SlideShare ist ein Scribd-Unternehmen logo
1 von 21
Vector Group defines the relationship between the
Primary Voltage Vectors and the Secondary Voltage
Vectors. The Primary or Secondary Voltage Vectors may
Star or Delta.
 It is necessary to ensure that transformers to be
connected in parallel have the same vector group to
avoid circulating currents in the paralleled transformers
among other including same voltage level, same
percentage impedance and the same frequency.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
The concept of vector groups was adopted for transformers in the Generation,
Transmission and Distribution Networks in a manner so as to avoid the transfer
of Zero Sequence Current from each of the networks into the other. Delta Blocks
the flow of Zero Sequence Current.
The vector groups was also chosen in manner so as to enable the Earthing or
grounding of the various networks to facilitate the control of earth fault current
by the use of Neutral Ground Resistor(NGR). Where the Network is solidly
earthed, the earthing system is designed based on the exact short circuit level of
the Network, be it Generation, Transmission and Distribution.
Resonant Grounding (Peterson Coil) is also used in countries like Germany,
where the Reactance of the Peterson coil is tuned to match the Fictitious
Capacitance of the network. This way the earth fault current is reduced to
approximately Zero at the instant of fault (Inductive Current minus (-) Capacitive
Current). By this means countries with these scheme do not normally trip on
earth fault.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
The concept of vector groups was adopted for
transformers in the Generation, Transmission and
Distribution Networks in a manner so as to make
the overall phase shift Zero (0) at the Distribution
end close to the Customer.
The following slides analysis the various vector
group of the Generation, Transmission and
Distribution Network of the Ghana Power System.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Generation (Ynd1) Transmission (Ynd11)
Shifts Star ahead Delta Nullifies the Phase shift
by 30° by 30° by shifting Delta at 30 °
ahead Star
Distribution (MV) (Dyn1) Distribution (LV) (Dyn11)
Shifts Delta ahead Star Nullifies the Phase shift
by 30° by 30° by shifting Star at 30 °
ahead Delta
•RESULTANT PHASE SHIFT = ZERO (0)
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
It can be seen clearly that the Resultant Phase Shift in the
overall Vector Group of the Ghana Power System from
Generation through to the Distribution (LV) Network is
Zero (0). This way Customer end power is not affected by the
overall vector group of the power system.
The following slides show the various vector groups
available for Star-Delta, Star-Star, Delta-Star and Delta-Delta
Transformers.
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Delta – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
11 3 7
Delta – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
5 9 1
As clearly shown above, there are six vector group options available for Delta –
Star Transformer Configuration. These are;
Dy1 Dy3 Dy5 Dyn1 Dyn3 Dyn5
Or
Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Star – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
1 9 5
Star – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a a a
11 3 7
As clearly shown above, there are six vector group options available for Star –
Delta Transformer Configuration. These are;
Yd1 Yd3 Yd5 Ynd1 Ynd3 Ynd5
Or
Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
 Yd1 or Ynd1 is the same as Dy11 or Dyn11 as in both cases Star (Y) leads
Delta (D) by 30°.
 Yd11 or Ynd11 is the same as Dy1 or Dyn1 as in both cases Delta (D) leads
Star (Y) by 30°.
Note: By Inspection
Delta – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
0 8 4
Delta – Delta
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary
Delta
Equi. Secondary
Delta
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
6 2 10
As clearly shown above, there are six vector group options available for Delta –
Delta Transformer Configuration. These are;
Dd0 Dd2 Dd4
Dd6 Dd8 Dd10
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Star – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
0 8 4
Star – Star
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
C B
A
Primary Star Equi. Secondary
Star
Options of Naming Transformer Secondary
a
b
c
b
a
c
c
b
a
A AA
a
a a
6 2 10
As clearly shown above, there are six vector group options available for Star – Star
Transformer Configuration. These are;
Yy0 Yy2 Yy4 Yyn0 Yyn2 Yyn4
Or
Yy6 Yy8 Yy10 Yyn6 Yyn8 Yyn10
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
As clearly shown in the previous slides, there are Twenty-Four (24) vector groups
for Star Delta Transformers. Below is the reiteration of these vector groups;
Dy1 Dy3 Dy5 Or Dyn1 Dyn3 Dyn5
Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11
Dd0 Dd2 Dd4
Dd6 Dd8 Dd10
Yd1 Yd3 Yd5 Or Ynd1 Ynd3 Ynd5
Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11
Yy0 Yy2 Yy4 Or Ynyn0 Ynyn2 Ynyn4
Yy6 Yy8 Yy10 Ynyn6 Ynyn8 Ynyn10
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
Dyn1
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
A
C B
c
b
a
30°
30°
30°
The Primary Voltage Vectors (Delta) leads the Secondary Voltage Vectors
(Star) by 30°. This is also known as lag in Aspen DistriView
Dyn11
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana
A
C B
c
b
a
30°
30°
30°
The Primary Voltage Vectors (Delta) lags the Secondary Voltage Vectors
(Star) by 30°. This is also known as lead in Aspen DistriView
Thank You Very Much For
Your Kind Attention
5/3/2016
Presentation By; Armstrong Okai Ababio
Electrical Engineer/ Electricity Company of
Ghana

Weitere ähnliche Inhalte

Was ist angesagt?

Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guideSlides Hub
 
Cpc 100 user manual
Cpc 100 user manualCpc 100 user manual
Cpc 100 user manualSARAVANAN A
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.Geetesh Verma
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptxMuhd Hafizi Idris
 
Analysis of on Load Tap Changing Transformer for Substation
Analysis of on Load Tap Changing Transformer for SubstationAnalysis of on Load Tap Changing Transformer for Substation
Analysis of on Load Tap Changing Transformer for Substationijtsrd
 
ETAP - Coordination and protecion
ETAP -  Coordination and protecionETAP -  Coordination and protecion
ETAP - Coordination and protecionHimmelstern
 
Characteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relaysCharacteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relaystahseen alshmary
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relaysRoberto Costa
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guideSlides Hub
 
ECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionChandrabhan Sharma
 
Three phase transformer
Three phase transformerThree phase transformer
Three phase transformerragulkncet
 
Differential protection
Differential protectionDifferential protection
Differential protectionRishi Tandon
 
Power Electronics - Power Semi – Conductor Devices
Power Electronics - Power Semi – Conductor DevicesPower Electronics - Power Semi – Conductor Devices
Power Electronics - Power Semi – Conductor DevicesBurdwan University
 

Was ist angesagt? (20)

Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Cpc 100 user manual
Cpc 100 user manualCpc 100 user manual
Cpc 100 user manual
 
Testing of Transformers.
Testing of Transformers.Testing of Transformers.
Testing of Transformers.
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Analysis of on Load Tap Changing Transformer for Substation
Analysis of on Load Tap Changing Transformer for SubstationAnalysis of on Load Tap Changing Transformer for Substation
Analysis of on Load Tap Changing Transformer for Substation
 
ETAP - Coordination and protecion
ETAP -  Coordination and protecionETAP -  Coordination and protecion
ETAP - Coordination and protecion
 
Faults in Power System
Faults in Power SystemFaults in Power System
Faults in Power System
 
Full transformer
Full transformerFull transformer
Full transformer
 
Characteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relaysCharacteristic of idmt curves for overcurrent relays
Characteristic of idmt curves for overcurrent relays
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relays
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
 
ECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent Protection
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
Three phase transformer
Three phase transformerThree phase transformer
Three phase transformer
 
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
BUS BAR  PROTECTION PPT BY:-R.K.PANDITBUS BAR  PROTECTION PPT BY:-R.K.PANDIT
BUS BAR PROTECTION PPT BY:-R.K.PANDIT
 
Differential protection
Differential protectionDifferential protection
Differential protection
 
33/11 KV SUBSTATION
33/11 KV SUBSTATION33/11 KV SUBSTATION
33/11 KV SUBSTATION
 
Power Electronics - Power Semi – Conductor Devices
Power Electronics - Power Semi – Conductor DevicesPower Electronics - Power Semi – Conductor Devices
Power Electronics - Power Semi – Conductor Devices
 

Andere mochten auch

Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...sunny katyara
 
Three phase vector groups
Three phase vector groupsThree phase vector groups
Three phase vector groupsMUHAMMAD USMAN
 
Guide to transformer resistance testing
Guide to transformer resistance testing Guide to transformer resistance testing
Guide to transformer resistance testing bbatlle
 
PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)Muhammad Gulzar
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersLiving Online
 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-enSuresh Patil
 
Optical Current Transformer (OCT)
Optical Current Transformer (OCT)Optical Current Transformer (OCT)
Optical Current Transformer (OCT)Seminar Links
 
Transformer testing
Transformer testingTransformer testing
Transformer testingajayknows
 
industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substationpk130992
 
Startup Ideas and Validation
Startup Ideas and ValidationStartup Ideas and Validation
Startup Ideas and ValidationYevgeniy Brikman
 

Andere mochten auch (12)

Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
Simulink Analysis of Vector groups of Transformers installed at 132kV Grid St...
 
Three phase vector groups
Three phase vector groupsThree phase vector groups
Three phase vector groups
 
Test vector compression
Test vector compressionTest vector compression
Test vector compression
 
Guide to transformer resistance testing
Guide to transformer resistance testing Guide to transformer resistance testing
Guide to transformer resistance testing
 
PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)PP10 startup manual (Unofficial as Requested)
PP10 startup manual (Unofficial as Requested)
 
Installation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of TransformersInstallation, Testing and Troubleshooting of Transformers
Installation, Testing and Troubleshooting of Transformers
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 
Best transformer-test-procedures-en
Best transformer-test-procedures-enBest transformer-test-procedures-en
Best transformer-test-procedures-en
 
Optical Current Transformer (OCT)
Optical Current Transformer (OCT)Optical Current Transformer (OCT)
Optical Current Transformer (OCT)
 
Transformer testing
Transformer testingTransformer testing
Transformer testing
 
industrial training on 132 kv substation
industrial training on 132 kv substationindustrial training on 132 kv substation
industrial training on 132 kv substation
 
Startup Ideas and Validation
Startup Ideas and ValidationStartup Ideas and Validation
Startup Ideas and Validation
 

Ähnlich wie Presentation on Vector Groups by Armstrong

IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
IRJET-  	  Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...IRJET-  	  Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...IRJET Journal
 
332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.pptSatish Pydimarla
 
A novel four wire inverter system using SVPWM technique for ups applications
A novel four wire inverter system using SVPWM technique for ups applicationsA novel four wire inverter system using SVPWM technique for ups applications
A novel four wire inverter system using SVPWM technique for ups applicationsIRJET Journal
 
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using TransformerIRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using TransformerIRJET Journal
 
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...IRJET Journal
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongArmstrong Okai Ababio
 
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...IRJET Journal
 
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...IRJET Journal
 
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...paperpublications3
 
Cascaded Open-End Winding Transformer based DVR
Cascaded Open-End Winding Transformer based DVRCascaded Open-End Winding Transformer based DVR
Cascaded Open-End Winding Transformer based DVRAsoka Technologies
 
Topological Advancement in DVR; A review
Topological Advancement in DVR; A reviewTopological Advancement in DVR; A review
Topological Advancement in DVR; A reviewIRJET Journal
 
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...Alexander Decker
 
11.modeling, analysis and control of hexagram inverter for three phase induc...
11.modeling, analysis and control of hexagram inverter for three  phase induc...11.modeling, analysis and control of hexagram inverter for three  phase induc...
11.modeling, analysis and control of hexagram inverter for three phase induc...Alexander Decker
 
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...IRJET Journal
 
Analysis of a novel seven phase uncontrolled rectifier system
Analysis of a novel seven phase uncontrolled rectifier systemAnalysis of a novel seven phase uncontrolled rectifier system
Analysis of a novel seven phase uncontrolled rectifier systemIRJET Journal
 

Ähnlich wie Presentation on Vector Groups by Armstrong (20)

IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
IRJET-  	  Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...IRJET-  	  Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
IRJET- Review Paper on SVPWM Technique based D-STATCOM to Improve Power Q...
 
332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt332038674-Vector-Group-of-Transformers.ppt
332038674-Vector-Group-of-Transformers.ppt
 
A novel four wire inverter system using SVPWM technique for ups applications
A novel four wire inverter system using SVPWM technique for ups applicationsA novel four wire inverter system using SVPWM technique for ups applications
A novel four wire inverter system using SVPWM technique for ups applications
 
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using TransformerIRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
IRJET- A Review on Three-Phase to Seven-Phase Power Converter using Transformer
 
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
IRJET- Three-Phase to Seven-Phase Power Converter using PI Controller and Tra...
 
FAULT Analysis presentation Armstrong
FAULT Analysis presentation ArmstrongFAULT Analysis presentation Armstrong
FAULT Analysis presentation Armstrong
 
A044040108
A044040108A044040108
A044040108
 
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
IRJET- SVPWM Technique based D-STATCOM to Improve Power Quality in Distributi...
 
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
Selection of Passive Component for Cockroft Walton Voltage Multiplier: A Low ...
 
Question bank Electrical Engineering
Question bank Electrical Engineering Question bank Electrical Engineering
Question bank Electrical Engineering
 
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
Simulation and Comparison of DVR and DSTATCOM Used for voltage sag mitigation...
 
Two-level inverter and three-level neutral point diode clamped inverter for t...
Two-level inverter and three-level neutral point diode clamped inverter for t...Two-level inverter and three-level neutral point diode clamped inverter for t...
Two-level inverter and three-level neutral point diode clamped inverter for t...
 
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
A New Structure of Dynamic Voltage Restorer Based on Asymmetrical ī-source In...
 
Cascaded Open-End Winding Transformer based DVR
Cascaded Open-End Winding Transformer based DVRCascaded Open-End Winding Transformer based DVR
Cascaded Open-End Winding Transformer based DVR
 
Topological Advancement in DVR; A review
Topological Advancement in DVR; A reviewTopological Advancement in DVR; A review
Topological Advancement in DVR; A review
 
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
4.[14 24]modeling, analysis and control of hexagram inverter for three- phase...
 
11.modeling, analysis and control of hexagram inverter for three phase induc...
11.modeling, analysis and control of hexagram inverter for three  phase induc...11.modeling, analysis and control of hexagram inverter for three  phase induc...
11.modeling, analysis and control of hexagram inverter for three phase induc...
 
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
Compensation of Balanced and Unbalanced Voltage Disturbance using SRF Control...
 
Cascade Protection with Transient Voltage copy
Cascade Protection with Transient Voltage copyCascade Protection with Transient Voltage copy
Cascade Protection with Transient Voltage copy
 
Analysis of a novel seven phase uncontrolled rectifier system
Analysis of a novel seven phase uncontrolled rectifier systemAnalysis of a novel seven phase uncontrolled rectifier system
Analysis of a novel seven phase uncontrolled rectifier system
 

Presentation on Vector Groups by Armstrong

  • 1. Vector Group defines the relationship between the Primary Voltage Vectors and the Secondary Voltage Vectors. The Primary or Secondary Voltage Vectors may Star or Delta.  It is necessary to ensure that transformers to be connected in parallel have the same vector group to avoid circulating currents in the paralleled transformers among other including same voltage level, same percentage impedance and the same frequency. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 2. The concept of vector groups was adopted for transformers in the Generation, Transmission and Distribution Networks in a manner so as to avoid the transfer of Zero Sequence Current from each of the networks into the other. Delta Blocks the flow of Zero Sequence Current. The vector groups was also chosen in manner so as to enable the Earthing or grounding of the various networks to facilitate the control of earth fault current by the use of Neutral Ground Resistor(NGR). Where the Network is solidly earthed, the earthing system is designed based on the exact short circuit level of the Network, be it Generation, Transmission and Distribution. Resonant Grounding (Peterson Coil) is also used in countries like Germany, where the Reactance of the Peterson coil is tuned to match the Fictitious Capacitance of the network. This way the earth fault current is reduced to approximately Zero at the instant of fault (Inductive Current minus (-) Capacitive Current). By this means countries with these scheme do not normally trip on earth fault. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 3. The concept of vector groups was adopted for transformers in the Generation, Transmission and Distribution Networks in a manner so as to make the overall phase shift Zero (0) at the Distribution end close to the Customer. The following slides analysis the various vector group of the Generation, Transmission and Distribution Network of the Ghana Power System. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 4. Generation (Ynd1) Transmission (Ynd11) Shifts Star ahead Delta Nullifies the Phase shift by 30° by 30° by shifting Delta at 30 ° ahead Star Distribution (MV) (Dyn1) Distribution (LV) (Dyn11) Shifts Delta ahead Star Nullifies the Phase shift by 30° by 30° by shifting Star at 30 ° ahead Delta •RESULTANT PHASE SHIFT = ZERO (0) 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 5. It can be seen clearly that the Resultant Phase Shift in the overall Vector Group of the Ghana Power System from Generation through to the Distribution (LV) Network is Zero (0). This way Customer end power is not affected by the overall vector group of the power system. The following slides show the various vector groups available for Star-Delta, Star-Star, Delta-Star and Delta-Delta Transformers. 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 6. Delta – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 11 3 7
  • 7. Delta – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 5 9 1
  • 8. As clearly shown above, there are six vector group options available for Delta – Star Transformer Configuration. These are; Dy1 Dy3 Dy5 Dyn1 Dyn3 Dyn5 Or Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 9. Star – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 1 9 5
  • 10. Star – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 11 3 7
  • 11. As clearly shown above, there are six vector group options available for Star – Delta Transformer Configuration. These are; Yd1 Yd3 Yd5 Ynd1 Ynd3 Ynd5 Or Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana  Yd1 or Ynd1 is the same as Dy11 or Dyn11 as in both cases Star (Y) leads Delta (D) by 30°.  Yd11 or Ynd11 is the same as Dy1 or Dyn1 as in both cases Delta (D) leads Star (Y) by 30°. Note: By Inspection
  • 12. Delta – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 0 8 4
  • 13. Delta – Delta 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Delta Equi. Secondary Delta Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 6 2 10
  • 14. As clearly shown above, there are six vector group options available for Delta – Delta Transformer Configuration. These are; Dd0 Dd2 Dd4 Dd6 Dd8 Dd10 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 15. Star – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 0 8 4
  • 16. Star – Star 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana C B A Primary Star Equi. Secondary Star Options of Naming Transformer Secondary a b c b a c c b a A AA a a a 6 2 10
  • 17. As clearly shown above, there are six vector group options available for Star – Star Transformer Configuration. These are; Yy0 Yy2 Yy4 Yyn0 Yyn2 Yyn4 Or Yy6 Yy8 Yy10 Yyn6 Yyn8 Yyn10 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 18. As clearly shown in the previous slides, there are Twenty-Four (24) vector groups for Star Delta Transformers. Below is the reiteration of these vector groups; Dy1 Dy3 Dy5 Or Dyn1 Dyn3 Dyn5 Dy7 Dy9 Dy11 Dyn7 Dyn9 Dyn11 Dd0 Dd2 Dd4 Dd6 Dd8 Dd10 Yd1 Yd3 Yd5 Or Ynd1 Ynd3 Ynd5 Yd7 Yd9 Yd11 Ynd7 Ynd9 Ynd11 Yy0 Yy2 Yy4 Or Ynyn0 Ynyn2 Ynyn4 Yy6 Yy8 Yy10 Ynyn6 Ynyn8 Ynyn10 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana
  • 19. Dyn1 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana A C B c b a 30° 30° 30° The Primary Voltage Vectors (Delta) leads the Secondary Voltage Vectors (Star) by 30°. This is also known as lag in Aspen DistriView
  • 20. Dyn11 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana A C B c b a 30° 30° 30° The Primary Voltage Vectors (Delta) lags the Secondary Voltage Vectors (Star) by 30°. This is also known as lead in Aspen DistriView
  • 21. Thank You Very Much For Your Kind Attention 5/3/2016 Presentation By; Armstrong Okai Ababio Electrical Engineer/ Electricity Company of Ghana