Copyright © 2011 Viridity Software, Inc. All Rights Reserved  Optimize Power and Cooling in the Data Center Presented by: Amir Radmehr, Director, Innovative Research (TileFlow Software), andMike Rowan, co-Founder and CTO, Viridity Software
The Leader in Data Center Infrastructure Management Software Energy Center connects equipment utilization and business value to power consumption Time-to-value in hours, not months Deploys in minutes, not weeks No additional hardware required No server agents required  Copyright © 2011 Viridity Software, Inc. All Rights Reserved  2
A Tool for Simulating Cooling Performance of Data Centers The first CFD tool dedicated to data centers Extensively validated against measurements Highly satisfied user base Has become the industry standard Actively enhanced every year Copyright © 2011 Viridity Software, Inc. All Rights Reserved  3
Drivers Impacting DC Thermal Management ,[object Object]
Building energy codes are causing companies to re-think DC thermal management:
(Standard 90.1) requires efficient cooling ; systems must use airside economizers; includes all commercial buildings DCs
Save Energy Now aims to reduce energy use in U.S. data centers 10% by 2011
Compliance with various standards such as ASHRAE TC9.9 and LEED75%  of medium-to-large enterprises are implementing “high density” computing platforms. - this number will approach 100% by 2010 .  –  IDC
Optimizing DC Thermal Management is Complex ,[object Object]
Pressure to optimize cooling schemas, equipment layout, and HVAC deployment
Effective ventilation and cooling is critical to ensure uninterrupted operation
The environmental conditions are controlled by numerous factors, these include:
Layout and open area of perforated tiles
Location and characteristics of the cooling units
Layout and heat loads of server racks
Presence of obstructions
Complex air flow and thermal dispersion,[object Object]
Modify layout and/or open area of the perforated tiles
Change locations of cooling units/add new cooling units
Include Return ceiling plenum - use of Chimney racks
Incorporate hot aisle/cold aisle containment systems
Managers of these facilities are turning to airflow modeling for cooling optimization
 Airflow modeling allows engineers to consider several design options in the minimum amount of time – eliminating “best-guess” approach to design.,[object Object]
Evaluate several options to determine optimum solution

Weitere ähnliche Inhalte

Was ist angesagt?

Denison university success story schneider electric
Denison university success story schneider electricDenison university success story schneider electric
Denison university success story schneider electricSchneider Electric
 
Mr. Scott Manson's presentation at QITCOM 2011
Mr. Scott Manson's presentation at QITCOM 2011Mr. Scott Manson's presentation at QITCOM 2011
Mr. Scott Manson's presentation at QITCOM 2011QITCOM
 
Improving your PUE while consolidating into an existing live data center
Improving your PUE while consolidating into an existing live data centerImproving your PUE while consolidating into an existing live data center
Improving your PUE while consolidating into an existing live data centerSchneider Electric
 
Actual Time Online Thermal Mapping Of significant Components In Data Hub
Actual Time Online Thermal Mapping Of significant Components In Data Hub Actual Time Online Thermal Mapping Of significant Components In Data Hub
Actual Time Online Thermal Mapping Of significant Components In Data Hub IRJET Journal
 
Optimized Energy Management and planning tools for the Iron and Steel Industr...
Optimized Energy Management and planning tools for the Iron and Steel Industr...Optimized Energy Management and planning tools for the Iron and Steel Industr...
Optimized Energy Management and planning tools for the Iron and Steel Industr...Schneider Electric
 
PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?SchneiderITB
 
Duhc ags and control strategy evaluation using 1 d model
Duhc ags and control strategy evaluation using 1 d modelDuhc ags and control strategy evaluation using 1 d model
Duhc ags and control strategy evaluation using 1 d modelJonathan Earley
 
Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?Schneider Electric
 
Industrial sawmill solution Wood Mizer
Industrial sawmill solution Wood MizerIndustrial sawmill solution Wood Mizer
Industrial sawmill solution Wood MizerSchneider Electric
 
Retrofit, build, or go cloud/colo? Choosing your best direction
Retrofit, build, or go cloud/colo?  Choosing your best directionRetrofit, build, or go cloud/colo?  Choosing your best direction
Retrofit, build, or go cloud/colo? Choosing your best directionSchneider Electric
 
The smart grid - Supply and demand side equivalent solutions
The smart grid - Supply and demand side equivalent solutionsThe smart grid - Supply and demand side equivalent solutions
The smart grid - Supply and demand side equivalent solutionsSchneider Electric
 
Transforming data into sustained energy performance
Transforming data into sustained energy performanceTransforming data into sustained energy performance
Transforming data into sustained energy performanceSchneider Electric
 

Was ist angesagt? (20)

B7 merlin
B7 merlinB7 merlin
B7 merlin
 
Denison university success story schneider electric
Denison university success story schneider electricDenison university success story schneider electric
Denison university success story schneider electric
 
Mr. Scott Manson's presentation at QITCOM 2011
Mr. Scott Manson's presentation at QITCOM 2011Mr. Scott Manson's presentation at QITCOM 2011
Mr. Scott Manson's presentation at QITCOM 2011
 
Engineer the Future Now!
Engineer the Future Now!Engineer the Future Now!
Engineer the Future Now!
 
Data Center Server Rack Strategies
Data Center Server Rack StrategiesData Center Server Rack Strategies
Data Center Server Rack Strategies
 
Improving your PUE while consolidating into an existing live data center
Improving your PUE while consolidating into an existing live data centerImproving your PUE while consolidating into an existing live data center
Improving your PUE while consolidating into an existing live data center
 
Actual Time Online Thermal Mapping Of significant Components In Data Hub
Actual Time Online Thermal Mapping Of significant Components In Data Hub Actual Time Online Thermal Mapping Of significant Components In Data Hub
Actual Time Online Thermal Mapping Of significant Components In Data Hub
 
Scada expert Clear Scada
Scada expert Clear ScadaScada expert Clear Scada
Scada expert Clear Scada
 
Data centers on the Edge
Data centers on the EdgeData centers on the Edge
Data centers on the Edge
 
Optimized Energy Management and planning tools for the Iron and Steel Industr...
Optimized Energy Management and planning tools for the Iron and Steel Industr...Optimized Energy Management and planning tools for the Iron and Steel Industr...
Optimized Energy Management and planning tools for the Iron and Steel Industr...
 
PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?PAC 2.5 Efficiency is Attainable, What are you Waiting for?
PAC 2.5 Efficiency is Attainable, What are you Waiting for?
 
Customer Case Study - PIK
Customer Case Study - PIKCustomer Case Study - PIK
Customer Case Study - PIK
 
Duhc ags and control strategy evaluation using 1 d model
Duhc ags and control strategy evaluation using 1 d modelDuhc ags and control strategy evaluation using 1 d model
Duhc ags and control strategy evaluation using 1 d model
 
Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?Asset Management - what are some of your top priorties?
Asset Management - what are some of your top priorties?
 
Advanced Engine Thermal Management – Key Considerations
Advanced Engine Thermal Management – Key ConsiderationsAdvanced Engine Thermal Management – Key Considerations
Advanced Engine Thermal Management – Key Considerations
 
Industrial sawmill solution Wood Mizer
Industrial sawmill solution Wood MizerIndustrial sawmill solution Wood Mizer
Industrial sawmill solution Wood Mizer
 
Retrofit, build, or go cloud/colo? Choosing your best direction
Retrofit, build, or go cloud/colo?  Choosing your best directionRetrofit, build, or go cloud/colo?  Choosing your best direction
Retrofit, build, or go cloud/colo? Choosing your best direction
 
The smart grid - Supply and demand side equivalent solutions
The smart grid - Supply and demand side equivalent solutionsThe smart grid - Supply and demand side equivalent solutions
The smart grid - Supply and demand side equivalent solutions
 
Transforming data into sustained energy performance
Transforming data into sustained energy performanceTransforming data into sustained energy performance
Transforming data into sustained energy performance
 
Green datacenters
Green datacentersGreen datacenters
Green datacenters
 

Andere mochten auch

Gimcana
GimcanaGimcana
Gimcanajoan
 
110516 application review report 상훈
110516 application review report 상훈110516 application review report 상훈
110516 application review report 상훈Sanghoon Kim
 
Obrazky lesley harrison
Obrazky lesley harrisonObrazky lesley harrison
Obrazky lesley harrisonVesdo 1
 
Krkonose
KrkonoseKrkonose
KrkonoseVesdo 1
 
Rohani abd. hamid_-_persepsi_guru_yang_berkualiti-_satu_tinjauan_di_daerah_ku...
Rohani abd. hamid_-_persepsi_guru_yang_berkualiti-_satu_tinjauan_di_daerah_ku...Rohani abd. hamid_-_persepsi_guru_yang_berkualiti-_satu_tinjauan_di_daerah_ku...
Rohani abd. hamid_-_persepsi_guru_yang_berkualiti-_satu_tinjauan_di_daerah_ku...Mior Shah
 
Presentatie Social Media Monitoring Klantendag Holiday Media
Presentatie Social Media Monitoring Klantendag Holiday MediaPresentatie Social Media Monitoring Klantendag Holiday Media
Presentatie Social Media Monitoring Klantendag Holiday Mediarogiervandenberg
 
Kevin Fahy Bi Portfolio
Kevin Fahy   Bi PortfolioKevin Fahy   Bi Portfolio
Kevin Fahy Bi PortfolioKevinPFahy
 
20140211 仙台市社会福祉協議会ボランティアフォーラム
20140211 仙台市社会福祉協議会ボランティアフォーラム20140211 仙台市社会福祉協議会ボランティアフォーラム
20140211 仙台市社会福祉協議会ボランティアフォーラムNPO法人アスイク
 
Classic photo album
Classic photo albumClassic photo album
Classic photo albumCTDMDC
 
La nit del terror. Euclides
La nit del terror. Euclides La nit del terror. Euclides
La nit del terror. Euclides joan
 
Hsbc correcion
Hsbc correcionHsbc correcion
Hsbc correcionipad4ever
 
Air Activities
Air ActivitiesAir Activities
Air Activitieszervoum
 

Andere mochten auch (20)

Gimcana
GimcanaGimcana
Gimcana
 
110516 application review report 상훈
110516 application review report 상훈110516 application review report 상훈
110516 application review report 상훈
 
Obrazky lesley harrison
Obrazky lesley harrisonObrazky lesley harrison
Obrazky lesley harrison
 
Krkonose
KrkonoseKrkonose
Krkonose
 
Rohani abd. hamid_-_persepsi_guru_yang_berkualiti-_satu_tinjauan_di_daerah_ku...
Rohani abd. hamid_-_persepsi_guru_yang_berkualiti-_satu_tinjauan_di_daerah_ku...Rohani abd. hamid_-_persepsi_guru_yang_berkualiti-_satu_tinjauan_di_daerah_ku...
Rohani abd. hamid_-_persepsi_guru_yang_berkualiti-_satu_tinjauan_di_daerah_ku...
 
Hurricane katrina
Hurricane katrinaHurricane katrina
Hurricane katrina
 
Presentatie Social Media Monitoring Klantendag Holiday Media
Presentatie Social Media Monitoring Klantendag Holiday MediaPresentatie Social Media Monitoring Klantendag Holiday Media
Presentatie Social Media Monitoring Klantendag Holiday Media
 
Kevin Fahy Bi Portfolio
Kevin Fahy   Bi PortfolioKevin Fahy   Bi Portfolio
Kevin Fahy Bi Portfolio
 
20140211 仙台市社会福祉協議会ボランティアフォーラム
20140211 仙台市社会福祉協議会ボランティアフォーラム20140211 仙台市社会福祉協議会ボランティアフォーラム
20140211 仙台市社会福祉協議会ボランティアフォーラム
 
FM June2012 Paper
FM June2012 PaperFM June2012 Paper
FM June2012 Paper
 
Classic photo album
Classic photo albumClassic photo album
Classic photo album
 
Revised checklist for Schedule VI
Revised checklist for Schedule VIRevised checklist for Schedule VI
Revised checklist for Schedule VI
 
La nit del terror. Euclides
La nit del terror. Euclides La nit del terror. Euclides
La nit del terror. Euclides
 
Syllabus for SFM - CA Final
Syllabus for SFM - CA FinalSyllabus for SFM - CA Final
Syllabus for SFM - CA Final
 
XBRL Workshop in Mumbai
XBRL Workshop in MumbaiXBRL Workshop in Mumbai
XBRL Workshop in Mumbai
 
Hsbc correcion
Hsbc correcionHsbc correcion
Hsbc correcion
 
Air Activities
Air ActivitiesAir Activities
Air Activities
 
New 2011 CPA Exam Guide
New  2011 CPA Exam GuideNew  2011 CPA Exam Guide
New 2011 CPA Exam Guide
 
The 80s Rock!!!
The 80s Rock!!!The 80s Rock!!!
The 80s Rock!!!
 
International Exam FAQ on USA CPA
International Exam FAQ on USA CPAInternational Exam FAQ on USA CPA
International Exam FAQ on USA CPA
 

Ähnlich wie Optimize power and cooling final

CoolSim Overview
CoolSim OverviewCoolSim Overview
CoolSim Overviewpaulbemis
 
Green IT @ STRATO - Rene Weinholtz
Green IT @ STRATO - Rene WeinholtzGreen IT @ STRATO - Rene Weinholtz
Green IT @ STRATO - Rene Weinholtzcatherinewall
 
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...IBMAsean
 
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...SimScale
 
E source energy managers conf 4 24-13-final
E source energy managers conf 4 24-13-finalE source energy managers conf 4 24-13-final
E source energy managers conf 4 24-13-finaljosh whitney
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingGraybar
 
Cooling a Data Center - DP Air
Cooling a Data Center - DP Air Cooling a Data Center - DP Air
Cooling a Data Center - DP Air dpsir
 
Datacenter Design - DP Air
Datacenter Design - DP AirDatacenter Design - DP Air
Datacenter Design - DP Airdpsir
 
TED LIVE - LEAN ENERGY MANAGEMENT
TED LIVE - LEAN ENERGY MANAGEMENTTED LIVE - LEAN ENERGY MANAGEMENT
TED LIVE - LEAN ENERGY MANAGEMENTDanny Scott
 
The Cloud & Its Impact on IT
The Cloud & Its Impact on ITThe Cloud & Its Impact on IT
The Cloud & Its Impact on ITAnand Haridass
 
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center OperationASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center OperationRobert Schmidt
 
Green it initiatives
Green it initiativesGreen it initiatives
Green it initiativesAparna Bulusu
 

Ähnlich wie Optimize power and cooling final (20)

Data center m&e
Data center  m&eData center  m&e
Data center m&e
 
CoolSim Overview
CoolSim OverviewCoolSim Overview
CoolSim Overview
 
Virtualización para la Eficiencia
Virtualización para la EficienciaVirtualización para la Eficiencia
Virtualización para la Eficiencia
 
Green IT @ STRATO - Rene Weinholtz
Green IT @ STRATO - Rene WeinholtzGreen IT @ STRATO - Rene Weinholtz
Green IT @ STRATO - Rene Weinholtz
 
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
Green & Beyond: Data Center Actions to Increase Business Responsiveness and R...
 
Ashrae thermal guidelines svlg 2015 (1)
Ashrae thermal guidelines  svlg 2015 (1)Ashrae thermal guidelines  svlg 2015 (1)
Ashrae thermal guidelines svlg 2015 (1)
 
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
 
E source energy managers conf 4 24-13-final
E source energy managers conf 4 24-13-finalE source energy managers conf 4 24-13-final
E source energy managers conf 4 24-13-final
 
Slides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for CoolingSlides: The Top 3 North America Data Center Trends for Cooling
Slides: The Top 3 North America Data Center Trends for Cooling
 
project report on DATACENTER
project report on DATACENTERproject report on DATACENTER
project report on DATACENTER
 
Tcc cooling
Tcc coolingTcc cooling
Tcc cooling
 
Cooling a Data Center - DP Air
Cooling a Data Center - DP Air Cooling a Data Center - DP Air
Cooling a Data Center - DP Air
 
Datacenter Design - DP Air
Datacenter Design - DP AirDatacenter Design - DP Air
Datacenter Design - DP Air
 
TED LIVE - LEAN ENERGY MANAGEMENT
TED LIVE - LEAN ENERGY MANAGEMENTTED LIVE - LEAN ENERGY MANAGEMENT
TED LIVE - LEAN ENERGY MANAGEMENT
 
The Cloud & Its Impact on IT
The Cloud & Its Impact on ITThe Cloud & Its Impact on IT
The Cloud & Its Impact on IT
 
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center OperationASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
 
Data Centers
Data CentersData Centers
Data Centers
 
Executive DCIM
Executive DCIMExecutive DCIM
Executive DCIM
 
Emerson Energy Logic
Emerson Energy LogicEmerson Energy Logic
Emerson Energy Logic
 
Green it initiatives
Green it initiativesGreen it initiatives
Green it initiatives
 

Mehr von Viridity Software

Data Center Infrastructure Trends
Data Center Infrastructure TrendsData Center Infrastructure Trends
Data Center Infrastructure TrendsViridity Software
 
Viridity software dcw presentation 3-1
Viridity software dcw presentation 3-1Viridity software dcw presentation 3-1
Viridity software dcw presentation 3-1Viridity Software
 
Better Data Center Infrastructure Management
Better Data Center Infrastructure ManagementBetter Data Center Infrastructure Management
Better Data Center Infrastructure ManagementViridity Software
 
Planning a Tech Refresh with the Right Information
Planning a Tech Refresh with the Right InformationPlanning a Tech Refresh with the Right Information
Planning a Tech Refresh with the Right InformationViridity Software
 
Best Practices in Data Center Energy Resource Management
Best Practices in Data Center Energy Resource ManagementBest Practices in Data Center Energy Resource Management
Best Practices in Data Center Energy Resource ManagementViridity Software
 
The Road to Data Center Energy Efficiency
The Road to Data Center Energy EfficiencyThe Road to Data Center Energy Efficiency
The Road to Data Center Energy EfficiencyViridity Software
 
Top Ten Reasons to Use Energy Resource Management Software
Top Ten Reasons to Use Energy Resource Management SoftwareTop Ten Reasons to Use Energy Resource Management Software
Top Ten Reasons to Use Energy Resource Management SoftwareViridity Software
 

Mehr von Viridity Software (8)

Data Center Infrastructure Trends
Data Center Infrastructure TrendsData Center Infrastructure Trends
Data Center Infrastructure Trends
 
Viridity software dcw presentation 3-1
Viridity software dcw presentation 3-1Viridity software dcw presentation 3-1
Viridity software dcw presentation 3-1
 
Better Data Center Infrastructure Management
Better Data Center Infrastructure ManagementBetter Data Center Infrastructure Management
Better Data Center Infrastructure Management
 
Planning a Tech Refresh with the Right Information
Planning a Tech Refresh with the Right InformationPlanning a Tech Refresh with the Right Information
Planning a Tech Refresh with the Right Information
 
EnergyCheck Installation
EnergyCheck InstallationEnergyCheck Installation
EnergyCheck Installation
 
Best Practices in Data Center Energy Resource Management
Best Practices in Data Center Energy Resource ManagementBest Practices in Data Center Energy Resource Management
Best Practices in Data Center Energy Resource Management
 
The Road to Data Center Energy Efficiency
The Road to Data Center Energy EfficiencyThe Road to Data Center Energy Efficiency
The Road to Data Center Energy Efficiency
 
Top Ten Reasons to Use Energy Resource Management Software
Top Ten Reasons to Use Energy Resource Management SoftwareTop Ten Reasons to Use Energy Resource Management Software
Top Ten Reasons to Use Energy Resource Management Software
 

Optimize power and cooling final

  • 1. Copyright © 2011 Viridity Software, Inc. All Rights Reserved Optimize Power and Cooling in the Data Center Presented by: Amir Radmehr, Director, Innovative Research (TileFlow Software), andMike Rowan, co-Founder and CTO, Viridity Software
  • 2. The Leader in Data Center Infrastructure Management Software Energy Center connects equipment utilization and business value to power consumption Time-to-value in hours, not months Deploys in minutes, not weeks No additional hardware required No server agents required Copyright © 2011 Viridity Software, Inc. All Rights Reserved 2
  • 3. A Tool for Simulating Cooling Performance of Data Centers The first CFD tool dedicated to data centers Extensively validated against measurements Highly satisfied user base Has become the industry standard Actively enhanced every year Copyright © 2011 Viridity Software, Inc. All Rights Reserved 3
  • 4.
  • 5. Building energy codes are causing companies to re-think DC thermal management:
  • 6. (Standard 90.1) requires efficient cooling ; systems must use airside economizers; includes all commercial buildings DCs
  • 7. Save Energy Now aims to reduce energy use in U.S. data centers 10% by 2011
  • 8. Compliance with various standards such as ASHRAE TC9.9 and LEED75% of medium-to-large enterprises are implementing “high density” computing platforms. - this number will approach 100% by 2010 . – IDC
  • 9.
  • 10. Pressure to optimize cooling schemas, equipment layout, and HVAC deployment
  • 11. Effective ventilation and cooling is critical to ensure uninterrupted operation
  • 12. The environmental conditions are controlled by numerous factors, these include:
  • 13. Layout and open area of perforated tiles
  • 14. Location and characteristics of the cooling units
  • 15. Layout and heat loads of server racks
  • 17.
  • 18. Modify layout and/or open area of the perforated tiles
  • 19. Change locations of cooling units/add new cooling units
  • 20. Include Return ceiling plenum - use of Chimney racks
  • 21. Incorporate hot aisle/cold aisle containment systems
  • 22. Managers of these facilities are turning to airflow modeling for cooling optimization
  • 23.
  • 24. Evaluate several options to determine optimum solution
  • 25. Reduce capital expense and running cost
  • 26. Save time on commissioning
  • 27.
  • 28.
  • 29. Robust models and algorithms
  • 33.
  • 34. Animations of air movement and temperature traverses
  • 35. Temperature fog to visualize hot spots
  • 36. Flashing lights for overheated racks
  • 38.
  • 40. Understand the operation of cooling devices
  • 42. Get guidance for expansion
  • 44.
  • 45.
  • 46.
  • 47.
  • 48.
  • 49. Server utilization views may be used to show trending of server utilization, power, and cost.16 Copyright © 2011 Viridity Software, Inc. All Rights Reserved Server Utilization view
  • 50.
  • 51. View may be filtered by asset owner, contact, or at application level
  • 52. Reports yearly power cost based on avg CPU utilization
  • 53. Assets can be considered for virtualization, consolidation, or elimination 17 Copyright © 2011 Viridity Software, Inc. All Rights Reserved
  • 54.
  • 55. 2-D visualization of the datacenter highlights racks with underutilized assets.
  • 56. Select a rack in the 2-D view to see the details in the right-side inspector window. Underutilized servers are highlighted in “blue”.18 Copyright © 2011 Viridity Software, Inc. All Rights Reserved
  • 57.
  • 58. EnergyCenter leverages its unique power profile database to graph the worst case power utilization value (in green).
  • 59. Remaining power capacity is the difference between the blue and green lines
  • 60. Change the view to “Average Power” to get a per-asset view of the power utilization in the rack.
  • 61. Move the cursor over specific slices to view average utilization and yearly cost info. 19 Copyright © 2011 Viridity Software, Inc. All Rights Reserved
  • 62.
  • 63.
  • 64. In the current layout, many servers inlet temperatures were measured above 90 degrees (with some over 100 degrees). Viridity’s on-site visual inspection of the datacenter confirmed these temperature calculations.ASHREA recommends for inlet temperatures for servers in category 1 datacenters remain below 98 degrees. 21 Copyright © 2011 Viridity Software, Inc. All Rights Reserved CFD Simulation – Rack Inlet Temperatures Using CFD tools like TileFlow with actual consumption information allow you to better predict air flow Using PDU based even distribution of power and consequential heal do not uncover as many potential areas of concern
  • 65. Copyright © 2010 Viridity Software, Inc. All Rights Reserved EnergyCenter “The only Data Center Energy Management solution that provides detailed understanding of power consumption within hours of beginning deployment” -- Andy Lawrence – The 451 Group 22
  • 66. Copyright © 2010 Viridity Software, Inc. All Rights Reserved Q & A
  • 67. Register for a Live DemoDiscover the full power of the EnergyCenter EnergyCenter Free TrialRun EnergyCenter in your data center!Download EnergyCheck Free energy health-check in your data center! Copyright © 2010 Viridity Software, Inc. All Rights Reserved 24 VIRIDITY.COM

Hinweis der Redaktion

  1. Who are we? Viridity Software is the leader in Data Center Infrastructure Management Software. Our software connects equipment utilization and business value to power consumption in the data center.Customers are finding time to value in hours, not months.And, because we are a software solution, there is no additional hardware or agents required.
  2. Who are we? Viridity Software is the leader in Data Center Infrastructure Management Software. Our software connects equipment utilization and business value to power consumption in the data center.Customers are finding time to value in hours, not months.And, because we are a software solution, there is no additional hardware or agents required.
  3. Key Points:EnergyCenter is Viridity’s Core PlatformIt provides end-to-end capabilities to understand actual power consumption and utilization at the IT asset levelIt further provides actionable reporting literally within a few hours of beginning deploymentPrevious Notes:Frictionless DeploymentDeploys in minutesNo hardware sensorsImmediate ResultsActionable reports within hours of first DiscoveryInsights across IT and Facilities infrastructureDirect ROI