Smart Lab Buildings




Marc Gomez, CIH, CSP, ARM, Interim Assistant Vice Chancellor,
    Facilities Management / Environmental Health & Safety
  Joel Azpuru, CIH, CSP, Industrial Hygiene Specialist, EH&S
 Chris Abbamonto, CEM, LEED-AP, Campus Energy Manager,
                     Facilities Management
University of California, Irvine




           Large research university
         $16M annual utilities budget
 Lab buildings consume 2/3 of campus energy
Many energy initiatives to reduce carbon footprint
Campus Energy $avings
          Team Synergy

  Safety                     Engineers
Management
                           Supportive
                           Users/
                           Researchers
 Visionary &
  Supportive
    Upper       Patience    Facility
 Management                Managers
Agenda
Smart Lab Overview
Centralized Demand Controlled Ventilation
Low Flow Fume Hoods
Exhaust System Optimization
Laboratory Smart Lighting Controls
Smart Lab Case Study: Gross Hall
Question and Answer Session
Balancing Lab Safety
  & Climate Safety
Create lab buildings that out perform
ASHRAE 90.1 / CA Title 24 by 50%

Combine energy initiatives such as
  Centralized demand controlled ventilation (CDCV)
  Low flow (high performance) fume hoods
  Reduced building exhaust stack airspeeds
  Energy-efficient lighting
Smart Lab Building Concept
Labs w/CDCV
real time lab air
monitoring          Building Exhaust System
4 ach occupied
2 ach
unoccupied




                                              Energy efficient
                                              lighting




                                              Labs with
                                              low flow
                                              fume hoods
                                              (as appropriate)
Smart Lab Parameters
                                                Current Best Practice        Smart Lab Parameters

Air-handler/filtration airspeeds                 400 ft/min. max                  350 ft/min. max
Total system (supply + exhaust) pressure-drop       6 in. w.g.          <5 in. w.g. (incl. dirty filter allow.)
Duct noise attenuators                                Few                             None

Occupied lab air-changes/hr. (ACH)                   6 ACH                4 ACH w/contaminant sensing
Night air-change setback (unoccupied)              No setback           2 ACH w/occupancy + contaminant sensing
                                                                          + no thermal inputs during setbacks
Low-flow/high-performance fume hoods                  No                  Yes, where hood density warrants

Fume hood face-velocities                           100 FPM                   70 FPM (low-flow hoods)

Fume hood face-velocities (unoccupied)              100 FPM                   40 FPM (low-flow hoods)
Fume hood auto-closers                               None                    Where hood density high
Exhaust stack discharge velocity                   ~3,500 FPM           Reduce or eliminate bypass air,
                                                                          wind responsive controls
Lab illumination power-density                      0.9 watt/SF            0 .6 watt/SF w/LED task lighting

Fixtures near windows on daylight sensors             No                                Yes
Energy Star freezers & refrigerators                  No                                Yes
Out-perform CA Title 24                             20-25%                              50%
Agenda
Smart Lab Overview
Centralized Demand Controlled Ventilation
Low Flow Fume Hoods
Exhaust System Optimization
Laboratory Smart Lighting Controls
Smart Lab Case Study: Gross Hall
Question and Answer Session
CDCV & Energy $avings
Monitor Air Contaminants

Reduce air changes per hour (ACH)
   if no contaminants detected

Increase air changes per hour (ACH)
    when contaminants detected
Question: Is Increased ACH Safer?
“Specification of Airflow Rates in Laboratories”
by Tom Smith, Exposure Control Technologies,
Conclusions:
  ACH as a metric for dilution is “too simplistic”.
  Must consider other factors that lead to exposure,
  (i.e. contaminant generation rate, air mixing, etc.)
  “Increased airflow [may increase] contaminant
  generation and distribution throughout the space”
  May lead to “false sense of safety”
Answer: Not Necessarily
Alternatives to simply increasing ACH:

  Base air exchange rate on contaminant generation
  Review lab practices
  Attain proper air mix ratios
  Reduce overall ACH to save energy and increase
  ACH as needed via “smart controls”
CA Ventilation Code Requirements:
Code in Effect        Ventilation Requirements                 Comments
California Building   B Labs: 6 ACH                             In effect through
Code 2001             H-8 Labs: 1 cfm/sf                       December, 2007
                          12 ft ceiling = 5 ACH                 Existing
                          10 ft ceiling = 6 ACH                Construction
                          8 ft ceiling = 7.5 ACH
California Mechanical B “Research” Labs:                         Effective 1/2008
Code 2007             0.43cfm/sf                                 Refers to
                         12 ft ceiling = 3.5 ACH               ASHRAE 62.1-2004
                         10 ft ceiling = 4.2 ACH                 New Construction
                         8 ft ceiling = 5.25 ACH                 No category for
                                                               university research
                      B“Science Classroom”/L
                                                               labs
                      (H-8): 1 cfm/sf
*Need “Alternative Means of Protection” from CA State Fire Marshal for less than
minimum required ventilation
Agenda
Smart Lab Overview
Centralized Demand Controlled Ventilation
Low Flow Fume Hoods
Exhaust System Optimization
Laboratory Smart Lighting Controls
Smart Lab Case Study: Gross Hall
Question and Answer Session
Low Flow (high performance) Fume Hoods
Operate safely at lower face velocities (i.e. 70 FPM rather than 100 FPM)



                         Exhaust
                         Plenum




      Sash                  Work                              Baffle
         Airfoil           Surface




                                           Increased Hood Depth
UCI Low Flow Fume Hood Study
            2008
Both traditional and low flow fume hoods
were subjected to 168 ASHRAE 110 tests
Low flow hoods performed better than
standard hoods at 80 & 100 fpm - fully
open sash
  Tracer gas results were well below the
  0.1ppm “as used” ASHRAE criteria
  Low flow hoods save energy, particularly in
  constant volume systems
  Low flow hoods may also be a good solution
  in buildings with limited HVAC capacity
Flow & Cost Comparison
HVAC           Flow at 100 fpm         Flow at 80 fpm          Flow at 70 fpm
System Type    nominal face velocity   nominal face velocity   nominal face velocity
and Fume       Annual Cost at $5 per   Annual Cost at $5 per   Annual Cost at $5 per
Hood           CFM                     CFM                     CFM
Equipment

Constant Air   900 CFM                   720 CFM               630 CFM
Volume         $4500 Institute of Environmental
                                         $3600                 $3150
Variable Air          Sciences designation: IES-RP-CC-008-84
               Good: 682 CFM/$3410 Good: 568 CFM/$2840 Good: 511 CFM/$2555
Volume         Poor: 851 CFM/$4255 Poor: 686 CFM/$3430 Poor: 604 CFM/$3020
(VAV)
VAV with ZPS Good: 492 CFM/$2460 Good: 470 CFM/$2350 Good: 462 CFM/$2310
             Poor: 558 CFM/$2790 Poor: 539 CFM/$2695 Poor: 530 CFM/$2650
VAV with       361 CFM                 343 CFM                 335 CFM
ASC            $1,805                  $1,715                  $1,675
VAV with       343 CFM                 331 CFM                 325 CFM
Perfect Sash   $1,715                  $1,655                  $1,625
Management
Flow & Cost Comparison
HVAC           Flow at 100 fpm         Flow at 80 fpm          Flow at 70 fpm
System Type    nominal face velocity   nominal face velocity   nominal face velocity
and Fume       Annual Cost at $5 per   Annual Cost at $5 per   Annual Cost at $5 per
Hood           CFM                     CFM                     CFM
Equipment

Constant Air   900 CFM                 720 CFM                 630 CFM
Volume         $4500                   $3600                   $3150
Variable Air   Good: 682 CFM/$3410 Good: 568 CFM/$2840 Good: 511 CFM/$2555
Volume         Poor: 851 CFM/$4255 Poor: 686 CFM/$3430 Poor: 604 CFM/$3020
(VAV)
VAV with ZPS Good: 492 CFM/$2460 Good: 470 CFM/$2350 Good: 462 CFM/$2310
             Poor: 558 CFM/$2790 Poor: 539 CFM/$2695 Poor: 530 CFM/$2650
VAV with       361 CFM                 343 CFM                 335 CFM
ASC            $1,805                  $1,715                  $1,675
VAV with       343 CFM                 331 CFM                 325 CFM
Perfect Sash   $1,715                  $1,655                  $1,625
Management
Agenda
Smart Lab Overview
Centralized Demand Controlled Ventilation
Low Flow Fume Hoods
Exhaust System Optimization
Laboratory Smart Lighting Controls
Smart Lab Case Study: Gross Hall
Question and Answer Session
Lab Building Exhaust

  Wind
                                  Re-Entrainment
Exhaust Fan      Bypass Damper    of Contaminated
                                  Air


      Plenum

                                   Supply Fan Duct


                                 Balcony
         Fume Hood
Wind Tunnel Testing
Challenge Conservative Assumptions
Wind Tunnel Testing
Build model of campus
Install model stacks
An abundance of air
sampling point
receptors
Wind Tunnel Testing
          Methodology
Build model of campus
Install model stacks
Install air sampling points
(“receptors”)
Ensure correct approach
flow
Wind tunnel testing
Exhaust Energy Reduction Solutions

         Slightly higher stacks, 4-5 feet


             Variable speed fans (reduce exhaust fan flows)
             Install wind responsive equipment (if needed)



               Reduce or eliminate bypass air
Sprague Hall

Install variable frequency
drives (VFD)
Close bypass dampers
No stack extension
needed
Energy Savings:
581,749 kWh
Croul Hall


      Install variable frequency
      drives (VFD)
      8’ Stack Extensions
      Static Pressure Reset
      Energy Savings:
      344,307 kWh
Natural Sciences II


           Install variable frequency
           drives (VFD)
           Static Pressure Reset
           4’ Stack Extensions
           Energy Savings:
           928,722 kWh
Hewitt Hall


No Stack Extensions
Install variable frequency
drives (VFD)
Static Pressure Reset
Energy Savings:
286,594 kWh
Agenda
Smart Lab Overview
Centralized Demand Controlled Ventilation
Low Flow Fume Hoods
Exhaust System Optimization
Laboratory Smart Lighting Controls
Smart Lab Case Study: Gross Hall
Question and Answer Session
Lighting Controls
       Reduce Power Density by 50%

Lab Area LPD
from 1.1 to 0.6



                                Lab Prep LPD
                                from 1.0 to 0.4

Prep Room LPD
 from 2.0 to 1.0

                                 Corridor LPD
                                from 0.6 to 0.3
Lower Blinds
to Allow for Daylighting
Fixture Closest to the Window is
             OFF
Manual Switch
    to Occupancy Sensor




               A-B CIRCUITING



50% Auto On - Manual to 100%
Auto on to 50% Light Level
Agenda
Smart Lab Overview
Centralized Demand Controlled Ventilation
Low Flow Fume Hoods
Exhaust System Optimization
Laboratory Smart Lighting Controls
Smart Lab Case Study: Gross Hall
Question and Answer Session
Bill & Sue Gross Hall
A Smart & Sustainable Design
Gross Hall Features
Centralized Demand Controlled Ventilation - real-time indoor
air quality monitoring, varies the ventilation rate
Occupancy Based Controls - controls both ventilation system &
lighting
Natural Ventilation - operable windows linked with mechanical
ventilation
Smart Lighting Controls - daylighting sensors used with
perforated blinds
Energy Star Equipment - freezers, refrigerators, ice machines &
copiers
Air Handling System - larger air handlers accommodate low
pressure-drop filtration
Building Exhaust - right sized exhaust system eliminates bypass air
Exceeding Title 24

 Gross Hall     Exceeded         Time
  Project       Title 24 By    Dependant
                                 Value
As Submitted       38%        TDV Office
to Utilities                  Bldg

Using Code         50%        TDV 24/7
Chiller

Using UCI          57%        TDV 24/7
Central Plant
with TES
Right Sized Air Handlers & Exhaust
Gross Hall Perforated Blinds


High performance
glazing
Perforated blinds allow
diffuse light to enter the
space when closed
Reduced glare
Increased occupant
control
Operable Windows Interlocked with
         HVAC System
Smart Lab “Safety Net”
            Phoenix Controls
            Celeris® Display
            Panels
              Currently in use at
              Gross Hall
              Programmed to
              display ACH,
              occupancy status and
              ventilation offset
              information within lab
Smart Lab “Safety Net”
            Emergency General
            Ventilation Purge “Red
            Button”
              Fully opens general
              exhaust ventilation valves
              Response within minutes
              Integrated alarm system
              Deactivates when button
              is pulled out
Smart Lab “Safety Net”
            Occupant Training
              Occupant welcome
              brochure
              “Red Button” signage
Estimated annual energy savings:
 • 890,080 kWh electrical with 193 kW demand reduction
             • 22,464 therms of natural gas
           Estimated annual energy cost savings:
        • $110,980 at $0.105/kWh and $0.78/therm
         Savings by Design payment of $397,836
               Exceeding Title 24 by 50%
      Bid as a LEED New Construction (NC) Silver
Design Build contractor proposed to increase the sustainable
     features to achieve LEED NC Gold certification
Smart Labs
   Considerations/Challenges

Maintenance
 Mechanical Repairs to Phoenix system (poppets,
 valves, etc)
 Software updates/adjustments to Johnson
 Controls
 Sensor calibration/replacement
 Calibration of sash sensors, zone presence
 sensors, etc.
 Tracking pair adjustments
Smart Labs
    Considerations/Challenges
Considerations
  Lack of “universal” CDCV sensor for all
  chemicals
  CA requires variance from Cal/OSHA to allow
  use of low flow hoods below 100 FPM
  Risk Assessment of lab operations needed to
  select the appropriate smart controls
Life cycle cost/payback analysis needed!
Agenda
Smart Lab Overview
Centralized Demand Controlled Ventilation
Low Flow Fume Hoods
Exhaust System Optimization
Laboratory Smart Lighting Controls
Smart Lab Case Study: Gross Hall
Question and Answer Session
As A Reminder…
We have your audio muted, so we
cannot hear you

If you have a question for the panel,
instead of using the “raising your
hand” button, use the chat tab
(Conversation) and preface your
comment with “Question for Panel”
Thank You!

Weitere ähnliche Inhalte

Andere mochten auch

Lab Lighting Controls Upgrade 07.01.09 CLTC UCI
Lab Lighting Controls Upgrade 07.01.09 CLTC UCILab Lighting Controls Upgrade 07.01.09 CLTC UCI
Lab Lighting Controls Upgrade 07.01.09 CLTC UCIChris Abbamonto
 
UCI Comprehensive Retrofits 10.29.09
UCI Comprehensive Retrofits 10.29.09UCI Comprehensive Retrofits 10.29.09
UCI Comprehensive Retrofits 10.29.09Chris Abbamonto
 
Exhaust Stack Discharge Velocity Reduction
Exhaust Stack Discharge Velocity ReductionExhaust Stack Discharge Velocity Reduction
Exhaust Stack Discharge Velocity ReductionChris Abbamonto
 
SMCHS Alumni Career Day 2010
SMCHS Alumni Career Day 2010SMCHS Alumni Career Day 2010
SMCHS Alumni Career Day 2010Chris Abbamonto
 
IAAM-UVMA Conference 2008 &quot;Going Green on Campus&quot;
IAAM-UVMA Conference 2008 &quot;Going Green on Campus&quot;IAAM-UVMA Conference 2008 &quot;Going Green on Campus&quot;
IAAM-UVMA Conference 2008 &quot;Going Green on Campus&quot;Chris Abbamonto
 
Gross Hall Smart Labs For Sustainability Committee 04.02.10
Gross Hall Smart Labs For Sustainability Committee 04.02.10Gross Hall Smart Labs For Sustainability Committee 04.02.10
Gross Hall Smart Labs For Sustainability Committee 04.02.10Chris Abbamonto
 
RENCANA PENANGANAN BANJIR DI KOTA TANGERANG
RENCANA PENANGANAN BANJIR DI KOTA TANGERANGRENCANA PENANGANAN BANJIR DI KOTA TANGERANG
RENCANA PENANGANAN BANJIR DI KOTA TANGERANGAnton Riyanto
 
Exhaust Stack Discharge Velocity Reduction Study for Labs21 2009
Exhaust Stack Discharge Velocity Reduction Study for Labs21 2009Exhaust Stack Discharge Velocity Reduction Study for Labs21 2009
Exhaust Stack Discharge Velocity Reduction Study for Labs21 2009Chris Abbamonto
 
penataan kampung kumuh
penataan kampung kumuhpenataan kampung kumuh
penataan kampung kumuhAnton Riyanto
 
Recycling Energy & Resources from Waste
Recycling Energy & Resources from WasteRecycling Energy & Resources from Waste
Recycling Energy & Resources from Wasteguest81fe20
 

Andere mochten auch (16)

Conc
ConcConc
Conc
 
Lab Lighting Controls Upgrade 07.01.09 CLTC UCI
Lab Lighting Controls Upgrade 07.01.09 CLTC UCILab Lighting Controls Upgrade 07.01.09 CLTC UCI
Lab Lighting Controls Upgrade 07.01.09 CLTC UCI
 
UCI Comprehensive Retrofits 10.29.09
UCI Comprehensive Retrofits 10.29.09UCI Comprehensive Retrofits 10.29.09
UCI Comprehensive Retrofits 10.29.09
 
Peru
PeruPeru
Peru
 
Exhaust Stack Discharge Velocity Reduction
Exhaust Stack Discharge Velocity ReductionExhaust Stack Discharge Velocity Reduction
Exhaust Stack Discharge Velocity Reduction
 
Conc
ConcConc
Conc
 
SMCHS Alumni Career Day 2010
SMCHS Alumni Career Day 2010SMCHS Alumni Career Day 2010
SMCHS Alumni Career Day 2010
 
IAAM-UVMA Conference 2008 &quot;Going Green on Campus&quot;
IAAM-UVMA Conference 2008 &quot;Going Green on Campus&quot;IAAM-UVMA Conference 2008 &quot;Going Green on Campus&quot;
IAAM-UVMA Conference 2008 &quot;Going Green on Campus&quot;
 
Gross Hall Smart Labs For Sustainability Committee 04.02.10
Gross Hall Smart Labs For Sustainability Committee 04.02.10Gross Hall Smart Labs For Sustainability Committee 04.02.10
Gross Hall Smart Labs For Sustainability Committee 04.02.10
 
Conc
ConcConc
Conc
 
Fs55 Manual
Fs55 ManualFs55 Manual
Fs55 Manual
 
RENCANA PENANGANAN BANJIR DI KOTA TANGERANG
RENCANA PENANGANAN BANJIR DI KOTA TANGERANGRENCANA PENANGANAN BANJIR DI KOTA TANGERANG
RENCANA PENANGANAN BANJIR DI KOTA TANGERANG
 
CDCV Webinar 01.28.09
CDCV Webinar 01.28.09CDCV Webinar 01.28.09
CDCV Webinar 01.28.09
 
Exhaust Stack Discharge Velocity Reduction Study for Labs21 2009
Exhaust Stack Discharge Velocity Reduction Study for Labs21 2009Exhaust Stack Discharge Velocity Reduction Study for Labs21 2009
Exhaust Stack Discharge Velocity Reduction Study for Labs21 2009
 
penataan kampung kumuh
penataan kampung kumuhpenataan kampung kumuh
penataan kampung kumuh
 
Recycling Energy & Resources from Waste
Recycling Energy & Resources from WasteRecycling Energy & Resources from Waste
Recycling Energy & Resources from Waste
 

Ähnlich wie UC Irvine Smart Labs Webinar 06.24.10

Smart Labs Labs21
Smart Labs   Labs21Smart Labs   Labs21
Smart Labs Labs21matt_UCI
 
Smart Lab Overview For Green Campus Interns 11 17 2010
Smart Lab Overview For Green Campus Interns 11 17 2010Smart Lab Overview For Green Campus Interns 11 17 2010
Smart Lab Overview For Green Campus Interns 11 17 2010matt_UCI
 
Sue and Bill Gross Hall Smart Labs Handout
Sue and Bill Gross Hall Smart Labs HandoutSue and Bill Gross Hall Smart Labs Handout
Sue and Bill Gross Hall Smart Labs Handoutmatt_UCI
 
Energy &amp; Environmental Design Approach Speculative Lab Building
Energy &amp; Environmental Design Approach   Speculative Lab BuildingEnergy &amp; Environmental Design Approach   Speculative Lab Building
Energy &amp; Environmental Design Approach Speculative Lab Buildinggreenbauer1
 
An overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testingAn overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testingBill Spohn
 
Fundamentals-of-CKV.pdf
Fundamentals-of-CKV.pdfFundamentals-of-CKV.pdf
Fundamentals-of-CKV.pdfSebaGmez4
 
Innovative compressed air case studies
Innovative compressed air case studiesInnovative compressed air case studies
Innovative compressed air case studiesZondits
 
CDCV Webinar Feb 191
CDCV Webinar Feb 191CDCV Webinar Feb 191
CDCV Webinar Feb 191matt_UCI
 
Cshema 2009 Master Energy
Cshema 2009   Master EnergyCshema 2009   Master Energy
Cshema 2009 Master Energydtsun
 
4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow management4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow managementUpsite Technologies
 
A practical approach to pharmaceutical HVAC energy reduction
A practical approach to pharmaceutical HVAC energy reductionA practical approach to pharmaceutical HVAC energy reduction
A practical approach to pharmaceutical HVAC energy reductionEECO2
 
Clean Room Opportunities
Clean Room OpportunitiesClean Room Opportunities
Clean Room OpportunitiesDIv CHAS
 
Erlab Captair Seminar
Erlab Captair Seminar Erlab Captair Seminar
Erlab Captair Seminar Joseph Chan
 
Estrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de ITEstrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de ITData Center Consultores
 

Ähnlich wie UC Irvine Smart Labs Webinar 06.24.10 (20)

Smart Labs Labs21
Smart Labs   Labs21Smart Labs   Labs21
Smart Labs Labs21
 
Smart Lab Overview For Green Campus Interns 11 17 2010
Smart Lab Overview For Green Campus Interns 11 17 2010Smart Lab Overview For Green Campus Interns 11 17 2010
Smart Lab Overview For Green Campus Interns 11 17 2010
 
Sue and Bill Gross Hall Smart Labs Handout
Sue and Bill Gross Hall Smart Labs HandoutSue and Bill Gross Hall Smart Labs Handout
Sue and Bill Gross Hall Smart Labs Handout
 
Energy &amp; Environmental Design Approach Speculative Lab Building
Energy &amp; Environmental Design Approach   Speculative Lab BuildingEnergy &amp; Environmental Design Approach   Speculative Lab Building
Energy &amp; Environmental Design Approach Speculative Lab Building
 
An overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testingAn overview of diagnostic tools used in RESNET testing
An overview of diagnostic tools used in RESNET testing
 
Appa
AppaAppa
Appa
 
Fundamentals-of-CKV.pdf
Fundamentals-of-CKV.pdfFundamentals-of-CKV.pdf
Fundamentals-of-CKV.pdf
 
Innovative compressed air case studies
Innovative compressed air case studiesInnovative compressed air case studies
Innovative compressed air case studies
 
CDCV Webinar Feb 191
CDCV Webinar Feb 191CDCV Webinar Feb 191
CDCV Webinar Feb 191
 
Gordon Sharp Handout
Gordon Sharp HandoutGordon Sharp Handout
Gordon Sharp Handout
 
Cshema 2009 Master Energy
Cshema 2009   Master EnergyCshema 2009   Master Energy
Cshema 2009 Master Energy
 
4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow management4 steps to quickly improve pue through airflow management
4 steps to quickly improve pue through airflow management
 
Laboratory Energy Conservation
Laboratory Energy ConservationLaboratory Energy Conservation
Laboratory Energy Conservation
 
A practical approach to pharmaceutical HVAC energy reduction
A practical approach to pharmaceutical HVAC energy reductionA practical approach to pharmaceutical HVAC energy reduction
A practical approach to pharmaceutical HVAC energy reduction
 
Clean Room Opportunities
Clean Room OpportunitiesClean Room Opportunities
Clean Room Opportunities
 
Erlab Captair Seminar
Erlab Captair Seminar Erlab Captair Seminar
Erlab Captair Seminar
 
Estrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de ITEstrategias para ahorro de energía en applicaciones de misión crítica de IT
Estrategias para ahorro de energía en applicaciones de misión crítica de IT
 
Cleanrooms 101
Cleanrooms 101Cleanrooms 101
Cleanrooms 101
 
Presentation mechanical car parking ventilation system
Presentation mechanical car parking ventilation systemPresentation mechanical car parking ventilation system
Presentation mechanical car parking ventilation system
 
Presentation mechanical car parking ventilation system
Presentation mechanical car parking ventilation systemPresentation mechanical car parking ventilation system
Presentation mechanical car parking ventilation system
 

UC Irvine Smart Labs Webinar 06.24.10

  • 1. Welcome to the Webinar! We hope you are logged in properly, if you are having trouble call 949-824-5828 We have your audio muted, so we cannot hear you We can read your comments under the “chat tab” (conversation) If you have a question for the panel, instead of using the “raising your hand” button, use the chat tab and preface your comment with “Question for Panel” We will take questions during the Q&A session
  • 2. Smart Lab Buildings Marc Gomez, CIH, CSP, ARM, Interim Assistant Vice Chancellor, Facilities Management / Environmental Health & Safety Joel Azpuru, CIH, CSP, Industrial Hygiene Specialist, EH&S Chris Abbamonto, CEM, LEED-AP, Campus Energy Manager, Facilities Management
  • 3. University of California, Irvine Large research university $16M annual utilities budget Lab buildings consume 2/3 of campus energy Many energy initiatives to reduce carbon footprint
  • 4. Campus Energy $avings Team Synergy Safety Engineers Management Supportive Users/ Researchers Visionary & Supportive Upper Patience Facility Management Managers
  • 5. Agenda Smart Lab Overview Centralized Demand Controlled Ventilation Low Flow Fume Hoods Exhaust System Optimization Laboratory Smart Lighting Controls Smart Lab Case Study: Gross Hall Question and Answer Session
  • 6. Balancing Lab Safety & Climate Safety Create lab buildings that out perform ASHRAE 90.1 / CA Title 24 by 50% Combine energy initiatives such as Centralized demand controlled ventilation (CDCV) Low flow (high performance) fume hoods Reduced building exhaust stack airspeeds Energy-efficient lighting
  • 7. Smart Lab Building Concept Labs w/CDCV real time lab air monitoring Building Exhaust System 4 ach occupied 2 ach unoccupied Energy efficient lighting Labs with low flow fume hoods (as appropriate)
  • 8. Smart Lab Parameters Current Best Practice Smart Lab Parameters Air-handler/filtration airspeeds 400 ft/min. max 350 ft/min. max Total system (supply + exhaust) pressure-drop 6 in. w.g. <5 in. w.g. (incl. dirty filter allow.) Duct noise attenuators Few None Occupied lab air-changes/hr. (ACH) 6 ACH 4 ACH w/contaminant sensing Night air-change setback (unoccupied) No setback 2 ACH w/occupancy + contaminant sensing + no thermal inputs during setbacks Low-flow/high-performance fume hoods No Yes, where hood density warrants Fume hood face-velocities 100 FPM 70 FPM (low-flow hoods) Fume hood face-velocities (unoccupied) 100 FPM 40 FPM (low-flow hoods) Fume hood auto-closers None Where hood density high Exhaust stack discharge velocity ~3,500 FPM Reduce or eliminate bypass air, wind responsive controls Lab illumination power-density 0.9 watt/SF 0 .6 watt/SF w/LED task lighting Fixtures near windows on daylight sensors No Yes Energy Star freezers & refrigerators No Yes Out-perform CA Title 24 20-25% 50%
  • 9. Agenda Smart Lab Overview Centralized Demand Controlled Ventilation Low Flow Fume Hoods Exhaust System Optimization Laboratory Smart Lighting Controls Smart Lab Case Study: Gross Hall Question and Answer Session
  • 10.
  • 11. CDCV & Energy $avings Monitor Air Contaminants Reduce air changes per hour (ACH) if no contaminants detected Increase air changes per hour (ACH) when contaminants detected
  • 12. Question: Is Increased ACH Safer? “Specification of Airflow Rates in Laboratories” by Tom Smith, Exposure Control Technologies, Conclusions: ACH as a metric for dilution is “too simplistic”. Must consider other factors that lead to exposure, (i.e. contaminant generation rate, air mixing, etc.) “Increased airflow [may increase] contaminant generation and distribution throughout the space” May lead to “false sense of safety”
  • 13. Answer: Not Necessarily Alternatives to simply increasing ACH: Base air exchange rate on contaminant generation Review lab practices Attain proper air mix ratios Reduce overall ACH to save energy and increase ACH as needed via “smart controls”
  • 14. CA Ventilation Code Requirements: Code in Effect Ventilation Requirements Comments California Building B Labs: 6 ACH In effect through Code 2001 H-8 Labs: 1 cfm/sf December, 2007 12 ft ceiling = 5 ACH Existing 10 ft ceiling = 6 ACH Construction 8 ft ceiling = 7.5 ACH California Mechanical B “Research” Labs: Effective 1/2008 Code 2007 0.43cfm/sf Refers to 12 ft ceiling = 3.5 ACH ASHRAE 62.1-2004 10 ft ceiling = 4.2 ACH New Construction 8 ft ceiling = 5.25 ACH No category for university research B“Science Classroom”/L labs (H-8): 1 cfm/sf *Need “Alternative Means of Protection” from CA State Fire Marshal for less than minimum required ventilation
  • 15. Agenda Smart Lab Overview Centralized Demand Controlled Ventilation Low Flow Fume Hoods Exhaust System Optimization Laboratory Smart Lighting Controls Smart Lab Case Study: Gross Hall Question and Answer Session
  • 16. Low Flow (high performance) Fume Hoods Operate safely at lower face velocities (i.e. 70 FPM rather than 100 FPM) Exhaust Plenum Sash Work Baffle Airfoil Surface Increased Hood Depth
  • 17. UCI Low Flow Fume Hood Study 2008 Both traditional and low flow fume hoods were subjected to 168 ASHRAE 110 tests Low flow hoods performed better than standard hoods at 80 & 100 fpm - fully open sash Tracer gas results were well below the 0.1ppm “as used” ASHRAE criteria Low flow hoods save energy, particularly in constant volume systems Low flow hoods may also be a good solution in buildings with limited HVAC capacity
  • 18. Flow & Cost Comparison HVAC Flow at 100 fpm Flow at 80 fpm Flow at 70 fpm System Type nominal face velocity nominal face velocity nominal face velocity and Fume Annual Cost at $5 per Annual Cost at $5 per Annual Cost at $5 per Hood CFM CFM CFM Equipment Constant Air 900 CFM 720 CFM 630 CFM Volume $4500 Institute of Environmental $3600 $3150 Variable Air Sciences designation: IES-RP-CC-008-84 Good: 682 CFM/$3410 Good: 568 CFM/$2840 Good: 511 CFM/$2555 Volume Poor: 851 CFM/$4255 Poor: 686 CFM/$3430 Poor: 604 CFM/$3020 (VAV) VAV with ZPS Good: 492 CFM/$2460 Good: 470 CFM/$2350 Good: 462 CFM/$2310 Poor: 558 CFM/$2790 Poor: 539 CFM/$2695 Poor: 530 CFM/$2650 VAV with 361 CFM 343 CFM 335 CFM ASC $1,805 $1,715 $1,675 VAV with 343 CFM 331 CFM 325 CFM Perfect Sash $1,715 $1,655 $1,625 Management
  • 19. Flow & Cost Comparison HVAC Flow at 100 fpm Flow at 80 fpm Flow at 70 fpm System Type nominal face velocity nominal face velocity nominal face velocity and Fume Annual Cost at $5 per Annual Cost at $5 per Annual Cost at $5 per Hood CFM CFM CFM Equipment Constant Air 900 CFM 720 CFM 630 CFM Volume $4500 $3600 $3150 Variable Air Good: 682 CFM/$3410 Good: 568 CFM/$2840 Good: 511 CFM/$2555 Volume Poor: 851 CFM/$4255 Poor: 686 CFM/$3430 Poor: 604 CFM/$3020 (VAV) VAV with ZPS Good: 492 CFM/$2460 Good: 470 CFM/$2350 Good: 462 CFM/$2310 Poor: 558 CFM/$2790 Poor: 539 CFM/$2695 Poor: 530 CFM/$2650 VAV with 361 CFM 343 CFM 335 CFM ASC $1,805 $1,715 $1,675 VAV with 343 CFM 331 CFM 325 CFM Perfect Sash $1,715 $1,655 $1,625 Management
  • 20. Agenda Smart Lab Overview Centralized Demand Controlled Ventilation Low Flow Fume Hoods Exhaust System Optimization Laboratory Smart Lighting Controls Smart Lab Case Study: Gross Hall Question and Answer Session
  • 21. Lab Building Exhaust Wind Re-Entrainment Exhaust Fan Bypass Damper of Contaminated Air Plenum Supply Fan Duct Balcony Fume Hood
  • 22. Wind Tunnel Testing Challenge Conservative Assumptions
  • 23. Wind Tunnel Testing Build model of campus Install model stacks An abundance of air sampling point receptors
  • 24. Wind Tunnel Testing Methodology Build model of campus Install model stacks Install air sampling points (“receptors”) Ensure correct approach flow Wind tunnel testing
  • 25. Exhaust Energy Reduction Solutions Slightly higher stacks, 4-5 feet Variable speed fans (reduce exhaust fan flows) Install wind responsive equipment (if needed) Reduce or eliminate bypass air
  • 26.
  • 27. Sprague Hall Install variable frequency drives (VFD) Close bypass dampers No stack extension needed Energy Savings: 581,749 kWh
  • 28. Croul Hall Install variable frequency drives (VFD) 8’ Stack Extensions Static Pressure Reset Energy Savings: 344,307 kWh
  • 29. Natural Sciences II Install variable frequency drives (VFD) Static Pressure Reset 4’ Stack Extensions Energy Savings: 928,722 kWh
  • 30. Hewitt Hall No Stack Extensions Install variable frequency drives (VFD) Static Pressure Reset Energy Savings: 286,594 kWh
  • 31. Agenda Smart Lab Overview Centralized Demand Controlled Ventilation Low Flow Fume Hoods Exhaust System Optimization Laboratory Smart Lighting Controls Smart Lab Case Study: Gross Hall Question and Answer Session
  • 32. Lighting Controls Reduce Power Density by 50% Lab Area LPD from 1.1 to 0.6 Lab Prep LPD from 1.0 to 0.4 Prep Room LPD from 2.0 to 1.0 Corridor LPD from 0.6 to 0.3
  • 33. Lower Blinds to Allow for Daylighting
  • 34. Fixture Closest to the Window is OFF
  • 35. Manual Switch to Occupancy Sensor A-B CIRCUITING 50% Auto On - Manual to 100%
  • 36. Auto on to 50% Light Level
  • 37. Agenda Smart Lab Overview Centralized Demand Controlled Ventilation Low Flow Fume Hoods Exhaust System Optimization Laboratory Smart Lighting Controls Smart Lab Case Study: Gross Hall Question and Answer Session
  • 38. Bill & Sue Gross Hall A Smart & Sustainable Design
  • 39. Gross Hall Features Centralized Demand Controlled Ventilation - real-time indoor air quality monitoring, varies the ventilation rate Occupancy Based Controls - controls both ventilation system & lighting Natural Ventilation - operable windows linked with mechanical ventilation Smart Lighting Controls - daylighting sensors used with perforated blinds Energy Star Equipment - freezers, refrigerators, ice machines & copiers Air Handling System - larger air handlers accommodate low pressure-drop filtration Building Exhaust - right sized exhaust system eliminates bypass air
  • 40. Exceeding Title 24 Gross Hall Exceeded Time Project Title 24 By Dependant Value As Submitted 38% TDV Office to Utilities Bldg Using Code 50% TDV 24/7 Chiller Using UCI 57% TDV 24/7 Central Plant with TES
  • 41. Right Sized Air Handlers & Exhaust
  • 42. Gross Hall Perforated Blinds High performance glazing Perforated blinds allow diffuse light to enter the space when closed Reduced glare Increased occupant control
  • 43. Operable Windows Interlocked with HVAC System
  • 44. Smart Lab “Safety Net” Phoenix Controls Celeris® Display Panels Currently in use at Gross Hall Programmed to display ACH, occupancy status and ventilation offset information within lab
  • 45. Smart Lab “Safety Net” Emergency General Ventilation Purge “Red Button” Fully opens general exhaust ventilation valves Response within minutes Integrated alarm system Deactivates when button is pulled out
  • 46. Smart Lab “Safety Net” Occupant Training Occupant welcome brochure “Red Button” signage
  • 47. Estimated annual energy savings: • 890,080 kWh electrical with 193 kW demand reduction • 22,464 therms of natural gas Estimated annual energy cost savings: • $110,980 at $0.105/kWh and $0.78/therm Savings by Design payment of $397,836 Exceeding Title 24 by 50% Bid as a LEED New Construction (NC) Silver Design Build contractor proposed to increase the sustainable features to achieve LEED NC Gold certification
  • 48. Smart Labs Considerations/Challenges Maintenance Mechanical Repairs to Phoenix system (poppets, valves, etc) Software updates/adjustments to Johnson Controls Sensor calibration/replacement Calibration of sash sensors, zone presence sensors, etc. Tracking pair adjustments
  • 49. Smart Labs Considerations/Challenges Considerations Lack of “universal” CDCV sensor for all chemicals CA requires variance from Cal/OSHA to allow use of low flow hoods below 100 FPM Risk Assessment of lab operations needed to select the appropriate smart controls Life cycle cost/payback analysis needed!
  • 50. Agenda Smart Lab Overview Centralized Demand Controlled Ventilation Low Flow Fume Hoods Exhaust System Optimization Laboratory Smart Lighting Controls Smart Lab Case Study: Gross Hall Question and Answer Session
  • 51. As A Reminder… We have your audio muted, so we cannot hear you If you have a question for the panel, instead of using the “raising your hand” button, use the chat tab (Conversation) and preface your comment with “Question for Panel”