1. OLCT 80 Wireless
Wireless Fixed Detector
Wireless field detector and transmitter for
detection of oxygen, combustible, toxic and
refrigerant gases in remote locations
Now Available in Wireless!
KEYBENEFITS
•
Suitable design for use in explosive
areas
•
Reduces installation costs by
eliminating cabling and wiring
•
Available with flameproof or
from distortion or interference
Lower Installation Costs
Eliminating the need for point-to-point wiring, the operation of the
OLCT80 wireless is as simple as one single field device communicating
intrinsic-safety sensors
•
wireless connectivity in ATEX 1 zones. Providing a range of up to 3km
the OLCT 80 utilises binding technology to ensure that the signal is free
On-board display allows
noninvasive one-man calibration
•
The new OLCT 80 model builds on an established design to provide
It can be linked via secure network
to monitor large remote areas
with a controller, remote display and alarm station.
Signal Processing you can Rely on
The transceivers operate at a universally accepted frequency of 2.4 GHz
and have the capability to transmit signal data from various inputs or
GASESANALYSED
serial MODBUS outputs.
H2S
O2
CO
NO2
SO2
Cl2
H2
AsH3
SiH4
HCl
NH3
PH3
O3
CH4
“
The OLCT 80 Wireless is suited for
transmitting signal data in a wide
range of industrial applications
“
NO
2. TECHNICALSPECIFICATION
SPECIFICATIONS ANTENNA
• Frequency band 900 MHz or 2400 MHz - to be specified
GENERAL
when ordering
• Low power requirement
• 1-3KM line-of-sight range
• Robust mesh network topology (option)
• Wireless connectivity in ATEX 1 zones
• Impedance : 50 Ω
• Gain 2dBi
• Power 2 watts
PERFORMANCE
• Logic: 3 dry relay contacts (Fault, Al1, Al2)
• Analogue: Standardised 4-20 mA output
• Digital: one serial RS485 output
• Signal faults: 1 < 0.5 mA
• Alarms: 2 programmable thresholds per channel
OUTPUT SIGNAL
• Operating Temp: -20°C to +55°C
• Pre-calibrated sensor
• Detected gases: Explosive or toxic gases, or O2
PHYSICAL
RELAYS
• Enclosure material: Epoxy coated aluminium
• 3 relays, RCT change over
• Relay rating: 2 A @250 VAC or 30 VDC
• Load resistance: 500 Ω
316 stainless steel sensor
• Weight: 4 kg
POWER
• Supply: 16 to 28 V DC optional solar panels available in
APPROVALS
• EEx d IIB T5 (T 100°C) for OLCT 80 with flameproof sensor
• EEx d [ia] ia IIB T4 (T 135°C) for OLCT 80 with intrinsically
ATEX version
• Cable entry: 4 M20 & 2 M25 cable entries
• Analogue input: 2 analog input 4-20 mA (load resistance
120 Ω)
• Loop impedance with OLDHAM controller:
safe sensor
• Certificate INERIS 03ATEX0240X
• Ingress protection: IP 66
128 Ω (electrochemical), 32 Ω (catalytic), 16 Ω (OLCT 80 XP IR)
POWER CONSUMPTION
• With digital link: 9 W (electrochemical) - 10 W (catalytic)
- 12.5 (IR)
• With signal output at 25mA: 9 W (electrochemical) - 10 W
(catalytic) - 13.2 (IR)
• With signal output set at 25 mA and activated relays:
10.4 W (electrochemical) - 11.5 W (catalytic) -14.7(IR)