Drive
Analysis of SVPWM for Inverter fed DTC of Induction motor DriveAnalysis of SVPWM for Inverter fed DTC of Induction motor Drive
Analysis of SVPWM for Inverter fed DTC of Induction motor Drive
 
Hq3513331337
Hq3513331337Hq3513331337
Hq3513331337
 
Q4502102105
Q4502102105Q4502102105
Q4502102105
 

More from IAEME Publication

IAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdfIAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdfIAEME Publication
 
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...IAEME Publication
 
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURSA STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURSIAEME Publication
 
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURSBROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURSIAEME Publication
 
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONSDETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONSIAEME Publication
 
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONSANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONSIAEME Publication
 
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINOVOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINOIAEME Publication
 
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...IAEME Publication
 
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMYVISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMYIAEME Publication
 
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...IAEME Publication
 
GANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICEGANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICEIAEME Publication
 
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...IAEME Publication
 
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...IAEME Publication
 
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...IAEME Publication
 
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...IAEME Publication
 
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...IAEME Publication
 
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...IAEME Publication
 
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...IAEME Publication
 
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...IAEME Publication
 
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENTA MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENTIAEME Publication
 

More from IAEME Publication (20)

IAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdfIAEME_Publication_Call_for_Paper_September_2022.pdf
IAEME_Publication_Call_for_Paper_September_2022.pdf
 
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
MODELING AND ANALYSIS OF SURFACE ROUGHNESS AND WHITE LATER THICKNESS IN WIRE-...
 
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURSA STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
A STUDY ON THE REASONS FOR TRANSGENDER TO BECOME ENTREPRENEURS
 
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURSBROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
BROAD UNEXPOSED SKILLS OF TRANSGENDER ENTREPRENEURS
 
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONSDETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
DETERMINANTS AFFECTING THE USER'S INTENTION TO USE MOBILE BANKING APPLICATIONS
 
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONSANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
ANALYSE THE USER PREDILECTION ON GPAY AND PHONEPE FOR DIGITAL TRANSACTIONS
 
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINOVOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
VOICE BASED ATM FOR VISUALLY IMPAIRED USING ARDUINO
 
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
IMPACT OF EMOTIONAL INTELLIGENCE ON HUMAN RESOURCE MANAGEMENT PRACTICES AMONG...
 
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMYVISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
VISUALISING AGING PARENTS & THEIR CLOSE CARERS LIFE JOURNEY IN AGING ECONOMY
 
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
A STUDY ON THE IMPACT OF ORGANIZATIONAL CULTURE ON THE EFFECTIVENESS OF PERFO...
 
GANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICEGANDHI ON NON-VIOLENT POLICE
GANDHI ON NON-VIOLENT POLICE
 
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
A STUDY ON TALENT MANAGEMENT AND ITS IMPACT ON EMPLOYEE RETENTION IN SELECTED...
 
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
ATTRITION IN THE IT INDUSTRY DURING COVID-19 PANDEMIC: LINKING EMOTIONAL INTE...
 
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
INFLUENCE OF TALENT MANAGEMENT PRACTICES ON ORGANIZATIONAL PERFORMANCE A STUD...
 
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
A STUDY OF VARIOUS TYPES OF LOANS OF SELECTED PUBLIC AND PRIVATE SECTOR BANKS...
 
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
EXPERIMENTAL STUDY OF MECHANICAL AND TRIBOLOGICAL RELATION OF NYLON/BaSO4 POL...
 
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
ROLE OF SOCIAL ENTREPRENEURSHIP IN RURAL DEVELOPMENT OF INDIA - PROBLEMS AND ...
 
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
 
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
APPLICATION OF FRUGAL APPROACH FOR PRODUCTIVITY IMPROVEMENT - A CASE STUDY OF...
 
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENTA MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
A MULTIPLE – CHANNEL QUEUING MODELS ON FUZZY ENVIRONMENT
 

Recently uploaded

Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...anilsa9823
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒anilsa9823
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMANIlamathiKannappan
 
Event mailer assignment progress report .pdf
Event mailer assignment progress report .pdfEvent mailer assignment progress report .pdf
Event mailer assignment progress report .pdftbatkhuu1
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsP&CO
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLSeo
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 DelhiCall Girls in Delhi
 
Best Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaBest Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaShree Krishna Exports
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Servicediscovermytutordmt
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Delhi Call girls
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdfRenandantas16
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxAndy Lambert
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesDipal Arora
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear RegressionRavindra Nath Shukla
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...Aggregage
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.Aaiza Hassan
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...lizamodels9
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...Suhani Kapoor
 

Recently uploaded (20)

Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
 
A DAY IN THE LIFE OF A SALESMAN / WOMAN
A DAY IN THE LIFE OF A  SALESMAN / WOMANA DAY IN THE LIFE OF A  SALESMAN / WOMAN
A DAY IN THE LIFE OF A SALESMAN / WOMAN
 
Event mailer assignment progress report .pdf
Event mailer assignment progress report .pdfEvent mailer assignment progress report .pdf
Event mailer assignment progress report .pdf
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRLMONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
MONA 98765-12871 CALL GIRLS IN LUDHIANA LUDHIANA CALL GIRL
 
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
9599632723 Top Call Girls in Delhi at your Door Step Available 24x7 Delhi
 
Best Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in IndiaBest Basmati Rice Manufacturers in India
Best Basmati Rice Manufacturers in India
 
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabiunwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
unwanted pregnancy Kit [+918133066128] Abortion Pills IN Dubai UAE Abudhabi
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Service
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptx
 
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best ServicesMysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
Mysore Call Girls 8617370543 WhatsApp Number 24x7 Best Services
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear Regression
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
 
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
VIP Call Girls Gandi Maisamma ( Hyderabad ) Phone 8250192130 | ₹5k To 25k Wit...
 

Application of svc for voltage control in wind farm power system 2

  • 1. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 95 APPLICATION OF SVC FOR VOLTAGE CONTROL IN WIND FARM POWER SYSTEM Dr. M. P. Sharma Devandra Saini AEN, RVPNL, Jaipur Asst. Prof., EE Deptt., SIT, Jaipur Swati Harsh Sarfaraz Nawaz Asst. Prof., EE Deptt.,AICE, Jaipur Associate Prof. Deptt., SKIT, Jaipur ABSTRACT Most of wind power plants are installed far away from load centers, hence require long EHV transmission lines for evacuation system for pooling the power and transmitting to far off load centers. Wind Power Generation is infirm and variable subject to vagaries of nature. Due to large variations in wind power generation, power flows on transmission lines are also vary and accordingly there is a wide variation in power transmission system voltage from minimum 0.8 pu to maximum 1.20 pu. Due to low & high power system voltages, transmission lines are tripped resulting constrained in wind power evacuation. In this paper Static Var Compensator is proposed at wind power plants penetrated power system. In this paper simulation studies have been carried out to validate the effectiveness of the SVC for voltage control with the variation in wind power generation. Case studies are carried out on 18-bus Rajasthan power system to demonstrate the performance of the SVC during high and low wind power generation conditions. Wind power plants penetrated part of Rajasthan power system has been modeled using Mi-Power power system analysis software designed by the M/s PRDC Bangalore. Results of tests conducted on the model system in various possible field conditions are presented and discussed. I. INTRODUCTION In Rajasthan, most of wind power plants are concentrated in western part i.e. Jaisalmer which is far away from load centers. As on 31-3-2013, total 2140 MW capacity wind power plants are installed in Jaisalmer area. For evacuation of wind power generation from Jaisalmer to load centers, 2 nos. 400 kV lines, 3 nos. 220 kV lines & 2 nos. 132 kV lines INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) ISSN 0976 – 6545(Print) ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), pp. 95-114 © IAEME: www.iaeme.com/ijeet.asp Journal Impact Factor (2013): 5.5028 (Calculated by GISI) www.jifactor.com IJEET © I A E M E
  • 2. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 96 have been constructed. There is a huge variations in wind generation i.e. variation is from zero to maximum generation. Variation in wind power generation on typical days is shown in following figures:- Fig-1: HOURLY AVERAGE WIND GENERATION for 15 March, 2013 Fig-2: HOURLY AVERAGE WIND GENERATION for 23 March, 2013
  • 3. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 97 Fig-3: HOURLY AVERAGE WIND GENERATION for 10 April,2013 Fig-4: HOURLY AVERAGE WIND GENERATION for 15 April, 2013
  • 4. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 98 Due to variation in wind power generation, power transmission voltage is fluctuated. Voltage fluctuations are mainly due to Long EHV transmission lines Lack of load in western Rajasthan Erratic variation in generation pattern Wind Generators do not provide the required VAR support Over-voltage causes over-fluxing in transformers resulting in tripping of transformers. Due to over voltages, transmission lines also tripped. With the help of FACTS devices, it is possible to regulate power system voltage with the variation of wind power generation. II. SVC AND POWER SYSTEM V-I CHARACTERISTICS SVC V-I Characteristic SVC composed of a controllable reactor and a fixed capacitor. The composite characteristic of SVC is derived by adding the individual characteristics of the components. SVC are defined by the slope reactance when the controlled voltage is within the control range. Fig 5: SVC V-I characteristics The V-I characteristics are described by the following three equations: Within control range (-Icmax ≤ Isvc ≤ ILmax ) V = Vref + XsL Isvc When V<Vmin , the SVC will reach its capacitive limit B= -Bcmax When Isvc>ILmax , the SVC will reach its inductive limit B= BLmax
  • 5. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 99 Power System V-I Characteristic The system V-I characteristic is determined by considering the Thevenin equivalent circuit as viewed from the bus whose voltage is to be regulated by the SVC. The Thevenin impedance in Fig-6 is predominantly an inductive reactance. The corresponding bus voltage versus reactive current characteristic is shown in fig-7. Bus voltage increases linearly with capacitive current injection at bus and decreases linearly with inductive current injection at bus. Fig-8 shows the effect of source voltage on the V-I characteristic of the power system bus. and Fig-9 shows the system equivalent reactance on the V-I characteristic of the power system bus Fig-6 : Thevenin equivalent circuit of HVAC network Fig-7: Power system bus Voltage-Reactive current characteristic
  • 6. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 100 Fig-8: Effect of varying source voltage on V-I characteristic of power system bus Fig-9: Effect of varying system reactance on V-I characteristic of power system bus Composite SVC-Power System V-I Characteristic The system characteristic may be expressed as V = Eth – Xth Is Where V = Power system bus voltage Is = Bus load current Eth = Source voltage Xth = System Thevenin reactance For inductive load current Is is positive and for capacitive load current Is is negative.
  • 7. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 101 The SVC characteristic may be expressed as V = V0 + XSL Is Where V = Power system bus voltage Is = SVC current Vo = SVC reference voltage where net SVC current is zero XSL = SVC slope reactance For inductive SVC current Is is positive and for capacitive SVC current Is is negative. For voltage outside the control range, the ratio V/Is is determined by the ratings of the inductor and capacitor. The solution of SVC and power system characteristic equations graphically illustrated in figure 10. Three system characteristics are considered in the figure, corresponding to three values of the source voltage. The middle characteristic represents the nominal system conditions and is assummed to intersect the SVC characteristic at Point A where V = V0 and I = Is . If the system voltage increases by Eth , due to decrease of system load level, bus voltage V will increase to V1 without an SVC. With the SVC, the operating point moves to B, by absorbing inductive current I3. Therefore, SVC hold the voltage V3 instead of V1 without the SVC. Similarly if the system voltage decreases by Eth , due to increase of system load level, bus voltage V will decrease to V2 without an SVC. With the SVC, the operating point moves to C, by injecting capacitive current I4. Therefore, SVC hold the voltage V4 instead of V2 without the SVC. Fig10: Graphical solution of SVC operating point for given system conditions
  • 8. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 102 III. RESPONSE OF SVC DURING LOW VOLTAGE AND HIGH WIND POWER GENERATION CONDITION SVC of (+)150/(-)150 MVAR capacity is connected at 400 kV GSS Jaisalmer through 400/33 kV transformer (Bus-19). Due to high wind power generation SVC reference voltage is set to 1.10 PU. The slope of SVC is 0.09. The purpose of connecting SVC at Bus number 19 is to regulate the voltage at bus number 2 i.e. Jaisalmer 400 kV bus with the increase in wind power generation. To demonstrate the effect of SVC on voltage and system losses, load flow studies have been carried out without and with (+)150/(-)150 MVAR SVC at Bus-19 for various wind power generation schedule. Following four cases have been considered in the load flow studies:- S. No. Particulars Connected capacity of wind power plants (MW) Net Wind Power Despatch (MW) Case-1 (45 % of IC) Case-2 (55 % of IC) Case-3 (65 % of IC) Case-4 (75 % of IC) 1 400 kV GSS Jaisalmer 1340 603 737 871 1005 2 220 kV GSS Amarsagar 760 342 408 494 570 3 132 kV GSS Jaisalmer 40 18 22 26 30 Total 2140 963 1177 1391 1605 OUTPUT OF LOAD FLOW STUDIES Case-1 : 45 % wind power generation of installed wind farms capacity Power plots of load flow study without SVC at Bus-19 is placed at fig-11A and Power plots of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged is placed at fig-11B. Case-2: 55 % wind power generation of installed wind farms capacity Power plots of load flow study without SVC at Bus-19 is placed at fig-12A and Power plots of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged is placed at fig-12B. Case-3: 65 % wind power generation of installed wind farms capacity Power plots of load flow study without SVC at Bus-19 is placed at fig-13A and Power plots of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged is placed at fig-13B.
  • 9. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 103 Case-4: 75 % wind power generation of installed wind farms capacity Power plots of load flow study without SVC at 400 kV GSS Jaisalmer is placed at fig-14A and Power plots of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged is placed at fig-14B. EFFECT OF SVC ON POWER SYSTEM VOLTAGE Power system voltage without and with SVC are tabulated in Table-1. With the increase of wind power generation, transmission voltages are decreased due to increase of power flow on transmission lines. With SVC fall in transmission voltages are much lesser than without SVC. Table-1: Bus voltages (kV) without and with SVC in high wind power generation condition S. No. Particulars Case-1 (45 % of IC) Case-2 (55 % of IC) Case-3 (65 % of IC) Case-4 (75 % of IC) Wind Power Generation (MW) 963 1177 1391 1605 A 400 kV bus voltage 1 400 kV GSS Jaisalmer Without SVC 401.48 396.19 388.46 377.40 With SVC 406.91 402.76 396.93 388..86 2 400 kV GSS Barmer Without SVC 402 398 392 384 With SVC 405 402 397 390 3 400 kV GSS Rajwest LTPS Without SVC 402 398 392 384 With SVC 405 401 397 390 B 220 kV bus voltage 1 400 kV GSS Jaisalmer Without SVC 221 217 213 206 With SVC 223 221 217 212 2 400 kV GSS Barmer Without SVC 219 216 212 205 With SVC 222 219 215 210 3 220 kV GSS Amarsagar Without SVC 219 216 211 204 With SVC 221 219 215 210 4 220 kV GSS Phalodi Without SVC 202 198 194 187 With SVC 203 200 196 191 5 220 kV GSS Tinwari Without SVC 205 203 202 199 With SVC 205 204 203 201 C 132 kV bus voltage 1 220 kV GSS Amarsagar Without SVC 131 129 126 122 With SVC 133 131 129 126 2 220 kV GSS Phalodi Without SVC 115 113 109 105 With SVC 116 114 111 107 3 220 kV GSS Tinwari Without SVC 119 118 117 116 With SVC 119 118 117 116 4 132 kV GSS Jaisalmer Without SVC 130 128 125 121 With SVC 131 130 128 126 D SVC Bus voltage Without SVC 33.97 33.52 32.87 31.93 With SVC 34.73 34.43 34.01 33.43 E MVAR loading on SVC (Capacitive) Without SVC - - - - With SVC 57 66 79 98
  • 10. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 104 EFFECT OF SVC ON POWER TRANSMISSION LOSSES Power system voltage without and with SVC for various wind power generation schedules are tabulated in Table-2. Table-2: Power System Losses without and with SVC in high wind power generation condition S. No. Particulars Case-1 (45 % of IC) Case-2 (55 % of IC) Case-3 (65 % of IC) Case-4 (75 % of IC) 1 Wind Power Generation (MW) 963 1177 1391 1605 2 Without SVC Losses (MW) 31.10 43.71 60.14 82.62 3 With SVC Losses (MW) 30.63 42.88 58.30 78.06 Above tabulated data indicates that with SVC transmission losses are reduced due to increase of system voltage and decrease of reactive power flow on transmission lines. Fig.11A: Without SVC at Bus-19 (45 % i.e. 963 MW wind power generation)
  • 11. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 105 Fig.11B: With (+) 150/(-)150 MVAR SVC at Bus-19 (45 % i.e. 963 MW wind power generation) Fig.12A: Without SVC at Bus-19 (55 % i.e. 1177 MW wind power generation)
  • 12. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 106 Fig.12B: With (+) 150/(-)150 MVAR SVC at 400 kV GSS Jaisalmer (55 % i.e. 1177 MW wind power generation) Fig.13A: Without SVC at Bus-19 (65 % i.e. 1391 MW wind power generation)
  • 13. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 107 Fig.13B: With (+) 150/(-)150 MVAR SVC at Bus-19 (65 % i.e. 1391 MW wind power generation) Fig.14A: With SVC at Bus-19 (75 % i.e. 1605 MW wind power generation)
  • 14. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 108 Fig.14B: With (+) 150/(-)150 MVAR SVC at Bus-19 (75 % i.e. 1605 MW wind power generation) Fig.15: Bus-2 Voltage without and with SVC with variation in wind power generation
  • 15. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 109 Fig.16: Loading (MVAR) on SVC with variation in wind power generation IV. EFFECT OF SVC DURING HIGH VOLTAGE AND LOW WIND POWER GENERATION CONDITION SVC of (+)150/(-)150 MVAR capacity is connected at 400 kV GSS Jaisalmer through 400/33 kV transformer (Bus-19). Due to low wind power generation SVC reference voltage is set to 0.90 PU. The slope of SVC is 0.09. The purpose of connecting SVC at Bus number 19 is to regulate the voltage at bus number 2 i.e. Jaisalmer 400 kV bus with the decrease in wind power generation. To demonstrate the effect of SVC on voltage load flow studies have been carried out without and with (+)150/(-)150 MVAR SVC at 400 kV GSS Jaisalmer for various wind power generation schedule. Following two cases have been considered in the load flow studies:- S. No. Particulars Connected capacity of wind power plants (MW) Net Wind Power Despatch (MW) Case-1 (35 % of IC) Case-2 (25 % of IC) 1 400 kV GSS Jaisalmer 1340 469 335 2 220 kV GSS Amarsagar 760 266 190 3 132 kV GSS Jaisalmer 40 14 10 Total 2140 749 535
  • 16. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 110 OUTPUT OF LOAD FLOW STUDIES Case-1 : 35 % wind power generation of installed wind farms capacity Power plots of load flow study without SVC at Bus-19 is placed at fig-17A and Power plots of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged is placed at fig-17B. Case-2: 25 % wind power generation of installed wind farms capacity Power plots of load flow study without SVC at Bus-19 is placed at fig-18A and Power plots of LFS with (+)150/(-)150 MVAR SVC at Bus-19 while other conditions remains unchanged is placed at fig-18B. EFFECT OF SVC ON POWER SYSTEM VOLTAGE Power system voltage without and with SVC are tabulated in Table-3. With the decrease of wind power generation, transmission voltages are increased due to decrease of power flow on transmission lines. With SVC rise in transmission voltages are less than without SVC. Table-3 : Bus voltages (kV) without and with SVC in low wind power generation condition S. No. Particulars Case-1 (35 % of IC) Case-2 (25 % of IC) Wind Power Generation (MW) 749 535 A 400 kV bus voltage 1 400 kV GSS Jaisalmer Without SVC 427.04 428.39 With SVC 412.80 414.14 2 400 kV GSS Barmer Without SVC 427 428 With SVC 419 420 3 400 kV GSS Rajwest LTPS Without SVC 426 428 With SVC 419 421 B 220 kV bus voltage 1 400 kV GSS Jaisalmer Without SVC 235 236 With SVC 228 228 2 400 kV GSS Barmer Without SVC 234 235 With SVC 228 229 3 220 kV GSS Amarsagar Without SVC 233 233 With SVC 226 227 4 220 kV GSS Phalodi Without SVC 218 219 With SVC 214 215 5 220 kV GSS Tinwari Without SVC 218 219 With SVC 217 218 C 132 kV bus voltage 1 220 kV GSS Amarsagar Without SVC 140 140 With SVC 136 136 2 220 kV GSS Phalodi Without SVC 125 126 With SVC 123 124 3 220 kV GSS Tinwari Without SVC 127 127 With SVC 126 127 4 132 kV GSS Jaisalmer Without SVC 139 139 With SVC 135 136 D SVC Bus voltage Without SVC 36.13 36.25 With SVC 34.11 34.21 E MVAR loading on SVC (Inductive) Without SVC - - With SVC 158 161
  • 17. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 111 Fig.17A: Without SVC at Bus-19 (35 % i.e. 749 MW wind power generation) Fig.17B: With (+) 150/(-)150 MVAR SVC at Bus-19 (35 % i.e. 749 MW wind power generation)
  • 18. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 112 Fig.18A: Without SVC at Bus-19 (25 % i.e. 535 MW wind power generation) Fig.18B: With (+) 150/(-)150 MVAR SVC at Bus-19 (25 % i.e. 535 MW wind power generation)
  • 19. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 113 V. CONCLUSION Most of wind power plants are installed far away from load centers. Long EHV transmission lines are being constructed for evacuation of wind power generation up to load centers without planning reactive power management and voltage control. Reactive power management using shunt reactors and shunt capacitors is not successful in wind power plants penetrated power system due to large & sudden variation in wind power generation. SVC is able to regulate the power transmission voltage with the variation in wind power generation. With the help of Static Var Compensator high as well as low transmission voltages can be controlled. During high power system voltage, SVC absorb reactive power and function as shunt reactor and there is less rise in system voltage with SVC as compared to without SVC. During low power system voltage, SVC generates reactive power & function as shunt capacitor. Therefore, there is less drop in system voltage with SVC as compared without SVC. VI. REFERENCE [1]. N.G. Hingorani and L. Gyugy, Understanding FACTS, Concepts and Technology of Flexible AC Transmission System. New York: Inst. Elect. Electron. Eng., Inc., 2000. [2]. J. J. Paserba, D. J. Leonard, N.W. Miller, S. T. Naumann, M. G. Lauby, and F. P. Sener, “Coordination of a distribution level continuously controlled compensation device with existing substation equipment for long term var management,” IEEE Trans. Power Del., vol. 9, no. 2, pp.1034–1040, Apr. 1994. [3]. K. M. Son, K. S. Moon, S. K. Lee, and J. K. Park, “Coordination of an SVC with a ULTC reserving compensation margin for emergency control,” IEEE Trans. Power Del., vol. 15, no. 4, pp. 1193–1198, Oct. 2000. [4]. Task Force no. 2 on Static Var Compensators, Static Var Compensators (1986). [5]. IEEE Special Stability Controls Working Group, “Static var compensator models for power flow and dynamic performance simulation,” IEEE Trans. Power Syst., vol. 9, no. 1, pp. 229–240, Feb. 1994. [6]. R.A. Schlueter, ,A voltage stability security assessment method,” IEEE Trans. on Power Systems, vol. 13, no. 4, November 1998, pp. 1423- 1438. [7]. D. Jovcic, Pahalawaththa, N., Zavahir, M. & Hassan, H.A. (2003) “SVC Dynamic analytical Model”_ IEEE Trans. On Power Delivery, Vol. 18, No. 4, (October), pp. 1455 - 1461. [8]. FACTS Controllers in Power Transmission and Distribution By- K.R. Padiyar. [9] Ameer H. Abd and D.S.Chavan, “Impact of Wind Farm of Double-Fed Induction Generator (Dfig) on Voltage Quality”, International Journal of Electrical Engineering & Technology (IJEET), Volume 3, Issue 1, 2012, pp. 235 - 246, ISSN Print : 0976-6545, ISSN Online: 0976-6553. [10] Dr. M. P. Sharma and Sarfaraz Nawaz, “Understanding Operation of Shunt Capacitors and Oltc for Transmission Loss Reduction”, International Journal of Electrical Engineering & Technology (IJEET), Volume 4, Issue 2, 2013, pp. 344 - 357, ISSN Print : 0976-6545, ISSN Online: 0976-6553. [11] T. Nageswara Prasad, V. Chandra Jagan Mohan and Dr. V.C. Veera Reddy, “Shunt Compensator for Integration of Wind Farm to Polluted Distribution System”, International Journal of Electrical Engineering & Technology (IJEET), Volume 3, Issue 3, 2012, pp. 89 - 101, ISSN Print : 0976-6545, ISSN Online: 0976-6553.
  • 20. International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 – 6545(Print), ISSN 0976 – 6553(Online) Volume 4, Issue 3, May - June (2013), © IAEME 114 BIOGRAPHIES Dr. M. P. Sharma received the B.E. degree in Electrical Engineering in 1996 Govt. Engineering College, Kota, Rajasthan and M. E. degree in Power Systems in 2001 and Ph.D. degree in 2009 from Malaviya Regional Engineering College, Jaipur (Now name as MNIT). He is presently working as Assistant Engineer, Rajasthan Rajya Vidhyut Prasaran Nigam Ltd., Jaipur. He is involved in the system studies of Rajasthan power system for development of power transmission system in Rajasthan and planning of the power evacuation system for new power plants. His research interest includes Reactive Power Optimization, Power System Stability, reduction of T&D losses and protection of power system.(email: mahavir_sh@rediffmail.com) Devendra Saini received the B.Tech. degree in electrical engineering from Rajasthan Technical University, Kota, in 2011. He is currently pursuing the M.Tech.degree in Power System from the Jodhpur National University ,Jodhpur. He is currently an Assistant Professor at the Electrical Engi. Dept. Shankara Institute Of Technology , Jaipur ,Rajasthan. His research interests are in the areas of FACTS power system problems, controls and transient stability (email :devendrasaini786@gmail.com) Swati Harsh has received her B.E. degree from University of Rajasthan. She is currently working as Assistant professor in department of Electrical Engineering at Anand International College of Engineering. She is currently pursuing M.Tech. (Power System) from Swami Keshvanand Institute of Technology, Management and Gramothan (SKIT) (email: swatiharsh1st@gmail.com) Sarfaraz Nawaz has received his B.E. degree from University of Rajasthan and M.Tech. degree from MNIT, Jaipur. His research interests include power systems and power electronics. He is currently an Associate Professor of the Electrical Engg. Dept., Swami Keshvanand Institute of Technology, Management and Gramothan (SKIT) , Jaipur, Rajasthan. (email: eesarfaraz1983@rediffmail.com)