Verwendung von cds-Gießbeton UW
beim Einbau von Unterflurfeuern
Utilisation of cds-Pouring Concrete UW at the installation of high intensity inset lights.
cds-Bautenschutzprodukte                           Hinweise zum Einbau der Unterflurfeuer
cds-Epoxy Systems &                                Hints for Installation of shallow base
Flooring materials




1. Bohren der Aussparung für den Lampenkörper      2. Vorbereitetes Bohrloch                           3. Trocknen/Ausblasen des Bohrlochs
   Making the borehole                                für Leitungszuführung von unten                     Drying of the borehole
                                                      Ready-made borehole (cabling from below)




4. Vorbereitetes Bohrloch mit cds-Mörtel LS        5. Einbau und Ausrichtung des Aufnahmetopfes        6. Eingießen von cds-Gießbeton UW
   Borehole filled with cds-Mortar LS                 Installation of the shallow base                    Filling in of cds-Pouring Concrete UW




7. Unterflurfeuer mit Grundfüllung cds-Gießbeton   8. Unterflurfeuer mit niveaugleicher Ringfuge       9. Befestigung der Unterflurfeuer im Aufnahmetopf
   UW (15 mm unter Oberkante Oberfläche)              Inset light fixed with cds-Pouring Concrete UW      Fixing of the lamp in the shallow base
   Borehole with shallow base fixed with
   cds-Pouring Concrete UW (15 mm below surface)
Beispiele von Lampen
Examples of shallow bases




cds-Gießbeton/Pouring Concrete

                                         Verarbeitungszeit (min.)                           Belastbar (Std.)                          Abnehmen der Justiereinrichtung
                                          Processing time (min.)                            stressable (hrs.)                         release of adjusting advice

                  PAT* MHT**       +10 C      +50C    +10 0C +150C +200C +250C +300C +10C   +50C     +10 0C +15 0C +200C +250C +300C +10 0C +200C +300C

UW
S-hardener       25-40     +15       -          -        -          -    -   25   15   -      -        -        -   -     8      6     -          -         2
FH-hardener       5-25     + 5       -         30       20          -   15    -    -   -      -        8        -   5     -      -     4          3         -

UW rapid
S-hardener       10-15     +10       -          -       12          9   -    -    -    -      -        7        4   -     -      -     -          2         -
FH-hardener       1-10     + 5       -         15       10          -   -    -    -    8      4        2        -   -     -      -     1          -         -



* Preferred application temperature/empfohlene Anwendungstemperatur
** Minimum hardening temperature/Mindesthärtetemperatur
Ausführungshinweise
Beschreibung:                                      ist am einheitlichen Aussehen des Materials er-       Verbrauch cds-Gieß-
                                                   kennbar. Hiernach das gemischte Material so-          beton UW bei 120
cds-Gießbeton UW/UW rapid sind mit Mineral-        fort vergießen.
stoffen gefüllte, gut gießbare, lösemittelfreie                                                          mm Tiefe und 345
2-Komponenten-Epoxidharzmaterialien.                                                                     mm Ø der Hauptboh-
                                                                                                         rung: ca. 7-8 kg.
                                                   Hinweis:
Anwendungsgebiete:                                                                                   3.2 Die verbliebene Ring-
                                                   Wurde beim Vermischen der Komp. A mit der
                                                   Härterkomp. B auf das nachträgliche Umtop-        EXPERTEN bis Oberkante des Feuer-Unterteils
                                                                                                         fuge FÜR OBERFLÄCHEN
Zum Befestigen von Unterflurfeuern in Beton                                                              mit cds-Gießbeton UW bzw. cds-Kabelfu-
und Asphaltbetondecken. Ein besonderer Vor-        fen und Nachmischen verzichtet, darf das Ma-
                                                   terial beim Verarbeiten nur ausgegossen und           genmasse vergießen
                                                                                                     EXPERTS FOR SURFACINGS
teil ist die schnelle Reaktion bei niedrigen Um-
gebungstemperaturen, sowie bei Einsatz von         nicht zusätzlich aus dem Gebinde ausgekratzt
speziellen Härtern praktikable Verarbeitungs-      werden, um zu verhindern, daß nicht oder nur      Wichtiger Hinweis:
zeiten bei hohen Temperaturen. Mit cds-Gieß-       unvollständig mit Härter vermischte Material-
beton UW/UW rapid kann auch auf schwach            anteile, die an den Gebindewandungen anhaf-       Die vorläufigen Abdichtungen am Feuer, den
feuchtem Untergrund vergossen werden. Das          ten, mitverarbeitet werden.                       Mittelbohrungen und den Kabelfugen sind be-
Material härtet praktisch schrumpffrei aus.                                                          sonders sorgfältig auszuführen, da eingeflosse-
                                                   1.   Einbau des Unterflurfeuers bei               ner, erhärteter cds-Gießbeton UW nicht mehr
                                                        Leitungsführung nach unten:                  entfernt werden kann. Ebenso sind Verschmut-
Eigenschaften:                                                                                       zungen am Feuer und auf der Startbahn im noch
                                                   1.1 Kabelzuführung gegen Einfließen des
Spez. Gewicht (Mischung): 1,9 g/cm3                                                                  nicht erhärteten Zustand sofort gründlichst zu
                                                       Vergußmaterials sichern
                                                                                                     entfernen, ggf. cds-EP-Verdünnung/Reiniger
Mischungsverhältnis:                                   (z.B. mit Schaumstoffdichtung)
                                                                                                     verwenden.
    1 kg + 90 g Härter (UW)                        1.2 Bei Bohrlochtiefe über 130 mm oder stark
    1 kg + 100 g Härter (UW rapid)                     unebenen Bodenflächen empfiehlt es sich,      Reinigung der Geräte:
Wasserdurchlässigkeit    nach    DIN     1048:         die Bohrlöcher mit einem Reaktionsharz-
                                                       mörtel, z.B. cds-Mörtel LS aufzufüllen.       Bei jeder Arbeitsunterbrechung sofort mit cds-
   undurchlässig                                                                                     EP-Verdünnung/Reiniger säubern. Material-
Druckfestigkeit:                                   1.3 Feuer mit Einbauvorrichtung in Bohrloch       komponenten sowie Reinigungsmittel nicht in
    über 70 N/mm2                                      einsetzen und justieren. Justiervorrich-      Kanalisation, Gewässer oder Erdreich gelangen
                                                       tung abnehmen und mit ca. 10 kg be-           lassen, sondern ordnungsgemäß entsorgen.
Biegezugfestigkeit:
                                                       schweren.
    über 30 N/mm2
                                                   1.4 Vergießen mit cds-Gießbeton UW                Lieferform:
Wärmeleitfähigkeit:
                                                       (siehe Pkt. 3).                               8 kg Gebinde inkl. Härter
   0,5 W/mK
                                                   2.   Einbau des Unterflurfeuers bei Leitungs-
Haftfestigkeit am Beton:
     über 2,5 N/mm2 (reißt im Beton)                    führung nach der Seite:                      Farbton:
                                                   2.1 Kabelzuführung gegen Einfließen des Ver-      grau (bei Beton) oder schwarz
Temperaturbeständigkeit:
   bis 80 0 C Dauertemperatur und                      gußmaterials sichern (z.B. mit Schaum-        (bei Asphaltbeton)
   bis 1200 C Spitzentemperatur                        stoffdichtung)
                                                   2.2 Schaumstoffdichtring an der zur Kabelfuge     Lagerung:
                                                       weisenden Verstärkung seitlich kreuzartig
Anforderungen an den Untergrund:                       durchstechen, Leitungen hindurchführen,       Lagerfähigkeit 2 Jahre. Gebinde gut verschlos-
                                                                                                     sen halten, trocken, und nach Möglichkeit bei
Bohrlöcher bzw. Aussparungen müssen frei von           ein dünnwandiges, flexibles Rohr (Innen-
                                                                                                     + 15 0 C bis + 200 C lagern. Direkte Sonnenein-
Staub, losem Gestein, Bohrschlamm und sons-            durchmesser mind. 15 mm) von mind.            strahlung vermeiden.
tigen Verschmutzungen sein. Stehendes Wasser           200 mm Länge über die Leitungen ziehen
muß entfernt, auf leicht feuchtem Untergrund           und durch den Schaumstoffdichtring hin-
kann vergossen werden. Steht ein Kompressor            durchführen.                                  Gefahrenhinweise:
zur Verfügung, empfiehlt es sich, die Bohrlöcher       Der Schaumstoffdichtring muß das Rohr         Hautkontakt, vor allem mit der Härterkompo-
bzw. Aussparungen mittels Druckluft auszu-             fest umschließen! Bei Verwendung von          nente, vermeiden. Fettfreie Hautschutzsalbe
blasen.
                                                       Kunststoffrohren muß eine Temperaturbe-       benutzen. Gelangen Spritzer ins Auge, sofort
                                                       ständigkeit bis 100 0 C gegeben sein (darf    intensiv mit Wasser spülen, anschließend un-
Mischvorgang:                                          nicht schmelzen, schrumpfen oder sich         verzüglich Arzt aufsuchen.
Stamm- (A) und Härterkomponente (B) sind im            verformen).
genau dosierten Mischungsverhältnis abge-          2.3 Feuer mit Einbauvorrichtung in das Bohr       Zur Beachtung:
packt. Die Komp. A muß klumpenfrei aufgerührt          loch einsetzen. Das Rohr muß in die Kabel-    Beachten Sie bitte die allgemeinen Schutzvor-
werden. Rührdauer 3 bis 5 Minuten (Kontrolle           fuge hineinragen. Die Kabelfuge zum Bohr-     schriften der Berufsgenossenschaften, insbe-
mittels Uhr!). Für das Aufrühren und Mischen           loch um das eingelegte Rohr exakt abdich-     sondere das Merkblatt M 023 für die Verarbei-
ist ein elektrisches Handrührgerät zu empfeh-
                                                       ten. Bis ca. 100 0 C temperaturbeständiges    tung von Poylester- und Epoxidharzen.
len, z.B. langsam laufende Bohrmaschine
(300-400 U/Min.) mit angesetztem Rührkorb.             Abdichtungsmaterial (ggf. Schaumstoffab-
                                                                                                     Die vorstehenden Angaben haben wir nach ei-
Sollte Komp. A durch langes Lagern einen har-          fälle) verwenden! Feuer justieren.            genen langjährigen Baustellenerfahrungen und
ten Bodensatz aufweisen, so ist dieser - vor dem   2.4 Vergießen von cds-Gießbeton UW                bestem Wissen zusammengestellt, sie sind je-
Aufrühren - mit einer Kelle aufzulockern. Nach         (siehe Punkt 3).                              doch allgemeiner Art und für den speziellen Fall
dem Aufrühren der Komp. A wird die Komp. B                                                           unverbindlich, da die örtlichen Gegebenheiten
vollständig in die Stammkomponente entleert        2.5 Elektrischen Anschluß in der Kabelfuge        und die Unterschiede der Konstruktion berück-
und beide Komponenten gut und intensiv mit-            durchführen.                                  sichtigt werden müssen.
einander vermischt. Beim Mischen sind Seiten-
und Bodenfläche des Gebindes mehrfach scharf       3.   Vergießen                                    Falls Sie besondere Fragen haben, rufen Sie un-
abzustreifen. Mischdauer 1-2 Minuten. Danach                                                         sere Fachleute in 55576 Sprendlingen an, die
                                                   3.1 In die Ringfuge um das Feuer mit Härter       Sie weiter beraten werden und Ihnen gegebe-
in ein sauberes Gefäß umgießen und nochmals            (Komp. B) vermischten cds-Gießbeton
gut nachmischen. Die vollständige Vermischung                                                        nenfalls auch zur Einarbeitung zur Verfügung
                                                       UW bis ca. 2 cm unter Oberkante Lam-          stehen.
                                                       pensockel vorsichtig eingießen.
Hints for Application
Description:                                          Note:                                                Important:
cds-Pouring Concrete UW/UW rapid are easily           When mixing base A with hardener B, the step         The temporary seals around the lamp, the inter-
poured, solvent-free, mineral-filled two-compo-       of turning out and remixing was omitted, the         mediate drillings and cable channels must be
nent-epoxy-resin materials.                           material must only be poured out; the packing        carried out with great care as any cds-Pouring
                                                      must not be scraped out, to prevent any materi-
                                                      al not, or incompletely mixed with the hardener      Concrete UW with hardener which is allowed to
Applications:                                         and still adhering to the sides ot the container,    cure cannot be removed. Similarly, any dirt on
                                                      being used.                                          the lamp and runaway must be removed wit-
For installing inset lights in concrete or asphalt.                                                        hout being allowed to harden, using cds-EP-
A particular advantage is the fast reaction, even     1.   Installation of the inset lights with cabling   Thinner/Cleaner if necessary.
at low ambient temperatures, and when using                from below:
special hardeners, the practicable workability at     1.1 Secure cable leads against influx of the
high temperatures. With cds-Pouring Concrete                                                               Cleaning tools and equipment:
                                                          casting material (e.g. using plastic foam
UW/UW rapid, even damp surfaces can be co-                seal)                                            At every interruption in work clean immediately
vered. The material dries almost shrink-free.                                                              with cds-EP-Thinner/Cleaner. Do not let either
                                                      1.2 Where boreholes are more than 130 mm             material components or thinner get into the
                                                          deep or surfaces are very uneven, the bore-      drains, water supply or ground, but dispose of
Properties:
                                                          holes should be filled with an epoxy mortar      according to regulations in force.
Density (mixture): 1,9 g/cm3                              e.g. cds-Mortar LS.
Mixing ratio:                                         1.3 Set the lamp with fixing in the borehole and
    1 kg + 90 g hardener (UW)                                                                              Packaging:
                                                          adjust. Remove the adjusting device and
    1 kg + 100 g hardener (UW rapid)                                                                       Containers of 8 kgs including hardener.
                                                          weight with about 10 kg.
Water permeability according to DIN 1048:
    impermeable                                       1.4 Pour in the cds-Pouring Concrete UW (see
                                                          point 3).                                        Colour:
Compression strength:
                                                      2.   Installation of the inset lights with cabling   Grey (for concrete) or black (for asphalt)
   greater than 70 N/mm2
                                                           from the side:
Tensile Bending strength:
    greater than 30 N/mm2                             2.1 Secure cable leads against influx of the cas-    Storage:
                                                          ting material (e.g. using plastic foam seal)
Heat conductivity: 0,5 W/mK                                                                                Can be stored up to 2 years. Keep the container
                                                      2.2 Pierce the plastic form seal on the side indi-   securely closed and dry, and store at 15 to
Bonding strength to concrete:                             cating the cable-gap crosswise, pull the         20 0 C if possible. Avoid direct sunlight.
    greater than 2,5 N/mm2                                lead(s) through, feed a thin-walled flexible
    (cracks in concrete)
                                                          tube at least 15 mm i.d., and 200 mm long
Temperature resistance:                                   over it and through the plastic sealing-ring.    Warning:
   up to + 80 0 C continuously and                        The seal between tube and plastic foam           Skin contact, particularly with the hardener, has
   up to + 1200 C peak temperatures.                      sealer must be tight! When using plastic         to be avoided. Use a non-greasy skin barrier-
                                                          piping, it must be able to withstand tempe-      cream. If any splashes get into the eyes, rins
                                                          ratures of up to 100 0 C - it must not melt,     immediately with plenty of water and visit your
Requirements for the base:                                                                                 doctor without delay.
                                                          shrink or deform.
Boreholes or cavities must be free of dust, loose                                                          The above details are given as the result of many
stones, grit, and similar dirt. Standing water        2.3 Insert the lamp with its fixings into the ca-
                                                                                                           years experience on building sites, and to the
must be removed, but slightly damp surfaces               vity. The tube must reach into the cable         best of our knowledge. They are perforce of a
may be covered. If a compressor is available, it          channel. Seal the cable channel to the ca-       general nature and not binding for every appli-
is recommended to blow the surface out with               vity precisely, around the tube inserted.        cation, as the local conditions and differences in
compressed air.                                           Use sealant able to withstand up to about        construction techniques must always be taken
                                                          1000 C - e.g. plastic foam offcuts - then        into account.
                                                          adjust lamp.                                     If you have any specific questions, please ring
Mixing:                                                                                                    our experts in 55576 Sprendlingen, who will be
                                                      2.4 Pour in cds-Pouring Concrete UW
The base (A) and hardener (B) are both packed             (see point 3).                                   able wo give you further advice, and may be
                                                                                                           able to help you with product familarisation.
in exactly-measured proportions. Component A          2.5 Lead the electric cable through the channel
must be stirred until free of lumps. Stirring must        provided.
be for 3 to 5 minutes (checked on a timepiece).
                                                      3.   Casting
An electric handmixer is recommended for stir-
ring and mixing, e.g. a slow-speed drill (running     3.1 Carefully pour the cds-Pouring Concrete
at 300 to 400 rpm) fitted with a mixer-paddle.            UW mixed with hardener into the circle
If as a result of long storage, component A has a         around the lamp, up to about 2 cm below
hard bottom skin, this must be broken up with a           the level of the lamp socket. Usage of cds-
trowel before mixing. Once component A is tho-            Pouring Concrete UW will be some 7 to 8
roughly stirred, component B is completely                kg for 120 mm depth and 345 mm diame-
emptied into the base, and both components                ter of the main boring.
well and intensively mixed. During the mixing
process, sides and bottom of the container must       3.2 Fill the remaining space to the level of the
be repeatedly scraped off with a sharp instru-            lamp with either cds-Pouring Concrete or
ment. Mixing time 1 to 2 minutes. After this,             cds-Cable Joint Filler.
transfer into a clean container, and thoroughly
remix once more. The material, when properly
mixed, will be of a uniform appearance. The
mixed material must now immediately be pou-
red.
EXPERTEN FÜR OBERFLÄCHEN

VERKEHRSFLÄCHEN
EXPERTS IN SURFACINGS

INDUSTRIE- UND BETRIEBSFLÄCHEN

FLUGBETRIEBSFLÄCHEN

cds-BAUTENSCHUTZPRODUKTE




POSSEHL SPEZIALBAU GMBH
cds-Bautenschutzprodukte
Gau-Bickelheimer-Straße 72
55576 Sprendlingen / Rhh.
Germany


Telefon +49 (67 01) 93 50-0
Telefax +49 (67 01) 93 50-49


info.cds@possehl-spezialbau.de
www.possehl-spezialbau.de




                                 ind0506

Weitere ähnliche Inhalte

Andere mochten auch

42 [pdf library]
42 [pdf library]42 [pdf library]
42 [pdf library]nourd
 
Journal%20 entries[1]
Journal%20 entries[1]Journal%20 entries[1]
Journal%20 entries[1]Jawz1615
 
HOLA in FRENCH
HOLA in FRENCHHOLA in FRENCH
HOLA in FRENCHdearl1
 
Tome 1 : Sensibilisation des publics aux usages
Tome 1 : Sensibilisation des publics aux usagesTome 1 : Sensibilisation des publics aux usages
Tome 1 : Sensibilisation des publics aux usagesparoles d'élus
 
Présentation défi entreprises_2012_employé
Présentation défi entreprises_2012_employéPrésentation défi entreprises_2012_employé
Présentation défi entreprises_2012_employéDanielriou
 
1ère journée etourisme du Lot : présentation Lot Tourisme
1ère journée etourisme du Lot : présentation Lot Tourisme1ère journée etourisme du Lot : présentation Lot Tourisme
1ère journée etourisme du Lot : présentation Lot TourismeCathy Seguy
 
Wie liest man als Laie medizinische Fachliteratur?
Wie liest man als Laie medizinische Fachliteratur? Wie liest man als Laie medizinische Fachliteratur?
Wie liest man als Laie medizinische Fachliteratur? jangeissler
 
Warum sollten Lernplattformen in den Sprachenunterricht integriert werden
Warum sollten Lernplattformen in den Sprachenunterricht integriert werden Warum sollten Lernplattformen in den Sprachenunterricht integriert werden
Warum sollten Lernplattformen in den Sprachenunterricht integriert werden suisusui
 
Actualités mobiles iOS8 / Android L - Juillet 2014
Actualités mobiles iOS8 / Android L - Juillet 2014Actualités mobiles iOS8 / Android L - Juillet 2014
Actualités mobiles iOS8 / Android L - Juillet 2014Damien Laureaux
 
Seguridad Informática
Seguridad InformáticaSeguridad Informática
Seguridad InformáticaLucy Gómez
 
Bremen 2008 Computerspiele FüR Kinder
Bremen 2008 Computerspiele FüR KinderBremen 2008 Computerspiele FüR Kinder
Bremen 2008 Computerspiele FüR KinderKarsten D. Wolf
 
Ensayo de la impuesto
Ensayo de la impuestoEnsayo de la impuesto
Ensayo de la impuestoZEIDALI
 
Compostion programme palais 3
Compostion programme palais 3Compostion programme palais 3
Compostion programme palais 3Tyty Kone
 

Andere mochten auch (20)

42 [pdf library]
42 [pdf library]42 [pdf library]
42 [pdf library]
 
Journal%20 entries[1]
Journal%20 entries[1]Journal%20 entries[1]
Journal%20 entries[1]
 
HOLA in FRENCH
HOLA in FRENCHHOLA in FRENCH
HOLA in FRENCH
 
Tome 1 : Sensibilisation des publics aux usages
Tome 1 : Sensibilisation des publics aux usagesTome 1 : Sensibilisation des publics aux usages
Tome 1 : Sensibilisation des publics aux usages
 
Présentation défi entreprises_2012_employé
Présentation défi entreprises_2012_employéPrésentation défi entreprises_2012_employé
Présentation défi entreprises_2012_employé
 
1ère journée etourisme du Lot : présentation Lot Tourisme
1ère journée etourisme du Lot : présentation Lot Tourisme1ère journée etourisme du Lot : présentation Lot Tourisme
1ère journée etourisme du Lot : présentation Lot Tourisme
 
TYPO3 Spezialist
TYPO3 SpezialistTYPO3 Spezialist
TYPO3 Spezialist
 
Wie liest man als Laie medizinische Fachliteratur?
Wie liest man als Laie medizinische Fachliteratur? Wie liest man als Laie medizinische Fachliteratur?
Wie liest man als Laie medizinische Fachliteratur?
 
Livret 2012
Livret 2012Livret 2012
Livret 2012
 
Warum sollten Lernplattformen in den Sprachenunterricht integriert werden
Warum sollten Lernplattformen in den Sprachenunterricht integriert werden Warum sollten Lernplattformen in den Sprachenunterricht integriert werden
Warum sollten Lernplattformen in den Sprachenunterricht integriert werden
 
Actualités mobiles iOS8 / Android L - Juillet 2014
Actualités mobiles iOS8 / Android L - Juillet 2014Actualités mobiles iOS8 / Android L - Juillet 2014
Actualités mobiles iOS8 / Android L - Juillet 2014
 
Présentation Réseau
Présentation RéseauPrésentation Réseau
Présentation Réseau
 
Keynote: Andreas Langegger
Keynote: Andreas LangeggerKeynote: Andreas Langegger
Keynote: Andreas Langegger
 
Seguridad Informática
Seguridad InformáticaSeguridad Informática
Seguridad Informática
 
Los virus
Los virusLos virus
Los virus
 
Ppt02
Ppt02Ppt02
Ppt02
 
Bremen 2008 Computerspiele FüR Kinder
Bremen 2008 Computerspiele FüR KinderBremen 2008 Computerspiele FüR Kinder
Bremen 2008 Computerspiele FüR Kinder
 
Zotero Pour Elico
Zotero Pour ElicoZotero Pour Elico
Zotero Pour Elico
 
Ensayo de la impuesto
Ensayo de la impuestoEnsayo de la impuesto
Ensayo de la impuesto
 
Compostion programme palais 3
Compostion programme palais 3Compostion programme palais 3
Compostion programme palais 3
 

Utilisation Of Cds Puring Concrete Uw

  • 1. EXPERTEN FÜR OBERFLÄCHEN EXPERTS IN SURFACINGS Verwendung von cds-Gießbeton UW beim Einbau von Unterflurfeuern Utilisation of cds-Pouring Concrete UW at the installation of high intensity inset lights.
  • 2. cds-Bautenschutzprodukte Hinweise zum Einbau der Unterflurfeuer cds-Epoxy Systems & Hints for Installation of shallow base Flooring materials 1. Bohren der Aussparung für den Lampenkörper 2. Vorbereitetes Bohrloch 3. Trocknen/Ausblasen des Bohrlochs Making the borehole für Leitungszuführung von unten Drying of the borehole Ready-made borehole (cabling from below) 4. Vorbereitetes Bohrloch mit cds-Mörtel LS 5. Einbau und Ausrichtung des Aufnahmetopfes 6. Eingießen von cds-Gießbeton UW Borehole filled with cds-Mortar LS Installation of the shallow base Filling in of cds-Pouring Concrete UW 7. Unterflurfeuer mit Grundfüllung cds-Gießbeton 8. Unterflurfeuer mit niveaugleicher Ringfuge 9. Befestigung der Unterflurfeuer im Aufnahmetopf UW (15 mm unter Oberkante Oberfläche) Inset light fixed with cds-Pouring Concrete UW Fixing of the lamp in the shallow base Borehole with shallow base fixed with cds-Pouring Concrete UW (15 mm below surface)
  • 3. Beispiele von Lampen Examples of shallow bases cds-Gießbeton/Pouring Concrete Verarbeitungszeit (min.) Belastbar (Std.) Abnehmen der Justiereinrichtung Processing time (min.) stressable (hrs.) release of adjusting advice PAT* MHT** +10 C +50C +10 0C +150C +200C +250C +300C +10C +50C +10 0C +15 0C +200C +250C +300C +10 0C +200C +300C UW S-hardener 25-40 +15 - - - - - 25 15 - - - - - 8 6 - - 2 FH-hardener 5-25 + 5 - 30 20 - 15 - - - - 8 - 5 - - 4 3 - UW rapid S-hardener 10-15 +10 - - 12 9 - - - - - 7 4 - - - - 2 - FH-hardener 1-10 + 5 - 15 10 - - - - 8 4 2 - - - - 1 - - * Preferred application temperature/empfohlene Anwendungstemperatur ** Minimum hardening temperature/Mindesthärtetemperatur
  • 4. Ausführungshinweise Beschreibung: ist am einheitlichen Aussehen des Materials er- Verbrauch cds-Gieß- kennbar. Hiernach das gemischte Material so- beton UW bei 120 cds-Gießbeton UW/UW rapid sind mit Mineral- fort vergießen. stoffen gefüllte, gut gießbare, lösemittelfreie mm Tiefe und 345 2-Komponenten-Epoxidharzmaterialien. mm Ø der Hauptboh- rung: ca. 7-8 kg. Hinweis: Anwendungsgebiete: 3.2 Die verbliebene Ring- Wurde beim Vermischen der Komp. A mit der Härterkomp. B auf das nachträgliche Umtop- EXPERTEN bis Oberkante des Feuer-Unterteils fuge FÜR OBERFLÄCHEN Zum Befestigen von Unterflurfeuern in Beton mit cds-Gießbeton UW bzw. cds-Kabelfu- und Asphaltbetondecken. Ein besonderer Vor- fen und Nachmischen verzichtet, darf das Ma- terial beim Verarbeiten nur ausgegossen und genmasse vergießen EXPERTS FOR SURFACINGS teil ist die schnelle Reaktion bei niedrigen Um- gebungstemperaturen, sowie bei Einsatz von nicht zusätzlich aus dem Gebinde ausgekratzt speziellen Härtern praktikable Verarbeitungs- werden, um zu verhindern, daß nicht oder nur Wichtiger Hinweis: zeiten bei hohen Temperaturen. Mit cds-Gieß- unvollständig mit Härter vermischte Material- beton UW/UW rapid kann auch auf schwach anteile, die an den Gebindewandungen anhaf- Die vorläufigen Abdichtungen am Feuer, den feuchtem Untergrund vergossen werden. Das ten, mitverarbeitet werden. Mittelbohrungen und den Kabelfugen sind be- Material härtet praktisch schrumpffrei aus. sonders sorgfältig auszuführen, da eingeflosse- 1. Einbau des Unterflurfeuers bei ner, erhärteter cds-Gießbeton UW nicht mehr Leitungsführung nach unten: entfernt werden kann. Ebenso sind Verschmut- Eigenschaften: zungen am Feuer und auf der Startbahn im noch 1.1 Kabelzuführung gegen Einfließen des Spez. Gewicht (Mischung): 1,9 g/cm3 nicht erhärteten Zustand sofort gründlichst zu Vergußmaterials sichern entfernen, ggf. cds-EP-Verdünnung/Reiniger Mischungsverhältnis: (z.B. mit Schaumstoffdichtung) verwenden. 1 kg + 90 g Härter (UW) 1.2 Bei Bohrlochtiefe über 130 mm oder stark 1 kg + 100 g Härter (UW rapid) unebenen Bodenflächen empfiehlt es sich, Reinigung der Geräte: Wasserdurchlässigkeit nach DIN 1048: die Bohrlöcher mit einem Reaktionsharz- mörtel, z.B. cds-Mörtel LS aufzufüllen. Bei jeder Arbeitsunterbrechung sofort mit cds- undurchlässig EP-Verdünnung/Reiniger säubern. Material- Druckfestigkeit: 1.3 Feuer mit Einbauvorrichtung in Bohrloch komponenten sowie Reinigungsmittel nicht in über 70 N/mm2 einsetzen und justieren. Justiervorrich- Kanalisation, Gewässer oder Erdreich gelangen tung abnehmen und mit ca. 10 kg be- lassen, sondern ordnungsgemäß entsorgen. Biegezugfestigkeit: schweren. über 30 N/mm2 1.4 Vergießen mit cds-Gießbeton UW Lieferform: Wärmeleitfähigkeit: (siehe Pkt. 3). 8 kg Gebinde inkl. Härter 0,5 W/mK 2. Einbau des Unterflurfeuers bei Leitungs- Haftfestigkeit am Beton: über 2,5 N/mm2 (reißt im Beton) führung nach der Seite: Farbton: 2.1 Kabelzuführung gegen Einfließen des Ver- grau (bei Beton) oder schwarz Temperaturbeständigkeit: bis 80 0 C Dauertemperatur und gußmaterials sichern (z.B. mit Schaum- (bei Asphaltbeton) bis 1200 C Spitzentemperatur stoffdichtung) 2.2 Schaumstoffdichtring an der zur Kabelfuge Lagerung: weisenden Verstärkung seitlich kreuzartig Anforderungen an den Untergrund: durchstechen, Leitungen hindurchführen, Lagerfähigkeit 2 Jahre. Gebinde gut verschlos- sen halten, trocken, und nach Möglichkeit bei Bohrlöcher bzw. Aussparungen müssen frei von ein dünnwandiges, flexibles Rohr (Innen- + 15 0 C bis + 200 C lagern. Direkte Sonnenein- Staub, losem Gestein, Bohrschlamm und sons- durchmesser mind. 15 mm) von mind. strahlung vermeiden. tigen Verschmutzungen sein. Stehendes Wasser 200 mm Länge über die Leitungen ziehen muß entfernt, auf leicht feuchtem Untergrund und durch den Schaumstoffdichtring hin- kann vergossen werden. Steht ein Kompressor durchführen. Gefahrenhinweise: zur Verfügung, empfiehlt es sich, die Bohrlöcher Der Schaumstoffdichtring muß das Rohr Hautkontakt, vor allem mit der Härterkompo- bzw. Aussparungen mittels Druckluft auszu- fest umschließen! Bei Verwendung von nente, vermeiden. Fettfreie Hautschutzsalbe blasen. Kunststoffrohren muß eine Temperaturbe- benutzen. Gelangen Spritzer ins Auge, sofort ständigkeit bis 100 0 C gegeben sein (darf intensiv mit Wasser spülen, anschließend un- Mischvorgang: nicht schmelzen, schrumpfen oder sich verzüglich Arzt aufsuchen. Stamm- (A) und Härterkomponente (B) sind im verformen). genau dosierten Mischungsverhältnis abge- 2.3 Feuer mit Einbauvorrichtung in das Bohr Zur Beachtung: packt. Die Komp. A muß klumpenfrei aufgerührt loch einsetzen. Das Rohr muß in die Kabel- Beachten Sie bitte die allgemeinen Schutzvor- werden. Rührdauer 3 bis 5 Minuten (Kontrolle fuge hineinragen. Die Kabelfuge zum Bohr- schriften der Berufsgenossenschaften, insbe- mittels Uhr!). Für das Aufrühren und Mischen loch um das eingelegte Rohr exakt abdich- sondere das Merkblatt M 023 für die Verarbei- ist ein elektrisches Handrührgerät zu empfeh- ten. Bis ca. 100 0 C temperaturbeständiges tung von Poylester- und Epoxidharzen. len, z.B. langsam laufende Bohrmaschine (300-400 U/Min.) mit angesetztem Rührkorb. Abdichtungsmaterial (ggf. Schaumstoffab- Die vorstehenden Angaben haben wir nach ei- Sollte Komp. A durch langes Lagern einen har- fälle) verwenden! Feuer justieren. genen langjährigen Baustellenerfahrungen und ten Bodensatz aufweisen, so ist dieser - vor dem 2.4 Vergießen von cds-Gießbeton UW bestem Wissen zusammengestellt, sie sind je- Aufrühren - mit einer Kelle aufzulockern. Nach (siehe Punkt 3). doch allgemeiner Art und für den speziellen Fall dem Aufrühren der Komp. A wird die Komp. B unverbindlich, da die örtlichen Gegebenheiten vollständig in die Stammkomponente entleert 2.5 Elektrischen Anschluß in der Kabelfuge und die Unterschiede der Konstruktion berück- und beide Komponenten gut und intensiv mit- durchführen. sichtigt werden müssen. einander vermischt. Beim Mischen sind Seiten- und Bodenfläche des Gebindes mehrfach scharf 3. Vergießen Falls Sie besondere Fragen haben, rufen Sie un- abzustreifen. Mischdauer 1-2 Minuten. Danach sere Fachleute in 55576 Sprendlingen an, die 3.1 In die Ringfuge um das Feuer mit Härter Sie weiter beraten werden und Ihnen gegebe- in ein sauberes Gefäß umgießen und nochmals (Komp. B) vermischten cds-Gießbeton gut nachmischen. Die vollständige Vermischung nenfalls auch zur Einarbeitung zur Verfügung UW bis ca. 2 cm unter Oberkante Lam- stehen. pensockel vorsichtig eingießen.
  • 5. Hints for Application Description: Note: Important: cds-Pouring Concrete UW/UW rapid are easily When mixing base A with hardener B, the step The temporary seals around the lamp, the inter- poured, solvent-free, mineral-filled two-compo- of turning out and remixing was omitted, the mediate drillings and cable channels must be nent-epoxy-resin materials. material must only be poured out; the packing carried out with great care as any cds-Pouring must not be scraped out, to prevent any materi- al not, or incompletely mixed with the hardener Concrete UW with hardener which is allowed to Applications: and still adhering to the sides ot the container, cure cannot be removed. Similarly, any dirt on being used. the lamp and runaway must be removed wit- For installing inset lights in concrete or asphalt. hout being allowed to harden, using cds-EP- A particular advantage is the fast reaction, even 1. Installation of the inset lights with cabling Thinner/Cleaner if necessary. at low ambient temperatures, and when using from below: special hardeners, the practicable workability at 1.1 Secure cable leads against influx of the high temperatures. With cds-Pouring Concrete Cleaning tools and equipment: casting material (e.g. using plastic foam UW/UW rapid, even damp surfaces can be co- seal) At every interruption in work clean immediately vered. The material dries almost shrink-free. with cds-EP-Thinner/Cleaner. Do not let either 1.2 Where boreholes are more than 130 mm material components or thinner get into the deep or surfaces are very uneven, the bore- drains, water supply or ground, but dispose of Properties: holes should be filled with an epoxy mortar according to regulations in force. Density (mixture): 1,9 g/cm3 e.g. cds-Mortar LS. Mixing ratio: 1.3 Set the lamp with fixing in the borehole and 1 kg + 90 g hardener (UW) Packaging: adjust. Remove the adjusting device and 1 kg + 100 g hardener (UW rapid) Containers of 8 kgs including hardener. weight with about 10 kg. Water permeability according to DIN 1048: impermeable 1.4 Pour in the cds-Pouring Concrete UW (see point 3). Colour: Compression strength: 2. Installation of the inset lights with cabling Grey (for concrete) or black (for asphalt) greater than 70 N/mm2 from the side: Tensile Bending strength: greater than 30 N/mm2 2.1 Secure cable leads against influx of the cas- Storage: ting material (e.g. using plastic foam seal) Heat conductivity: 0,5 W/mK Can be stored up to 2 years. Keep the container 2.2 Pierce the plastic form seal on the side indi- securely closed and dry, and store at 15 to Bonding strength to concrete: cating the cable-gap crosswise, pull the 20 0 C if possible. Avoid direct sunlight. greater than 2,5 N/mm2 lead(s) through, feed a thin-walled flexible (cracks in concrete) tube at least 15 mm i.d., and 200 mm long Temperature resistance: over it and through the plastic sealing-ring. Warning: up to + 80 0 C continuously and The seal between tube and plastic foam Skin contact, particularly with the hardener, has up to + 1200 C peak temperatures. sealer must be tight! When using plastic to be avoided. Use a non-greasy skin barrier- piping, it must be able to withstand tempe- cream. If any splashes get into the eyes, rins ratures of up to 100 0 C - it must not melt, immediately with plenty of water and visit your Requirements for the base: doctor without delay. shrink or deform. Boreholes or cavities must be free of dust, loose The above details are given as the result of many stones, grit, and similar dirt. Standing water 2.3 Insert the lamp with its fixings into the ca- years experience on building sites, and to the must be removed, but slightly damp surfaces vity. The tube must reach into the cable best of our knowledge. They are perforce of a may be covered. If a compressor is available, it channel. Seal the cable channel to the ca- general nature and not binding for every appli- is recommended to blow the surface out with vity precisely, around the tube inserted. cation, as the local conditions and differences in compressed air. Use sealant able to withstand up to about construction techniques must always be taken 1000 C - e.g. plastic foam offcuts - then into account. adjust lamp. If you have any specific questions, please ring Mixing: our experts in 55576 Sprendlingen, who will be 2.4 Pour in cds-Pouring Concrete UW The base (A) and hardener (B) are both packed (see point 3). able wo give you further advice, and may be able to help you with product familarisation. in exactly-measured proportions. Component A 2.5 Lead the electric cable through the channel must be stirred until free of lumps. Stirring must provided. be for 3 to 5 minutes (checked on a timepiece). 3. Casting An electric handmixer is recommended for stir- ring and mixing, e.g. a slow-speed drill (running 3.1 Carefully pour the cds-Pouring Concrete at 300 to 400 rpm) fitted with a mixer-paddle. UW mixed with hardener into the circle If as a result of long storage, component A has a around the lamp, up to about 2 cm below hard bottom skin, this must be broken up with a the level of the lamp socket. Usage of cds- trowel before mixing. Once component A is tho- Pouring Concrete UW will be some 7 to 8 roughly stirred, component B is completely kg for 120 mm depth and 345 mm diame- emptied into the base, and both components ter of the main boring. well and intensively mixed. During the mixing process, sides and bottom of the container must 3.2 Fill the remaining space to the level of the be repeatedly scraped off with a sharp instru- lamp with either cds-Pouring Concrete or ment. Mixing time 1 to 2 minutes. After this, cds-Cable Joint Filler. transfer into a clean container, and thoroughly remix once more. The material, when properly mixed, will be of a uniform appearance. The mixed material must now immediately be pou- red.
  • 6. EXPERTEN FÜR OBERFLÄCHEN VERKEHRSFLÄCHEN EXPERTS IN SURFACINGS INDUSTRIE- UND BETRIEBSFLÄCHEN FLUGBETRIEBSFLÄCHEN cds-BAUTENSCHUTZPRODUKTE POSSEHL SPEZIALBAU GMBH cds-Bautenschutzprodukte Gau-Bickelheimer-Straße 72 55576 Sprendlingen / Rhh. Germany Telefon +49 (67 01) 93 50-0 Telefax +49 (67 01) 93 50-49 info.cds@possehl-spezialbau.de www.possehl-spezialbau.de ind0506