Energy Audit Summary
1. 1 of 26
ENERGY AUDITDarshan Vithani ,Pranav Pathak
ME-CSE
2. 2 of 26
Energy Audit
ENERGY AUDIT (EA)
pool of activities (systematic procedure) focused on
analysis of current energy need and consumption
going out of valid technical standards,
analysis of problems (weaknesses and deficiencies),
EA identifies and in detail quantifies effective
possibilities of energy savings tailored to the object
being analyzed,
3. 3 of 26
Energy Audit
AIM OF ENERGY AUDIT
to minimize costs for energy
to minimize operational costs
to minimize costs for repairs
and reconstruction
increase quality of environment that
contributes to increased work productivity
4. 4 of 26
Energy Audit
AIM OF ENERGY AUDIT
to minimize costs for energy
to minimize operational costs
to minimize costs for repairs
and reconstruction
increase quality of environment that
contributes to increased work productivity
5. 5 of 26
Energy Audit
TYPE OF ENERGY AUDIT
The type of Energy Audit to be performed depends on:
- Function and type of industry
- Depth to which final audit is needed, and
- Potential and magnitude of cost reduction desired
Thus Energy Audit can be classified into the following two
types.
i) Preliminary Audit
ii) Detailed Audit
6. 6 of 26
Energy Audit
PRELIMINARY ENERGY AUDIT METHODOLOGY
Establish energy consumption in the organization
Estimate the scope for saving
Identify the most likely (and the easiest areas for attention
Identify immediate (especially no-/low-cost) improvements/
savings
Set a ‘reference point’
Identify areas for more detailed study/measurement
Preliminary energy audit uses existing, or easily obtained
data
7. 7 of 26
Energy Audit
DETAILED ENERGY AUDIT METHODOLOGY
It is offers most accurate estimate of energy savings and cost
This is based on an inventory of energy using systems,
assumptions of current operating conditions and calculations
of energy use.
Detailed energy auditing is carried out in three phases: Phase
I, II and III.
Phase I - Pre Audit Phase
Phase II - Audit Phase
Phase III - Post Audit Phase
8. 8 of 26
Energy Audit
Steps For DETAILED ENERGY AUDIT METHODOLOGY
9. 9 of 26
Energy Audit
Steps For DETAILED ENERGY AUDIT METHODOLOGY
10. 10 of 26
Energy Audit
Steps For DETAILED ENERGY AUDIT METHODOLOGY
11. 11 of 26
Energy Audit
Steps For DETAILED ENERGY AUDIT METHODOLOGY
12. 12 of 26
Energy Audit
Steps For DETAILED ENERGY AUDIT METHODOLOGY
13. 13 of 26
Energy Audit
Steps For DETAILED ENERGY AUDIT METHODOLOGY
14. 14 of 26
Energy Audit
AREAS OF ENERGY AUDIT
Subject of energy consumption analysis are energy resources
consumed in the industrial area, i.e.
Electricity
Natural gas
Steam
Coal
Wood, wood chips/pellets
Fuels (petrol, oil, propane-butane).....
15. 15 of 26
Energy Audit
AREAS OF ENERGY AUDIT
• thermal-technical protection of buildings,
• heating systems
• hot water preparation,
• ventilation systems and air-conditioning (buildings and technology)
• electric appliances (administrative and technological incl. electrical
connection, transformation, distribution network, el. switchboards, el.
compensation)
• gas or other energy resources consuming appliances (furnaces, cleaning
devices,..)
• Indoor/outdoor lighting,
• measurement and regulation.
16. 16 of 26
Energy Audit
ENERGY AUDIT METHODOLOGY
Pre-audit presentation.
Collection of data / information.
Measurements and monitoring with instruments.
Computation and in-depth analysis.
Post-audit presentation to discuss the Energy Conservation
Opportunities identified by the audit team.
17. 17 of 26
Energy Audit
INSTRUMENTS USED
Flue Gas Analyzer
Power Analyzer, Tachometer
Ultrasonic Flow Meter
Trap Man (For Steam Trap Survey)
Raytech Gun & Digital Thermometer (Non-contact and Contact type
both)
Anemometer, pH/TDS/Conductivity meter
LUX Meter, Digital Manometer
19. 19 of 26
Energy Audit
BASE LINE DATA
Product Bulk Processed Milk (Toned, Double Toned
& Full Cream)
Capacity of the plant 8 Lac liters of Milk per day
Annual Fuel / Energy Consumption PNG: 17,76,000 SCM
Worth: Rs 3.7 Crores
Electricity: 134.6 Lac kVAh
Worth: Rs 6.68 Crores
Annual Energy Bill Rs 10.38 Crores
Compressed Air generation 180 cfm
Steam Consumption 65,000 kg/month for Milk Plant
15,000 kg/month for Ice Cream Plant
20. 20 of 26
Energy Audit
Summary of Savings Identified & Realized
(Year 2003 & 2004)
Major recommendations implemented:
1. Boiler fuel switched over to PNG from LDO
2. Steam supplied to ICP from this boiler
3. Improvement of Power Factor from 0.9 to 0.996
4. New air compressor installed lowering SEC
5. Installation of Auto Blow Down system for Boiler
Total Savings projected by
PCRA
Electricity: 21,43,360 kVAh Worth: Rs 78.24 Lac
LDO: 184.31 KL Worth: 85.8 Lac
Total Savings Realised till
date
Electricity: 5,21,017 kVAh Worth: Rs 19.02 Lac
LDO: 130.06 KL Worth: Rs 60.55 Lac
% Savings Realised of total
energy consumption
Electricity: 3.7%
LDO: 20.3%
21. 21 of 26
Energy Audit
Summary of Savings Identified
(Year 2005)
Total savings identified Electricity: 7,17,004 kVAh
PNG: 1,36,042 SCM
Worth: Rs 59.18 Lac
No cost savings with immediate
payback
Electricity: 95,308 kVAh
Worth: Rs 4.1 Lac
Low cost savings with payback < 1
year
Electricity: 5,41,796 kVAh
Worth: Rs 23.3 Lac
High cost savings with payback
between 1-2 years
Electricity: 79,900 kVAh
Worth: Rs 3.44 Lac
Gas: 1,36,042 SCM
Worth: Rs 28.34 Lac
% savings identified of total energy
consumption
Electricity: 5.32%
Gas: 7.66%
22. 22 of 26
Energy Audit
BOILERS
Observations:
1. Condensate recovery is not being done.
2. Feed water temperature presently is 50C.
Recommendations:
1. Recover condensate to raise feed water temperature to upto 85C
2. Install de-aerator head on feed water tank and recover condensate.
3. Install steam operated condensate recovery pump
Savings Estimated / year Investment Payback Period
Rs 28.34 Lac Rs 25 Lac 11 Months
23. 23 of 26
Energy Audit
Air Compressors
Observations:
1. Air leakage are about 26%.
Recommendations:
1. Plugging of air leakages
Savings Estimated / year Investment Payback Period
Rs 4.0 Lac Nominal Immediate
24. 24 of 26
Energy Audit
Illumination
Observations:
1. HPMV lamps are used for street lighting.
2. 36 Watt Tube lights with copper chokes are used.
Recommendations:
1. Replace HPMV lamps by HPSV lamps
2. Replace 36 Watt Tube lights with T-5 28 Watt with electronic choke in
a phased manner.
Savings Estimated / year Investment Payback Period
Rs 3.34 Lac Rs 4.0 Lac 16 Months
25. 25 of 26
Energy Audit
Conclusion
The gaps may exist in design & actual operations for large complexes due
to integration of :
Steam thermal systems.
Electrical systems
Process systems (Motive/ Thermal loads) due to variation in
efficiencies/ actual requirements
Continuous monitoring and analysis of integrated systems is essential
for improvements.
Energy Audits will identify such gaps.
Implementation of recommendations will result into considerable