SlideShare a Scribd company logo
1 of 7
Download to read offline
Technical Application Papers




                                                        6 Protection against overcurrents and overvoltages
                                                        When defining the layout of a photovoltaic plant it is                                      The short-circuit current Isc3 = y . 1.25 . Isc coincides with the
                                                        necessary to provide, where needed, for the protection                                      service current of the circuit between the subfield switch-
6 Protection against overcurrents and overvoltages




                                                        of the different sections of the plant against overcurrents                                 board and inverter, whereas the current Isc4 = (x-y) . 1.25 . Isc
                                                        and overvoltages of atmospheric origin.                                                     is higher than the service current if x-y > y ⇒ x > 2y.
                                                        Here are given, firstly, the conditions for the protection                                  In this case it is necessary to protect the cable against
                                                        against overcurrents in the PV plant on the supply (DC                                      short-circuit if its current carrying capacity is lower than
                                                        side) and on the load side of the inverter (AC side), then                                  Isc4, that is Iz<(x-y).1.25.Isc.
                                                        the methods for the protection of the plant against any
                                                                                                                                                    Figure 6.1
                                                        damage caused by possible direct or indirect fulmina-
                                                                                                                                                    “A” 	represents the protective device in the subfield switchboard for the pro-
                                                        tion1.                                                                                           tection of the “cable 1” connecting the string to the switchboard itself.
                                                                                                                                                    “B” 	represents the protection device installed in the inverter switchboard
                                                                                                                                                         to protect the “cable 2” for the connection between the inverter and
                                                                                                                                                         the subfield switchboard.
                                                                                                                                                    “y” 	number of strings connected to the same subfield switchboard.
                                                        6.1 Protection against overcurrents on DC side                                              “x” 	total number of strings connected to the same inverter.



                                                        6.1.1	 Cable protections                                                                             String
                                                                                                                                                                        +    Cable 1
                                                                                                                                                                                       Subfield
                                                                                                                                                                        –              switchboard
                                                        From the point of view of the protection against over-                                                                            A
                                                        loads, it is not necessary to protect the cables (CEI 64-
                                                        8/7) if they are chosen with a current carrying capacity
                                                        not lower than the maximum current which might affect                                                                                        Cable 2
                                                                                                                                                                                              +
                                                        them (1.25 Isc)2.                                                                               y
                                                                                                                                                                                              –

                                                        As regards the short-circuit, the cables on the DC side                                                                                              Isc3
                                                        are affected by such overcurrent in case of:                                                                   Fault 1
                                                        •	 fault between the polarity of the PV system;                                                                                                        Fault 2
                                                        •	 fault to earth in the earthed systems;
                                                                                                                                                                      Isc1   Isc2
                                                        •	 double fault to earth in the earth-insulated systems.

                                                                                                                                                                                                      Isc4
                                                        A short-circuit on a cable for the connection string to                                                                        Subfield
                                                        subfield switchboard (fault 1 of Figure 6.1) is supplied                                                                       switchboard

                                                        simultaneously upstream of the load side by the string
                                                        under consideration (Isc1 = 1.25 . Isc) and downstream by                                                                                                            parallel point
                                                                                                                                                                                                                             with the grid
                                                        the other x-1 strings connected to the same inverter (Isc2                                                                                     –
                                                                                                                                                                                                             B
                                                                                                                                                                                              +                          +
                                                        = (x-1) . 1.25 . Isc).
                                                                                                                                                    x                                         –                +         –
                                                        If the PV plant is small-sized with two strings only (x=2),
                                                        it results that Isc2 = 1.25 . Isc = Isc1 and therefore it is not                                                                                     Inverter
                                                                                                                                                                                                             switchboard
                                                        necessary to protect the string cables against short-
                                                        circuit.
                                                        On the contrary, when three or more strings (x≥3) are
                                                        connected to the inverter, the current Isc2 is higher than
                                                        the service current and therefore the cables must be pro-
                                                        tected against the short-circuit when their current carrying
                                                        capacity is lower than Isc2, that is Iz< (x-1) . 1.25 . Isc .
                                                        A short-circuit between a subfield switchboard and the
                                                        inverter switchboard (fault 2 of the Figure 6.1) is supplied
                                                        upstream by the y strings in parallel of the subfield (Isc3)
                                                        and downstream by the remaining (x-y) strings relevant                                                                                +
                                                        to the same inverter switchboard.                                                                                                     –



                                                        1
                                                         As regards the power factor correction of a user plant in the presence of a PV plant see
                                                        Annex E of the QT8 “Power factor correction and harmonic filtering in electrical plants”.

                                                        2
                                                           Isc is the short-circuit current in the module under standard test conditions and the
                                                        twenty-five per cent rise takes the insolation values exceeding 1kW/m2 (see Chapter 3)
                                                        into account.



                                                     42 Photovoltaic plants
6.1.2	 Protection of the strings against reverse                                            a drop of the direct voltage, the inverter certainly shuts
       current                                                                              down and probably is disconnected from the grid. Nor-




                                                                                                                                                                                             6 Protection against overcurrents and overvoltages
                                                                                            mally the shut down times of the inverter are of the order
Due to shading or fault a string becomes passive, absorbing                                 of some milliseconds, while the disconnection times may
and dissipating the electric power generated by the other                                   be of the order of some dozens of milliseconds. In the
strings connected in parallel to the same inverter through                                  interval between the shut down and the disconnection,
a current which flows through the string under considera-                                   the grid might cause the above mentioned effect, while
tion in a reverse direction with respect to that of standard                                the internal capacitors, if involved, participate up to their
operation, with possible damages to the modules.                                            complete discharge.
These are able to withstand a reverse current ranging                                       The effects on the short-circuit of both the grid as well
from 2.5 and 3 Isc (IEC TS 62257-7-1). Since with x strings                                 as of the internal capacitors are just of transitory nature
                                                                                            and usually are not such as to affect the dimensioning
in parallel connected to the same inverter the highest
                                                                                            of the protective, switching and disconnection devices
reverse current is equal to Iinv = (x-1) . 1.25 . Isc, it is not
                                                                                            positioned on the d.c side. However, it is necessary to
necessary to protect the strings if Iinv ≤ 2.5 . Isc that is                                consider case-by-case the advisability of such choice:
(x-1) . 1.25 ≤ 2.5 ⇒ x ≤ 33.                                                                in particular, a very high discharge current of the capaci-
                                                                                            tors, combined with long time constants, might force to
                                                                                            increase the current breaking capacity of the circuit-
6.1.3	 Behaviour of the inverter                                                            breakers.


The contribution to the short-circuit on the DC side of the
inverter may come from the grid and from the discharge
                                                                                            6.1.4 Choice of the protective devices
of the capacitors inside the inverter.                                                      As regards the protection against the short-circuits on the
The grid current is due to the recirculating diodes of the                                  DC side, the devices shall be obviously suitable for DC
bridge inverter which in this case act as a bridge recti-                                   use and have a rated service voltage Ue equal or higher
fier. Such current is limited by the impedances of the                                      than the maximum voltage of the PV generator which is
transformer and of the inductors belonging to the output                                    equal to 1.2 Uoc4 (IEC TS 62257-7-1).
circuit and by the protection fuses of the inverter on the
AC side chosen so that they can limit the thermal effects                                   Moreover the protection devices shall be positioned at
of possible internal faults on the semiconductors. As a                                     the end of the circuit to be protected, proceeding from
consequence the I2t passing through will be normally                                        the strings towards the inverter, that is in the various
reduced. Indicatively a final current value (internal ca-                                   subfield switchboards and inverter switchboards since
pacitors completely discharged) of 10In can be an upper                                     the short-circuit currents come from the other strings,
limit value. This current is present in case of inverter with                               that is from the load side and not from the supply side
galvanic insulation at 50Hz, while it is null in case of in-                                (IEC TS 62257-7-1).
verter without transformer. In fact these inverters usually
have an input DC/DC converter so that the operation on
                                                                                            In order to avoid unwanted tripping under standard opera-
a wide voltage range of the PV generator is guaranteed;
                                                                                            tion conditions, the protective devices positioned in the
this converter, due to its constructive typology, includes at
least one blocking diode which prevents the contribution                                    subfield switchboards (device A in the Figure 6.1) shall
of the grid current to the short-circuit.                                                   have a rated current In5:
The discharge current of the capacitors is limited by the
                                                                                                                     In ≥ 1.25 . Isc                [6.1]
cables between inverter and fault and exhausts itself with
exponential trend: the lowest the impedance of the cable                                    These devices shall protect:
stretch, the highest the initial current, but the lowest the                                •	 every single string against the reverse current;
time constant of the discharge. The energy which flows                                      •	 the connection cable6 string to subswitchboard (cable
is limited to that one initially stored in the capacitors.                                     1 of Figure 6.1) if the latter has a current carrying ca-
Moreover, if a blocking diode or other similar device is in                                    pacity lower than the maximum short-circuit current of
series with one of the two poles, this contribution to the                                     the other x-1 strings connected to the same inverter
short-circuit is null.                                                                         switchboard7, i.e. if:
In each case, the short-circuit on the DC side causes                                                       I < I = (x - 1) . 1.25 . I              [6.2]
                                                                                                                        z     sc2                                sc

3
  The blocking diodes can be used, but they do not replace the protections against          4
                                                                                                Uoc is the no load voltage coming out of the strings (see Chapter 3).
overcurrent (IEC TS 62257-7-1), since it is taken into consideration the possibility that
the blocking diode does not work properly and is short-circuited. Moreover the diodes       5
                                                                                             For thermomagnetic circuit-breakers the [6.1] becomes Ioverload ≥ 1.25 . Isc, while for mag-
introduce a loss of power due to the voltage drop on the junction, a loss which can be      netic only circuit-breakers Iu ≥ 1.25 . Isc so that their overheating can be avoided.
reduced by using Schottky diodes with 0.4V drop instead of 0.7V of conventional diodes.
However the rated reverse voltage of the diodes shall be ≥ 2 Uoc and the rated current ≥    6
                                                                                                Protection against short-circuit only because Iz ≥ 1.25 . Isc.
1.25 Isc (CEI Guide 82-25).
                                                                                            7
                                                                                             The short-circuit Isc1 = 1.25 . Isc (fig. 6.1) (Figure 6.1) is unimportant because the string
                                                                                            cable has a current carrying capacity not lower than 1.25 . Isc.


                                                                                                                                                        Photovoltaic plants 43
Technical Application Papers




                                                        To the purpose of protection for the string, the rated                                             6.2	 Protection against overcurrents on AC side
                                                        current of the protective device (either thermomagnetic
6 Protection against overcurrents and overvoltages




                                                        circuit-breaker or fuse) must not exceed that one declared                                         Since the cable connecting the inverter to the point of
                                                        by the manufacturer for the panel protection (clause                                               connection with the grid is usually dimensioned to obtain
                                                        6.1.2); if no indications are given by the manufacturer,                                           a current carrying capacity higher than the maximum cur-
                                                        the following is assumed (IEC TS 62257-7-1):                                                       rent which the inverter can deliver, a protection against
                                                                                                                                                           overload is not needed. However the cable must be
                                                                                      1.25 . Isc ≤ In ≤ 2 . Isc                                  [6.3]
                                                                                                                                                           protected against a short circuit supplied by the grid10
                                                        In spite of the simplicity of use of fuses, when sizing and                                        through a protective device positioned near the point of
                                                        choosing these devices it is necessary to take into account
                                                                                                                                                           parallel with the grid.
                                                        that they not only must have a rated current obtained by
                                                        the relationship [6.3], but that they must have a trip char-                                       To protect such cable the main circuit-breaker of the con-
                                                        acteristic type gR (i.e. suitable for the protection of circuits                                   sumer plant can be used if the specific let-through energy
                                                        by means of semiconductors), they must be mounted                                                  is withstood by the cable. However, the trip of the main
                                                        on fuse holders and they must be able to dissipate the                                             circuit-breaker put all the consumer plant out of service.
                                                        power generated under the worst operating conditions.
                                                                                                                                                           In the multi-inverter plants (Figure 6.2), the presence of
                                                        To the purpose of protection for the connection ca-
                                                        ble, the protective device must be chosen so that the                                              one protection for each line allows, in case of fault on
                                                        following relation is satisfied for each value of short-                                           an inverter, the functioning of the other ones, provided
                                                        circuit (IEC 60364)8 up to a maximum of (x-1) . 1.25 . Isc:                                        that the circuit-breakers on each line are selective with
                                                                                                                                                           the main circuit-breaker.
                                                                                             (I2t) ≤ K2 S2                                       [6.4]
                                                        where:                                                                                             Figure 6.2
                                                        (I2t) is the Joule integral referred to the short-circuit dura-
                                                        tion (in A2s);
                                                        K is a characteristic constant of the cable depending on
                                                        the type of conductor and on the insulating material;
                                                        S is the cross-sectional area of the cable (in mm2).

                                                        The breaking capacity of the device must not be lower
                                                        than the short-circuit current of the other n-1 strings,                                                                                                                      Point of
                                                                                                                                                                                                                                      parallel with
                                                        that is:                                                                                                                                                                      the grid

                                                                                      Icu ≥ (x-1) . 1.25 . Isc                                   [6.5]


                                                        The devices in the inverter switchboard must protect
                                                        against the short-circuit the connection cables subfield
                                                        switchboard-inverter switchboard when these cables have
                                                        a current carrying capacity lower than Isc4 = (x-y) . 1.25 . Isc9
                                                        (Figure 6.1). In this case these devices shall satisfy the
                                                        relations [6.1] and [6.4], while their current carrying ca-
                                                        pacity shall not be lower than the short-circuit current of
                                                        the other n-m strings, that is:
                                                                                                                                                           6.3	 Choice of the switching and disconnecting
                                                                                      Icu ≥ (x-y) . 1.25 . Isc                                   [6.6]          devices

                                                        In short, the cable for the connection inverter switchboard                                        The installation of a disconnecting device on each string
                                                        to inverter must not be protected if its current carrying                                          is advisable in order to allow verification or maintenance
                                                        capacity is chosen at least equal to (CEI 64-8/7):                                                 interventions on the string without putting out of service
                                                                                          Iz ≥ x . 1.25 . Isc                                    [6.7]     other parts of the PV plant (CEI Guide 82-25 II ed.)11.


                                                        8
                                                          For the magnetic only circuit-breaker it is necessary, if possible, to set the protection        10
                                                                                                                                                              The inverter generally limits the output current to a value which is the double of its
                                                        function at a value equal to the value Iz of the cable in order to determine the tripping of the   rated current and goes in stand-by in few tenths of seconds due to the trip of the internal
                                                        device when the short circuit current exceeds the current carrying capacity of the protected       protection. As a consequence, the contribution of the inverter to the short-circuit current
                                                        cable. Besides, it is possible to use a magnetic only circuit-breaker if the number of strings     is negligible in comparison with the contribution of the grid.
                                                        connected to the same inverter is maximum 3; otherwise for the protection of the string it
                                                        is necessary to use a thermomagnetic circuit-breaker chosen according to [6.3].                    11
                                                                                                                                                              When an automatic circuit-breaker is used the switching and disconnecting function
                                                                                                                                                           is already included.
                                                        9
                                                         The short-circuit current Isc3 = y . 1.25 . Isc (Figure 6.1) is unimportant since the string
                                                        cable has a current carrying capacity not lower than y . 1.25 . Isc.


                                                     44 Photovoltaic plants
The disconnection of the inverter must be possible both                                     Figure 6.3
on the DC side as well as on the AC side so that main-




                                                                                                                                                                                          6 Protection against overcurrents and overvoltages
tenance is allowed by excluding both the supply sources
(grid and PV generator) (CEI 64-8/7).
On the DC side of the inverter a disconnecting device
shall be installed which can be switched under load,
such as a switch-disconnector. On the AC side a general
disconnecting device shall be provided. The protective
device installed at the point of connection with the grid
can be used; if this device is not close to the inverter, it is
advisable to position a disconnecting device immediately
on the load side of the inverter.


6.4	 Protection against overvoltages

The PV installations, since they usually are outside the                                    On the contrary, in case the PV installation changes
buildings, may be subject to overvoltages of atmospheric                                    significantly the outline of the building, it is necessary
origin, both direct (lightning striking the structure) as well                              to reconsider the frequency of fulminations on it and
as indirect (lightning falling near to the structure of the                                 consequently to take into consideration the necessity of
building or affecting the energy or signaling lines entering                                realizing an LPS (CEI Guide 82-25 II ed.) (Figure 6.4).
the structure) through resistive or inductive coupling.
The resistive coupling occurs when lightning strikes the
                                                                                            Figure 6.4
electrical line entering the building. The lightning cur-
rent, through the characteristic impedance of the line,
originates an overvoltage which may exceed the impulse
withstand voltage of the equipment, with consequent
damaging and fire hazard.
The inductive coupling occurs because the lightning
current is impulsive and therefore it generates in the sur-
rounding space an electromagnetic field highly variable.
As a consequence, the variation in the magnetic field
generates some overvoltages induced on the electric
circuits nearby.
In addition to the overvoltages of atmospheric origin,
the PV plant may be exposed to internal switching ov-
ervoltages.

6.4.1 Direct lightning
6.4.1.1	Building without LPS12
Generally, the erection of a PV plant does not change                                       6.4.1.2	Building with LPS
the outline of a building and therefore the frequency of                                    In case of presence of a protection system against at-
the fulminations; therefore no specific measures against                                    mospheric discharges13, if the PV plant does not alter
the risk of fulmination are necessary (CEI Guide 82-25,                                     the outline of the building and if the minimum distance d
II ed.) (Figure 6.3).                                                                       between the PV plant and the LPS plant is higher than the
                                                                                            safety distance s (EN 62305-3) other additional measures

12
  Lightning Protection System: it is constituted by the protective systems both external    13
                                                                                               It is advisable that the protection grounding plant is connected to that for the protec-
(detectors, lightning conductors and ground electrodes) as well as internal (protective     tion against lightning.
measures in order to reduce the electromagnetic effects of the lightning current entering
the structure to be protected).




                                                                                                                                                    Photovoltaic plants 45
Technical Application Papers




                                                        for the protection of the new plant (CEI Guide 82-25 II       Finally, if the PV plant alters the outline of the building a
                                                        ed.) are not required (Figure 6.5).                           new risk evaluation and/or a modification of the LPS are
6 Protection against overcurrents and overvoltages




                                                        Figure 6.5                                                    necessary (CEI Guide 82-25, II ed.) (Figure 6.7).
                                                                                                                      Figure 6.7




                                                                                                                      6.4.1.3	PV plant on the ground
                                                                                                                      If a PV plant is erected on the ground there is no fire risk
                                                                                                                      due to direct fulmination and the only hazard for human
                                                                                                                      beings is represented by the step and touch voltages.
                                                        On the contrary, if the PV plant does not alter the outline   When the surface resistivity exceeds 5 kΩm (e.g. rocky
                                                        of the building, but the minimum distance d is lower than     asphalted ground, at least 5 cm thickness or laid with
                                                        the distance s it is appropriate to extend the LPS plant      gravel for minimum 15 cm), it is not necessary to take
                                                        and connect it to the metal structures of the PV installa-    any particular measure since the touch and step voltage
                                                        tion (CEI Guide 82-25, II ed.) (Figure 6.6).                  values are negligible (CEI 81-10). Instead, if the ground
                                                                                                                      resistivity were equal to or lower than 5 kΩm, it would
                                                        Figure 6.6                                                    be necessary to verify theoretically whether some pro-
                                                                                                                      tective measures against the step and touch voltages
                                                                                                                      are necessary; however, in this case, the probability of
                                                                                                                      lightning strikes is very small and therefore the problem
                                                                                                                      occurs only with very large plants.


                                                                                                                      6.4.2 Indirect lightning
                                                                                                                      Also in case lightning does not strike directly the structure
                                                                                                                      of the PV plant, it is necessary to take some measures to
                                                                                                                      minimize the overvoltages caused by any likely indirect
                                                                                                                      strike of lightning:
                                                                                                                      •	 shielding of the circuits in order to reduce the magnetic
                                                                                                                         field inside the enclosure with a consequent reduction
                                                                                                                         of the induced overvoltages14;
                                                                                                                      •	 reduction of the area of the turn of the induced circuit
                                                                                                                         obtained by connecting suitably the modules one to the
                                                                                                                         other (Figure 6.8), by twisting the conductors together
                                                                                                                         and bringing the live conductor as much as possible
                                                                                                                         near to the PE.

                                                                                                                      14
                                                                                                                        The shielding effect of a metal enclosure originates thanks to the currents induced in
                                                                                                                      the enclosure itself; they create a magnetic field which by Lenz’s law opposes the cause
                                                                                                                      generating them, that is the magnetic field of the lightning current; the higher the currents
                                                                                                                      induced in the shield (i.e. the higher its conductance), the better the shielding effect.




                                                     46 Photovoltaic plants
Figure 6.8

                                                              6.4.2.1	Protection on DC side




                                                                                                                                                           6 Protection against overcurrents and overvoltages
                                                              For the protection on the DC side it is advisable to use
                                                              varistors SPDs or combined SPDs.
                                                              Inverters usually have an internal protection against
                                                              overvoltages, but if SPDs are added to the inverter ter-
                                                              minals, its protection is improved and at the same time
                                                              it is possible to avoid that the tripping of the internal
                                                              protections put out of service the inverter, thus causing
                                                              suspension of energy production and making necessary
                                                              the intervention of skilled personnel.
                                                              These SPDs should have the following characteristics:
                                                              •	 Type 2
                                                              •	 Maximum rated service voltage Ue > 1.25 Uoc
                                                              •	 Protection level Up ≤ Uinv15
                                                              •	 Nominal discharge current In ≥ 5 kA
                                                              •	 Thermal protection with the capability of estinguishing
                                                                 the short-circuit current at the end of life and coordina-
                                                                 tion with suitable back-up protection.

                                                              Since the modules of the strings generally have an im-
                                                              pulse withstand voltage higher than that of the inverter,
                                                              the SPDs installed to protect the inverter generally allow
                                                              the protection of the modules too, provided that the
                                                              distance between modules and inverter is shorter than
The overvoltages, even if limited, which may be generated     10 m16.
must be discharged to ground by means of SPD (Surge
Protective Device) to protect the equipment. In fact,
SPDs are devices with impedance variable according to
the voltage applied: at the rated voltage of the plant they
have a very high impedance, whereas in the presence of
an overvoltage they reduce their impedance, deriving the
current associated to the overvoltage and keeping the
latter within a determined range of values. According to
their operation modalities SPDs can be divided into:
•	 switching SPDs,  such as spinterometers or controlled
   diodes, when the voltage exceeds a defined value,
   reduce instantaneously their impedance and conse-
   quently the voltage at their ends;
•	 limitation SPDs, such as varistors or Zener diodes,
   have an impedance which decreases gradually at the
   increase of the voltage at their ends;
•	 combined SPDs which comprise the two above men-
   tioned devices connected in series or in parallel.




                                                              15
                                                                   Uinv is the impulse withstand voltage of the inverter DC side.

                                                              16
                                                                The SPD shall be installed on the supply side (direction of the energy of the PV genera-
                                                              tor) of the disconnecting device of the inverter so that it protects the modules also when
                                                              the disconnecting device is open.




                                                                                                                         Photovoltaic plants 47
Technical Application Papers




                                                        6.4.2.2	Protection on AC side                                                                        If the risk analysis for the building prescribes the instal-
                                                        A PV plant connected to the grid is subject also to the                                              lation of an outside LPS, it is necessary to position an
6 Protection against overcurrents and overvoltages




                                                        overvoltages coming from the line itself. If a separation                                            SPD for the protection against direct lightning at the
                                                        transformer is present, with earthed metal shield, the                                               power delivery point. Such SPD should have the follow-
                                                        inverter is protected against the overvoltages of the trans-                                         ing characteristics:
                                                                                                                                                             •	 Type 1
                                                        former itself. If the transformer is not present or in case
                                                                                                                                                             •	 Maximum rated service voltage  Ue > 1.1 Uo
                                                        of a transformer without shield, it is necessary to install
                                                                                                                                                             •	 Protection level Up ≤ Uinv
                                                        a suitable SPD immediately downstream the inverter.
                                                                                                                                                             •	 Impulse current Iimp ≥ 25 kA for each pole
                                                        This SPDs should have the following characteristics:
                                                                                                                                                             •	 Extinction of the follow-up current Ifi exceeding the
                                                        •	 Type 2
                                                                                                                                                                short-circuit current at the installation point and coor-
                                                        •	 Maximum rated service voltage  Ue > 1.1 Uo17
                                                                                                                                                                dination with a suitable back-up protection.
                                                        •	 Protection level Up ≤ Uinv18
                                                        •	 Nominal discharge current In ≥ 5 kA                                                               The figures below show the layout of a PV plant divided
                                                        •	 Thermal protection with the capability of estinguishing                                           in zones from A to E and indicate the protection function
                                                           the short-circuit current at the end of life and coordina-                                        carried out by the SPD when installed in each zone.
                                                           tion with suitable back-up protection.

                                                                                                                                                             External limit of the collecting area of the lightning rod
                                                                                                        Lightning rod
                                                                                                                                                                                          Equipotential bonding zone
                                                                                                                                                                                          of the building masses


                                                                                                                                                                  String
                                                                                          A                                                                        +
                                                                            A
                                                                                   B                                                                                                 L1           L2
                                                                                               C
                                                                                                                                                                       G
                                                                                                         D                                                         –
                                                                                                                 E


                                                                                                                                                                            A                 B           C        D               E




                                                                   SPD position                Function                            Recommendation                                            Remarks
                                                                                               Protection of each solar            Recommended if the distance L1 exceeds                    The connection to the panel must be as short
                                                                                               panel (cell+connections)            10 m or if there is a risk of inductive                   and straight as possible. If required by the
                                                               A                                                                   coupling                                                  environment, the SPD shall be installed in an
                                                               A
                                                               A                                                                                                                             enclosure with suitable IP degree
                                                               A
                                                               A                               Protection of the main              Always recommended                                        The connection to the equipotential bonding bar
                                                               B                               DC line (at the entrance                                                                      must be as short and straight as possible
                                                               B                               of the building)
                                                               B
                                                               B
                                                               B
                                                               C                               Protection of the inverter          Recommended if the distance L2 exceeds                    The connection to the equipotential bonding bar
                                                               C                               input, on DC side                   10 m                                                      and to the mass of the inverter on ther DC side
                                                               C                                                                                                                             must be as short and straight as possible
                                                               C
                                                               C
                                                               D
                                                               D                               Protection of the inverter          Always recommended                                        The connection to the equipotential bonding bar
                                                               D                               output, on AC side                                                                            and to the mass of the inverter on the AC side
                                                               D
                                                               D                                                                                                                             must be as short and straight as possible
                                                               E
                                                               E
                                                               E                               Main protection at the              Always recommended                                        The connection to the equipotential bonding bar
                                                               E
                                                               E
                                                                                               delivery point of energy                                                                      must be as short and straight as possible




                                                        17
                                                             Uo is the voltage to earth for TT and TN systems; in case of an IT system it is Ue > 1.73 Uo.   18
                                                                                                                                                                  Uinv is the impulse withstand voltage of the inverter on the AC side.




                                                     48 Photovoltaic plants

More Related Content

What's hot

Master thesis presentation
Master thesis presentationMaster thesis presentation
Master thesis presentation
Mayur Sarode
 
RF to dc generator
RF to  dc generatorRF to  dc generator
RF to dc generator
qureshiamin
 
Lec6 impact of embedded generation (1)
Lec6 impact of embedded generation (1)Lec6 impact of embedded generation (1)
Lec6 impact of embedded generation (1)
iqra26279
 
A low power rf id transponder
A low power rf id transponderA low power rf id transponder
A low power rf id transponder
Bien Morfe
 
1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)
nikeshdubey
 

What's hot (20)

Sasaki_M1GP
Sasaki_M1GPSasaki_M1GP
Sasaki_M1GP
 
800%20k v%20paper
800%20k v%20paper800%20k v%20paper
800%20k v%20paper
 
Electron Tube Afs Epri R5
Electron Tube   Afs Epri R5Electron Tube   Afs Epri R5
Electron Tube Afs Epri R5
 
Insulation coordination
Insulation coordinationInsulation coordination
Insulation coordination
 
Vfd white paper_2012
Vfd white paper_2012Vfd white paper_2012
Vfd white paper_2012
 
Frequency response
Frequency responseFrequency response
Frequency response
 
Your electrical safety specilist for all equipments Powered AC and DC
Your electrical safety specilist for all equipments   Powered AC and DCYour electrical safety specilist for all equipments   Powered AC and DC
Your electrical safety specilist for all equipments Powered AC and DC
 
Master thesis presentation
Master thesis presentationMaster thesis presentation
Master thesis presentation
 
Design of a low-power compact CMOS variable gain amplifier for modern RF rece...
Design of a low-power compact CMOS variable gain amplifier for modern RF rece...Design of a low-power compact CMOS variable gain amplifier for modern RF rece...
Design of a low-power compact CMOS variable gain amplifier for modern RF rece...
 
RF to dc generator
RF to  dc generatorRF to  dc generator
RF to dc generator
 
Lec6 impact of embedded generation (1)
Lec6 impact of embedded generation (1)Lec6 impact of embedded generation (1)
Lec6 impact of embedded generation (1)
 
A low power rf id transponder
A low power rf id transponderA low power rf id transponder
A low power rf id transponder
 
Xd 8550-6000
Xd 8550-6000Xd 8550-6000
Xd 8550-6000
 
Catching a Wave
Catching a WaveCatching a Wave
Catching a Wave
 
ESP D1 Series - Enhanced mains power protectors
ESP D1 Series - Enhanced mains power protectorsESP D1 Series - Enhanced mains power protectors
ESP D1 Series - Enhanced mains power protectors
 
PWST and High Function RFID
PWST and High Function RFIDPWST and High Function RFID
PWST and High Function RFID
 
Powerharvester Selection Guide
Powerharvester Selection GuidePowerharvester Selection Guide
Powerharvester Selection Guide
 
Surge Protective Device -Meba
Surge Protective Device -MebaSurge Protective Device -Meba
Surge Protective Device -Meba
 
1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)1 residual current circuit breaker (rccb) ( elcb)
1 residual current circuit breaker (rccb) ( elcb)
 
L3 electronics pn junction
L3 electronics   pn junctionL3 electronics   pn junction
L3 electronics pn junction
 

Viewers also liked

Viewers also liked (19)

Setting up the Arduino ATTiny
Setting up the Arduino ATTinySetting up the Arduino ATTiny
Setting up the Arduino ATTiny
 
Lezione 2
Lezione 2Lezione 2
Lezione 2
 
Cm05 huongdan tt23_trich
Cm05 huongdan tt23_trichCm05 huongdan tt23_trich
Cm05 huongdan tt23_trich
 
Minoranza Creativa Pasian di Prato
Minoranza Creativa Pasian di PratoMinoranza Creativa Pasian di Prato
Minoranza Creativa Pasian di Prato
 
Lezione 1
Lezione 1Lezione 1
Lezione 1
 
Cm05 huongdan tt23_trich
Cm05 huongdan tt23_trichCm05 huongdan tt23_trich
Cm05 huongdan tt23_trich
 
How Podcasting Can Build a Community
How Podcasting Can Build a CommunityHow Podcasting Can Build a Community
How Podcasting Can Build a Community
 
Chapter 02
Chapter 02Chapter 02
Chapter 02
 
NSTA 2013 Denver - ArduBlock and Arduino
NSTA 2013 Denver - ArduBlock and ArduinoNSTA 2013 Denver - ArduBlock and Arduino
NSTA 2013 Denver - ArduBlock and Arduino
 
Pv 3 lez
Pv 3 lezPv 3 lez
Pv 3 lez
 
T21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMini
T21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMiniT21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMini
T21Con 2013 SparkFun Presentation - Arduino and ArduBlock with Protosnap ProMini
 
Strategies for Educators Using Microcontrollers in the Classroom
Strategies for Educators Using Microcontrollers in the ClassroomStrategies for Educators Using Microcontrollers in the Classroom
Strategies for Educators Using Microcontrollers in the Classroom
 
ATTiny Light Sculpture Project - Part I (Setup)
ATTiny Light Sculpture Project - Part I (Setup)ATTiny Light Sculpture Project - Part I (Setup)
ATTiny Light Sculpture Project - Part I (Setup)
 
Open-Source Hardware, Tinkering, and Physics Education
Open-Source Hardware, Tinkering, and Physics EducationOpen-Source Hardware, Tinkering, and Physics Education
Open-Source Hardware, Tinkering, and Physics Education
 
Scratch for Data Logging and Graphing
Scratch for Data Logging and GraphingScratch for Data Logging and Graphing
Scratch for Data Logging and Graphing
 
Introduction to Arduino with ArduBlock & SparkFun LilyPad
Introduction to Arduino with ArduBlock & SparkFun LilyPadIntroduction to Arduino with ArduBlock & SparkFun LilyPad
Introduction to Arduino with ArduBlock & SparkFun LilyPad
 
Maker Science with Arduino and SparkFun Electronics @NSTA14 Boston
Maker Science with Arduino and SparkFun Electronics @NSTA14 BostonMaker Science with Arduino and SparkFun Electronics @NSTA14 Boston
Maker Science with Arduino and SparkFun Electronics @NSTA14 Boston
 
Pop up paper engineering - cu boulder & centaurus
Pop up paper engineering - cu boulder & centaurusPop up paper engineering - cu boulder & centaurus
Pop up paper engineering - cu boulder & centaurus
 
ATTiny Light Sculpture Project - Part II (MultiLEDs)
ATTiny Light Sculpture Project - Part II (MultiLEDs)ATTiny Light Sculpture Project - Part II (MultiLEDs)
ATTiny Light Sculpture Project - Part II (MultiLEDs)
 

Similar to Pv lez 6

CN 203 - Lightning and Power Frequency Performance of MV Pole Mounted Transfo...
CN 203 - Lightning and Power Frequency Performance of MV Pole Mounted Transfo...CN 203 - Lightning and Power Frequency Performance of MV Pole Mounted Transfo...
CN 203 - Lightning and Power Frequency Performance of MV Pole Mounted Transfo...
kevinrisi
 
HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)
Allied Power APS
 
Comprehensive Long-Run Incremental Cost (LRIC)-Voltage Network Pricing Approa...
Comprehensive Long-Run Incremental Cost (LRIC)-Voltage Network Pricing Approa...Comprehensive Long-Run Incremental Cost (LRIC)-Voltage Network Pricing Approa...
Comprehensive Long-Run Incremental Cost (LRIC)-Voltage Network Pricing Approa...
IJMER
 

Similar to Pv lez 6 (20)

CN 203 - Lightning and Power Frequency Performance of MV Pole Mounted Transfo...
CN 203 - Lightning and Power Frequency Performance of MV Pole Mounted Transfo...CN 203 - Lightning and Power Frequency Performance of MV Pole Mounted Transfo...
CN 203 - Lightning and Power Frequency Performance of MV Pole Mounted Transfo...
 
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINECOMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
COMPENSATION OF FAULT RESISTANCE IN DISTANCE RELAY FOR LONG TRANSMISSION LINE
 
Application data explusion links
Application data explusion linksApplication data explusion links
Application data explusion links
 
Electrical protection in mines John Ainsworth
Electrical protection in mines   John AinsworthElectrical protection in mines   John Ainsworth
Electrical protection in mines John Ainsworth
 
Arrester
ArresterArrester
Arrester
 
Surge Protect, a critical issue you could not fail to know while implementing...
Surge Protect, a critical issue you could not fail to know while implementing...Surge Protect, a critical issue you could not fail to know while implementing...
Surge Protect, a critical issue you could not fail to know while implementing...
 
Smart Grid Overvoltage Protection
Smart Grid Overvoltage ProtectionSmart Grid Overvoltage Protection
Smart Grid Overvoltage Protection
 
SA2004-000711_en_Calculation_and_choice_of_setting_values_for_protection_term...
SA2004-000711_en_Calculation_and_choice_of_setting_values_for_protection_term...SA2004-000711_en_Calculation_and_choice_of_setting_values_for_protection_term...
SA2004-000711_en_Calculation_and_choice_of_setting_values_for_protection_term...
 
Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...Performance of quadrilateral relay on EHV transmission line protection during...
Performance of quadrilateral relay on EHV transmission line protection during...
 
Pv lez 5
Pv lez 5Pv lez 5
Pv lez 5
 
Ce31533536
Ce31533536Ce31533536
Ce31533536
 
LECT_1_E_1435_POWER_SYSTEM_PROTECTION.ppt
LECT_1_E_1435_POWER_SYSTEM_PROTECTION.pptLECT_1_E_1435_POWER_SYSTEM_PROTECTION.ppt
LECT_1_E_1435_POWER_SYSTEM_PROTECTION.ppt
 
HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)
 
113
113113
113
 
G.r.s. 02 04-01-12
G.r.s. 02 04-01-12G.r.s. 02 04-01-12
G.r.s. 02 04-01-12
 
01. betagard mcb
01. betagard mcb01. betagard mcb
01. betagard mcb
 
RAMS Tech Paper
RAMS Tech PaperRAMS Tech Paper
RAMS Tech Paper
 
Comprehensive Long-Run Incremental Cost (LRIC)-Voltage Network Pricing Approa...
Comprehensive Long-Run Incremental Cost (LRIC)-Voltage Network Pricing Approa...Comprehensive Long-Run Incremental Cost (LRIC)-Voltage Network Pricing Approa...
Comprehensive Long-Run Incremental Cost (LRIC)-Voltage Network Pricing Approa...
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
 
D010622334
D010622334D010622334
D010622334
 

Recently uploaded

Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
Matteo Carbone
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
lizamodels9
 
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
amitlee9823
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
daisycvs
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
dlhescort
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
amitlee9823
 
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
amitlee9823
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
Renandantas16
 

Recently uploaded (20)

Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service AvailableCall Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
Call Girls Ludhiana Just Call 98765-12871 Top Class Call Girl Service Available
 
Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1Katrina Personal Brand Project and portfolio 1
Katrina Personal Brand Project and portfolio 1
 
Insurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usageInsurers' journeys to build a mastery in the IoT usage
Insurers' journeys to build a mastery in the IoT usage
 
Monthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptxMonthly Social Media Update April 2024 pptx.pptx
Monthly Social Media Update April 2024 pptx.pptx
 
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
Russian Call Girls In Gurgaon ❤️8448577510 ⊹Best Escorts Service In 24/7 Delh...
 
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
Call Girls Electronic City Just Call 👗 7737669865 👗 Top Class Call Girl Servi...
 
Phases of Negotiation .pptx
 Phases of Negotiation .pptx Phases of Negotiation .pptx
Phases of Negotiation .pptx
 
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
Quick Doctor In Kuwait +2773`7758`557 Kuwait Doha Qatar Dubai Abu Dhabi Sharj...
 
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdfDr. Admir Softic_ presentation_Green Club_ENG.pdf
Dr. Admir Softic_ presentation_Green Club_ENG.pdf
 
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
Call Girls in Delhi, Escort Service Available 24x7 in Delhi 959961-/-3876
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
Call Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine ServiceCall Girls In Panjim North Goa 9971646499 Genuine Service
Call Girls In Panjim North Goa 9971646499 Genuine Service
 
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Hebbal Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
 
Business Model Canvas (BMC)- A new venture concept
Business Model Canvas (BMC)-  A new venture conceptBusiness Model Canvas (BMC)-  A new venture concept
Business Model Canvas (BMC)- A new venture concept
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptx
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
 

Pv lez 6

  • 1. Technical Application Papers 6 Protection against overcurrents and overvoltages When defining the layout of a photovoltaic plant it is The short-circuit current Isc3 = y . 1.25 . Isc coincides with the necessary to provide, where needed, for the protection service current of the circuit between the subfield switch- 6 Protection against overcurrents and overvoltages of the different sections of the plant against overcurrents board and inverter, whereas the current Isc4 = (x-y) . 1.25 . Isc and overvoltages of atmospheric origin. is higher than the service current if x-y > y ⇒ x > 2y. Here are given, firstly, the conditions for the protection In this case it is necessary to protect the cable against against overcurrents in the PV plant on the supply (DC short-circuit if its current carrying capacity is lower than side) and on the load side of the inverter (AC side), then Isc4, that is Iz<(x-y).1.25.Isc. the methods for the protection of the plant against any Figure 6.1 damage caused by possible direct or indirect fulmina- “A” represents the protective device in the subfield switchboard for the pro- tion1. tection of the “cable 1” connecting the string to the switchboard itself. “B” represents the protection device installed in the inverter switchboard to protect the “cable 2” for the connection between the inverter and the subfield switchboard. “y” number of strings connected to the same subfield switchboard. 6.1 Protection against overcurrents on DC side “x” total number of strings connected to the same inverter. 6.1.1 Cable protections String + Cable 1 Subfield – switchboard From the point of view of the protection against over- A loads, it is not necessary to protect the cables (CEI 64- 8/7) if they are chosen with a current carrying capacity not lower than the maximum current which might affect Cable 2 + them (1.25 Isc)2. y – As regards the short-circuit, the cables on the DC side Isc3 are affected by such overcurrent in case of: Fault 1 • fault between the polarity of the PV system; Fault 2 • fault to earth in the earthed systems; Isc1 Isc2 • double fault to earth in the earth-insulated systems. Isc4 A short-circuit on a cable for the connection string to Subfield subfield switchboard (fault 1 of Figure 6.1) is supplied switchboard simultaneously upstream of the load side by the string under consideration (Isc1 = 1.25 . Isc) and downstream by parallel point with the grid the other x-1 strings connected to the same inverter (Isc2 – B + + = (x-1) . 1.25 . Isc). x – + – If the PV plant is small-sized with two strings only (x=2), it results that Isc2 = 1.25 . Isc = Isc1 and therefore it is not Inverter switchboard necessary to protect the string cables against short- circuit. On the contrary, when three or more strings (x≥3) are connected to the inverter, the current Isc2 is higher than the service current and therefore the cables must be pro- tected against the short-circuit when their current carrying capacity is lower than Isc2, that is Iz< (x-1) . 1.25 . Isc . A short-circuit between a subfield switchboard and the inverter switchboard (fault 2 of the Figure 6.1) is supplied upstream by the y strings in parallel of the subfield (Isc3) and downstream by the remaining (x-y) strings relevant + to the same inverter switchboard. – 1 As regards the power factor correction of a user plant in the presence of a PV plant see Annex E of the QT8 “Power factor correction and harmonic filtering in electrical plants”. 2 Isc is the short-circuit current in the module under standard test conditions and the twenty-five per cent rise takes the insolation values exceeding 1kW/m2 (see Chapter 3) into account. 42 Photovoltaic plants
  • 2. 6.1.2 Protection of the strings against reverse a drop of the direct voltage, the inverter certainly shuts current down and probably is disconnected from the grid. Nor- 6 Protection against overcurrents and overvoltages mally the shut down times of the inverter are of the order Due to shading or fault a string becomes passive, absorbing of some milliseconds, while the disconnection times may and dissipating the electric power generated by the other be of the order of some dozens of milliseconds. In the strings connected in parallel to the same inverter through interval between the shut down and the disconnection, a current which flows through the string under considera- the grid might cause the above mentioned effect, while tion in a reverse direction with respect to that of standard the internal capacitors, if involved, participate up to their operation, with possible damages to the modules. complete discharge. These are able to withstand a reverse current ranging The effects on the short-circuit of both the grid as well from 2.5 and 3 Isc (IEC TS 62257-7-1). Since with x strings as of the internal capacitors are just of transitory nature and usually are not such as to affect the dimensioning in parallel connected to the same inverter the highest of the protective, switching and disconnection devices reverse current is equal to Iinv = (x-1) . 1.25 . Isc, it is not positioned on the d.c side. However, it is necessary to necessary to protect the strings if Iinv ≤ 2.5 . Isc that is consider case-by-case the advisability of such choice: (x-1) . 1.25 ≤ 2.5 ⇒ x ≤ 33. in particular, a very high discharge current of the capaci- tors, combined with long time constants, might force to increase the current breaking capacity of the circuit- 6.1.3 Behaviour of the inverter breakers. The contribution to the short-circuit on the DC side of the inverter may come from the grid and from the discharge 6.1.4 Choice of the protective devices of the capacitors inside the inverter. As regards the protection against the short-circuits on the The grid current is due to the recirculating diodes of the DC side, the devices shall be obviously suitable for DC bridge inverter which in this case act as a bridge recti- use and have a rated service voltage Ue equal or higher fier. Such current is limited by the impedances of the than the maximum voltage of the PV generator which is transformer and of the inductors belonging to the output equal to 1.2 Uoc4 (IEC TS 62257-7-1). circuit and by the protection fuses of the inverter on the AC side chosen so that they can limit the thermal effects Moreover the protection devices shall be positioned at of possible internal faults on the semiconductors. As a the end of the circuit to be protected, proceeding from consequence the I2t passing through will be normally the strings towards the inverter, that is in the various reduced. Indicatively a final current value (internal ca- subfield switchboards and inverter switchboards since pacitors completely discharged) of 10In can be an upper the short-circuit currents come from the other strings, limit value. This current is present in case of inverter with that is from the load side and not from the supply side galvanic insulation at 50Hz, while it is null in case of in- (IEC TS 62257-7-1). verter without transformer. In fact these inverters usually have an input DC/DC converter so that the operation on In order to avoid unwanted tripping under standard opera- a wide voltage range of the PV generator is guaranteed; tion conditions, the protective devices positioned in the this converter, due to its constructive typology, includes at least one blocking diode which prevents the contribution subfield switchboards (device A in the Figure 6.1) shall of the grid current to the short-circuit. have a rated current In5: The discharge current of the capacitors is limited by the In ≥ 1.25 . Isc [6.1] cables between inverter and fault and exhausts itself with exponential trend: the lowest the impedance of the cable These devices shall protect: stretch, the highest the initial current, but the lowest the • every single string against the reverse current; time constant of the discharge. The energy which flows • the connection cable6 string to subswitchboard (cable is limited to that one initially stored in the capacitors. 1 of Figure 6.1) if the latter has a current carrying ca- Moreover, if a blocking diode or other similar device is in pacity lower than the maximum short-circuit current of series with one of the two poles, this contribution to the the other x-1 strings connected to the same inverter short-circuit is null. switchboard7, i.e. if: In each case, the short-circuit on the DC side causes I < I = (x - 1) . 1.25 . I [6.2] z sc2 sc 3 The blocking diodes can be used, but they do not replace the protections against 4 Uoc is the no load voltage coming out of the strings (see Chapter 3). overcurrent (IEC TS 62257-7-1), since it is taken into consideration the possibility that the blocking diode does not work properly and is short-circuited. Moreover the diodes 5 For thermomagnetic circuit-breakers the [6.1] becomes Ioverload ≥ 1.25 . Isc, while for mag- introduce a loss of power due to the voltage drop on the junction, a loss which can be netic only circuit-breakers Iu ≥ 1.25 . Isc so that their overheating can be avoided. reduced by using Schottky diodes with 0.4V drop instead of 0.7V of conventional diodes. However the rated reverse voltage of the diodes shall be ≥ 2 Uoc and the rated current ≥ 6 Protection against short-circuit only because Iz ≥ 1.25 . Isc. 1.25 Isc (CEI Guide 82-25). 7 The short-circuit Isc1 = 1.25 . Isc (fig. 6.1) (Figure 6.1) is unimportant because the string cable has a current carrying capacity not lower than 1.25 . Isc. Photovoltaic plants 43
  • 3. Technical Application Papers To the purpose of protection for the string, the rated 6.2 Protection against overcurrents on AC side current of the protective device (either thermomagnetic 6 Protection against overcurrents and overvoltages circuit-breaker or fuse) must not exceed that one declared Since the cable connecting the inverter to the point of by the manufacturer for the panel protection (clause connection with the grid is usually dimensioned to obtain 6.1.2); if no indications are given by the manufacturer, a current carrying capacity higher than the maximum cur- the following is assumed (IEC TS 62257-7-1): rent which the inverter can deliver, a protection against overload is not needed. However the cable must be 1.25 . Isc ≤ In ≤ 2 . Isc [6.3] protected against a short circuit supplied by the grid10 In spite of the simplicity of use of fuses, when sizing and through a protective device positioned near the point of choosing these devices it is necessary to take into account parallel with the grid. that they not only must have a rated current obtained by the relationship [6.3], but that they must have a trip char- To protect such cable the main circuit-breaker of the con- acteristic type gR (i.e. suitable for the protection of circuits sumer plant can be used if the specific let-through energy by means of semiconductors), they must be mounted is withstood by the cable. However, the trip of the main on fuse holders and they must be able to dissipate the circuit-breaker put all the consumer plant out of service. power generated under the worst operating conditions. In the multi-inverter plants (Figure 6.2), the presence of To the purpose of protection for the connection ca- ble, the protective device must be chosen so that the one protection for each line allows, in case of fault on following relation is satisfied for each value of short- an inverter, the functioning of the other ones, provided circuit (IEC 60364)8 up to a maximum of (x-1) . 1.25 . Isc: that the circuit-breakers on each line are selective with the main circuit-breaker. (I2t) ≤ K2 S2 [6.4] where: Figure 6.2 (I2t) is the Joule integral referred to the short-circuit dura- tion (in A2s); K is a characteristic constant of the cable depending on the type of conductor and on the insulating material; S is the cross-sectional area of the cable (in mm2). The breaking capacity of the device must not be lower than the short-circuit current of the other n-1 strings, Point of parallel with that is: the grid Icu ≥ (x-1) . 1.25 . Isc [6.5] The devices in the inverter switchboard must protect against the short-circuit the connection cables subfield switchboard-inverter switchboard when these cables have a current carrying capacity lower than Isc4 = (x-y) . 1.25 . Isc9 (Figure 6.1). In this case these devices shall satisfy the relations [6.1] and [6.4], while their current carrying ca- pacity shall not be lower than the short-circuit current of the other n-m strings, that is: 6.3 Choice of the switching and disconnecting Icu ≥ (x-y) . 1.25 . Isc [6.6] devices In short, the cable for the connection inverter switchboard The installation of a disconnecting device on each string to inverter must not be protected if its current carrying is advisable in order to allow verification or maintenance capacity is chosen at least equal to (CEI 64-8/7): interventions on the string without putting out of service Iz ≥ x . 1.25 . Isc [6.7] other parts of the PV plant (CEI Guide 82-25 II ed.)11. 8 For the magnetic only circuit-breaker it is necessary, if possible, to set the protection 10 The inverter generally limits the output current to a value which is the double of its function at a value equal to the value Iz of the cable in order to determine the tripping of the rated current and goes in stand-by in few tenths of seconds due to the trip of the internal device when the short circuit current exceeds the current carrying capacity of the protected protection. As a consequence, the contribution of the inverter to the short-circuit current cable. Besides, it is possible to use a magnetic only circuit-breaker if the number of strings is negligible in comparison with the contribution of the grid. connected to the same inverter is maximum 3; otherwise for the protection of the string it is necessary to use a thermomagnetic circuit-breaker chosen according to [6.3]. 11 When an automatic circuit-breaker is used the switching and disconnecting function is already included. 9 The short-circuit current Isc3 = y . 1.25 . Isc (Figure 6.1) is unimportant since the string cable has a current carrying capacity not lower than y . 1.25 . Isc. 44 Photovoltaic plants
  • 4. The disconnection of the inverter must be possible both Figure 6.3 on the DC side as well as on the AC side so that main- 6 Protection against overcurrents and overvoltages tenance is allowed by excluding both the supply sources (grid and PV generator) (CEI 64-8/7). On the DC side of the inverter a disconnecting device shall be installed which can be switched under load, such as a switch-disconnector. On the AC side a general disconnecting device shall be provided. The protective device installed at the point of connection with the grid can be used; if this device is not close to the inverter, it is advisable to position a disconnecting device immediately on the load side of the inverter. 6.4 Protection against overvoltages The PV installations, since they usually are outside the On the contrary, in case the PV installation changes buildings, may be subject to overvoltages of atmospheric significantly the outline of the building, it is necessary origin, both direct (lightning striking the structure) as well to reconsider the frequency of fulminations on it and as indirect (lightning falling near to the structure of the consequently to take into consideration the necessity of building or affecting the energy or signaling lines entering realizing an LPS (CEI Guide 82-25 II ed.) (Figure 6.4). the structure) through resistive or inductive coupling. The resistive coupling occurs when lightning strikes the Figure 6.4 electrical line entering the building. The lightning cur- rent, through the characteristic impedance of the line, originates an overvoltage which may exceed the impulse withstand voltage of the equipment, with consequent damaging and fire hazard. The inductive coupling occurs because the lightning current is impulsive and therefore it generates in the sur- rounding space an electromagnetic field highly variable. As a consequence, the variation in the magnetic field generates some overvoltages induced on the electric circuits nearby. In addition to the overvoltages of atmospheric origin, the PV plant may be exposed to internal switching ov- ervoltages. 6.4.1 Direct lightning 6.4.1.1 Building without LPS12 Generally, the erection of a PV plant does not change 6.4.1.2 Building with LPS the outline of a building and therefore the frequency of In case of presence of a protection system against at- the fulminations; therefore no specific measures against mospheric discharges13, if the PV plant does not alter the risk of fulmination are necessary (CEI Guide 82-25, the outline of the building and if the minimum distance d II ed.) (Figure 6.3). between the PV plant and the LPS plant is higher than the safety distance s (EN 62305-3) other additional measures 12 Lightning Protection System: it is constituted by the protective systems both external 13 It is advisable that the protection grounding plant is connected to that for the protec- (detectors, lightning conductors and ground electrodes) as well as internal (protective tion against lightning. measures in order to reduce the electromagnetic effects of the lightning current entering the structure to be protected). Photovoltaic plants 45
  • 5. Technical Application Papers for the protection of the new plant (CEI Guide 82-25 II Finally, if the PV plant alters the outline of the building a ed.) are not required (Figure 6.5). new risk evaluation and/or a modification of the LPS are 6 Protection against overcurrents and overvoltages Figure 6.5 necessary (CEI Guide 82-25, II ed.) (Figure 6.7). Figure 6.7 6.4.1.3 PV plant on the ground If a PV plant is erected on the ground there is no fire risk due to direct fulmination and the only hazard for human beings is represented by the step and touch voltages. On the contrary, if the PV plant does not alter the outline When the surface resistivity exceeds 5 kΩm (e.g. rocky of the building, but the minimum distance d is lower than asphalted ground, at least 5 cm thickness or laid with the distance s it is appropriate to extend the LPS plant gravel for minimum 15 cm), it is not necessary to take and connect it to the metal structures of the PV installa- any particular measure since the touch and step voltage tion (CEI Guide 82-25, II ed.) (Figure 6.6). values are negligible (CEI 81-10). Instead, if the ground resistivity were equal to or lower than 5 kΩm, it would Figure 6.6 be necessary to verify theoretically whether some pro- tective measures against the step and touch voltages are necessary; however, in this case, the probability of lightning strikes is very small and therefore the problem occurs only with very large plants. 6.4.2 Indirect lightning Also in case lightning does not strike directly the structure of the PV plant, it is necessary to take some measures to minimize the overvoltages caused by any likely indirect strike of lightning: • shielding of the circuits in order to reduce the magnetic field inside the enclosure with a consequent reduction of the induced overvoltages14; • reduction of the area of the turn of the induced circuit obtained by connecting suitably the modules one to the other (Figure 6.8), by twisting the conductors together and bringing the live conductor as much as possible near to the PE. 14 The shielding effect of a metal enclosure originates thanks to the currents induced in the enclosure itself; they create a magnetic field which by Lenz’s law opposes the cause generating them, that is the magnetic field of the lightning current; the higher the currents induced in the shield (i.e. the higher its conductance), the better the shielding effect. 46 Photovoltaic plants
  • 6. Figure 6.8 6.4.2.1 Protection on DC side 6 Protection against overcurrents and overvoltages For the protection on the DC side it is advisable to use varistors SPDs or combined SPDs. Inverters usually have an internal protection against overvoltages, but if SPDs are added to the inverter ter- minals, its protection is improved and at the same time it is possible to avoid that the tripping of the internal protections put out of service the inverter, thus causing suspension of energy production and making necessary the intervention of skilled personnel. These SPDs should have the following characteristics: • Type 2 • Maximum rated service voltage Ue > 1.25 Uoc • Protection level Up ≤ Uinv15 • Nominal discharge current In ≥ 5 kA • Thermal protection with the capability of estinguishing the short-circuit current at the end of life and coordina- tion with suitable back-up protection. Since the modules of the strings generally have an im- pulse withstand voltage higher than that of the inverter, the SPDs installed to protect the inverter generally allow the protection of the modules too, provided that the distance between modules and inverter is shorter than The overvoltages, even if limited, which may be generated 10 m16. must be discharged to ground by means of SPD (Surge Protective Device) to protect the equipment. In fact, SPDs are devices with impedance variable according to the voltage applied: at the rated voltage of the plant they have a very high impedance, whereas in the presence of an overvoltage they reduce their impedance, deriving the current associated to the overvoltage and keeping the latter within a determined range of values. According to their operation modalities SPDs can be divided into: • switching SPDs, such as spinterometers or controlled diodes, when the voltage exceeds a defined value, reduce instantaneously their impedance and conse- quently the voltage at their ends; • limitation SPDs, such as varistors or Zener diodes, have an impedance which decreases gradually at the increase of the voltage at their ends; • combined SPDs which comprise the two above men- tioned devices connected in series or in parallel. 15 Uinv is the impulse withstand voltage of the inverter DC side. 16 The SPD shall be installed on the supply side (direction of the energy of the PV genera- tor) of the disconnecting device of the inverter so that it protects the modules also when the disconnecting device is open. Photovoltaic plants 47
  • 7. Technical Application Papers 6.4.2.2 Protection on AC side If the risk analysis for the building prescribes the instal- A PV plant connected to the grid is subject also to the lation of an outside LPS, it is necessary to position an 6 Protection against overcurrents and overvoltages overvoltages coming from the line itself. If a separation SPD for the protection against direct lightning at the transformer is present, with earthed metal shield, the power delivery point. Such SPD should have the follow- inverter is protected against the overvoltages of the trans- ing characteristics: • Type 1 former itself. If the transformer is not present or in case • Maximum rated service voltage Ue > 1.1 Uo of a transformer without shield, it is necessary to install • Protection level Up ≤ Uinv a suitable SPD immediately downstream the inverter. • Impulse current Iimp ≥ 25 kA for each pole This SPDs should have the following characteristics: • Extinction of the follow-up current Ifi exceeding the • Type 2 short-circuit current at the installation point and coor- • Maximum rated service voltage Ue > 1.1 Uo17 dination with a suitable back-up protection. • Protection level Up ≤ Uinv18 • Nominal discharge current In ≥ 5 kA The figures below show the layout of a PV plant divided • Thermal protection with the capability of estinguishing in zones from A to E and indicate the protection function the short-circuit current at the end of life and coordina- carried out by the SPD when installed in each zone. tion with suitable back-up protection. External limit of the collecting area of the lightning rod Lightning rod Equipotential bonding zone of the building masses String A + A B L1 L2 C G D – E A B C D E SPD position Function Recommendation Remarks Protection of each solar Recommended if the distance L1 exceeds The connection to the panel must be as short panel (cell+connections) 10 m or if there is a risk of inductive and straight as possible. If required by the A coupling environment, the SPD shall be installed in an A A enclosure with suitable IP degree A A Protection of the main Always recommended The connection to the equipotential bonding bar B DC line (at the entrance must be as short and straight as possible B of the building) B B B C Protection of the inverter Recommended if the distance L2 exceeds The connection to the equipotential bonding bar C input, on DC side 10 m and to the mass of the inverter on ther DC side C must be as short and straight as possible C C D D Protection of the inverter Always recommended The connection to the equipotential bonding bar D output, on AC side and to the mass of the inverter on the AC side D D must be as short and straight as possible E E E Main protection at the Always recommended The connection to the equipotential bonding bar E E delivery point of energy must be as short and straight as possible 17 Uo is the voltage to earth for TT and TN systems; in case of an IT system it is Ue > 1.73 Uo. 18 Uinv is the impulse withstand voltage of the inverter on the AC side. 48 Photovoltaic plants